COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

Similar documents
Study of R161 Refrigerant for Residential Airconditioning

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

Low GWP Refrigerants for Air Conditioning Applications

Low Global Warming Refrigerants For Commercial Refrigeration Systems

AHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Evaluation of HCFC Alternative Refrigerants

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

R-407A R-448A R-449A

JJMIE Jordan Journal of Mechanical and Industrial Engineering

2016 Annual Conference

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Solstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Performance Measurement of R32 Vapor Injection Heat Pump System

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

R-404A Alternative with Low Compressor Discharge Temperature

Refrigerant Glide and Effect on Performances Declaration

BRA FACT FINDER Number 19

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

CHAPTER 1 INTRODUCTION

Energy Use in Refrigeration Systems

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Sustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

A Comparison Between Refrigerants Used In Air Conditioning

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

CHAPTER 1 INTRODUCTION

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

January 16 th, 2014 New York City

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

THE USE OF HYDROCARBONS PROPANE AND ISOBUTANE IN REFRIGERATION SYSTEMS

Performance Assessment of Three Eco-Friendly Hydro-Fluorocarbon and Hydrocarbon Refrigerant Mixtures as R22 Alternatives in Refrigeration Systems

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

ENVIRONMENTALLY SAFE R-410A SERVICE TECHNIQUES

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Specifications for Fluorocarbon Refrigerants

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

International Journal of Advance Engineering and Research Development

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

REFRIGERANT CHANGEOVER

Performance Rating of Refrigerant Pressure Regulating Valves

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Why Hydrocarbons Save Energy

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Flow Capacity Rating of Suction Line Filters and Suction Line Filter Driers

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Specifications for Fluorocarbon Refrigerants

March 10, 2016 San Joaquin Valley RETA Meeting

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

The Current Path of Refrigerants

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Understanding Applications for Alternative Refrigerants

Effect of magnetic field on the performance of new refrigerant mixtures

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Effect of evaporator temperature on vapor compression refrigeration system

HFO-1234yf Performance in a Beverage Cooler

Development of Environmentally Benign Heat Pump Water Heaters for the US Market

Gary Parker Refrigerants Product Manager

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

Transcription:

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22 2013.12.26 prepared by James M. Calm, P.E. Engineering Consultant 10887 Woodleaf Lane Great Falls, VA 22066-3003 USA for Refrigerant Management Services of Georgia, LLC (RMS of Georgia) 610 McFarland / 400 Drive Alpharetta, GA 30004 USA Copyright 2013 James M. Calm, Engineering Consultant, USA all rights reserved except as granted by written consent. This report is proprietary; it was prepared pursuant to the scope and subject to the limitations, terms, and conditions of a consulting agreement with RMS of Georgia, LLC. No further reproduction or use by other parties is allowed without explicit written consent from James M. Calm, Engineering Consultant, USA. - i - 2013 James M. Calm, Engineering Consultant, USA

Please refer questions or comments on this document to: James M. Calm, P.E. Engineering Consultant 10887 Woodleaf Lane Great Falls, VA 22066-3003 USA phone: +1 (703) 636-9500 e-mail: jmc@jamesmcalm.com RMS of Georgia 610 McFarland / 400 Drive Alpharetta, GA 30004 USA phone: +1 (770) 777-0597, +1 (800) 347-5872 e-mail: info@rmsgas.com Neither James M. Calm, RMS of Georgia, nor any person acting on behalf of them (a) makes any warranty expressed or implied with respect to the accuracy, completeness, suitability, or usefulness of any information, apparatus, material, method, or process disclosed in this document or that use may not infringe privately owned rights; or (b) assumes any liabilities with respect to use of, or direct or indirect damages resulting from use of, any information, apparatus, material, method, or process disclosed in this document. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise, does not necessarily constitute or imply its endorsement, recommendation, or favoring. - ii - 2013 James M. Calm, Engineering Consultant, USA

TABLE OF CONTENTS Comparative Properties and Efficiency of R-421A for Retrofit Use to Replace R-22... 1 Summary... 1 Retrofit Refrigerant Options... 1 Pressure-Temperature Comparisons... 2 Performance Comparisons... 8 Representative Properties... 10 References... 13 LIST OF FIGURES Figure 1: Pressure-Temperature Comparison... 5 Figure 2: Cooling Coefficient of Performance (COP) Comparison without Adjustment for Pressure-Temperature Differences... 9 Figure 3: Relative COP Degradation with Increasing Condensing Temperature for Equipment Designed for Equivalent Performance at the Nominal Rating Point (35 C, 95 F) without Adjustment for Pressure-Temperature Differences... 10 LIST OF TABLES Table 1: Pressure-Temperature Data for Selected Refrigerants (SI units)... 3 Table 2: Pressure-Temperature Data for Selected Refrigerants (IP units)... 4 Table 3: Pressure-Temperature Similarity for R-22 and R-421A (SI units)... 6 Table 4: Pressure-Temperature Similarity for R-22 and R-421A (IP units)... 7 Table 5: Conditions for Performance Comparison... 8 Table 6: Data for Selected Refrigerants (SI units)... 11 Table 7: Data for Selected Refrigerants (IP units)... 12 - iii - 2013 James M. Calm, Engineering Consultant, USA

blank page - iv - 2013 James M. Calm, Engineering Consultant, USA

2013.12.26 Comparative Properties and Efficiency of R-421A for Retrofit Use to Replace R-22 SUMMARY prepared by James M. Calm, P.E. Engineering Consultant This report addresses the properties and performance of R-421A and other replacement refrigerants for R-22 for aftermarket not included in original equipment manufacturer (OEM) use for refrigerant retrofits. R-22 was the most widely used refrigerant in the identified applications from the 1950s through 2009 (and for some products or countries even later). Retrofit use implies consideration of property similarity between the original (design) and replacement refrigerants, often as a drop-in substitute without equipment modification to accommodate the differences. The pressure-temperature (PT) relations of the fluids are a key issue for air-conditioner and heat pump retrofits, as significant deviations alter both general operation and thermostatic expansion valve (or similar device) flow metering. While the expansion device can be modified or replaced during the retrofit, that is not the norm for such equipment due to the costs, selection intricacies, and other considerations. Another key factor is temperature glide and especially so in the evaporator. Increased glide, for systems not explicitly designed for it, may lead to preferential flow of one or more refrigerant blend components and departure from intended operation. Comparative efficiency, expressed as the relative degradation in coefficient of performance (COP), implies the comparative operating cost after retrofit. These data are provided herein along with representative properties for seven retrofit refrigerant options, namely R-407C, R-410A, R-421A, R-422B, R-422D, R-427A, and R-438A along with reference data for R-22. RETROFIT REFRIGERANT OPTIONS The refrigerants addressed herein include: R-22 [chlorodifluoromethane, CHClF 2 ] as the primary reference for comparisons and normalizing data R-407C [R-32/125/134a (23.0/25.0/52.0)], marketed under various trade names including as DuPont Suva AC9000 R-410A [R-32/125 (50.0/50.0)], marketed under various trade names including as Honeywell Genetron AZ-20 Copyright 2013 James M. Calm, Engineering Consultant, USA all rights reserved except as granted by written consent. This report is proprietary; it was prepared pursuant to the scope and subject to the limitations, terms, and conditions of a consulting agreement with RMS of Georgia, LLC. No further reproduction or use by other parties is allowed without explicit written consent from James M. Calm, Engineering Consultant, USA. - 1-2013 James M. Calm, Engineering Consultant, USA

R-421A [R-125/134a (58.0/42.0)], marketed under various trade names including as RMS Choice R-421A R-422B [R-125/134a/600a (55.0/42.0/3.0)], marketed under various trade names including as ICOR NU-422B R-422D [R-125/134a/600a (65.1/31.5/3.4)], marketed under various trade names including as DuPont Isceon MO29 R-427A [R-32/125/143a/134a (15.0/25.0/10.0/50.0)], marketed under various trade names including as Arkema Forane FX 100 R-438A [R-32/125/134a/600/601a (8.5/45.0/44.2/1.7/0.6)], marketed under various trade names including as DuPont Isceon MO99 * The R- number designations are standard identifiers as assigned in and according to ASH- RAE standard 34. 1 No inference is intended that the seven cited refrigerant blends are the only retrofit options to replace R-22, rather they are the primary competitors in markets in which R-421A is offered. RMS of Georgia, LLC, markets R-421A as Choice Refrigerant R-421A, a non-ozonedepleting alternative for R-22 for use in air-conditioning as well as medium- and hightemperature residential, commercial, and industrial refrigeration applications. R-421A is a binary zeotrope formulated as 58.0 ±1.0% R-125 and 42.0 ±1.0% R-134a by mass R- 125/134a (58.0/42.0) (±1.0/±1.0). The blend molar mass is 111.746487 g/mol (0.24635883 lb/mol) and the component mole fractions are 54.001 and 45.999 %, respectively. Both components are hydrofluorocarbons (HFCs). The blend has low acute toxicity and ASHRAE Standard 34-2013 classifies it as an A1 refrigerant, signifying lower toxicity and no flame propagation for prescribed safety criteria. 1 PRESSURE-TEMPERATURE COMPARISONS Table 1 and Table 2, in metric (SI) and inch-pound (IP) units of measure, respectively, compare the pressure-temperature (PT) relationships for coexisting vapor and liquid of the selected refrigerants. Similar PT relationships indicate a basic level of operational comparability including for thermostatic expansion valve (TXV) sensing bulbs that regulate refrigerant flow. PT similarity also implies that internal (inside the refrigerant circuit) low- and high-side (evaporator and condenser) pressures are similar for the compared refrigerants operating between the same evaporating and condensing temperatures. * Forane; Genetron; MO29, MO99, and Suva; and NU-422B are trademarks or registered trademarks of Arkema, Honeywell, DuPont, and ICOR, respectively. - 2-2013 James M. Calm, Engineering Consultant, USA

Table 1: Pressure-Temperature Data for Selected Refrigerants (SI units) temperature pressure of vapor coexisting with liquid at the bubble temperature (kpa) ( C) ( F) R-22 R-407C R-410A R-421A R-422B R-422D R-427A R-438A -40-40 105 120 176 105 108 118 116 113-35 -31 132 151 219 131 135 147 146 142-30 -22 164 187 270 163 167 182 181 176-25 -13 201 230 331 201 205 223 222 216-20 -4 245 280 401 245 250 270 270 263-15 5 296 338 482 296 301 326 326 318-10 14 355 405 575 355 360 389 390 380-5 23 422 481 681 422 428 461 463 452 0 32 498 568 801 499 505 543 546 534 5 41 584 666 936 585 592 636 641 626 10 50 681 776 1088 683 689 740 746 729 15 59 789 900 1258 792 799 856 865 845 20 68 910 1038 1448 914 920 985 997 974 25 77 1044 1190 1657 1049 1056 1128 1143 1117 30 86 1192 1359 1889 1199 1205 1286 1305 1275 35 95 1355 1545 2145 1364 1370 1460 1483 1449 40 104 1534 1749 2426 1545 1550 1651 1678 1640 45 113 1729 1972 2734 1744 1749 1860 1892 1850 50 122 1943 2216 3071 1961 1965 2089 2125 2078 55 131 2175 2481 3439 2198 2201 2338 2379 2326 60 140 2428 2769 3842 2456 2458 2609 2656 2596-3 - 2013 James M. Calm, Engineering Consultant, USA

Table 2: Pressure-Temperature Data for Selected Refrigerants (IP units) temperature pressure of vapor coexisting with liquid at the bubble temperature (psig) ( F) ( C) R-22 R-407C R-410A R-421A R-422B R-422D R-427A R-438A -40-40.0 0.6 2.7 10.8 0.5 0.9 2.4 2.2 1.7-30 -34.4 4.9 7.7 17.8 4.8 5.4 7.1 7.0 6.4-20 -28.9 10.2 13.7 26.3 10.1 10.7 12.9 12.8 12.0-10 -23.3 16.5 20.9 36.5 16.5 17.1 19.8 19.7 18.8 0-17.8 24.0 29.5 48.4 24.0 24.7 27.9 27.9 26.8 10-12.2 32.8 39.5 62.4 32.8 33.6 37.5 37.6 36.3 20-6.7 43.1 51.2 78.7 43.1 43.9 48.5 48.8 47.3 30-1.1 55.0 64.7 97.4 55.0 55.9 61.3 61.7 59.9 40 4.4 68.6 80.2 118.8 68.7 69.6 75.9 76.6 74.5 50 10.0 84.1 97.9 143.2 84.3 85.3 92.6 93.6 91.1 60 15.6 101.6 117.9 170.7 102.0 103.0 111.4 112.8 109.8 70 21.1 121.4 140.5 201.8 122.0 123.0 132.6 134.4 131.0 80 26.7 143.6 165.8 236.5 144.4 145.4 156.3 158.6 154.7 90 32.2 168.4 194.1 275.4 169.5 170.4 182.8 185.7 181.2 100 37.8 195.9 225.5 318.5 197.4 198.2 212.2 215.8 210.6 110 43.3 226.4 260.3 366.4 228.3 229.0 244.7 249.1 243.1 120 48.9 260.0 298.6 419.4 262.4 263.1 280.7 285.8 279.1 130 54.4 296.9 340.7 477.9 300.1 300.6 320.2 326.2 318.5 140 60.0 337.4 386.9 542.5 341.5 341.8 363.7 370.4 361.9 150 65.6 381.7 437.5 613.9 386.9 387.1 411.4 418.9 409.2-4 - 2013 James M. Calm, Engineering Consultant, USA

The PT comparisons are summarized in Figure 1. 4000 temperature ( F) -40 0 40 80 120 R-407C R-410A 500 pressure (kpa) 3000 2000 R-427A R-422D R-438A 400 300 200 pressure (psia) 1000 R-422B R-421A R-22 100 0-40 -20 0 20 40 60 temperature ( C) 0 Figure 1: Pressure-Temperature Comparison - 5-2013 James M. Calm, Engineering Consultant, USA

Examination of the PT data in the preceding figure and tables show remarkable similarity between R-22 and R-421A, further indicated by the very small pressure differences shown in Table 3 (SI) and Table 4 (IP) below: Table 3: Pressure-Temperature Similarity for R-22 and R-421A (SI units) pressure (kpa) temperature ( C) R-22 R-421A difference (%) -40 105 105-0.60% -35 132 131-0.47% -30 164 163-0.35% -25 201 201-0.25% -20 245 245-0.16% -15 296 296-0.08% -10 355 355 0.00% -5 422 422 0.07% 0 498 499 0.14% 5 584 585 0.21% 10 681 683 0.27% 15 789 792 0.34% 20 910 914 0.41% 25 1044 1049 0.48% 30 1192 1199 0.56% 35 1355 1363 0.64% 40 1534 1545 0.73% 45 1729 1743 0.83% 50 1943 1961 0.93% 55 2175 2198 1.04% 60 2427 2456 1.16% 65 2701 2736 1.29% - 6-2013 James M. Calm, Engineering Consultant, USA

Table 4: Pressure-Temperature Similarity for R-22 and R-421A (IP units) pressure (psig) temperature ( F) R-22 R-421A difference (%) -40 0.6 0.5-16.08% -30 4.9 4.8-1.81% -20 10.2 10.1-0.81% -10 16.5 16.5-0.42% 0 24.0 24.0-0.20% 10 32.8 32.8-0.05% 20 43.1 43.1 0.06% 30 55.0 55.0 0.16% 40 68.6 68.7 0.24% 50 84.1 84.3 0.32% 60 101.6 102.0 0.40% 70 121.4 122.0 0.48% 80 143.6 144.4 0.56% 90 168.4 169.5 0.65% 100 195.9 197.4 0.74% 110 226.4 228.3 0.84% 120 260.0 262.4 0.95% 130 296.9 300.1 1.08% 140 337.4 341.5 1.21% 150 381.7 386.9 1.35% The reason the difference values appear slightly lower in Table 3 (metric units, SI) than in Table 4 (inch-pound units, IP), for example at 60 C and 140 F that are equivalent, is the SI pressures indicated are absolute and the IP are gauge, consistent with common convention for the respective units. When consistently expressed in either absolute or gauge pressures, the difference values are the same. The important conclusion is that the saturation pressure-temperature dependence for R-421A is nearly identical to R-22 with less than 1% difference for most of the temperature range of interest, as shown in the figure and tables above. - 7-2013 James M. Calm, Engineering Consultant, USA

PERFORMANCE COMPARISONS The following discussion addresses comparative R-421A performance relative to R-22 based on ideal cycle analyses, using the National Institute of Standards and Technology (NIST) Cycle_D program, for conditions consistent with those used and discussed in prior studies by Calm and Domanski. 2,3 Theoretical cycle analyses for ideal conditions indicate the limits or comparative limits to attainable performance for simple cycles without regard to differences in equipment and component deviations from ideal, heat transfer, additional thermophysical properties, and lubricant differences. The resulting coefficients of performance (COPs) indicate thermodynamic limits to what is attainable for different refrigerants in comparably optimized systems, but do not imply either that all systems will achieve such performance or that performance rankings of different refrigerants would not change in order of preference for systems not comparably optimized for the individual refrigerants. 3,4 Although excluded from the analyses herein to focus on refrigerant influences, real-world equipment performance properties will be lower than theoretical limits not only for the reasons mentioned, but also because fan, control, and sometimes pump burdens as well as start-up transients factor into standard equipment ratings. Table 5 summarizes the cycle conditions used for the analyses addressed herein. Table 5: Conditions for Performance Comparison theoretical cycle limit parameter for air conditioning average evaporating temperature input temperature 10 C (50 F) superheat 0 C (0 F) more rigorously expressed as 0 K (0 F) average condensing temperature input temperature 35-65 C (95-149 F) superheat 0 K, 0 C (0 F) compressor efficiencies isentropic 100% volumetric 100% motor 100% piping losses (drop) suction line none: 0 K, 0 C (0 F) discharge line none: 0 K, 0 C (0 F) suction line / liquid line heat exchanger none (0%) fans and control power burdens indoor fan / chilled water pump not included (0 W) outdoor fan / condensing water pump not included (0 W) controls not included (0 W) - 8-2013 James M. Calm, Engineering Consultant, USA

The following figure compares the COPs for cooling (air conditioning) for a range of refrigerant condensing temperatures (necessarily higher than a corresponding range of ambient temperatures for air-cooled equipment). The range shown reaches extreme temperatures, at which the R-125 component of R-421A approaches its critical point temperature and reduces the accuracy of modeling. 10 average condensing temperature ( F) 95 105 115 125 135 145 8 cooling COP 6 4 top to bottom: R-22 R-407C R-427A R-438A R-421A R-422B R-410A R-422D R-421A R-22 2 0 35 40 45 50 55 60 65 average condensing temperature ( C) Figure 2: Cooling Coefficient of Performance (COP) Comparison without Adjustment for Pressure-Temperature Differences As shown, the R-421A efficiency is approximately 4.8% lower at 35 C (95 F), the most common comparative rating point for air conditioners. While real equipment (including equipment and deviations from ideal and burdens such as fan power) would not approach the theoretical limits indicated, the limits are a good indicator of relative performance with variations by temperature and for refrigerants with adjusted charge amounts and expansion device flow metering. - 9-2013 James M. Calm, Engineering Consultant, USA

Figure 3 depicts the comparative cooling efficiency of R-421A at increasing condensing temperatures relative to that of R-22 for cycles each optimized for equivalent performance at standard rating conditions (35 C, 95 F), but again excluding control, fan power, and similar power burdens. 5 average condensing temperature ( F) 95 105 115 125 135 145 0 COP loss relative to R-22 in new equipment (%) R-407C R-438A R-427A -5-10 R-421A R-422B R-410A R-422D -15 35 40 45 50 55 60 65 average condensing temperature ( C) Figure 3: Relative COP Degradation with Increasing Condensing Temperature for Equipment Designed for Equivalent Performance at the Nominal Rating Point (35 C, 95 F) without Adjustment for Pressure-Temperature Differences REPRESENTATIVE PROPERTIES Without further consideration of temperature glide, R-421A offers neither the highest nor lowest cooling efficiency based on theoretical limits compared to R-22, but affords simpler retrofit based on the PT similarities addressed above. Refrigerant blends with higher temperature glide, such as R-407C that also offers good PT similarity to R-22, are subject to higher blend fractionation in typical evaporators. That effect reduces or eliminates theoretical performance advantages without equipment modification to maintain operating blend composition. Likewise, blends with higher latent heat by mass (or more accurately by volume for positive-displacement compressors, such as rotary, scroll, or reciprocating-piston compres- - 10-2013 James M. Calm, Engineering Consultant, USA

sors) require equipment optimization (new designs) to exploit such differences, but with appropriate equipment design offer capacity more similar to or even better than R-22. Reduced capacity below design conditions translates to increased equipment run time and lower cooling output at and above such conditions (particularly at extreme condensing temperatures). Table 6 compares representative properties of R-22 and R-421A based on data calculations using NIST REFPROP 9.1. 6 As shown, the three refrigerants offering slightly higher theoretical COP all exhibit notably higher glide than R-421A. The table also summarizes key indicators for environmental and safety considerations. As shown, R-438A has a lower Refrigerant Concentration Limit (RCL) approximately a third that of R-22 potentially requiring other building or system modifications in refrigerant retrofits. Table 6: Data for Selected Refrigerants (SI units) properties R-22 R-407C R-410A R-421A R-422B R-422D R-427A R-438A molar mass (g/mol) 86.468000 86.203637 72.585414 111.746487 108.518417 109.935124 90.444001 99.100017 normal boiling point (NBP).bubble point for blends ( C) -40.81-43.63-51.44-40.68-41.31-43.20-42.96-42.33 blend dew point ( C) -40.81-36.63-51.36-35.36-35.89-38.34-36.20-36.14 maximum temperature glide at NBP (K) 0.000 6.998 0.079 5.316 5.427 4.860 6.758 6.189 at 20 C (K) 0.000 5.592 0.116 3.657 3.464 2.985 5.179 4.781 density at NBP saturated liquid (kg/m 3 ) 1409 1381 1350 1461 1398 1402 1369 1391 saturated vapor (kg/m 3 ) 4.704 4.631 4.174 5.976 5.818 5.956 4.854 5.316 latent heat of vaporization at NBP (kj/kg) 233.8 249.1 273.0 191.8 195.7 190.0 236.5 215.7 at NBP (kj/m 3 ) vapor 1100 1153 1139 1146 1139 1132 1148 1147 at 60 C (kj/kg) 139.9 130.8 105.1 96.4 97.1 88.2 123.2 109.9 saturated vapor pressure at 20 C (kpa) 910 880 1443 821 832 904 856 847 at 60 C (kpa) 2427 2529 3834 2333 2346 2512 2447 2411 critical point temperature ( C) 96.15 86.03 71.34 82.78 83.21 79.57 85.32 85.27 pressure (kpa) 4990 4629 4901 3919 3958 3905 4392 4304 specific volume (L/kg) 1.909 2.065 2.178 1.818 1.900 1.890 2.041 1.959 ozone depletion potential (ODP) relative to R-11 scientific 0.040 0 0 0 0 0 0 0 regulatory (MP) 0.055 global warming potential (GWP) for 100 yr ITH scientific relative to CO 2 1790 1700 2100 2600 2500 2700 2100 2200 ASHRAE 34 / ISO 817 safety classification A1 A1 A1 A1 A1 A1 A1 A1 ASHRAE 34 Refrigerant Concentration Limit (RCL) (ppm v/v ) 59,000 81,000 140,000 61,000 56,000 58,000 79,000 20,000-11 - 2013 James M. Calm, Engineering Consultant, USA

Table 7: Data for Selected Refrigerants (IP units) properties R-22 R-407C R-410A R-421A R-422B R-422D R-427A R-438A molar mass (lb/mol) 0.190629 0.190046 0.160023 0.246359 0.239242 0.242365 0.199395 0.218478 normal boiling point (NBP).bubble point for blends ( F) -41.46-46.53-60.60-41.22-42.36-45.76-45.33-44.19 blend dew point ( F) -41.46-33.93-60.46-31.65-32.59-37.01-33.16-33.05 maximum temperature glide at NBP ( F) 0.000 12.597 0.142 9.569 9.769 8.747 12.164 11.140 at 68 F ( F) 0.000 10.065 0.209 6.582 6.234 5.373 9.323 8.605 density at NBP saturated liquid (lb/ft 3 ) 87.97 86.19 84.26 91.19 87.25 87.51 85.46 86.84 saturated vapor (lb/ft 3 ) 0.2936 0.2891 0.2606 0.3731 0.3632 0.3718 0.3030 0.3319 latent heat of vaporization at NBP (Btu/lb) 100.6 107.2 117.4 82.5 84.2 81.8 101.8 92.8 at NBP (Btu/ft 3 ) vapor 29.53 30.98 30.60 30.78 30.58 30.40 30.83 30.80 at 140 C (Btu/lb) 60.20 56.29 45.23 41.48 41.78 37.94 53.00 47.28 saturated vapor pressure at 68 F (psia) 132.0 127.7 209.3 119.0 120.7 131.1 124.2 122.8 at 140 F (psia) 352.1 366.8 556.1 338.3 340.3 364.3 355.0 349.7 critical point temperature ( F) 205.1 186.9 160.4 181.0 181.8 175.2 185.6 185.5 pressure (psia) 723.7 671.4 710.9 568.4 574.0 566.3 637.0 624.3 specific volume (ft 3 /lb) 0.0306 0.0331 0.0349 0.0291 0.0304 0.0303 0.0327 0.0314 ozone depletion potential (ODP) relative to R-11 scientific 0.04 0 0 0 0 0 0 0 regulatory (MP) 0.055 global warming potential (GWP) for 100 yr ITH scientific relative to CO 2 1790 1700 2100 2600 2500 2700 2100 2200 ASHRAE 34 / ISO 817 safety classification A1 A1 A1 A1 A1 A1 A1 A1 ASHRAE 34 Refrigerant Concentration Limit (RCL) (lb/mcf) 13 18 26 17 16 16 18 4.9 The grey regions of Table 6 and Table 7 indicate inapplicable data, namely the absence of composition-based glide based for the single-compound R-22. They also signify inapplicable data for blends not directly regulated by ozone depletion potential (ODP) in international treaties (notably the Montreal Protocol) and most regulations, though regulatory consequences result indirectly based on mass-weighted formulations of the blends. - 12-2013 James M. Calm, Engineering Consultant, USA

REFERENCES 1 Designation and Safety Classification of Refrigerants, ANSI/ASHRAE Standard 34-2013, American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), Atlanta, GA, USA, 2013 2 P. A. Domanski, D. A. Didion, and J. S. W. Chi, CYCLE_D: NIST Vapor-Compression Design Program (version 5.0), Standard Reference Database 49, National Institute of Standards and Technology (NIST), Gaithersburg, MD, USA, 2011.10.20 (and updates thereto) 3 J. M. Calm and P. A. Domanski, R-22 Replacement Status, ASHRAE Journal, 46(8):29-39, August 2004; erratum, 46(10):8, 2004.10 4 J. M. Calm and D. A. Didion, Trade-Offs in Refrigerant Selections: Past, Present, and Future, Refrigerants for the 21st Century (proceedings of the ASHRAE/NIST Refrigerants Conference, Gaithersburg, MD, 1997.10.06-07), 6-19, American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE), Atlanta, GA, USA, 1997 5 Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment, ARI Standard 210-240-2008, Air-Conditioning and Refrigeration Institute (ARI) now the Air-Conditioning, Heating, and Refrigeration Institute (AHRI), Arlington, VA, USA, 2008 6 E. W. Lemmon, M. L. Huber, and M. O. McLinden, NIST Reference Fluid Thermodynamic and Transport Properties REFPROP," Standard Reference Database (SRD) 23 version 9.1, National Institute of Standards and Technology (NIST), Gaithersburg, MD, USA, 2013.05 (and updates thereto) - 13-2013 James M. Calm, Engineering Consultant, USA

blank page - 14-2013 James M. Calm, Engineering Consultant, USA