New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

Similar documents
Energy Impacts of Various Residential Mechanical Ventilation Strategies

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Ventilation in Humid Climates: Data from Field Experiments

Energy Consumption Data Analysis Phase II Final Report

Why Thermostats Matter

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

Flexible Roofing Facility: 2004 Summer Test Results

Electronic Refrigerant Leak Detector DE-FG36-98G Micronic, Inc. Elie Talamas, Jr. Period: 10/1/99 to 12/31/99

Dehumidification at Part Load

Optimizing Energy Efficiency and Improved Dehumidification Performance of Variable Capacity Air Conditioning Systems

A Cost Effective Multi-Spectral Scanner for Natural Gas Detection

Relative Humidity in Schools Jim Cummings and Chuck Withers

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

FINAL ABSTRACT. CRADA TITLE. Miniature Transducers for Flight Test Unit Instrumentation - Magnetic Field Detector CRADA NUMBER: LA98C10367.

Equipment Specifications and Required Information Quantity Rebate

Application of Air Source Variable Refrigerant Flow in Cold Climates

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

NATURAL CONVECTION HEAT EXCHANGERS FOR SOLAR WATER HEATING SYSTEMS. Technical Progress Report April 1,1995 to May 31,1995

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

ENERGY SYSTEMS LABORATORY

Evaporative Cooling in a Hot-Dry Climate

TESTS OF ADSIL COATING

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

Final Report. Investigation of Energy Impacts of Ducted Dehumidifier Duct Configurations and Location. DBPR Project #B21551 UCF/FSEC #

RESNET HERS Rater Sample Test Questions 2

A FIRST RESPONDERS GUIDE TO PURCHASING RADIATION PAGERS

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Displacement Ventilation in Classrooms

Neil A. Moyer James B. Cummings David Chasar Principal Research Engineer Program Manager Research Engineer

Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles

2019 Smart Energy Existing Homes Program Manual

From Energy Guzzler to Near-Zero Energy Home: Lessons from the Phased Deep Retrofit Project

Are Residential Whole-House Mechanical Ventilation Systems Reliable Enough to Mandate Tight Homes?

p?:uam SYSTEMS Technical Progress Report Jane H. Davidson NAllJRAL CONVECTION HEAT EXCHANGERS FOR SOLAR WATER HEATING February 1,1996 to March 31,1996

Model 5190-F Temperature/Humidity Probe

Systems Engineering Approach to Development of Advanced Residential Buildings

Food Service Technology Center

Builder s Technical Sessions. Attic Ventilation. Presented by: Rob Kaethler. Presented in Partnership with: Insert your logo here

Unvented Roof Assemblies for All Climates by Chris Schumacher

An Assessment of Building Energy Efficiency Options at Horn Island Ranger Station, Gulf Islands National Seashore

Calculated Energy Savings for Disabling Anti- Sweat Door Heat on Glass Display Case Doors

Basic Building Science insights for Spray Foam, HVAC and Moisture

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

Closing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner

Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate

Model 5190-E Temperature/Humidity Probe

F Prepared by: Kong Sham. Prepared for: PO Box Technology Center

Heat Pump Water Heaters: A Key Energy Technology for California

Title Page. Report Title: Downhole Power Generation and Wireless Communications. for Intelligent Completions Applications

ASHRAE JOURNAL ON REHEAT

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

SN5446A, 47A, 48, SN54LS47, LS48, LS49 SN7446A, 47A, 48, SN74LS47, LS48, LS49 BCD-TO-SEVEN-SEGMENT DECODERS/DRIVERS

Unvented Roof Summary Article

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

W. T. Roybal J. T. Bradley III D. E. Rees P. Torrez D. K. Warner J. Debaca. LINAC 2000 Monterey, CA August ,2000

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

EnergyGauge USA Release Notes

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Appendix A. Glossary of Common Terms

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

HVAC Design Industrial Ventilation

STER 1981 ANNUAL INDUSTRIAL SUMMARY OF FIRE AND PROPERTY DAMAGE EXPERIENCE. Monsanto. MOUND FACILITY Miemisburg. Ohio MLM.ML

Performance of Solar Water Heating Systems in the United States

Building and Remodeling to Save Energy 1

Managing HVAC in High Performance Buildings

FSEC-CR Final Report September Authors. Charles Withers Jr. James Cummings Bereket Nigusse

Build your own SOLAR FURNACE

ENERGY STAR V2.5 & 3 Designed to Qualify AIA Annual Convention

NightCool: A Nocturnal

Air Conditioning Clinic

Task Force. Rewarming Supercold Grain. Dirk E. Maier, Agricultural Engineering

The Use Of Attic Space For Cooling and Dehumidification

What is Energy Star?

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Report on the Suitability of Class 6, U.S. Government Security Repositories for the Storage of Small Quantities of High Explosives

2018 Smart Energy Existing Homes Program Manual

MAKING IT GREEN AND SAVING ENERGY WITH NSP

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

AVIATION TECHNOLOGY SERVICES: PIPELINE LEAK DETECTION

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Air-Conditioning Buying Guide

Southern California Gas Company Customer Programs Department

FAN WALL Technology. Product

Air Distribution Systems in Conditioned Spaces i.e. Ducts in Unvented Attics

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

EXHIBIT 1. Washington Home Energy Savings

Brine Generation Study

PHASE II Analytical Assessment of Field Data for Sealed Attics in Florida Climate Zones 1 and 2 Predicting Moisture Buildup in Roof Sheathing

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

SolarSheat Solar Heating and Ventilation. Todd Kirkpatrick-President Your Solar Home Inc. Vaughan, Ontario, Canada

REQUIRED CONTRACT DETAIL. $2, , Direct DC Fuel Cell Power System, Stationary PACE Power output < 40 kw

SAFETY AND INSTALLATION MANUAL MODEL 8100

The Unplanned Impacts On Houses By Powered Attic Ventilators

Nest Learning Thermostat Summer 2012 Savings

Transcription:

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review FSEC-PF-454-11 May 2011 Author Carlos Colon Copyright 2011 Florida Solar Energy Center/University of Central Florida All Rights Reserved.

Disclaimer The Florida Solar Energy Center/University of Central Florida nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the Florida Solar Energy Center/University of Central Florida or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the Florida Solar Energy Center/University of Central Florida or any agency thereof.

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review Monitored Prototypes - Springwater Homes In 2010, the Florida Solar Energy Center (FSEC), with funding from the Building America program, was involved with a new Builders Challenge builder located in Rockledge, Florida -- Springwater Homes (see Figure 1). The home was constructed in March 2010 and features a sealed attic with R-27 open cell sprayed foam roof deck insulation (shown in Figure 2). Selection of the HVAC system, an important aspect to achieve high efficiency levels in buildings, ended with one of the highest residential equipment systems available in the U.S. the Nutone IQ Drive (SEER 21). The house was confirmed with a HERS index of 53 using the EnergyGauge simulation program. By April 2010, FSEC researchers had installed a variety of sensors and a data logger to investigate the power consumption of the mechanical HVAC equipment and, most importantly, the humidity characteristics inside the sealed attic. Figure 1: Builder s Challenge home (2127 Sq. Ft.) construction with conventional hip roof and shingles in Rockledge, FL. Figure 2: Roof deck insulation (R-27) featured on Builders Challenge Home in Rockledge, FL Instrumentation and Measurements A data logger at the site collected power measurements of the total building, power consumption of the high efficiency 3-ton (SEER 21) HVAC equipment and water heating energy consumption. The house was also equipped with a solar water heater; however no representative data was gathered since the house remains a model home. In April 2010, FSEC completed installation of instrumentation wiring and sensors for temperature and relative humidity (RH) measurements in the conditioned space, attic and outdoors. The attic temperatures and RH sensors were positioned in the attic at mid and peak levels, as shown in Figure 3. 1 Figure 3: RH and temperatures were measured at peak and mid levels within the sealed attic.

The home is also outfitted with a Honeywell outside air damper control to provide fresh air intake. Instructions provided with this device recommend an outside air intake of 80 cfm for a 2,200 ft 2 home. The unit was setup as recommended by the manufacturer s instructions. After setup, measurements were made by FSEC researchers to determine the outside airflow intake. Results of the outside fresh air intake can be seen in the table at right. High Efficiency Air Conditioner (SEER 21) Electricity Use Fan speed Medium High Outside fresh air intake 52 cfm 72 cfm HVAC electricity used at the Builders Challenge home site, although it does not represent a typical family use pattern, was kept at a comfortable 73 F during the monitoring period (summer included). Average daily electricity consumption for the HVAC system can be observed in Figure 4. The months of June and July measured a daily electric consumption slightly above 15 kwh/day. The indoor air handler unit during cooling months (May-Oct 2010) represents 28% of the total air conditioner power consumption on average. Figure 4 Average Daily electric consumption by month for the SEER 21 air conditioner on a 2,127 sq, ft. model home in Rockledge, FL. At the end of September 2010, data also showed the standby power consumption characteristic of this unit. Surprisingly, the outdoor condenser and indoor air handler unit draws about 50 and 28 watts respectively (78 watt combined) when on standby. Interior and Sealed Attic Conditions Interior Conditions Indoor temperature and relative (RH) humidity sensors were installed above (and offset) to the IQ drive thermostat on a hallway wall of the house to measure comfort levels. During the initial months of data collection, analysis revealed that the high efficiency air conditioner kept interior temperatures at a comfortable average of 73 F with relative humidity (RH) levels below 58% on 2

average. The trend of relative humidity throughout the following months is shown in Figure 5 along with the interior temperatures. The relative humidity trend indicates that the HVAC equipment slowly brings interior conditions of the new constructed house slowly towards the target of 50%. High humidity content is typically found in new construction due to moisture in building materials. Furthermore, the Manual on Moisture Analysis in Buildings states that a newly constructed house can release an estimated 5,730 lb of water from concrete foundation and construction lumber. Thus, moisture from construction materials can be a serious source of humidity in the first year and second year. Figure 5: Average monthly interior temperatures and progressive downward trend of relative humidity. Sealed Attic Conditions In Florida, as recommended by code, it may be standard practice to apply a vapor barrier underlayment on a shingle roof constructed with sealed attic. Averaged hourly data collected during May 2010 clearly indicates high relative humidity measurements appearing at 4:00 PM at the peak of the attic. This measurement is being taken at 6 inches below the sprayed roof deck insulation. Relative humidity levels reached as high as 83% in May 2010 and 78.3% during April 2011 as indicated from 15-minute data interval. The relative humidity levels almost seem inversely proportional with respect to the outdoors, as shown in Figure 6. 3

Figure 6: Sealed attic (peak) and outdoor relative humidity averaged daily by hour for May 2010. Initially, during May 2010, humidity levels in the attic appeared high, but consecutive months showed a steady downward trend in magnitude, as seen on the top plot in Figure 7, for the first eight months ending on December 2010. However the latest data analysis clearly shows a reverse trend with increasing relative humidity levels beginning in January of 2011 (Figure 7, bottom plot). Relative humidity levels in the attic during April 2011 appear to exceed those high levels measured almost a year before during May 2010. These monthly averaged measurements of relative humidity conditions have prompted further investigation of the humidity in this particular sealed attic configuration. Relative humidity and attic temperature measurements were used to calculate the amount of moisture content in the air, also known as humidity ratio (W). Figure 7: Monthly trend of relative humidity levels in sealed attics for 2010 and 2011. 4

The humidity ratio (W), as defined in the ASHRAE handbook of fundamentals, is the ratio of the mass water vapor to the mass of dry air. The humidity ratio is expressed as pounds of moisture per pound of dry air in the British (IP) system. Analysis of sealed attic humidity content may be easier to analyze by looking at the calculated W values of the sealed attic air and adjacent air spaces. In this manner, the source of moisture can be easier to identify on a 24-hour day period, for example. Figure 8 shows the calculated moisture content (W) found in the attic plotted along with the W ratios found for outdoor air on April 1, 2011. Air temperature measured at the sealed attic peak level is also shown in degrees Fahrenheit (F). The temperature data is helpful to identify trends of moisture. As indicated previously, this model home does not have the typical moisture generation of an occupied residence (i.e., showers, cooking, occupants). The plot on Figure 8 may indicate that a year after the home was built, wood truss components exposed in the sealed attic are prone to sorption and desorption trends throughout the day. Figure 8: Humidity content plot for sealed attic and outside air on April 1, 2011. Furthermore, the same plot was enhanced to examine humidity content in the sealed attic at midlevel (Figure 9). Data points representing indoor relative humidity conditions are also shown to represent interior conditions. Although the air conditioner did not operate until late afternoon this day, relative humidity in the conditioned space did not vary much from 50% throughout the day. The interior temperature that day (April 1, 2011) was kept by the air conditioner at or below 73.1 F, and relative humidity reached 52.7% at its highest. A small reduction in moisture content can be seen due to the operation of the variable speed HVAC unit between 4:45 PM and 6:00 PM. 5

Lessons Learned Figure 9: Enhanced plot showing humidity content at two levels in attic and temperatures along with interior home conditions The moisture content absorbed (sorption) and moisture released (desorption) by the pine trusses appears to explain the time-varying moisture content in the sealed attic. Pine trusses in this particular sealed attic configuration undergo the sorption process during cooler attic temperatures and desorption at higher attic temperatures. This indicates that changes in temperature in a sealed attic with the substantial mass of pine wood can be considered the driving force for humidity content in the unvented space. As a reference to demonstrate the dynamic amount of moisture content in pine wood, properties for pine published by the IEA in Canada reported during a sorption test (68 F [20 C]), the moisture content in pine at relative humidity levels of 43.5% is 0.094 kg/kg. 1 Also during sorption under the same 68 F temperature conditions and relative humidity of 85.8%, the moisture content of pine is 0.177 kg/kg. This data indicates the ability of pine wood to act as a variable moisture storage medium. At this point, it is unknown whether the high levels of moisture will have a degrading effect on the longevity of roof materials. The fact that peak humidity content is detectable and that it reverses on a daily cycle could mean that humidity may not fully transfer through the open-cell sprayed insulation core. Placement of the RH sensor itself may be leading to false indication of high peak humidity levels. Another sensor positioned away from the wood truss may be needed to verify RH levels at the peak attic space. The overall concern here is that moisture or water content in this sealed attic configuration may not leave the attic envelope as quickly as in standard vented attics. More analysis is underway to investigate the moisture content in this particular sealed attic. More investigation is also needed 1 M, Kumar Kumaran, Heat Air and Moisture Transfer in Insulated Envelope Parts, Final Report Volume 3, Task 3: Materials Properties, International Energy Agency (IEA). 6

to verify conditions in sealed attics where the sorption and desorption point process is reversed. Data for this particular site is collected, reported and archived on a daily basis at FSEC s Infomonitors website. (http://infomonitors.com/spw/). 7