PRODUCT DATA VPL 28 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

Similar documents
PRODUCT DATA VPL 15 TOP M2 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

PRODUCT DATA VP 18 BY NILAN. Sanitary hot water production. Heating. Active heat recovery. Comfort heating. Ventilation < 300 m 3 /h.

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMPACT S BY NILAN. Sanitary hot water production. Passive heat recovery. Comfort heating. Ventilation < 375 m 3 /h. Active heat recovery

PRODUCT DATA COMFORT 302 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 345 m 3 /h

PRODUCT DATA NILAIR BY NILAN. Air distribution. Domestic. Ventilation

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

Comfortable indoor climate regardless of the season

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

VENTILATION = WELL-BEING

Technical specifications

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

Air handling unit. REC Temovex 400S-EC-RS. Experts on indoor climate in low-energy houses

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

PRODUCT DATA COMPACT P RANGE BY NILAN. Heating. Sanitary hot water production. Ventilation < 300 m 3 /h. Passive heat recovery.

AIR HANDLING UNITS RIS P EKO 3.0. New range - 5 sizes, 20 models! Efficient EC. E f f i c i e n c y up to 94%! E x t r e m e l y low height! fans!

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

VERSO DOMEKT. Residential ventilation units m³/h. Non residential ventilation units m³/h

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

Installation Instruction

Installation instruction

USER MANUAL CTS700 TOUCH BY NILAN. Compact P / Compact P Polar (English)

TSEK VHR EC HEAT RECOVERY UNITS

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Installation instruction

VEX100 series Air handling units with cross-flow heat exchanger

Heat Recovery ventilation Dee Fly Cube 550 Field of application Description Advantages Range Technical details Installation Remote controls Servicing

Installation instruction

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

User's Guide. CTS6000 control panel

Technical Information HXV - HRV Ventilation

FLOWAY. Floway Range. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution. use.

MAXI CENTRALIZED VENTILATION WITH HEAT RECOVERY

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

Operation and maintenance instructions

GLOBAL LP. Ceiling-mounted ventilation unit with plate heat exchanger

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

InspirAIR Home RESIDENTIAL AIR PURIFICATION

Ventilation in balance

THE ROAD TO A HEALTHY INDOOR CLIMATE

DVU-HP. Integrated Reversible Heat Pump System

VERSO Air Handling Units

VEX250H with rotary heat exchanger and EXact control system

EC L2. and humidity sensors. All units are supplied tested and ready to install.

Installation instruction

Endura Delta. Demand- and app-controlled ventilation system with heat recovery

CDP 40 SWIMMING POOL DEHUMIDIFIER

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

OVERVIEW and SYSTEM GUIDE. Swegon CASA. Residential ventilation for optimal operating economy and the greatest comfort.

Zehnder ComfoAir 550. Ventilation unit

RoofVent Design Handbook

Small Room Heat Recovery Ventilation

VERSO Air Handling Units

TopMaster Air Handling unit. Technical data

KOMFORT EC DB Suspended heat recovery air handling units

Flexit air handling units UNI 2, 3 og 4

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions)

VENTILATION WITH HEAT RECOVERY

Energy-efficient heat source provides comfort in large rooms

KOMFORT EC S5B KOMFORT EC D5B KOMFORT EC S. Heat and Energy Recovery Ventilators

CONTENT: VEX308 Decentralised ventilation VEX308

CDP 40T SWIMMING POOL DEHUMIDIFIER FEATURES

Flexit air handling units C2 and UNI 2, 3,4

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Leading edge reverse cycle air conditioning. Ducted and ceiling cassette

Heat recovery unit RDKS

MRXBOXAB-ECO4 100% and Opposite Handed version. Typical Installation

VEX280H with rotary heat exchanger and EXact control system

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

TopVent Design Handbook

RIS V EKO A1/L2 RIS 700 V E L EKO 3.0 AIR HANDLING UNITS. Application

TECHNICAL INFORMATION HCV 4 - HCV 5 - HCH 5 - HCH 8 Demand-controlled home ventilation

New rooftop series UATYQ-ABAY1 AFC2Y1 AFC3Y1. Extensive option package included in all models. ErP. years warranty. compliant 2018

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

MRXBOXAB-ECO3 MRXBOX-ECO3

MRXBOXAB-ECO2 MRXBOX-ECO2

Eco Active H E A T R E C O V E R Y S Y S T E M S. Heat Recovery Penthouse Turret. W: T:

The new Xcell EC High Efficiency Range Fresh air pure and simple

CLIMASTER ZCF AIR HANDLING UNITS

We simplify construction

DUCTED AIR CONDITIONER RANGE YOUR COMFORT ZONE.

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11

SOFTWARE MANUAL CTS700 TOUCH BY NILAN. Compact P / Compact P Polar GEO (English)

Suxess Compact Top HEALTHY INDOOR ENVIRONMENT WITH ENERGY EFFICIENT VENTILATION

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

EASYAIR COMPACT DEVICE THE EASY WAY OF AIR HANDLING.

for a considerable reduction of the supply air temperature which, in turn, reduces the air conditioning

AHU N : Range: VERSO VERSO. Heat Recovery Air Handling Units. Plug & Play Energy Saving Smart Design Reliable & Safe

Technical Information HCV - HCH Demand-controlled home ventilation

Ducted inverter reverse cycle air conditioning

Transcription:

PRODUCT DATA VPL 28 BY NILAN Ventilation & active heat recovery Domestic Active heat recovery Ventilation < 1000 m 3 /h Comfort heating Comfort cooling

VPL 28 Product description VPL 28 is an energy-efficient ventilation unit for heat recovery and cooling of homes and small commercial buildings with a ventilation requirement of up to 1000 m 3 /h. Heat recovery is via a heat pump that can utilise the recovered energy better than with e.g. a counterflow heat exchanger. The heat pump has a reversible cooling circuit, which means that the unit can both heat and cool the air. VPL 28 is supplied fully tested and ready for use. Fitting and commissioning must be carried out by an authorised electrician or plumber. VPL 28 is supplied with a closed cooling circuit. The unit can therefore be installed without the help of a cooling technician. The efficient fans run on low-energy EC motors. The cooling circuit is driven by a reliable reciprocating compressor. Intelligent humidity sensors provide an option for controlling the ventilation as required, based on the average air humidity in the home. A CO 2 sensor can be purchased as an accessory. Reversible cooling circuit, which means that the heat pump can heat and cool the supply air. The bypass valve regulate the intakes air temperature, maintaining it at a constant level. The powder-coated condensate drain prevents the formation of acid water and allows the condensate to be drained away. The option of the FU 28 heat pipe unit with heat pipe will significantly increase the unit efficiency. This can maintain a high intake air temperature without using a heating coil. Time-controlled alarm for filter exchange. G4 duct filter can be installed. By connecting of FU28 heat pipe unit a M5 and F7 filter can be installed. The alternative to an FU 15 heat pipe unit is the installation of an external water heater or electrical heating element (accessory). The unit comes with a clear and user-friendly operating panel. The modern CTS 602 control panel runs Modbus communication. 2

VPL 28 BY NILAN Technical specifications Dimensions (W x D x H) 700 x 570 x 765 mm Supply voltage 230 V (±10 %), 50/60 HZ Weight 65 kg Max. input/power 2139 W / 9.3 A Plate type casing Aluzinc steel plate, white powder coating RAL9016 Tightness class IP31 Compressor type Piston compressor Standby power 3 W Refrigerant Refrigerant filling Fan type Filter class Duct connections Condensate drain R407C 1,25 kg EC, constant volume G4 duct filter Ø250 mm PVC, Ø 20 1,5 mm Ambient temperature -20 / 40 C Dimensional drawing All dimensions are in mm. Connections 1: Fresh air 2: Supply air 3: Extract air 4: Discharge air 5: Condensate drain 3

FU 28 Product description An option is a FU 28 heat pipe unit with filter, which is connected to the VPL 28 unit. The heat pipe slightly raises the temperature of the outdoor air, thereby increasing the heat pump s efficiency in the VPL 28 aggregate significantly during the winter. With an integrated FU 28 heat pipe unit, in most cases there is no need for a heating coil with mixing circuit. For FU 28 a bag filter M5 and F7 can be ordered. Dimensional drawing A A A Connections 1 2 4 1: 2: 3: 4: 3 All dimensions are in mm. D D D E Scan the QR code Nilan A/S Nilanvej 2 8722 Hedensted Initialer ha ha Tlf: 76 75 25 00 Fax: 76 75 25 25 www.nilan.dk Nilan A/S Nilanvej 2 8722 Hedensted Dato Scan the QR code with your smartphone or tablet and view a brief film gon: Initialer Tlf: 76 75 25 00 Fax: 76 75 25 25 www.nilan.dk Dato ha F ha How the VPL aggregates function How efficient heat recovery is How the cooling functions 4 g Fresh air Supply air Extract air Discharge air

OPERATION VPL 28 BY NILAN Intelligent humidity control Nilan s humidity control automatically adapts to the needs of the family or the building. The intelligent CTS 602 control unit does not need to have a set level input for air humidity (RH) to control the air exchange. By using the integrated humidity sensor, the control unit calculates the average level itself for the last 24 hours. The average level provides a basis for deciding whether to change the air exchange if the air humidity fluctuates. This ensures that the unit always runs at its most efficient, based on the actual air humidity level and not on a theoretical one. Immediately change in % of RH 11 10 9 8 7 6 5 4 3 2 1 Reduced ventilation Forced ventilation Normal ventilation This helps save energy because it automatically adapts to the requirements in the home. Whether a large family or a single person is living in the building has a considerable influence on how much humidity is produced. The unit also adjusts automatically to summer and winter level. 10 20 30 40 50 60 70 80 90 100 Average RH (the last 24 hours) If the air humidity changes by more than 5-10% in relation to the average level, the unit responds with a higher rate of air exchange accordingly. At an air humidity below 30% is reduced ventilation stp activated (adjustable between 15 and 45%) COMMUNICATION External communication The CTS 602 control unit communicates by default with Modbus RTU RS485 communication. A CTS system using this form of communication can easily be connected to the unit. Nilan units have an open Modbus communication, i.e. not only can the unit be monitored, but its operation can also be set in the same way as it can via the operating panel. CTS / Computer Konverter Modbus The protocol is set up by default for a Modbus RTU 30 address, but can be set to a value between 1 and 247. A Modbus converter allows you to connect one or more units to a computer to monitor and control the unit. 5

PLANNING DATA Capacity Max Pa capacity of standard unit, P t,ext as a function of q v, with regard to SEL-values. 500 p t,ext (Pa) SEL-values according to EN13414-7 for a standard unit with G4-filters an no heating element. 400 SFP values comprise the unit total power comsumption incl. control. 300 200 2100 J/m 3 1800 J/m 3 1500 J/m 3 Max Pa Conversion factor: J/m 3 = W/m 3 /h 3600 100 Pressure loss heating element 0 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 100 125 150 175 200 225 250 275 300 325 350 375 400 Without heat pipe With heat pipe q v [m 3 /h] q v [l/s] COP (heating) 8 Heat effect factor COP [-] supply air as function of outdoor temperature [ C] and volume flow q v [m 3 /h]. 7 According to EN14511, extract air = 21 C. COP [-] 6 5 1100 m 3 /h 4 800 m 3 /h 500 m 3 /h 3 2-15 -10-5 0 5 10 15 20 Outdoor temperature [ C] Without heat pipe With heat pipe Heat effect (supply air) 9000 8000 Heat effect Q c [W] as a function of q v [m 3 /h] and fresh air temperature [ C]. According to EN 14511, extract air = 21 C Q c [W] 7000 6000 5000 4000 1100 m 3 /h 800 m 3 /h 500 m 3 /h 3000 2000 1000 Compressor effect 0-15 -10-5 0 5 10 15 20 Outdoor temperature [ C] Uden heat pipe Med heat pipe 6

VPL 28 BY NILAN Supply air temperature (heating) Supply air temperature [ C] as a function of fresh air temperature [ C] and volume flow q v [m 3 /h] balanced flow. Extract air temperature = 21 [ C], 45 RH [%] Supply air temperature [ C] 45,0 40,0 35,0 30,0 25,0 20,0 15,0 10,0 5,0 0,0-15 500 m 3 /h 800 m 3 /h 1100 m 3 /h -10-5 0 5 10 15 20 Outdoor air [ C] Without heat pipe With heat pipe Supply air temperature (cooling) Supply air temperature [ C] as a function of fresh air temperature [ C] and volume flow q v [m 3 /h] balanced flow. Extract air temperature = 24 C Supply air temperature [ C] 24 23 22 21 20 19 18 17 16 15 1100 m 3 /h 800 m 3 /h 14 18 23 28 33 38 Outdoor air [ C] Sound data Sound data for q V = 1000 m 3 /h and P t, ext = 200 Pa according to EN 9614-2 for surfaces and EN 5136 for ducts. Sound output level L WA drops with falling air volume and falling back pressure. Sound output level L pa at a given distance will depend on acoustic conditions in the place of installation. Sound output level (L WA ) Octave band Hz Surface db(a) Supply air db(a) Extract air db(a) Fresh air db(a) Discharge air db(a) 125 60.3 70.6 69.0 68.3 70.3 250 50.7 72.4 70.4 69.7 72.3 500 32.6 69.6 59.4 58.6 69.4 1.000 31.3 72.5 59.9 58.3 72.3 2.000 34.1 71.7 55.9 53.1 71.6 4.000 33.5 69.2 47.3 44.5 69.1 Total ±2 db(a) 65.0 82.0 76.0 75.0 81.0 7

AUTOMATION CTS 602 Control The VPL 28 is controlled by using the CTS 602 operating panel, featuring a wide range of functions, e.g., menu-controlled operation, weekly programme settings, filter monitor with timer, fan speed adjustment, summer bypass (free cooling), post-heating element control, error messages etc. The CTS 602 comes with factory settings, including a default setting which can be customised to operational requirements to achieve optimum operation and utilisation of the system. The operating panel must be placed in a dry, frost-free loction, at least 1.5 m above floor level and at least 0.5 m from any corner. Avoid placing the panel on an external wall or in areas in direct sunlight. Operating instructions for the CTS 602 can be found in a separate user manual supplied with the unit. Functional diagrams Heating Cooling 2 T7 T9 TC T2 T1 1 2 T2 T1 1 6 T5 6 T5 TC TC TC TC 4 3 4 3 5 T6 5 T6 Connections Automatik 1: Fresh air 2: Supply air 3: Extract air 4: Discharge air 5: Condensate drain 6: Electric and water heating T1: Outdoor air sensor T2/T7: Supply air sensor T9: Heating element frost protection T5: Capacitor sensor T6: Evaporator sensor T10: Room sensor 8

VPL 28 BY NILAN Functional overview Standard - Accessories 3 levels The control function is divided into 3 levels: User/Service/Factory with various options at each level Weekly plan User option 1 The unit has 3 weekly programmes (with a factory setting of off ) Programme 1: for working families Programme 2: for stay-at-home families Programme 3: for businesses There is also an option for you to set your own weekly programme. This allows you to overwrite the operating mode in the main menu via an external potential-free contact or PIR sensor. Alarms Alarm log featuring the last 16 alarms. Filter monitor Filter monitor with timer (factory setting of 90 days). Adjustable to 30/90/180/360 days. Bypass Bypassing the outdoor air reduces heat recovery, enabling the desired supply air temperature to be maintained spring, summer and autumn. Air quality Allows you to choose whether to switch humidity sensors and/or CO 2 sensors on and off. - Humidity control Allows you to set a higher or lower ventilation step in the case of high/low air humidity. CO 2 control Allows you to set a higher or lower ventilation step in the case of a high/low CO 2 level. - Air exchange Allows you to select a low ventilation step in the case of low outside temperatures and air humidity. Frostprotection Temperature control Room low In case of failing heating system, the unit is turned off to avoid further cooling with a risk of the water heating coil frost bursting. Allows you to select the temperature sensor which will control the unit. T15 ROOM (panel sensor) T10 EXT (fitted in a representative extraction valve) T3 EXHAUST (extract air) Stops the unit at a low room temperature. Hereby is cooling of the home avoided in case of a failing central heating system. Standard set to OFF. Can be set from 1 to 20 degrees and is controlled by: T15 ROOM (panel sensor) T10 EXT (fitted in a representative extraction valve) T3 EXHAUST (extract air) Room control Allows you to set the regulator to control the room temperature. Air volume Fire alarm Allows you to set four ventilation steps. Supply air and extract air are set individually. Step 1 < 25% - Step 2 < 45% - Step 3 < 70% - Step 4 < 100% This allows you to connect fire-detecting thermostats, smoke detectors and other fire alarm contacts. In case of an alarm, smoke dampers are closed and the unit stops. Joint alarm Outlet for joint alarm Constant pressure control Allows control from both the extract air and supply air side. - Cooling The heat pump has a reversible cooling circuit, which means that the cooling circuit can be reversed, with the unit cooling instead of heating the supply air. Night cooling It is possible the set the control to run night cooling. Intake air control External heating element External electric heating element Allows you to set the regulator to control the intake air temperature/supply air (only available if the control unit has been configured for a supply-heating element). Temperature sensor T7 is an supply air sensor Integrated frost protection for external water heating element Motorised valve and circulation pump control unit Temperature sensor T7 is an supply air sensor Overheating protection Delayed start-up There is a possibility for a delayed start-up by the fans, when a closing damper is installed. Expansion PCB Allows you to make additional connections, e.g. User option 2 overrides User option 1 (e.g. connecting an EM box) Up to 500 W direct Can give the signal for external heating if the defrost function is used Switching the central heating system on/off Reset Allows you to restore the factory settings. Manual test Allows you to test the unit s functions manually. Language Option for setting the relevant language (Danish/Finnish/Norwegian/Swedish/German/English/French). - - - 9

ACCESSORIES CO 2 -sensor With a CO 2 -sensor installed, the ventilation speed can be pre-programmed with CTS 602 to run at a higher ventilation steps when CO 2 reaches high level in the extract air. CO 2 -level is programmable. Water heating element incl. regulation The supply temperature can always be raised to the required level using a water heating element. The water heating element is designed to be built into the duct and must be connected to the primary heating supply. Supplied with two-way adjustment valve, temperature sensor and frost thermostat. Electrical heating surface incl. regulation When you fit an electrical heating surface, you can raise the fresh air temperature to the desired level at any time. The electrical heating surface is supplied ready to fit into the fresh air duct and, for easy fitting, the device is pre-fitted with all the required sensors. EM-box An EM-box allows heat recovery from the air from the range hood and thereby helps to heat the supply air. The EM-box is equipped with a special filter which efficiently cleans the range hood air of fat particles and thereby protects the system. Expansion PCB The expansion PCB provides additional functions for the CTS 602 control unit, e.g., controlling the EM box (see list of functions on page 9). Installation kit The installation kit comprises of four vibration absorbers and a water trap for the condensation outlet. The water trap can be ordered separately. Heating cable To protect the condensation outlet against frost, a 3 metre-long self-regulating heating cable can be ordered. 10

DELIVERY AND HANDLING VPL 28 BY NILAN Transport and storage VPL 28 comes in factory packaging that protects it during transport and storage. VPL 28 must be stored in a dry place in its original packaging until installation. The packaging should only be removed immediately prior to installation. VPL 28 Installation conditions When installing, plan ahead for service and maintenance. We recommend minimum clearance in front of the unit of 60 cm. Ensure the unit is level, with regard to the condensation drain. The condensation drain requires clearance of min. 10.5 cm under the drain spout. Min. 60 cm Use a flexible connection between the unit s nozzle and duct system. The unit is quiet and low vibration, but the fact that vibrations can still be transmitted to the building fabric should be taken into account. We recommend a minimum distance of 30 mm to the building fabric and other fixtures. We recommend erecting the unit on vibration dampers to separate it from the surface it stands on. VPL 15 28 FU 15 28 Min. 60 cm Min. 12,5 cm Installation of electric heating element Min. 10,5 cm Electric heating elements (accessories) are fitted in the duct. The fitter should ensure that there is a safe distance of at least 15 cm between the electric heating element and any inflammable material. The heating element must be insulated using fire-resistant insulation material. Min. 15 cm Min. 15 cm The electric heating element must be connected by an authorised electrician. Min. 32 cm El-varmeflade Heizregister Electric heating element 11

INFORMATION FROM A TO Z Nilan develops and manufactures premium-quality, energy-saving ventilation and heat pump solutions that provide a healthy indoor climate and low-level energy consumption with the greatest consideration for the environment. In order to facilitate each step in the construction process from choosing the solution through to planning, installation and maintenance we have created a series of information material which is available for download at www.nilan.dk. Brochure General information about the solution and its benefits. WWW.NILAN.DK Nilan A/S Nilanvej 2 8722 Hedensted DEnmark Tel. 45 76 75 25 00 Fax 45 76 75 25 25 nilan@nilan.dk www.nilan.dk Product data Technical information to ensure correct choice of solution. Installation instructions Detailed guide for installation and initial adjustment of the solution. Visit us at www.nilan.dk to find out User manual Detailed guide for regulation of the solution to ensure optimum day-to-day operation. more about our company and solutions, download further information and find your nearest dealer. Drawings Tender documents and 3D drawings are available to download for planning purposes. Ver. 2.05-2017.02 Nilan A/S påtager sig intet ansvar for eventuelle fejl og mangler i trykt informationsmateriale eller for tab eller skader som følge af det publicerede materiale, hvad enten dette skyldes fejl eller uhensigtsmæssigheder i materialet eller andre årsager. Nilan A/S forbeholder sig ret til uden forudgående varsel at foretage ændringer af produkter og informationsmaterialer. Alle varemærker tilhører Nilan A/S, og alle rettigheder forbeholdes.