INSTALLATION AND MANINTENANCE INSTRUCTIONS

Similar documents
ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Heating Equipment. gas boilers RX GB. installation and servicing instructions

PEGASUS F2 N 2S. CAST IRON GAS BOILER for heating with electronic ignition and flame control INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mod. ANBR9..G. CR DOC. NO. GAS-HEATED TILTING BRATT PAN. INSTRUCTIONS FOR INSTALLATION, ADJUSTMENT, USE AND MAINTENANCE...

MULTIPOINT BF Gas Fired Balanced Flue Water Heater

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

RMG IT ES PT GB FR BE

Light oil burners. One stage operation

KEY TO COMPONENTS. 1. Heat exchanger 2. Pilot gas pipe 3. Gas injector nozzle 4. Measuring point

SIGMA WALL MOUNTED CAST IRON, GAS FIRED BOILER FOR CENTRAL HEATING FAN ASSISTED, ROOM SEALED, ELECTRONIC FLAME IGNITION AND CONTROL

Proline GAS HOB Model TCG40IX Instruction Book

A/23 MFFI - A/27 MFFI

BG2000S PRE-MIX GAS BURNER

Gas Instantaneous Water Heater

Mikrofill Ethos Condensing combination boiler

GAS GRIDDLE INSTRUCTIONS MODEL: PGG6 MODEL: PGG7

Forced draught gas burner

SECTION 1 - INSTALLATION UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER 1.1 MODE

USHO COOKER INSTALLATION INSTRUCTIONS SAFETY INSTRUCTIONS USER INSTRUCTIONS MODEL: USHO. INSTRUCTION REF: IN152 ISSUE No. 4 DATE

Installation & Maintenance Manual

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

SIGMA. Wall Mounted Cast Iron, Gas Fired Boiler for Central Heating Fan Assisted, Room Sealed, Electronic Flame Ignition and Control

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

Osprey 2 CFL

EDENA CLASSIC E. Model : kw INTALLATION AND SERVICING INSTRUCTIONS. Gas Fired Floor Standing Boiler. Réf. : CH I EN 09/05

Open Vented Condensing Boilers

TC MODULE (FFD) (with Gas Hob)

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER

These Appliances must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations.

21 20 LITER GAS FRYER FFA3200 INSTALLATION AND SERVICING.

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

SECTION 1 - INSTALLATION UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER 1.1 MODE

Dovre 250 Cast Iron Gas Stove

MAINTENANCE AND SERVICE GUIDE

Parts Available from

400G/L PX (CF) Servicing Instructions. For use in GB and IE PLEASE READ THESE INSTRUCTIONS BEFORE SERVICING THIS APPLIANCE

USERS INFORMATION MANUAL FOR GAS FIRED BOILERS

W - WR - WD. Technical information W- WR - WD. Gas-fired convection heaters with fan

Indirect gas-fired air heater

F900 SERIES BOILING PAN G9781. User, installation and servicing instructions. Read these instructions before use T REV.

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

BAXI BOSTON ALL MODELS FLOOR STANDING OPEN FLUE (OF) CENTRAL HEATING BOILERS INSTALLATION AND SERVICING INSTRUCTIONS. GAS TYPE G20 (Natural Gas)

400GL PX (PF) Servicing Instructions. For use in GB and IE PLEASE READ THESE INSTRUCTIONS BEFORE SERVICING THIS APPLIANCE

Oil burners Brûleurs fioul Stookoliebranders

The guarantee on this appliance is valid for 12 months from the first day of installation.

Installation, Operating and Servicing Instructions

INSTALLATION INSTRUCTIONS SAFETY INSTRUCTIONS USER INSTRUCTIONS PARAGON GAS SALAMANDER

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

User s Information Manual

DH-Direct Fired Poultry Farm Diesel Heater

This appliance must be installed and serviced by a competent person as stipulated by the

Operating instructions

Cast Iron Gas Boiler For Forced Hot Water REPAIR PARTS AND OPTIONAL ACCESSORIES

User's Instructions. Alpha CB50

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Installation & Maintenance Manual

INSTRUCTION MANUAL FOR OIL BURNER MODELS

This appliance must be installed and serviced by a competent person as stipulated by the Gas Safety (Installation & Use) Regulations.

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

Forced draught gas burner

Synergy Grill User & Engineer Installation & Conversion Guide

PARAGON GAS FRYER INSTALLATION INSTRUCTIONS SAFETY INSTRUCTIONS USER INSTRUCTIONS MODEL : PDGF/PDGFP

F900 SERIES GAS CHARGRILL G9440, G9460, G9490, G User, installation and servicing instructions T Read these instructions before use

USER S INFORMATION MANUAL

FERROLI ROMA 55 FF WALL MOUNTED, FANNED FLUE BOILER INSTALLATION & SERVICING INSTRUCTIONS. Phone numbers:

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTALLATION, OPERATION AND SERVICE MANUAL GAS COOKER MODEL CPG. Page 1 / 18

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Cast Iron Gas Boiler For Forced Hot Water REPAIR PARTS AND OPTIONAL ACCESSORIES

15B Cast Iron Gas Fired Boilers For Forced Hot Water

GB24 & GB30. User Manual

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

GAS OVEN SERVICE MANUAL

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

Model BR660VA Heat Engine

2.1 BOILER ROOM BOILER ROOM DIMENSIONS 2.3 CONNECTING UP SYSTEM 2.4 CONNECTING UP FLUE 2.5 ELECTRICAL CONNECTION

USER'S INFORMATION MANUAL

User Manual for model RK 18 RK 25 RK 34 CE 0694 RK 18_25_34 - RAD - ING - MAN.UT A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Columbia Boiler Company

LGB Gas fired boiler

QHT Manual for: SU-2A Gas Burner

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

MULTIPOINT FF Room Sealed Fan-Assisted Water Heater

Emberglow COAL EFFECT BALANCED FLUE GAS FIRE

UBGHFF60W 60cm Gas on Glass Gas Hob

Vortex 15/21 Utility and Outdoor Module Vortex Combi 21 and Outdoor Vortex Combi 21

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

MHG201 Gas Hob Manual for Installation, Use and Maintenance

HVG620 & HVG720 Gas Hob Manual for Installation, Use and Maintenance

User Manual. 600mm, 700mm & 900mm Gas Cooktops Model No. CF6GS, CF6GW, CF7GS, CF9GS

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

Installation & Servicing Manual. for the Ultra range of wall mounted fan assisted balanced flue gas boilers

Transcription:

INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102

2

Contents 1. General technical data 2. Dimensional and technical characteristics 3. Installation. Wiring diagrams 5. Startup and shutdown 6. Gas regulation and conversion 7. Maintenance and cleaning 8. Fault finding 3

1. GENERAL TECHNICAL DATA 1.01 Introduction The Pegasus F2 T, with CE approval, is a designed foruse with NATURAL GAS (G 20) or LPG (G 31) for indirect central heating and hot water. 1.02 Installation requirements Only CORGI registered installers should fit the Pegasus boilers. The boiler installation should comply with relevant British standards specifications, codes of practice, and current building Regulations, together with any special regional requirements of the local authorities, gas supplier and insurance companies. 2. DIMENSIONS AND TECHNICAL DATA 2.01 Dimensional data (see fig. 1 and table 2) A 900 B C D a3 a2 1000 762.5 E a1 222.5 672.5 Fig. 1 a1 - Return 1 1/2 a2 - Flow 11/2 a3 - Gas inlet 3/

2.02 Technical data The standard cast-iron PEGASUS F2 T boiler is set to operate on NATURAL GAS (G 20). Tgned to operate with a flow temperature of 82 C and a maximum t of 20 C. The limit thermostat is adjustable up to a maximum of 110 C. MODEL NUMBER OF SECTIONS HEAT OUTPUT kw HEAT INPUT (NET) kw HEAT INPUT (GROSS) kw Table 1 Pegasus F2 51 T Pegasus F2 68 T 5 51 68 56 7,8 62,2 83 Pegasus F2 85 T 6 85 93,5 103,8 Pegasus F2 102 T 7 102 112 12,3 MODEL A mm B mm DIMENSIONS C fl mm D mm E mm RETURN a1 fl CONNECTIONS FLOW a2 fl GAS a3 fl WEIGHT INCLUDING PACKAGE Kg. WATER CONTENT litres MAX WORKING PRESS. bar Table 2 Pegasus F2 51 T Pegasus F2 68 T 550 60 96,5 96,5 180 180 3 6 35 38 11/2" 11/2" 11/2" 11/2" 3/" 3/" 260 300 22 26 Pegasus F2 85 T 720 106,5 200 36 11/2" 11/2" 3/" 350 30 Pegasus F2 102 T 800 106,5 200 2 3 11/2" 1 1/2" 3/" 00 3 MODEL No. of MAIN BURNER BARS MAIN INJECTOR fl mm LPG G31 Nat. GAS G20 PILOT INJECTOR fl mm LPG G31 Nat. Gas G20 GAS SUPPLY PRESSURE mbar LPG G31 Nat. Gas G20 GAS PRESSURE AT BURNER MANIFOLD mbar LPG G31 Nat. Gas G20 GAS FLOW RATE Nat. Gas G20 m 3 /h LPG G31 kg/h Table 3 Pegasus F2 51 T Pegasus F2 68 T 3 3,5 3,5 2,15 2,15 0, 0, 0,2 0,2 15 to 23 15 to 23 37 37 13,3 13,3 36 36 5,9 7,9,3 5,79 Pegasus F2 85 T 5 3,5 2,15 0, 0,2 15 to 23 37 13,3 36 9,9 7,2 Pegasus F2 102 T 6 3,5 2,15 0, 0,2 15 to 23 37 13,3 36 11,8 8,68 5

2.03 Main components 1 2 15 5 6 13 3 7 8 12 1 9 11 10 Front view of the boiler without door Fig. 2a 1 2 3 5 6 Control panel Fig. 2b Key 1. Temperature-pressure gauge 2. Boiler control thermostat 3. Boiler on/off switch. Flue gas re-set thermostat 5. Electronic panel (nto available) 6. Control panel 7. Gas valve 8. Limit thermostat re-set 9. Pilot burner 10. Burner manifold 11. Gas pressure test point 12. Piezo igniter 13. Automatic air vent 1. Drain cock 15. Flue gas sampling point 6

2.0 Characteristic pressure drop curve Water pressure drop in all models is shown in fig. 3. The following diagram shows the pressure drop in the boiler as a function of the water flow rate. P mbar 200 100 90 80 70 60 50 0 EL. 5 EL. 6 EL. 7 EL. 30 20 Fig. 3 10 1 2 3 5 6 7 8 9 10 Q m 3 /h Flow rate 2.05 Safe discharge of combustion products - The boiler comes with a FLUE GAS DISCHARGE THERMOSTAT, which provides a high level of safety and control over the discharge of combustion products. This thermostat cuts off the supply of gas to the burner in the event of a faulty flue draft. - If the FLUE GAS DISCHARGE THERMO- STAT has been activated, you should unscrew the control panel protection cover Boiler rear view (part no. in fig. 2a and 2b) and manually reset the thermostat. After that, the boiler will return to normal operation. - If the FLUE GAS DISCHARGE THERMO- STAT needs to be replaced, use original manufacturer s parts only and make sure the electric connections and positioning of the bulb (see fig. ) are correct; NEVER UNDER ANY CIRCUMSTANCES LEAVE THE FLUE GAS DISCHARGE THERMO- STAT DISCONNECTED FROM THE ELEC- TRIC CIRCUIT. - In case of frequent switching off of the thermostat, contact qualified personnel only. - During cleaning of the draft diverter, be careful not to damage the thermostat phial. Fig. Phial of flue gas discharge thermostat 7

3. BOILER INSTALLATION (To be performed by qualified personnel only) 3.01 General warnings The boiler should be installed according to current regulations. (see para 1.02) We suggest fitting isolating valves between the boiler and the heating system to isolate the boiler from the system if necessary. The rise in temperature of the heating water (the difference between the water flow and return temperatures) should not exceed 20 C. This is to prevent possible damage caused by condensation forming in the boiler. Combustion products should be discharged through a flue with a cross section in accordance with current standards and in any not less than the boiler flue outlet connection. Connect the gas supply to the boiler in accordance with current regulations. The diameter of the gas connection entering the boiler does not dictate the choice of diameter for the pipe between the boiler and the gas meter which should be selected based upon the pipework lecgth and pressure drop. Connect the boiler to a single-phase 230 V ~ 50 Hz power supply through a standard terminal block or outlet, with 2A max. fuses connected between the boiler and the power line. 3.02 Boiler water characteristics When the water supply has a high hardness, it should be treated before entering the heating system to prevent both scaling (caused by hard water) and corrosion (caused by aggressive water) in the boiler. Please remember that because of their low thermal conductivity, even small scales just a few millimetres thick cause the boiler walls to overheat considerably with serious consequences. You must treat the water used for the heating system in the following cases: A) Very large systems (with large volumes of water). B) Systems where partial or complete draining - and water refilling - are frequent. 8

. WIRING AND CONNECTIONS DIAGRAMS - Electrical connections should be performed according to the diagrams shown below. - Connect the boiler to a single-phase, phase neutral, 230 V ~ 50 Hz power supply through a standard terminal block or outlet with 2A max. fuses connected between the boiler and the power supply. Remember that the boiler should always be provided with a good earth. IMPORTANT: The manufacturer disclaims any liability for damage to property or persons caused by failure to earth the boiler correctly. Electrical connections diagram General wiring diagram TS L 230V 50Hz 1 3 1 9 10 CA 1 2 TF TR TR 3 IC TS IC 8 7 TA F 1 2 3 5 6 7 8 9 10 F 6 TF L N 230V ~ 50Hz VG TA CA N 2 3 2 VG 5 Fig. 5 Key IC - Boiler ON/OFF switch TA - Room thermostat TR - Control thermostat TF - Flue gas thermostat VG - Gas valve TS - Limit thermostat manual re-set F - Thermocouple interruptor CA - Auxiliary contact Note: Dotted lines indicate connections to be performed during installation. 9

.02 Access to the internal components of the control panel For access to the terminal block and the internal components of the control panel, proceed as follows: a - Switch off the power supply to the boiler. b - Lift off the boiler cover (held in place by slot pins). c - Unscrew the four screws that hold the plastic panel against the side of the boiler. d - Rotate the panel to the front to its locked position. e - Carry out the work and reassemble in reverse order..03 Exploded view of the control panel (fig. 6) Fig. 6 Key 1. Control panel 2. Wiring harness protection plate 3. Terminal block. Temperature-pressure gauge 5. Control thermostat 6. Boiler on/off switch 7. Flue gas thermostat re-set 10

5. STARTUP AND SHUTDOWN 5.01 Checks to be carried out on initial lighting It is good practice to check the following on initial lighting: that the cutoff valves between the boiler and heating system are open; that all is well pressurized and vented; that there are no gas or water leaks from the water system or boiler; that the electrical connections are correct and the earthing cable connected to a good earthing system; that there are no inflammable liquids or materials in the immediate vicinity of the boiler and that the flue is not blocked. 5.02 Startup with the HONEYWELL V600C valve in models 51-68 (fig. 7a) Set the boiler control thermostat 2 (fig. 2) to minimum. Switch off the electrical power. Open the gas cock upstream from the boiler. Release the air held in the gas pipes by opening the incoming gas valve test point marked with the number 3 (fig. 7a). Press and keep pressed the gas valve control knob 1. Ignite the pilot burner by repeatedly pressing the piezoelectric ignition button 12 (fig. 2). Once the pilot light has been ignited, keep the gas valve knob pressed for another 15-20 seconds and then release it slowly checking that the pilot light remains lit. If it does not, wait 30 seconds before igniting it again. Power up the boiler electric circuit (control thermostat and electrical power). Set the boiler control thermostat 2 (fig. 2) to the desired temperature (no less than 50 C). At this point the main burner should ignite and the boiler operate automatically. HONEYWELL V600C Key 1 Gas valve control knob 2 Burner pressure regulating screw 3 Incoming gas pressure test point Outgoing gas pressure test point 5 Pilot light adjusting screw Fig. 7a 11

5.03 Startup with the HONEYWELL V00C in models 85-102 (fig. 7b) Set the boiler control thermostat 2 (fig. 2), to minimum. Switch off electrical power. Open the gas cock upstream from the boiler. Release the air held in the gas pipes by opening the incoming gas valve test point marked with the number 3 (fig. 7b). Press and keep pressed the gas valve control knob A. Ignite the pilot burner by repeatedly pressing the piezoelectric ignition button 12 (fig. 2). Once the pilot light has been ignited, keep the gas valve knob pressed for another 15-20 seconds and then release it slowly checking that the pilot light remains lit. If it does not, wait 30 seconds before igniting it again. Switch on boiler. Set the boiler regulating thermostat 2 (fig. 2) to the desired temperature (no less than 50 C). At this point the main burner should ignite and the boiler operate automatically. HONEYWELL V00C VALVE Key 1 Ignition button 2 Gas pressure regulating screw 3 Incoming gas pressure test point Pilot light adjusting screw 5 Shutdown button Fig. 7b 12

5.0 Temporary shutdown To turn the boiler off for a short period of time, simply switch off the power supply (using the boiler switch). All electrical elements are thus turned off and only the pilot light remains lit. 5.05 Long-term boiler shutdown Turn knob 1 as indicated in fig. 7a - 7b (in models 51-68), press button 5 as indicated in fig. 7c (in models 85-102). This turns off the flow of gas to both the main burner and the pilot light. Turn off the gas cock upstream from the boiler and switch off the power supply. 5.06 Inspections and controls after startup At first startup: - Make sure the gas circuit is perfectly leakproof. - Make sure the pilot light is adequate and well adjusted; if it is not, adjust it using the gas valve adjusting screw (fig. 7a-7b-7c). - Test boiler ignition by starting it and turning it off using the regulating thermostat. - Check that no combustion gas escapes from the rear of the boiler at the height of the draft diverter, indicating that either the flue is blocked or the draft is insufficient. - Check that the pipe connecting the boiler to the flue is perfectly leakproof at the point of connection between the flue and the boiler. - Check that gas consumption, measured by the gas meter, matches that indicated in the technical data table. 6. REGULATING 6.01 Adjusting the pressure at the burner As described above, the boiler is set up to operate on NATURAL GAS (G 20); gas pressure has been tested and calibrated by the manufacturer. However, due to possible differences in pressure in the gas supply system, at first startup you should check and if necessary adjust the pressure at the injectors to match the pressure level shown in table 3 of the technical data (page 5). Test pressure at test point 11 fig. 2a/2b. 6.02 Gas pressure adjustment and gas conversion with the HONEYWELL V600C valve Adjust the burner pressure at the main burners by turning screw 2 (fig. 7a): turn it clockwise to increase the burner pressure and anticlockwise to decrease it. (burner pressure test point 11 fig. 2a/2b. The pilot light may be adjusted by eye, without the use of instruments, by checking that the flame correctly envelopes the thermocouple without burning excessive gas. To adjust the flame, turn screw 5 (fig. 7a). To convert the boiler from NATURAL GAS to LPG, besides replacing the injectors you should carefully set the pressure regulating screw 2 all the way in. 13

6.0 Gas pressure adjustment and gas conversion with the HONEYWELL V00C valve Adjust the burner pressure at the main burners by turning screw 2 (fig. 7C): turn it clockwise to increase the pressure and anticlockwise to decrease it. (burner pressure: test point 11 fig. 2a/2b). The pilot light may be adjusted by eye, without the use of instruments, by checking that the flame correctly envelopes the thermocouple without burning excessive gas. To adjust this flame, turn screw 5 (fig. 7C). To convert the boiler from NATURAL GAS to LPG, besides replacing the injectors you should carefully set the pressure regulating screw 2 all the way in. REMEMBER: The complete LPG conversion kit is supplied on request only. 6.05 Replacing the main and pilot burner injectors. Caution: The following adjustment and conversion operations are to be performed by qualified personnel only. To replace the main and pilot injectors proceed as follows: Turn off the gas and switch off the power supply to the boiler. Replace the main and pilot injector taking care not to damage the main injectors sealing gaskets. If they have been damaged, replace them. Re-assemble with care. Adjust the gas pressure at the main injectors, and the pilot flame. Check that the boiler functions properly and that there are no gas leaks. 6.06 Pilot burner assembly 3 3- mm 5 7 Fig. 8 Key 1 Burner plate 2 Pilot light viewing cover 3 Pilot burner Ignition electrode 5 Thermocouple 6 Pilot injector 7 Pilot gas supply 1

7. MAINTENANCE AND CLEANING The following operations are to be performed by qualified personnel only. We recommend you contact our local Customer Technical Support Centers. 7.01 Seasonal inspection of the boiler and flue Before the beginning of winter you should perform a general inspection of the boiler, heating system and flue. The inspection should verify: That the boiler sections, burner and flue are clean. That the water in the system is at the correct pressure. That all control and safety devices operate properly. That the thermocouple and ignition electrode are free of carbon deposits. That the pilot flame correctly envelopes the thermocouple. That circulation pumps are free running. That there gas leaks. That the gas flow rate and pressure are correct. 7.02 Cleaning the boiler and the flue To clean the boiler and the flue, remove the burner unit from the boiler. For access to the cast-iron heat exchanger, proceed as follows (fig. 9): Remove the cover of the casing secured by slot pins; pull out the insulation covering the draft diverter, remove the flue collector inspection cover 2 and its insulation, secured with self-tapping screws 1. Now you may clean all the flue gas passages in the boiler using a brush 3. Remember you should check and if necessary clean the flue and its connection to the boiler. Be careful not to damage the flue gas thermostat phial or capillary. Important - Do not clean the burners with chemicals or a steel brush, as these might change the air-gas mixture outlet holes. When cleaning is complete, re-assemble carefully and in the correct position. Then check the seal along the gas and flue gas circuits, functioning of the control and safety devices and gas pressure and gas flow rate. 1 2 3 Key 1 Securing screws 2 Inspection cover with insulation 3 Cleaning brush Flue gas sampling point Fig. 9 15

9. FAULT FINDING Fault No ignition spark No pilot ignition Cause and Corrective Action Piezoelectric igniter failure. Replace the igniter. Spark electrode is broken or badly positioned. Replace the electrode or position it correctly (see fig. 8). Faulty contact between terminal and cable. Screw the terminal tightly onto the igniter cable. No gas. Open the gas cock. Air is held in the pipes. Vent it as described in the chapter on startup. Pilot injector is clogged. Clean the injector (with compressed air). Gas flow rate is insufficient. Adjust flow rate by turning the screw on the gas valve. Poor pilot flame Pilot light goes out No ignition of main burner Instable main burner The flame has been adjusted wrongly. Check that the gas inlet pressure is correct. Pilot burner is dirty. Clean the pilot burner (with compressed air). Thermocouple is faulty. Check and replace the thermocouple. Insufficient flame. Adjust the flame, turning the screw on the gas valve, until it envelopes the thermocouple. Loose contact with the gas valve. Tighten the connection to the gas valve. No power supply. Switch the power on. Nozzles are clogged. Carefully clean the nozzles. Gas valve is faulty. Repair or replace gas valve. Flue gas thermostat switched off. Check the flue for any obstructions, then manually reset the flue gas thermostat. Lack of gas. Check the gas pressure at the main burner. Boiler is dirty. Inspect and clean the boiler body. 16

Burner is dirty. Inspect and clean the burner. Main burner burns poorly Smell of unburnt gas No rise in temperature while the boiler is working Control thermostat restarts high temperature differential Condensation in boiler Boiler becomes dirty quickly Boiler shuts off for no apparent reason Flame is not adjusted properly. Adjust the gas pressure at the main burner (see table 3 page 5). Boiler is dirty. Inspect and clean the boiler body. Flue draft is insufficient. Check flue draft. Air ventilation is insufficient. Increase ventilation in the room. Flame has been adjusted too high. Check the gas flow rate and gas pressure at the main burner. Flame is not adjusted properly. Check that gas consumption is correct. Boiler is dirty. Inspect and clean the boiler body. Output is too low. Check that the boiler model matches the heating system requirements. Control thermostat has broken down. Replace the thermostat. Thermostat bulb is outside its sheath. Check that the bulb is inserted in place. Control thermostat is adjusted incorrectly. Raise the thermostat temperature. Gas flow is insufficient. Check that gas flow conforms to data in table 3 (fig. 2). Flame is adjusted incorrectly. Check that the main burner flame is adjusted properly and that gas flow is in proportion to boiler output. Flue gas thermostat switched off. Inspect the flue draft for obstructions, then reset the flue gas thermostat manually. Safety thermostat switched off. The boiler water temperature has exceeded safe operating temperature. Remember - To avoid unnecessary expenses, before contacting Technical Support, make sure that any boiler failure is not due to the absence of electric power or gas. 17

18

19

350723/0-01/01 ALL SPECIFICATIONS SUBJECT TO CHANGE Lichfield Road, Branston Industrial Estate, Burton Upon Trent, Staffordshire DE1 3HD Tel. 08707 282 885 - Fax 08707 282 886