TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

Similar documents
Temperature Sensor TRG Original Installation Instructions English

NRG NRG NRG NRG

SMK 22 SMK SMK SMK 22-82

TRG 5-6x. GESTRA Steam Systems. Installation Instructions

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

Level Electrode NRG NRG Original Installation Instructions English

Conductivity Electrode LRG Original Installation Instructions English

GESTRA. GESTRA Steam Systems TRS English. Installation & Operating Instructions Temperature Switch TRS 5-50

Level Electrode NRG Original Installation Instructions English

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

Installation & Operating Instructions

BK 45 BK 45-U BK 45-LT BK 46

GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

GESTRA. GESTRA Steam Systems NRS For ONE Electrode. English. Installation Instructions Level Switch NRS 1-50

GESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45

GESTRA Steam Systems NRGS 11-2, NRGS Installation Instructions Level Electrode Types

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

GESTRA Steam Systems NRS For TWO Electrodes. English. Installation Instructions Level Switch NRS 1-50

BK 46. Installation Instructions Steam Trap BK 46

MK 45 A. Stainless Steel Design. Installation Instructions Steam Trap MK 45 A

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

GESTRA Steam Systems OR 52-5 OR English. Installation & Operating Instructions Oil & Turbidity Detector OR 52-5, OR 52-6

Flow switch. Operating Manual. English manual page Page 1 of 15 Fax:

1592P01. for liquids in piping DN max. DC 48 V, 1 A, 20 W

Mechanical seals external, single or double, to DIN EN 12756

Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100

GESTRA. Program for Universal Connections. The Smart Solutions

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218

1592P01. for liquids in piping DN

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

! WARNING. Before using product, read and understand instructions.

FSW300 Series Flow Switch

! WARNING. Before using product, read and understand instructions.

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 236

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

! WARNING. Before using product, read and understand instructions.

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld

ORIGA-SENSOFLEX Displacement Measuring System for Cylinder Series OSP-P

GENERAL SPECIFICATION ELECTRICAL

Frost Protection Thermostat

INSTRUCTION MANUAL (ATEX / IECEx)

Installation manual plugs and connectors QUICK-CONNECT (63 A)

Part No KEMPER Filter-Master XL

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

OPERATING MANUAL CDP 115 Peltier cooling unit for waterbaths

Magnetic-Inductive Flow Velocity Sensor PIT. Device Description

Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA

SCHMIDT Flow Sensor SS Ex - Supplementary instructions for use in explosive atmospheres ATEX

Model: 1100 Float-Controlled Condensate Trap, PN 25

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Mounting and Operating Instructions EB 2231 EN

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

INSTRUCTION MANUAL (ATEX)

Sensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0

Water level controller and limiter

Survey of electrical equipment installed in hazardous areas on tankers

GESTRA. Product Overview. The optimum components for every application

INSTRUCTION MANUAL (ATEX / IECEx)

Adsorption dryer PDAD. (en) Operating instructions g [ ]

INSTRUCTION MANUAL (ATEX / IECEx)

Flameproof Manual Call Points

Operating Instructions Edition 11/2005. Process monitoring Ex-barrier for Diagnostics Unit SITRANS DA400 7MJ2010-1AA. sitrans

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

4) Intrinsic Safety Certification

Operating manual GTL 369 GTL 369M GTL 389 GTL 389M. Temperature probe. Please keep the manual for future use.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Consignes d installation

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

GTF 103-Ex. GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26. Temperature Probe for potentially explosive atmospheres

INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FAW, FAW-C & FAW-C-T TYPE AIR WARMERS FCR & FCR-A TYPE CONVECTORS

Immersion heaters for ATEX/IECEx hazardous areas or in non-atex version

VERSAFLOW VORTEX Supplementary instructions

Snifter ATEX22 VERSION. User Manual. Distributor

RTK Instruments Limited St James Business Park, Knaresborough, North Yorkshire, England. HG5 8PJ

Explosion Proof Combination Signal db (A) / 5 Joule

Operation Manual. Diaphragm pumps 2-headed. Types MP 101 Zp, MP 201 Ep MPC 101 Zp, MPC 201 Ep

INSTRUCTION MANUAL IS-mB1 Minialite Intrinsically Safe Round LED Beacon

Installation manual surface mounting plugs and socket outlets, panel mounting plugs and socket outlets with screw connection (16/32 A)

CP-200 Push Button. CP Warewash Pump Instruction & Operation Manual Push Button , Rev1.0,

Installation, operating and servicing instructions

PROCESS AUTOMATION. Instruction manual. Fieldbus Terminators F*-FT-EX1.I.IEC F*-FT-EX1.D.IEC

Installation and Operating Instruction

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

GESTRA. Product Overview. The optimum components for every application

Product overview. the optimum components for every application

INSTRUCTION & SERVICE MANUAL

SAFETY AND OPERATING MANUAL. Original Instructions 5.0

Manual Power relay SR853

13-1. Temperature Regulator

Instruction Manual. Electronic gas and smoke detector GRM

HKF 8180 Operating instructions

Transcription:

GESTRA GESTRA Steam Systems TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57 EN English Installation & Operating Instructions 810428-05 Temperature Sensor TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57 1

Contents Application Page Usage for the intended purpose...4 Function...4 Safety note...4 Directives and standards EC Pressure Equipment Directive 97/23/EC...5 VdTÜV Bulletin Temperature 100 / DIN EN 14597...5 Approvals for Marine Applications...5 LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)...5 ATEX (Atmosphère Explosible)...5 Note on the Declaration of Conformity / Declaration by the Manufacturer...5 Technical data TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57...6 Name plate / marking...7 Scope of supply...7 Installation Dimensions TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57...8 Component parts of TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57...9 Key...9 Examples of installation...10 Key...10 TRG 5-53, TRG 5-54...11 TRG 5-55, TRG 5-57...11 Tools...11 Electrical connection TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57...12 Connecting the measuring element...12 Wiring diagram...13 Tools...12 Key...12 2

Contents - continued - Commissioning procedure Page Checking electrical connection...13 Switching on supply voltage...13 Measuring fluid temperature...13 Troubleshooting Troubleshooting...14 Maintenance Spare parts...14 Replacing the temperature sensing element...14 Decommissioning Removing and disposing of temperature sensor TRG 5-53, TRG 5-54...15 3

Application Usage for the intended purpose The temperature sensors TRG 5-5..in conjunction with temperature switches TRS 5-6 and TRS 5-8 are used as temperature monitors or safety temperature monitors/limiters, for instance in steam boilers and hot-water plants. Safety temperature monitors or limiters switch the heating off as soon as the max. admissible temperature in the superheater or the inlet line is reached. A temperature monitor gives a signal when the preset MIN and MAX temperature limit is reached. The temperature sensors TRG 5-53, TRG 5-54, TRG 5-55 and TRG 5-57 are designed to be used with temperature switches TRS 5-6 and TRS 5-8. Function A platinum resistance thermometer Pt 100 to EN 60751 is used as temperature sensor for the temperature switch TRS 5-6 and TRS 5-8. A three-wire configuration is used for the electrical connection. The resistance thermometer is supplied with constant current and its voltage is a function of temperature. The changes in voltage are measured in the temperature switch and used for further processing. To connect additional display units the temperature sensor TRG 5-54 is provided with two platinum resistance thermometers Pt 100. Safety note This device is an item of equipment with safety function (PED) and must only be installed, wired and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who - through adequate training - have achieved a recognised level of competence. Danger When loosening the temperature sensor steam or hot water might escape! This presents the risk of severe scalding all over the body! It is therefore essential not to dismantle the temperature sensor unless the boiler pressure is verified to be 0 bar. The temperature sensor becomes hot during operation. Risk of severe burns to hands and arms. Before carrying out installation and maintenance work make sure that the equipment is cold. Attention The name plate specifies the technical features of the equipment. Do not commission or operate any item of equipment that does not bear its specific name plate. 4

Directives and standards EC Pressure Equipment Directive 97/23/EC Safety temperature limiters/monitors are safety accessories as defined in the Pressure Equipment Directive (PED). The temperature switch TRS 5-6 in conjunction with temperature sensors TRG 5-5.. is EC type approved according to EN 12952/EN 12953. These Directives state, among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hotwater installations. VdTÜV Bulletin Temperature 100 / DIN EN 14597 The temperature switches TRS 5-6 and TRS 5-8 in conjunction with temperature sensors TRG 5-5.. are type approved according to VdTÜV Bulletin Temperature 100 / DIN EN 14597. The VdTÜV Bulletin Temperature 100 and the DIN EN 14597 describe the requirements made on temperature limiters and monitors. Approvals for Marine Applications The temperature switch TRS 5-6 in conjunction with temperature sensors TRG 5-5.. is approved for marine applications. LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility) In conjunction with the temperature switches TRS 5-6 and TRS 5-8 the temperature sensors TRG 5-5.. meet the requirements of the Low Voltage Directive 2006/95/EC and the EMC Directive 2004/108/EC. ATEX (Atmosphère Explosible) The temperature sensors TRG 5-53, TRG 5-54, TRG 5-55 and TRG 5-57 are simple items of electrical equipment as specified in EN 60079-11 section 5.7. According to the European Directive 94/9/EC the equipment must be equipped with approved Zener barriers if used in potentially explosive areas. Applicable in Ex zones 1, 2 (1999/92/EC). The equipment does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate wiring diagram provided by the manufacturer. Note on the Declaration of Conformity / Declaration by the Manufacturer For details on the conformity of our equipment according to the European Directives see our Declaration of Conformity or our Declaration of Manufacturer. The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under www.gestra.com/documents or can be requested from us. 5

Technical data TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57 Service pressure TRG 5-53, TRG 5-54: Nominal length 100 mm, 160 mm, 250 mm 40 bar at 251 C 36 bar at 400 C Nominal length 400 mm 18 bar at 400 C TRG 5-55, TRG 5-57: 160 bar at 345 C 120 bar at 540 C End connection TRG 5-53, TRG 5-54: Screwed G ½, ISO 228-1 TRG 5-55, TRG 5-57: Weld-in protection tube 18 mm Temperature sensing element (3-wire connection) TRG 5-53, TRG 5-55, TRG 5-57: 1x Pt 100 to EN 60751, removable TRG 5-54: 2x Pt 100 to EN 60751, removable Admissible flow velocity TRG 5-53, TRG 5-54: Air 25 m/s Superheated steam 25 m/s Water 3 m/s TRG 5-55, TRG 5-57: Air 60 m/s Superheated steam 60 m/s Water 5 m/s Materials TRG 5-53, TRG 5-54: Protection tube 1.4571, X6 CrNiMoTi 17 122 TRG 5-55, TRG 5-57: Protection tube 1.7335, 13 CrMo 4-5 Cable entry / electrical connection Cable gland M 20x1.5 Protection IP 66 to DIN EN 60529 Ambient temperature Max. 70 C Weight TRG 5-53, TRG 5-54: 1.3 kg TRG 5-55, TRG 5-57: 1.5 kg Approvals: EC type approval 01 202 931-B-10-0002 TÜV approval, VdTÜV Bulletin Temperature 100, DIN EN 14597 Type approval Registration number DIN STW(STB) 98507S, DIN TW 106807 Marine applications GL 99251-96 HH 6

Technical data - continued - Name plate/marking TRG 5-... DIN STW ( STB ) 98507S GL 99 251-96 HH L= 100 390477 GESTRA AG, Münchener Str. 77, D-28215 Bremen 40 bar / 251 C 36 bar / 400 C 0525 Fig. 1 Scope of supply TRG 5-53 1 Temperature sensor 1 Installation manual TRG 5-54 1 Temperature sensor 1 Installation manual TRG 5-55 1 Temperature sensor 1 Installation manual TRG 5-57 1 Temperature sensor 1 Installation manual 7

Installation Dimensions TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57 84 9 84 TRG 5-53, TRG 5-54 TRG 5-55, TRG 5-57 11 120 27 mm A. F. 2 140 15 26 9 3 G ½", ISO 228-1 17/24 A. F. 5 L 100 160 250 400 1 L 115 140 6 1 7 4 Fig. 3 8 4 Fig. 2 26 G½", DIN 228-1 N8 N10 0.5 4 [mm] TRG 5-53 40 TRG 5-54 40 5 [mm] 6 [mm] 7 [mm] 8 [mm] TRG 5-55 30 25 18 40 9 TRG 5-57 30 25 24 65 12.5 Fig. 2 8

Installation - continued - Component parts of TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57 9 0 b K a Fig. 4 Key 1 Protection tube / welding sleeve 2 Seating surface 3 Joint ring 13 x 26 4 Temperature-sensitive length 5 Threaded area 6 Diameter of welding sleeve 7 Cone-shaped part 8 Tip of cone-shaped part 9 Top 0 Temperature sensing element (removable) a Terminal box b Cable gland M20 x 1.5 9

Installation - continued - Examples of installation 2 100 100 1 1 Fig. 5 Fig. 6 3 3 Fig. 7 Fig. 8 Key 1 Protection tube / welding sleeve 2 Thermal insulation 3 Elbow 10

Installation - continued - TRG 5-53, TRG 5-54 1. Check seating surface Fig. 2. 2. Put the supplied joint ring onto the sealing surface Fig. 2 3. 3. Screw in the temperature sensor and fasten it with an open-end spanner 27 mm A. F. The torque required for tightening when cold is 150 Nm. TRG 5-55, TRG 5-57 1. Provide a penetration for the socket-weld end on site. 2. Unscrew the upper part of the temperature sensor from the welding sleeve 1. 3. Weld welding sleeve 1 in place. Arc-weld the equipment only manually in place, applying welding process 111 and 141 in accordance with ISO 4063). 4. Put copper ring onto welding sleeve 1 and screw the upper part of the temperature sensor into the welding sleeve 1. Fasten the upper part of the temperature sensor when cold with an open-end spanner (17 or 24 mm A. F.). Tools Attention Only qualified welders certified according to EN 287-1 may weld welding sleeves into lines or vessels. Note When installing the electrode in pipes, weld the elbow onto the pipe, ensuring that the temperature sensitive part 4 of the temperature sensor is exposed to the fluid against the flow direction. Fig. 7, Fig. 8 Make sure that the measuring tip of the temperature sensitive part 4 of the temperature sensor is always in contact with the fluid. Do not completely insulate the temperature sensors. See examples of installation Fig. 5, Fig. 6. Open-end spanner 17 mm A. F. Open-end spanner 24 mm A. F. Open-end spanner 27 mm A. F. 11

Electrical connection TRG 5-53, TRG 5-54, TRG 5-55, TRG 5-57 To connect the temperature sensor use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 4 x 0.5 mm 2. Max. cable length between temperature sensor and temperature switch TRS 5-6, TRS 5-8: 100 m. Connecting the measuring element 1. Take the cover 9 off the terminal box a. Fig. 4 2. Unscrew cable gland b. 3. Pull cable through cable gland b, ring, joint ring and terminal box a. 4. Wire the connecting terminals of the temperature sensing element 0 in accordance with the wiring diagram Fig. 9, Fig. 10. 5. You can also connect other equipment, e. g. display units, to the terminals marked in yellow and black of the TRG 5-54. Fig. 10 6. Fasten the cable gland b. 7. Put cover 9 back on and secure it with screws. Wiring diagram e c 3 6 i 3 6 f 5 h d 5 2 g Fig. 9 Fig. 10 Tools Screwdriver for slotted screws, size 2,5, completely insulated according to DIN VDE 0680 01 Screwdriver for slotted screws, size 8 Key c Terminal, red d Terminal, red e Terminal, black f Terminal, black g Terminal, red h Terminal, red i Terminal, yellow 12

Commissioning procedure Checking electrical connection Make sure that the TRG 5-5... is wired to the associated control unit TRS 5-6 or TRS 5-8 according to the wiring diagram. Fig. 9, Fig. 10 Switching on supply voltage Apply supply voltage to temperature switch TRS 5-6 or TRS 5-8. Measuring fluid temperature Use table Fig. 11 to ascertain the current temperature of the fluid via the resistance value of the Pt 100. 1. Take the cover 9 off the terminal box a. Fig. 4 2. Attach the test line directly to the temperature sensing element 0. 3. Use an ohmmeter for measuring the resistance value. 4. Look up the corresponding resistance value in the table, interpolate if necessary and read off the temperature. 5. Put cover 9 back on and secure it with screws. C 0 10 20 30 40 50 60 70 80 90 100 Ω/deg 0 100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50 0.385 100 138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84 0.373 200 175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03 0.361 300 212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06 0.350 400 247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93 0.338 500 280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65 0.327 600 313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21 0.315 700 345.21 384.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61 0.304 800 375.61 378.59 381.55 384.50 387.45 390.38 0.295 Basic values of the measuring resistors according to IEC 751 for Pt100. Fig. 11 Attention Please replace the measuring element if the temperature measured by the temperature sensor deviates from the plant temperature. The temperature sensor element must also be replaced by a new one if a malfunction occurred and the rated pressure/temperature limits of 251 C / 400 C or 345 C / 540 C are exceeded. See Technical Data, service pressure, on page 6. 13

Troubleshooting For troubleshooting please refer to the installation manuals for the temperature switches TRS 5-6 and TRS 5-8. Maintenance Spare Parts Resistance thermometer type Designation Item Stock code # TRG 5-53 Dimension 1 = 160 mm see Fig. 2 TRG 5-54 Dimension 1 = 160 mm see Fig. 2 TRG 5-55 TRG 5-57 Temperature sensing element 1x Pt 100 0 052260 Temperature sensing element 2x Pt 100 0 052264 Temperature sensing element 1x Pt 100 0 052386 Temperature sensing element 1x Pt 100 0 052388 Replacing the temperature sensing element The temperature sensing element 0 can be replaced during operation if necessary. 1. Take the cover 9 off the terminal box a. Fig. 4 2. Detach temperature sensing element 0. 3. Slacken fixing screws for temperature sensing element 0. Pull out temperature sensing element. 4. Insert new temperature sensing element and fasten fixing screws. 5. Attach temperature sensing element 0. 6. Put cover 9 back on and secure it with screws. 14

Decommissioning Danger When loosening the temperature sensor steam or hot water might escape! This presents the risk of severe scalding all over the body! It is therefore essential not to dismantle the temperature sensor unless the boiler pressure is verified to be 0 bar. The temperature sensor becomes hot during operation. Risk of severe burns to hands and arms. Before carrying out installation and maintenance work make sure that the equipment is cold. Removing and disposing of temperature sensor TRG 5-53, TRG 5-54 1. Take the cover 9 off the terminal box a. Fig. 4 2. Unscrew cable gland b. 3. Detach temperature sensing element 0. 3. Pull cable out of the cable gland b, ring, joint ring and terminal box a. 4. Before removing the temperature sensor make sure that is is neither hot nor under pressure. For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. Note When ordering spare parts or replacement equipment please state the material number indicated on the name plate. If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country. 15

GESTRA Agencies all over the world: www.gestra.com Great Britain Flowserve GB Limited Abex Road Newbury, Berkshire RG14 5EY Tel. 0044 16 35 / 46 99 90 Fax 0044 16 35 / 3 60 34 E-Mail gestraukinfo@flowserve.com Web www.flowserve.com Singapore Flowserve Pte. Ltd. 12 Tuas Avenue 20 Singapore 63882 Tel. 0065 / 68 79 89 00 Fax 0065 / 68 62 49 40 E-Mail fcd_gestra_singapore@flowserve.com Web www.gestra.com South Africa Flowserve SA (Pty) Ltd. Unit No. 1 Director Road Spartan Extension 2 Kempton Park 1613 Tel. 0027 11 / 9 23 73 00 Fax 0027 11 / 9 74 64 20 E-Mail tvniekerk@flowserve.com Web www.flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel. 001 502 / 267-22 05 Fax 001 502 / 266-53 97 E-Mail fcd-gestra-usa@flowserve.com GESTRA AG P. O Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Tel. 0049 (0) 421 / 35 03-0 Fax 0049 (0) 421 / 35 03-393 E-mail gestra.ag@flowserve.com Web www.gestra.com 810428-05/11-2012cm (808412-06) GESTRA AG Bremen Printed in Germany 16