LNB 1000 Series Low Nox Burner

Similar documents
Installation and Service Instructions Economite DS24A

LGB Gas fired boiler

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

THC 85N / 175N INDUSTRIAL / COMMERCIAL SPACE HEATER

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

ECLIPSE INFORMATION GUIDE

Multi-Function Cooktop

GAS COOKTOP INSTALLATION INSTRUCTIONS

USER'S INFORMATION MANUAL

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

USER'S INFORMATION MANUAL

THC 85N / 175N INDUSTRIAL / COMMERCIAL SPACE HEATER

USER'S INFORMATION MANUAL

Installation Guide. 5 Series VGC and VGSU Built-In Gas Cooktops

CSD-1 COMMERCIAL BOILER CONTROLS

Fire-Water Bowls Model 100

Viking Installation Guide

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

GAS COOKTOP INSTALLATION INSTRUCTIONS

INSTALLATION AND SERVICE INSTRUCTIONS

CBO-750 HYBRID-R OVEN Instructions Manual

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

USER S INFORMATION MANUAL

Owner s Information Manual

THC 85 / 175 INDUSTRIAL / COMMERCIAL SPACE HEATER

Dexter Industrial On Premise Dryer. Troubleshooting, Fault Codes, And Schematics. Starting serial number Part # /13

Fig. 1 - Unit PGD4, PGS4, WPG4

GAS COOKTOP INSTALLATION INSTRUCTIONS BEFORE YOU BEGIN. IMPORTANT Save these instructions for local electrical inspector s use.

Burn Easy Installation Instructions LP or Natural Gas Fired Units. Cremator Setup:

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

INSTALLATION GUIDE Dual Fuel Ranges

Viking Installation Guide

PrecisionTemp Shower-Mate

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

Installation Requirements for Models:

USER S INFORMATION MANUAL

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER

DIVISION FINNED WATER-TUBE WATER HEATERS

DESIGN CLASS FUNCTION

MIDCO International Inc. INSTALLATION AND SERVICE INSTRUCTIONS. ECONOMITE MODELS E20B & E20BP Gas Conversion Burner

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

GRAND EFFECTS Fire-Water Bowls Model 100

USER'S MANUAL PGE Single Package Rooftop

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

*p * HWC4 Model THRU-THE-WALL UNIT INSTALLATION INSTRUCTIONS WARNING WARNING WARNING WARNING CAUTION CAUTION TABLE OF CONTENTS

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

THC- 355DF (Dual Fuel)

Installation. Built-In Electric Cooktop. Viking Range, LLC 111 Front Street Greenwood, Mississippi USA (662)

Installation Instructions Dual Fuel Ranges

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

Typical Mount Height. Combustion Chamber

THC-175DF INDUSTRIAL / COMMERCIAL SPACE HEATER. Certified to / Certifié à CGA 2.14 M2011 Conforms to / Conforme à ANSI std Z83.

25M01A-100 to 25M01A-199 HSI Single Stage Combination Gas Valve

GUIDE. Installation 5 SERIES. Built-In Electric Cooktops Built-In Induction Cooktops

Insert Manual. RHT Series WARNING. For Your Safety

MODEL 1082 FREE-STANDING REFRIGERATOR

INSTALLATION INSTRUCTIONS FOR FREESTANDING DUAL FUEL

CINCINNATI, OH USA

UNITARY PRODUCTS GROUP

USERS INFORMATION MANUAL

Indirect gas-fired air heater

WATER-TUBE POOL HEATERS

BEACON/MORRIS RBD SERIES INFRARED RADIANT HEATER

ASSEMBLY and INSTALLATION INSTRUCTIONS. Pipe wrench Ratchet 3/8 socket 9/16 socket 11/16 socket 3/16 Allen key 3/32 Allen key 9/64 Allen key

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LUMINOUS A PATIO HEATER LIKE NO OTHER

TECHNICAL INSTRUCTIONS

FOR YOUR SAFETY WARNING FOR YOUR SAFETY IMPORTANT CAUTION

User s Information Manual Models: 45, ,000 Btu/hr

Installation. 3 Series Built-In Electric Cooktop RVEC330 / CRVEC330 RVEC336 / CRVEC336 RVEC345 / CRVEC345

INSTALLATION INSTRUCTIONS

Installation Instructions. Parts Included. Materials Needed. Tools You Will Need. 30 Sealed Gas Cooktop

Dexter Commercial Vended Stack Washer Dryer. Dryer Troubleshooting, Fault Codes, And Schematics. Starting serial number (12/13)

Insert Manual. DET3 Series WARNING. For Your Safety

For use with models: PGM304-1, versions M-B PGM365-1, versions M-E, M-F & M-G

USER'S INFORMATION MANUAL

Insert Manual. DES Series WARNING. For Your Safety

DIVISION FINNED WATER-TUBE BOILERS

Installation and Service Instructions. name

WATER-TUBE POOL HEATERS

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded

PBG PACKAGED GAS BURNER

TECHNICAL INSTRUCTIONS

Bosch 80% AFUE Gas Furnace BGS80 Model

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

Installation Manual. For Australian refrigerator models: N304M.3 (93 liter 3-way operation with LP gas, 240 volts AC, or 12 volts DC )

Installation Instructions

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

12.0 cu.ft., 2 way, 4-door, R.V. refrigerator with ice maker.

Model SSV-399 GAS BOILER PARTS, KITS & OPTIONAL ACCESSORIES

FGR. Installation, Operation and Startup Instruction Manual FOR FLUE GAS RECIRCULATION SYSTEM. FGR-8 through FGR-22 (25 HP to 1000 HP)

Series RE Infrared Heater

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

Installation Guide. Built-In Electric Cooktops Built-In Induction Cooktops

Transcription:

Installation and Service Instructions ARNIN: If the information in these instructions is not followed exactly, a fi re or explosion may result, causing property damage, personal injury or death. In the United States, installation must conform with local codes or in the absence of local codes, with the National Fuel as Code, ANSI Z223.1-latest edition available from American National Standard Institute. Further reference should be made to the recommendation of your fuel supplier. ARNIN: Additions, changes, conversions and service must be performed by an authorized Midco representative, service agency or the fuel supplier. Use only MIDCO specifi ed and approved parts. INSTALLER: Inform and demonstrate to the user the correct operation and maintenance of the gas utilization equipment. Inform the user of the hazards of storing fl ammable liquids and vapors in the vicinity of this gas utilization equipment and remove such hazards. Affix this manual and associated literature to the burner or on makeup air unit. CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER. USER: Retain this manual for future reference. If other than routine service or maintenance as described in this manual and associated literature is required, contact a qualifi ed service agency. DO NOT ATTEMPT REPAIRS. An inadvertent service error could result in a dangerous condition. AVOID ERROR IN PARTS SELECTION. hen ordering use complete MIDCO Part Number and Description. Furnish Burner Model Number, Bill of Material Number and Date Code (if available) from the specification plate found on the product IMPORTANT: Availability of parts as well as specifi cations are subject to change without notice. Please consult factory for item availability. Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance. HAT TO DO IF YOU SMELL AS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately phone your gas supplier from another building. Follow the gas supplier s instructions. If you cannot reach your gas supplier call the fire department. Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier. BURNER MODEL: BILL OF MATERIAL NUMBER: SERIAL NUMBER #: IRIN DIARAM: Name: FOR SERVICE CONTACT Address: Phone: LNB 1000 Series Low Nox Burner Rule #1147 Code Compliance: CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER. The Midco LNB 1000 burner has been approved to meet Rule 1147 when applied to the model makeup air unit tested. Any modifi cations to the LNB 1000 burner will void code compliance. Review the information included in the Installation and Service Manual on proper operation. Refer to page 6 for additional information. Date of Installation: Midco International Inc. 4140 est Victoria Street Chicago, Illinois 60646 tel 866.705.0514 fax 866.580.8700 web www.midcointernational.com e-mail sales@midcointernational.com SAFETY INFORMATION TERMS: The following terms are used to identify hazards, safety precaution of special notations and have standard meanings throughout this manual. They are printed in all capital letters using a bold type face as shown below, and preceded by the exclamation mark symbol. hen you see the safety alert symbol and one of the safety information terms as shown below, be aware of the hazard potential. DANER: Identifi es the most serious hazards which will result in severe personal injury or death. ARNIN: CAUTION: Signifi es a hazard that could result in personal injury or death. Identifi es unsafe practices which would result in minor personal injury or product and property damage. Quality Designed for Proven Performance 911 Printed in USA Revision 1

Part 1 - Installation Specifications 1 The LNB Series burners are adaptable to most makeup air units. The Midco LNB 1000 LO NOx gas burner was developed to meet the changing emission requirements required today. FIRIN RATE (NATURAL) 2 Push Through Pull Through MIN MBH 3 150 225 MAX MBH 3 1000 1000 AS SUPPLY PRESSURE REQUIRED NATURAL... Min 5.0.C. Max 14.0.C. ELECTRICAL SUPPLY... 120 VAC/ 60 Hz / 5 AMPS 4 INITION CONTROL MODULE VOLTAE... 24 VAC FLAME SAFETY... Electronic fl ame Safety with Spark Ignited Pilot and 100% Sut-Off 5 Table 1. Burner Specifications 1 Standard burners are shipped as NATURAL gas models. 2 All Ratings Based on 1000 BTU/Cu. Ft. NATURAL, at sea level. 3 1 MBH = 1,000 BTU/hr. 4 Inrush AMP draw is higher - if needed, consult the factory. 5 See Section VI of Operational Sequence. Part 1 Installation I Equipment Preparation LNB 1000 Installation procedure: hen installing the Midco LNB 1000 into a spray booth makeup air heater the following instructions must be followed. The Midco LNB 1000 must be installed per the makeup air manufacturer s instructions. If not available take the following steps. To install the burner an opening on the side of the makeup air heater must be provided. See Figure 1 for opening size and mounting information. The Midco LNB 1000 burner should be centrally located on a pull through unit to promote even heat distribution. For a push through unit the Midco LNB burner should be located in the center of the blower discharge. The opening of the combustion chamber must be facing the blower inlet (pull through type) or 90 degree to the blower inlet (push through type). See Figure 2 for proper chamber orientation. Clearance around heat chamber must be a minimum of 6 on all sides. 10.500 Ø16.000 10.500 10.50 x 10.50 Opening for Combustion Chamber Figure 1 - LNB 1000 Mounting Flange Bolt Size 1/2 2 Midco International Inc.

Typical Push Thru LNB Part 1 - Installation Typical Pull Thru I Equipment Preparation Blower Continued LNB Blower Figure 2 - Pull Through / Push Through Chamber Orientation The Midco LNB 1000 wiring is included with the makeup air heater. Follow wiring diagram 5246-25 for proper wiring connections. hen installing the Midco LNB 1000 all safety and operating controls must be included and connected so if any safety fails the LNB burner will not operate. Do not bypass any safety or operating control or equipment might be damaged. II iring MV P 5 LEEND SOLID IRIN AND COMPONENTS BY MIDCO OPTIONAL IRIN AND COMPONENTS BY OTHERS ENCIRCLED: SPARK INITION CONTROLLER SOLID ROUND: TERMINAL STRIP OPEN ROUND: COMPONENT TERMINAL P# TERMINAL ON RTC BOARD 120/1/60 HOT NEUTRAL L1 SPARK ROD FLAME SENSE ROD MAIN VALVE INITION TRANSFORMER 24V STEPDON TRANSFORMER 120V RENDUNDANT VALVE 24V BR BR/ L1 MV1 S1 /120 Y / BR L1 S2 /FS ND / BR BR/ P1 (120VAC) P3 P7 (MAIN) P8 P10 (PILOT) P12 ROUND 0-10 VDC TEMPERATURE CONTROLLER (BY OTHERS) + P2 (+10V) M TO OER MOTOR R Y P9 P11 P13 (V+) (PM) (ND) - P4 (-10V) 5246-25 Figure 3 - iring Diagram Midco International Inc. 3

Part 1 - Installation III Piping The Midco LNB1000 is provided with all required components to install the gas train assembly. Refer to piping diagram 5246-34 for a typical installation. Required modifi cations can be made to the piping layout if required. The Dungs FR valve position CAN NOT be changed as this is critical in burner performance. There is an orifi ce located downstream from the Dungs FR valve and must not be modifi ed. hen complete with gas train assembly installation turn on gas to the unit and check for any gas leaks. Repair any that were found at this time. The minimum required gas pressure at the inlet of the valve train is 5 C and maximum gas pressure not above 14 C. Turn off main manual gas valve before starting the unit. Consult the Midco technical support team if there are any piping questions. EBM 170 OER 8435-23 OER INLET 8416-18 1" UNION 8493-06 1"x 2" 8488-52 DUNS ZERO OVERNOR 8416-04 1" ELBO 8495-24 1" COUPLIN ITH PRESSURE TAP 5246-36 1" x 3" ITH AS ORIFICE & PRESSURE TAP 5246-28 LO FIRE BYPASS 8416-14 PRE ASSEMIED SECTION 1"x 4" ITH PRESSURE TAP 5243-46 1"x 3" 8488-61 1"x 2" 8488-52 1"x 2" 8488-52 1"x 6" 8488-63 FUEL AS 1" T HAND BALL VALVE 8402-29 1" REULATOR RV61 8416-33 1" SOLENOID VALVE 24 V 8402-36 1" SOLENOID VALVE 24 V 8402-36 1" ELBO 8495-24 Figure 4 - Piping 5246-34 IV Burner Startup Do not have gas turned on at this time. Power up air makeup unit and the starting sequence begins. The EBM blower motor is energized and will run up to high blower speed for 20 seconds. After initial prepurge the EBM blower motor will modulate down to low fi re. Once EBM blower motor reaches low speed the main solenoid gas valves and ignition control will be energized. If the burner lights and the temperature control is calling for heat the burner will be modulated depending on the DC Volt signal being generated from temperature control. For complete burner startup and diagnostic information refer to complete spray booth startup instructions provided. If not available contact Midco International or spray booth manufacturer. V Burner Setup The Midco LNB 1000 burner comes with a limiting gas orifi ce which is required to maintain the Low NOx readings and fi ring rate. The orifi ce is located between the dungs valve and EBM blower inlet. Do not attempt to modify the location or orifi ce size. The burner is factory set and should not require any additional setup. Attach a differential gas pressure manometer to check gas fl ow. The locations for attaching the gas pressure manometer are located on the 1 coupling and 1 X 3 nipple where the orifi ce is located. Refer to piping diagram, Figure # 4, for proper location. Remove the 1/8 plug on both fi ttings. Attach a barb fi tting in order to hook up the required tubing to the gas pressure manometer. Set temperature control below booth temperature so burner will light and stay at low fi re. Energize burner power switch. 4 Midco International Inc.

The burner blower will be energized and start sequence will begin. Once main fl ame established the burner will start at low fi re. The gas pressure at the two gas pressure taps will be approximately.1 C to.25 C. This is the minimum fi ring rate for the Midco LNB 1000 burner. Set temperature control to 70 degrees above booth temperature. The EBM blower will begin to increase in speed and the gas pressure will increase to approximately 5 C differential pressure. If the settings are not within the required pressures check to make sure there is a minimum gas pressure of 5 C at the side tap on the upstream solenoid gas valve. Part 1 - Installation & Service V Burner Setup Continued Burner Ignition Sequence: Burner Ignition Sequence: 1. Call for heat a. LNB Burner blower will go to maximum speed b. Ignition control will pre-purge for 30 seconds c. SCEBM-1 control LED will fl ash red 2. After 30 seconds delay, ignition control is energized a. LNB burner will go to minimum speed b. Ignition control will send 120V to the spark generator c. SCEBM-1 control LED will remain solid red. 3. Trial for ignition. a. LNB burner blower stays at minimum speed b. Main gas valves will be energized c. SCEBM-1 control LED will fl ash red/green. If Burner ignites A. Ignitor will be de-energized B. Check DC micro amps signal which needs to be above 1.5 micro amps C. LNB Burner will modulate based on 2-10 VDC signal from the temperature control D. SCEBM-1 control LED will remain solid green If Burner does not ignite A. Igniter will be de-energized B. LNB burner blower will go to maximum speed C. SCEBM-1 control LED will slowly fl ash red. D. Power will need to be de-energized For additional trouble shooting information contact Midco International as shown on front page. VI Burner Ignition The LNB 1000 burner will require maintenance every 12-18 months depending on usage. There are four components that should be inspected. The EBM blower, pilot assembly, burner chamber and burner head should be inspected. Turn off the main gas manual valve and main panel disconnect to insure unit will not start. Remove the fl ame sensor wire, spark cable and wiring harness attached to the EMB blower. To inspect the blower inlet loosen the union between the Dungs valve and blower. Loosen the 4 ½ bolts attaching the burner to the makeup air heater. This will allow removal of the Midco LNB 1000 burner. Inspect the heat chamber. To inspect the burner head you can look into the heat chamber and if any issue contact Midco for replacement. The fl ame sensor and spark rod can be removed by loosen to two nuts holding the pilot assembly. To clean the sensor and spark rod if required you can use steel wool or sand paper. If any crack on the porcelain then the sensor or igniter needs replacing. Reinstall the LNB burner and make sure gas union and wiring were reinstalled. Open manual gas valve and reenergize makeup air heater and cycle as shown in section IV - Burner Startup. VII Maintenance Midco International Inc. 5

Part 1 - Installation & Service VIII Pilot Assembly The Midco LNB 1000 burner uses a direct spark pilot. The LNB direct spark pilot is factory set. The spark gap should be set an 3/16 from center ground rod. Inspect porcelain on the fl ame rod and spark rod. Any signs of a crack the rods should be replaced. For proper parts selection contact Midco Internation as shown on the front page. 1.25" 1 5 FROM TIP TO TIP 3/16" AP 1" 3 4 6 2 5246-42 Item Part # Description Qty 1 5246-17 Flame Rod LNB Assembly 1 2 5246-24 1/2" O.D. Electrode Bush 1 3 5246-43 Spark Rod Assembly LNB 1 4 5246-48 Igniter Flange asket Spark 1 5 8451-06 9/16" I.D. Electrode Bushing 1 6 Hardware #8-32 X 1/4" Slotted Pan Head Screw 2 Figure 5 - Pilot assembly IX Code Compliance Code Compliance To maintain the Midco burner certifi cation to Rule # 1147 Follow Section V for Burner Setup. Do not modify or replace any component supplied with the LNB 1000 burner or the Midco Certifi cation will be voided. To properly identify which air makeup unit is certifi ed to be code compliant contact sales@midcointernational.com Midco International Inc. - 4140 est Victoria Street - Chicago, Illinois 60646 tel: 866.705.0514 - fax: 866.580.8700 - web: www.midcointernational.com - e-mail: sales@midcointernational.com 911 Printed in USA