PIP PNE00004 Steam Trap Guidelines

Similar documents
PIP ELIMTD00 Motor Installation Details for Class I, Division 1 Areas (Motors 600 Volts and Below, 60 hp Maximum)

PIP PCTPA001 Testing of Process Analyzer Systems

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

Chapter 2.3: Steam System

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

August Process Industry Practices Electrical. PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

Armstrong Steam System Solutions for the Hydrocarbon and Chemical Processing Industries

PIP ELEHA01 Engineering Guide for Determining Electrical Area Classification

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

Economical and simplified solutions that offer quality and optimum steam trap service.

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

THE THERMOSTATIC STEAM TRAP

REFRIGERANT PIPING

Yarway Repairable Drip and Tracer Steam Traps Series 751/761, 711/721, 731/741, 500/546, 460/515/D3

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel:

UNIVERSAL STYLE STEAM TRAPS WU450 Series

PRODUCTS. Expansion Joints Fire Fighting. Flexible Metal Hoses. Equipments. Insulation Solutions. Steam. Valves. Level Control.

Why steam trap survey?

BASICS OF STEAM TRAPS BASICS OF STEAM TRAPS

Installation and Testing of Inverted Bucket Steam Traps Manual

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

THERMOSTATIC STEAM TRAPS

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

Steam trap checking WHY WE NEED TO CHECK STEAM TRAPS METHODS OF CHECKING TRAPS ADVANTAGES AND DISADVANTAGES PRACTICAL DEMONSTRATION

UFGS (May 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

The right trap for the right application.

What is a Secondary Pressure Drainer?

Water Fuel + Air for combustion Blowdown

Steam Traps and Steam Specialties

YARWAY PROCESS THERMOSTATIC STEAM TRAPS SERIES 151 AND AV5

Silhouette. Feedwater Heater. Boiler Feedwater

Steam trapping overview STEAM & CONDENSATE MANAGEMENT SOLUTIONS

Element D Services Heating, Ventilating, and Air Conditioning

5.07 Air Replenishment Systems

How to Trap: Installation and Testing

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

Steam Site Guide. Steam Site Guide. Heat Exchange Applications - SI Units

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

Service Step by Step Trouble-Shooting Check-List

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

VIFB Coil Technical Guide

Owner s Manual Therma-Stor II Heat Recovery System

VIFB Coil Technical Guide

CD-33/CD-33S Controlled Disc Steam Traps

FT600 & FT601* Steam Traps Float & Thermostatic Steam Trap. Float & Thermostatic STEAM TRAPS

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld

GESTRA Information A 1.7

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

DIVISION 23 HVAC Hydronic Piping Systems

BuildingName The Description of the Project P DOCUMENTS

PROJ. NO SECTION REFRIGERANT PIPING

Series 151 and AV5. A wide range of process thermostatic steam traps is available to match almost any application need.

Steam and Condensate Technology. Solutions which are brilliant in their simplicity. combined with a first-class design & consultancy service.

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Inverted Bucket Steam Traps

How to Trap: Trap Selection and Safety Factors

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Hoffman Specialty General Catalog

Spirax-Sarco Industrial Thermostatic Steam Traps

GESTRA Information A 1.5

Product. Add Efficiency To Your Steam Investment... Steam Traps Drain Traps Air Vents & Eliminators Accessories Piping Assemblies Replacement Kits

Bringing Energy Down to Earth

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

Niles Steel Tank Hot Water Generator Installation and Operation Manual

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

Liquid Drainers LIQUID DRAINERS

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

Yarway Narvik Steam Desuperheater Series 4300 TempLow

SECTION AIR COILS

Design & Construction Standards, Revised January

Removal of Non-condensable Gases and Air Is Critical In A Steam System

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Steam Trap Selection

Heat Transfer Packages

Hydrocarbon & Chemical Processing Solutions

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Steam: Yesterday, Today and Tomorrow The Use of Steam as an Efficient Heat Source

VERTICAL TUBE HEATING COILS MV & VIFB MODELS

Blowdown Separator & Aftercoolers Installation, Operation, & Maintenance

Ratio Architects, Inc. Section Refrigerant Piping

MFP14 Automatic pumps for condensate and other industrial fluids

STEAM TRAPS

INSTALLATION & TESTING MANUAL

Our Know-How. Your Peace of Mind. Steam Solutions

CONSIDERATIONS IN CONVERTING A DUAL SHELL OR A DUAL PRESSURE COAL FIRED PLANT CONDENSER INTO A COMBINED CYCLE PLANT CONDENSER

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

LIQUIDATOR 450 SERIES

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Transcription:

July 2016 Piping PIP PNE00004 Steam Trap Guidelines

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice. This Practice is subject to revision at any time. Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP Member Companies and Subscribers may copy this Practice for their internal use. Changes or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP. Authorized Users may attach addenda or overlays to clearly indicate modifications or exceptions to specific sections of PIP Practices. Authorized Users may provide their clients, suppliers and contractors with copies of the Practice solely for Authorized Users purposes. These purposes include but are not limited to the procurement process (e.g., as attachments to requests for quotation/ purchase orders or requests for proposals/contracts) and preparation and issue of design engineering deliverables for use on a specific project by Authorized User s client. PIP s copyright notices must be clearly indicated and unequivocally incorporated in documents where an Authorized User desires to provide any third party with copies of the Practice. PUBLISHING HISTORY October 2009 Issued July 2016 Complete Revision Not printed with State funds

July 2016 Piping PIP PNE00004 Steam Trap Guidelines Table of Contents 1. Introduction... 2 1.1 Purpose... 2 1.2 Scope... 2 2. References... 2 2.1 Process Industry Practices... 2 2.2 Industry Codes and Standards... 2 3. Definitions... 2 4. Design, Layout, and Piping... 3 4.1 General... 3 4.2 Design... 3 4.3 Layout... 4 4.4 Piping... 5 5. Selection... 7 6. Installation... 8 Process Industry Practices Page 1 of 9

1. Introduction 1.1 Purpose This Practice provides guidelines for steam traps. 1.2 Scope This Practice provides guidelines for selection, design, layout and installation of steam traps. 2. References Applicable parts of the following Practices and industry codes and standards shall be considered an integral part of this Practice. The edition in effect on the date of contract award shall be used, except as otherwise noted. Short titles will be used herein where appropriate. 2.1 Process Industry Practices (PIP) PIP CTSE1000 Application of External Coatings PIP PNSC0035 Steam Tracing Specification PIP PN01CS1S02 Piping Material Specification 01CS1S02, Class 150, Carbon Steel, Socket Weld, 0.063 C.A., Steam/Condensate PIP PN03CS1S02 Piping Material Specification 031CS1S02, Class 300, Carbon Steel, Socket Weld, 0.063 C.A., Steam/Condensate PIP PN06CS1S01 Piping Material Specification 06CS1S01, Class 600, Carbon Steel, Socket Weld, 0.063 C.A., Steam/Condensate 2.2 Industry Codes and Standards 3. Definitions American Society of Mechanical Engineers (ASME) ASME B31.3 Process Piping (Code) ASME Boiler and Pressure Vessel Code, Section IX Welding and Brazing Qualifications backpressure: Gauge pressure measured at the steam trap or condensate removal device outlet. Typically, backpressure is the sum of: a. Pressure in the condensate receiver or header b. Static head from lift after the trap (2.3 ft of head = 1 psig) c. Friction losses inlet pressure: Gauge pressure measured at the steam trap or condensate removal device inlet non-pumped condensate header: Piping system that conveys condensate directly from a steam trap or multiple steam traps to a collection vessel. This type of header typically transports condensate under two-phase conditions (condensate and flash steam). Process Industry Practices Page 2 of 9

pressure powered pump: Positive displacement device for discharging liquids by using steam, air, or other inert gases as a motive force if the differential pressure is too low, or negative, causing a line or vessel to retain condensate pumped condensate header: Piping system that conveys condensate to a collection vessel by using a pump to drive the condensate into a line that is fully flooded with condensate (single phase flow) stall: Condition that exists if there is insufficient differential pressure to drive condensate through the steam trap into a condensate return system steam trap: An automatic device that permits the discharge of condensate, air and other noncondensable gases from steam systems at or below saturated steam temperature and prevents or minimizes the discharge of live steam steam trap station: device, which incorporates a universal steam trap connector with an integral inlet and outlet isolation valves, and may incorporate a strainer, blowdown valve, and test valve 4. Design, Layout, and Piping 4.1 General 4.1.1 All materials used in the design and installation of steam traps should be new and in accordance with this Practice and its references. See appropriate PIP piping material specifications and piping details. 4.1.2 Welded joints for pipe elements should be in accordance with ASME Boiler and Pressure Vessel Code, Section IX. 4.2 Design 4.2.1 Steam trap bodies should have a design pressure/temperature rating that is equal to or greater than the design conditions of the inlet pipe. 4.2.2 Materials of construction should be suitable for the application and consistent with local and external conditions related to corrosion and tensile strength. 4.2.3 The following information should be used for sizing steam traps: a. Condensate loads at start up and normal running conditions b. Steam inlet pressure and total condensate system backpressure c. Design conditions of the inlet pipe including maximum operating pressure and maximum operating temperature d. Application e. Equipment Process Data Sheet (if applicable) 4.2.4 Safety factors for sizing steam traps vary considerably. Consult steam trap manufacturers for their company s recommended safety factors. Table 1 may be used for preliminary sizing purposes. Process Industry Practices Page 3 of 9

Mains Drainage Tracing Lines Application Table 1. Safety Factors General x2 With Temp. Control Heat Exchangers & General Process x2 x3 Space Unit Heaters x2 x3 Air Heating Coils x2 x3 Submerged Coils Submerged Coils with siphon drain Rotating Cylinders x2 x2 x2 x2 4.3 Layout 4.2.5 For negative differential pressure or vacuum conditions, a pressure powered pump or pressure powered pump/steam trap combination should be considered. Pressure powered pump systems should include vacuum condensers and for stall conditions, heat exchangers. The sizing and installation details for pressure powered pumps are specific to each application and should be developed in consultation with the pump manufacturer. 4.3.1 Typical steam trap locations are shown in the following list. Steam trap sizing and installation details for other locations should be developed in consultation with the steam trap manufacturer. a. Upstream of vertical risers and at low points of the distribution system b. At intervals of 45 m (150 ft) of horizontal steam lines c. Steam lines terminal points (e.g., end of mains) d. Upstream of pressure reducing valves, control valves, block valves and process equipment e. Steam tracers outlets f. Heat exchangers and process equipment outlets g. Steam turbine cases h. Steam coils outlets i. Steam jacket drains j. Steam distribution manifold drains k. Moisture separators l. Upstream of expansion joints, bends and raised expansion loops 4.3.2 For freezing climates, steam traps should be resistant to damage from freezing or protected with freeze protection devices. 4.3.3 Except for coils with siphon drain, steam traps should be installed below the equipment served and accessible for maintenance. Process Industry Practices Page 4 of 9

4.3.4 Steam traps should have one of the following configurations: a. Integral strainer with blowdown valve in accordance with PIP PNSC0035, drawing PNSC0035-08 b. Separate Y-type strainer and blowdown valve in accordance with PIP PNSC0035, drawing PNSC0035-07 4.3.5 Steam traps discharging into elevated or pressurized condensate returns should have a check valve installed downstream. 4.4 Piping 4.4.1 Steam Traps Discharging into Condensate Return Systems 4.4.1.1 Traps should have the following minimum auxiliary equipment: a. Upstream and downstream isolation valves b. For steam traps without integral strainers, strainer with blowdown valve c. Downstream check valve 4.4.1.2 Traps may be provided with any of the following optional auxiliary equipment: a. Upstream bleed valve b. Bypass line with globe valve c. Downstream test/depressurization valve 4.4.2 Steam Traps Discharging into Open Drains 4.4.2.1 Traps should have the following minimum auxiliary equipment: a. Upstream isolation valve b. For steam traps without integral strainers, strainer with blowdown valve 4.4.2.2 Traps may be provided with any of the following optional auxiliary equipment: a. A bypass globe valve. b. If multiple steam traps connect to a common discharge line before discharging to an open drain, a downstream isolation valve may be provided for each trap. c. If conditions exist for high velocity, blast type discharge (e.g. thermodynamic and inverted bucket steam traps are used), traps should have a diffuser that cushions the high velocity discharge and reduces noise and erosion. 4.4.3 If feasible, universal connector technology steam traps should be used. This technology can significantly reduce the time required to replace failed steam traps and is suitable for most drip and tracing applications, as well as small processes. Process Industry Practices Page 5 of 9

4.4.4 Lightweight steam trap stations that include isolation valves, and depressurization and test ports can be used for the steam trap installations described in Sections 4.4.1 and 4.4.2. 4.4.5 All condensate removal points should be individually trapped. Group trapping should not be permitted. 4.4.6 Steam distribution manifolds should be used to supply steam-tracing lines in close proximity in accordance with PIP PNSC0035, drawing PNSC0035-04. Steam distribution manifolds should be fabricated and provided in accordance with the following: a. Manifold body material, normalized carbon steel b. Welding in accordance with ASME Boiler and Pressure Vessel Code, Section IX c. Maximum operating pressure, 4140 kpag (600 psig) or greater at 260ºC (500ºF) d. Hydrotested by manifold fabricator in accordance with ASME B31.3 e. 1-½ inches steam inlet connection f. ¾-inch NPT drain connection for condensate removal using a steam trap g. Unless otherwise specified, 4, 8 or 12 connections in ½- or ¾-inch NPT or SW h. May have isolation valves i. Support brackets j. Paint in accordance with PIP CTSE1000, for maximum temperature of 454ºC (850ºF) 4.4.7 Condensate collection manifolds should be used to collect condensate from steam tracing lines in close proximity in accordance with PIP PNSC0035, drawing PNSC0035-05. Condensate collection manifolds should be fabricated and provided in accordance with the following: a. Manifold body material, killed carbon steel b. Welding in accordance with ASME Boiler and Pressure Vessel Code, Section IX c. Hydrotested by manifold fabricator in accordance with ASME B31.3 d. 1-inch discharge connection e. ¾-inch drain connection f. Unless otherwise specified, 4, 8 or 12 connections in ½- or ¾-inch NPT or SW g. Internal siphon pipe for even temperature distribution and freeze protection h. Support brackets i. Paint in accordance with PIP CTSE1000, for maximum temperature of 454ºC (850ºF) 4.4.8 If two or more traps are required to drain a piece of equipment, the traps should be installed in parallel. Each steam trap should be fitted with isolation valves, Process Industry Practices Page 6 of 9

5. Selection strainer, and downstream check valve. Adequate spacing between steam traps should be provided for maintenance. 4.4.9 A bypass or drain line with a globe valve may be installed if a steam trap drains a piece of equipment that cannot be shut down to maintain the steam trap. 4.4.10 If a steam trap failure cannot be tolerated, a redundant steam trap should be installed in parallel. 4.4.11 Steam trap discharges should be directed to an appropriate condensate return. 4.4.12 If a condensate return system is not available, steam trap condensate should be discharged in accordance with local environmental regulations into a suitable dry well or French drain designed for the specific conditions of surrounding soil. 5.1 Steam trap selection should be based on the application, process conditions and pressure, and should include consultation with the steam trap manufacturer. 5.2 The following information should be obtained and used for steam trap selection: a. Minimum and maximum steam pressure at the trap after pressure drop through upstream control valves or equipment b. Backpressure c. Quantity of condensate to be handled determined by any of the following methods: (1) Measurement (2) Calculation of heat load (3) Process equipment manufacturers data d. Safety factor in accordance with Table 1 5.3 For existing condensate systems, a pressure survey of the condensate return header should be performed to verify the backpressure of the system. 5.4 Steam trap selection should be in accordance with Table 2. Process Industry Practices Page 7 of 9

Table 2. Steam Trap Selection Legend: F&T Float and Thermostatic BP - Balanced Pressure Thermostatic TD Thermodynamic (Note 1) BM Bimetallic IB Inverted Bucket LE Liquid Expansion Thermostatic Steam Mains Application 1 st Choice 2 nd Choice 207 kpag (30 psig) or less 207 to 13790 kpag (30 to 2000 psig) F&T TD (Note 2) Superheated TD BM IB IB Separators F&T IB Steam Tracers Product Temp. < 66ºC (150ºF) Product Temp. > 66ºC (150ºF) BP TD TD BP Process Equipment 3.2 MPag (465 psig) or less F&T IB 3.2 to 13.8 MPag (465 to 2,000 psig) Bulk Storage Tanks BP F&T Line Heaters F&T IB Process Vats F&T TD Vulcanizers TD F&T Evaporators F&T IB Reboilers F&T IB Rotating Cylinders F&T (Note 3) Freeze Protection Notes: 1. If the back pressure of an application is greater than 50% of the inlet pressure, thermodynamic steam traps should not be used. 2. If backpressure is greater than 50% of inlet pressure, IB or F&T should be used. 3. Steam lock release should be provided. 5.5 Pressure powered pumps should be used for negative differential pressure applications including vacuum. See Section 4.2.5 for design considerations. 6. Installation 6.1 Steam tracing traps should be installed in accordance with PIP PNSC0035. 6.2 The use of steam distribution manifolds and condensate collection manifolds is preferred for steam tracing applications. 6.3 For process applications, installation details should be developed with consultation from the steam trap manufacturer. IB LE Process Industry Practices Page 8 of 9

6.4 Steam traps should be installed near and below the condensate source, and in a location that is readily accessible for maintenance. 6.5 Inlet and discharge piping for steam traps should be in accordance with PIP Piping Material Specifications PN01CS1S02, PN 03CS1S02, and PN06CS1S01, and equal to or greater than the sizes of the steam trap connections. 6.6 Steam traps should discharge into non-pumped condensate headers. Discharges into pumped condensate headers should not be permitted. 6.7 Non-pumped condensate headers should be sized to limit the flash steam velocity to less than 20 m/s (4,000 ft/min). Header should be sloped in the direction of the flow a minimum of 1 cm per 24 m (1/2 inch per 100 ft) of straight pipe. Condensate should drain freely towards the condensate receiver or final destination. Vertical risers in non-pumped condensate headers should not be permitted. 6.8 For freezing conditions, condensate inlet and discharge piping shall be self-draining. If a self-draining pipe configuration is not feasible, steam trap freeze protection should be provided. Process Industry Practices Page 9 of 9