Building Codes, Ventilation Rates, and Certified Performance. Ventilation Track Comfortech 2007 St Louis, MO September 27, 2007

Similar documents
Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Put the V back in HVAC

Mechanical Ventilation for Kansas Weatherization Programs

BEST PRACTICE RECOMMENDATIONS

Ventilation for New Low-Rise Residential Buildings July 20, 2015

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

BPI 1200 and ASHRAE Standards

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

Applying the latest version of the National Ventilation Standard Heyoka Solutions, LLC Paul H. Raymer

State of MN Energy Code Ventilation Review for 2017 Energy Design Conference. By 1. Mike D. Wilson Dakota Supply Group

The 2018 Ventilation Extravaganza. Rick Karg Residential Energy Dynamics 2018

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Why ventilate? Dilute contaminants Control or aggravate humidity Comfort or lack of cooling Odors Provide oxygen

Indoor Environmental Quality

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

Ventilation BCBC 9.32 & Richard Kadulski Architect

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

Ventilation BCBC & Richard Kadulski Architect

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

The V in HVAC: Mechanical Ventilation in ENERGY STAR Certified Homes

LEED for Homes Points

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

NEW HOME CERTIFICATION PROGRAM 2018 PROGRAM GUIDE

Applying the latest version of the National Ventilation Standard Heyoka Solutions, LLC Paul H. Raymer

Outside Air Requirements... SOLVED!

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

2018 International Energy Conservation Code (IECC) Updates

(A) ft 3. cfm. cfm (Q

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Uniform Dwelling Code 2017 Updates SPS 323

Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

Trend in the US ventilation market and drivers for change Max Sherman LBNL, USA

An Introduction to Energy Efficient and Effective Whole-House Ventilation

MECHANICAL VENTILATION STANDARDS V.1

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

EARTH ADVANTAGE HVAC REQUIREMENTS

Bill McCullough. Director ERV Products. Dallas, TX

WHAT S CHANGED WITH ANSI/RESNET/ICC STANDARD 380. Iain Walker, Residential Building Systems Group

Heat & Energy RECOVERY VENTILATORS

Joseph Lstiburek, Ph.D., P.Eng, ASHRAE Fellow. Building Science. Adventures In Building Science. presented by

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (6)

INSTALLATION GUIDE. Horizontal series. HRV MODEL 8160 and MODEL 8220 ERV MODEL 3160 and MODEL 3220

Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1

ACCA Quality Homes ACCA 12 QH 2011 (Existing Home Evaluation and Performance Improvement) Developed in cooperation with RESNET

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

Breathe Easy With. Out. Out 54 FINE HOMEBUILDING. COPYRIGHT 2014 by The Taunton Press, Inc. Copying and distribution of this article is not permitted.

Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships. John Tooley Advanced Energy (919)

Ventilation Techniques. Topic 5 - Audio 53

Notable Changes in the Mechanical Codes

Building Science Basics

Residential Heat & Energy Recovery

Tech to Tech May 07 HRV s & ERV s

Spray Polyurethane Foam and Open-Combustion Appliances

Home Performance Science

wattsmart New Homes Contractor-Certified HVAC Quality Assurance (HVAC-QI)

Featuring Vent Lights and Premium Grilles

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Ventilation Strategies in Weatherization

1 Ventilation Checklist 1 Forced Air Systems SENTENCE (2)

Building Regulations Approved Document F1 Means of Ventilation April 2006

FV-08VKML1, FV-08VKSL1, FV-08VKM1, FV-08VKS1, FV-08VKL1, FV-08VK1, FV-05VK1

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

TR Series - The Ultimate ERV

RESNET HERS Rater Sample Test Questions 2

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

Practical and Effective Approaches to Residential Ventilation for Production Builders

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

b) Medium dwelling units that are not included in (a) above {small dwelling}, OR (c) below {large dwelling} Requires 3.5 credits

IAQ VENTILATION SOLUTIONS

Supplement A- Improving Forced Air Heating Systems

HEALTHY CLIMATE Heat / Energy Recovery Ventilator

Mechanical Ventilation Checklists

The best way to enhance indoor air quality

MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS

EnergyGauge USA Release Notes

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs

Residential Makeup Air Systems & Requirements

Revolutionizing Renovation one building at a time

Mechanical Compliance Certificate

Comfort Series. Energy Recovery Ventilator. Why Fresh Air Ventilation is Vital for Today s Energy-Efficient Homes

Ventilation Solutions IAQ Canada

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

SUPPORTING DOCUMENT RESIDENTIAL ENERGY CODE WORKSHEET (2015) EFFECTIVE JANUARY 1, 2017

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

18. Mechanical Ventilation

50% 80% 7 Years. Filter. Ventilation Solutions IAQ Canada. Ventilate. of our time is spend indoors. Limited warranty on motors

SLAB ON GRADE CONSTRUCTION Meeting the MN Energy Code ( air tightness) for 2017 Energy Design Conference. By Mike D. Wilson Dakota Supply Group

SMART ERV Energy Recovery Ventilator. Build It Tight / Ventilate It Right!

Moisture, Ventilation & Global Weirding NEHERS Webinar Series

Indoor Air Quality 101

Time-Based Scheduling of Residential Ventilation

IAQ VENTILATION SOLUTIONS

Transcription:

Building Codes, Ventilation Rates, and Certified Performance Ventilation Track Comfortech 2007 St Louis, MO September 27, 2007

Don T. Stevens National Research & Development Manager, Panasonic Home & Environment Company Voting Member, SPC 62.2 and SSPC 62.2 Vice-Chair, SSPC 62.2 Past Chair, Home Ventilating Institute (HVI) Consultant to ventilation manufacturers, utilities, and agencies on codes, standards, and product development 1983-2007 Participant in development of ventilation codes nationally since 1984

Building and Ventilation Codes Ventilation Rates Certified Performance Q&A

Ventilation Codes IRC-2006 Washington State VIAQ 1991/2006 Minnesota Energy Code 1998/2006 California Title 24 2008

Ventilation Codes IRC-2006 Residential one and two family Adopted in many states Requires whole house ventilation at 0.35 ACH but can be met with windows Requires bath fans only if no operable window Requires kitchen ventilation if no operable window

Ventilation Codes Washington State Ventilation and Indoor Air Quality Code (VIAQ) Adopted first in 1990 Updated to current 2006 version Requires mechanical whole house ventilation at least eight hours a day with 1.5 sones max fan or remote fan or airhandler Requires bath fans and range hoods

Ventilation Codes Minnesota Energy Code First adopted in 1997 and updated several times Requires mechanical ventilation, generally with tempering because of extreme climate Stringent limits on depressurization because of combustion safety Limits primary IAQ fans to 1.5 sones

Ventilation Codes California Title 24 California Energy Commission is adopting ASHRAE 62.2-2007 2007 as ventilation requirement Effective date 2009 when training materials are in place

Ventilation Standards ASHRAE Standard 62-1989 ASHRAE Standard 62R-1995 ASHRAE Standard 62.2-2003 2003 ASHRAE Standard 62.2-2004 2004 ASHRAE Standard 62.2-2007 2007

Background of ASHRAE 62.2-2007 2007 ASHRAE 62-1989 Based on 15 cfm/person or 0.35 ACH Allowed leakiness to provide IAQ ventilation SPC 62 Formed in 1993 to revise ASHRAE 62-1989 First Public Review of 62R in 1995 13,000+ comments on residential portion Residential broken off as new ASHRAE SPC 62.2

Background (cont) Standard Project Committee 62.2 Formed in 1996 with new members First Public Review in 2000 (over 400 comments from 197 commentors) Second Public Review in 2001 (414 comments from 134 commentors) Third Public Review (IRC) early 2002 (66 comments from 19 commentors) Fourth Public Review (IRC) late 2002 (28 comments from 7 commentors)

SSPC 62.2 Background (cont) Formed in January, 2004 for continuous maintenance of high profile standard

Requirements of ANSI/ASHRAE 62.2-2007 2007 Scope Definitions Whole Building Ventilation Local Exhaust Other Requirements Air-Moving Equipment Venting of Combustion Appliances Operations and Maintenance

Scope of ASHRAE 62.2-2007 2007 Covered in Section 2, Page 2 This standard applies to spaces intended for human occupancy within single-family houses and multifamily structures of three stories or fewer above grade, including manufactured and modular houses. This standard does not apply to transient housing such as hotels, motels, nursing homes, dormitories or jails.

Scope (cont) It does not address high-polluting events such as hobbies, painting, cleaning, or smoking. It does not address unvented combustion space heaters such as unvented decorative gas appliances.

Whole Building Ventilation Requirements for General IAQ Covered in Section 4, pages 4 & 5 Applies to all low-rise residential single family and multifamily buildings. Exemption to mechanical IAQ ventilation for limited situations. Sound rating of 1.0 sones or less is required for exposed whole building ventilation fans.

Whole Building Ventilation Requirements (cont) Sizing Table 4.1a is provided based on 7.5 cfm/person plus 1 cfm/100 ft 2 of conditioned space. 62.2-2007 2007 assumes 2 people in the master bedroom like ASHRAE 62-1989. Table 4.1a reduces ventilation of larger residences compared to old 0.35 ACH method.

Whole Building Ventilation Requirements (cont) Table 4.1a (cfm) Number of Bedrooms <1500 ft 2 0-1 30 2-3 45 4-5 60 6-7 75 >7 90 1501-3000 45 60 75 90 105 3001-4500 60 75 90 105 120 4501-6000 75 90 105 120 135 6001-7500 90 105 120 135 150 >7500 ft 2 105 120 135 150 165

Whole Building Ventilation Requirements (cont) This level of ventilation is intended to be provided continuously whenever the building is occupiable. This can be supply ventilation, exhaust ventilation, or balanced ventilation. This level of ventilation was set including a default credit of 2 cfm/100 ft 2 for infiltration.

Whole Building Ventilation Requirements (cont) Exception to Section 4.1 if one of the following conditions is met: The building is located in Zone 3B or 3C of the 2004 IECC climate map. The building has no central A/C and is in a climate with less than 500 heating F F days. The building is thermally conditioned for human occupancy for less than 876 hours per year.

IECC Climate Map

Whole Building Ventilation Requirements (cont) Under these circumstances, it is assumed that windows could be used for natural ventilation, so mechanical whole building ventilation is not required. Local exhaust ventilation would still be required for kitchens and baths.

Whole Building Ventilation Requirements (cont) Operating time for the whole building ventilation can be reduced if the fan is increased in size and a control is used to control the on-time of the fan. This requires increasing the fan size by a factor larger than the on-time factor if the duty cycle is over 3 hours. The fan size and on-time can be calculated and evaluated in the design phase.

Whole Building Ventilation Requirements (cont) Ventilation effectiveness is a measure of the amount of intermittent ventilation required to maintain the same level of IAQ that would be provided by continuous ventilation. It takes into account the lead and lag times of intermittent IAQ ventilation.

Local Exhaust Requirements Covered in Section 5 on page 5. ASHRAE 62.2-2007 2007 addresses commonly-occurring occurring IAQ sources through local ventilation in baths and kitchens. Bathroom ventilation can operate intermittently at a minimum of 50 cfm or continuously at a minimum of 20 cfm, the same as 62-1989.

Local Exhaust Requirements (cont) Bath fans must meet the design airflow either through on-site testing or using their certified rated flow at 0.25 water column. Bath fans must be rated at 3.0 sones or less or be replaced by a pickup grille for a remote fan.

Local Exhaust Requirements (cont) Mechanical kitchen ventilation must be provided by a range hood, a microwave/hood combination, a downdraft fan, a kitchen ceiling or wall fan, or a pickup grille for a remote fan. The fan must remove at least 100 cfm if operated intermittently by the occupant or at least five air changes per hour (ACH) if operated continuously.

Local Exhaust Requirements (cont) The range hood or microwave/hood combination must be rated at 3.0 sones or less at the minimum flow of 100 cfm. Other kitchen exhaust fans must be rated at 3.0 sones or less at their required flow unless over 400 cfm. Kitchen fans must meet the design airflow either through on-site testing or using their certified rated flow at 0.25 water column.

Other Requirements in 62-2-2007 2007 Transfer Air Instructions and Labeling Combustion Appliances 15 cfm/10 sq ft max Garages Minimum Filtration MERV 6 filter required if over 10 of supply duct and a thermal conditioning element Ventilation Openings

Air-Moving Equipment Requirements Ventilation devices must be selected using tested and certified ratings of performance for both airflow and sound in accordance with HVI procedures. HVI Certified Products Directory (www.hvi.org ) Continuous fans rated 1.0 sones or less Intermittent fans rated at 3.0 sones or less at the minimum operating airflow of 100 cfm (400 cfm max)

Air-Moving Equipment (cont) Airflows must be tested as installed or fans must be sized using the rated flow at 0.25 water column for surface mounted fans and using the maximum duct lengths provided in Table 7.1. Normal name plate data is at 0.1 w.c.

Air-Moving Equipment (cont) Home Ventilating Institute (HVI) Certified Products Directory is updated online every month at www.hvi.org.

Design Examples For Meeting ANSI/ASHRAE 62.2-2007 2007 Whole Building IAQ Ventilation Examples Continuous Ventilation Approaches Timer-Based Ventilation Approaches Climate Impacts on System Selection Local Exhaust Ventilation Examples Kitchen Ventilation Bathroom Ventilation Other Room Ventilation

Whole Building IAQ Ventilation Examples 2,400 ft 2 3 bedroom house Can calculate or use Table 4.1a 3 bedrooms assumes 4 occupants 4 occupants x 7.5 cfm/occ + 2400 ft 2 x 1/100 ft 2 = 54 cfm required flow Using Table 4.1a, go across table at 1500-3000 ft 2 and down from 2-32 bedrooms = 60 cfm required flow

Whole Building Ventilation Requirements (cont) Table 4.1a (cfm) Number of 0-1 2-3 4-5 6-7 >7 Bedrooms <1500 ft 2 30 45 60 75 90 1501-3000 45 60 75 90 105 3001-4500 60 75 90 105 120 4501-6000 75 90 105 120 135 6001-7500 90 105 120 135 150 >7500 ft 2 105 120 135 150 165

Whole Building IAQ Ventilation Examples (cont) 7,000 ft 2 4 bedroom house 4 bedrooms assumes 5 occupants 5 occupants x 7.5 cfm/occ + 7,000 ft 2 x 1/100 ft 2 = 108 cfm required flow Using Table 4.1a, go across table at 6001-7500 ft 2 and down from 4-54 bedrooms = 120 cfm required flow

Whole Building Ventilation Requirements (cont) Table 4.1a (cfm) Number of 0-1 2-3 4-5 6-7 >7 Bedrooms <1500 ft 2 30 45 60 75 90 1501-3000 45 60 75 90 105 3001-4500 60 75 90 105 120 4501-6000 75 90 105 120 135 6001-7500 90 105 120 135 150 >7500 ft 2 105 120 135 150 165

Whole Building IAQ Ventilation Examples (cont) 1,100 ft 2 two bedroom apartment 2 bedrooms assumes 3 occupants 3 occupants x 7.5 cfm/occ + 1,100 ft 2 x 1/100 ft 2 = 34 cfm required flow Using Table 4.1a, go across table at <1500 ft 2 and down from 2-32 3 bedrooms = 45 cfm required flow

Whole Building Ventilation Requirements (cont) Table 4.1a (cfm) Number of 0-1 2-3 4-5 6-7 >7 Bedrooms <1500 ft 2 30 45 60 75 90 1501-3000 45 60 75 90 105 3001-4500 60 75 90 105 120 4501-6000 75 90 105 120 135 6001-7500 90 105 120 135 150 >7500 ft 2 105 120 135 150 165

Continuous Ventilation Approaches Section 4.2 allows supply, exhaust, or balanced flow to ensure that the above amount of outdoor air is introduced into the house or apartment No specific requirement for distribution to every room, but some concern

Performance Testing and Certification Home Ventilating Institute Ventilation Industry Trade Association 85%+ of North American products Airflow and sound testing Certification program Certified Product Directory www.hvi.org 1-847-526-20102010

Testing and Certification at HVI Testing done at third party labs: Energy Systems Lab (ESL) at Texas A&M University in College Station, TX All fan products down to less than 0.3 sones AMCA Lab in Arlington Heights, IL All fan products down to 1.5 sones Bodycote Lab in Mississauga, Ontario HRV and ERV products

Testing and Certification (cont.) Fans are mounted on a stand for airflow testing A calibrated airflow test chamber is used

Fan mounted for airflow testing

Fan for Figure 12 air tests

Tachometer on bath fan

Testing and Certification (cont.) Fan airflow is monitored automatically by the ESL technician Measurements are taken at a variety of pressures from 0 w.c. to shutoff of fan at 0.4-0.8 0.8 w.c.

Data on screen

Testing and Certification (cont.) Sound testing is done in a certified sound chamber A rotating microphone is used to measure sound power at 24 frequencies Sound room is concrete double-wall, isolated from the rest of lab, and floats on rubber cushions or sand

Boom mike for sound test

Testing and Certification (cont.) Sound measurements are collected by computer software Measurement of background noise and a standard Reference Sound Source are taken Computer compares sound pressure level at 24 frequencies and calculates linear sound level in sones

Fan mounted on stand for sound test

Testing and Certification (cont.) Final output does weighted average of sone levels at all 24 frequencies This determines final sone rating

Testing and Certification (cont.) The final airflow and sound ratings are submitted by the manufacturer for certification by HVI HVI publishes certified results on HVI web site (www.hvi.org( www.hvi.org) HVI Certified Products Directory is updated online monthly

HRV/ERV Testing and Certification Energy recovery, moisture transfer, cross- leakage, fan power, fan flow in 4 legs, etc Measured at -13,, 32,, and 95 F

Why use certified products? Certified performance from HVI is the best way to ensure expected performance in the field. US and Canadian building codes require HVI Certified Performance ratings when using prescriptive compliance methods to avoid field testing. Data on about 1500 products is available at www.hvi.org

Questions? Don Stevens Panasonic Home and Environment Company PO Box 398 Keyport, WA 98345 360-697 697-5414 stevensd@us.panasonic.com