Job Sheet 1. Geothermal Energy OBJECTIVES. Familiarization with the training system components PROCEDURE

Similar documents
The Refrigeration Cycle

The Refrigeration Cycle

Geothermal Training System (46126-A0)

Geothermal Training System

46126-A2 Geothermal Training System

3400-3A Refrigeration System Demonstrator

Refrigeration Training System

Information Job Sheet 4. Closed-Loop Drainback Systems. Drainback tanks

The Book of AERMEC NRL Sequence of Operation

How Ground Source Heat Pumps Work

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Agent - Manufacturer of Boreal geothermal heat pumps

BasicTroubleshooting Information and Guidelines

CONTROL PANEL INSTRUCTIONS RSQ-4

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

HVAC Basics RESIDENTIAL AIR CONDITIONING

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Shell-and-Tube Heat Exchanger (Four Passes) - Optional

Multi-Zone Wireless Control Training Systems ( )

Supply air temperature reset

WIRING DIAGRAMS R410A MODELS PAC 2OAC/2OACH CAC OWC PWC

CB 8000 AMBIENT AIR CONDITIONED FRESH AIR SUPPLY SYSTEM OPERATOR S MANUAL

Heat Pump Defrost Board Replacement Kit

Installation and Maintenance Manual OM

Lennox Climatic 50 and BMS Modbus, Trend or BACnet.

Model: PRT2-TS / PRT2-NTS EU. Model: Touch Duo

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

Siemens RDY2000BN. Start Up Guide

ETN-24-SUPER-SF Series

Siemens Thermostats. RDY2000BN Thermostat

All alerts are still logged as alarms and also show up in the current alarm list.

OPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB

Service Step by Step Trouble-Shooting Check-List

FAQs Air conditioning systems / Air conditioners

OFFICE OF THE PRINCIPAL GOVERNMENT ENGINEERING COLLEGE JAGDALPUR (C.G.)494005

DXM2 Digital Heat Pump Controller

Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz Technical Manual

AIR CONDITIONING UNIT WITH AN INTEGRATED HEAT PUMP

CWS AIR-CONDITIONERS

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

INSTALLATION INSTRUCTIONS

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

TC-9102 Applications

OWNER S MANUAL. Geothermal Heat Pumps. Product Family: HB, HP, HS, HW A NOTE ABOUT SAFETY ! WARNING YOUR NEW SYSTEM. Register Your System

SERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

Heat Pump Training Course 128 hours, 128 NATE CEHs, 12.8 CEUs Volume Pages, Volume Pages

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool

INSTALLATION INSTRUCTIONS

*20D082-05NN* 20D082-05NN

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

REPAIR PARTS. GSZ14 R-410A Remote Heat Pumps GSZ140181AA GSZ140241AA GSZ140301AA GSZ140361AA GSZ140421AA GSZ140481AA GSZ140601AA

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Programmable Outlet Thermostat. User Manual. Version 1.5s. Inkbird Tech. Co., Ltd.

Installation and Operations Manual

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

Thermography Inspection SAMPLE REPORT

Geothermal Heat Pump Systems

CIATCOOLER LJA. Chilled water production units USE. Attractive design, Compact and quiet

OPERATION MANUAL. Packaged air-cooled water chillers and packaged reversible air to water heatpumps EWAQ009ACV3 EWAQ010ACV3 EWAQ011ACV3

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN August 1, 2002

Verasys System Operation Overview Technical Bulletin

OWC series Deluxe Portable Water-Cooled Spot Cooler ENGINEERING, INSTALLATION AND SERVICE MANUAL

SECTION 50 - CAB CLIMATE CONTROL

MARINE SELF-CONTAINED DIRECT EXPANSION AIR CONDITIONING SYSTEMS

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain. Operation & Maintenance Manual MODELS MDX

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

MDX. Non-Cycling Refrigerated Compressed Air Dryers with zero-loss Intellidrain Drain Trap. Operation & Maintenance Manual MDX MODELS 18 THRU 250

Water chillers water/water type SIGMA Technical information manual

CRIMSON & CRIMSON MAX

HVAC/R Refrigerant Cycle Basics

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

Field Setting for Smart IOT Inverter Outdoor Unit

General Information: Greenhouse and Shelter Equipment Packs

Model: Touch-RS. 1 Touch-RS

Table of Contents. Product Image Table of Contents What is a Programmable Room Thermostat? Installation Procedure

TRACE 700. Slide 1. Hello, my name is Nick Cavitt and I m a marketing engineer in the C.D.S. group at TRANE.

HYDRO-TEMP. Earth Coupled Heat Pumps HYDRO-TEMP CORPORATION P.O. BOX HWY 67 S POCAHONTAS, AR 72455

Refrigeration and Air Conditioning

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

passport I/O controls

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Service Manual. Solar Direct Drive Vaccine refrigerator. Haier Medical and Laboratory Products Co,.Ltd. Model:HTC-60H & HTCD-160.

Safety & Installation Instructions

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual

CHILLER. Modelli CWS BASIC CWS AQUACONTROL INSTALLATION MANUAL USAGE AND SCHEMATICS

TWLC - Tempered Water Logic Controller. The Intelligent Control

HEAT COOL 5+2 DAY PROGRAMMABLE 1-STAGE HEAT, 1-STAGE COOL. Installation Instructions TSTATCCPQ501 TSTATBBPQ501 P Digital Thermostat I2:00

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

CONTENTS AUTOMATIC TRANSFER SWITCHES

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Transcription:

Job Sheet 1 Geothermal Energy OBJECTIVES In this job sheet, you will become familiar with the training system components. You will operate your training system in heating and cooling mode and observe the temperature at various locations on the system. Familiarization with the training system components PROCEDURE In this part of the job sheet, you will locate and identify some training system components. Festo Didactic 89952-20 21

. Record your answers in the table below. Circled letter A B C D E Component Figure 16. Training system diagram. 22 Festo Didactic 89952-20

1. Locate the priming tank (Figure 17) on your training system. Observe the current position of the three-way valves. In the rectangle to the right of the image, draw the diagram corresponding to the position of the three-way valves. Priming tank 3-way valves Pumping station Pump nameplate Figure 17. Priming tank and pumping station. 2. Locate the pumping station. Read the electrical characteristics indicated on the pump nameplate and complete Table 4. Table 4. Electrical characteristics of the pump. Parameter Voltage Frequency Current Number of phase Nameplate data 3. Locate the following indicator lights on the Geothermal Heat Pump control panel: Loop pump Reversing valve Festo Didactic 89952-20 23

Compressor Desuperheater Heat pump fault Circulation pump 4. Which ranges and units can the loop pressure gauge (PI-1) read? 5. What information can be read on the refrigerant high-pressure (HP) and low-pressure (LP) gauges located on the right side of your training system? Temperature at various locations on the training system in heating mode In this part of the job sheet, you will operate your training system in heating mode and observe the temperature at various locations. a In many job sheets throughout this manual, you will have to set switches, valves, the thermostat, and the air distribution register to achieve specific operating conditions required by the topics covered. In each case, you will be supplied with a list of components and the required settings. For instance, in the following list, the main power switch must be set to Off. 24 Festo Didactic 89952-20

6. Perform the following settings: Main power switch... On Thermostat... Off Valve HV-1... Open Valve HV-2... Open Valve HV-3... Open Valve HV-4... Open Valve HV-5... Open Valve HV-6... Open Valve HV-7... Open Valve HV-8... Closed Valve HV-9... No adjustments required Valve HV-10... Handle in horizontal position Valve HV-11... Open Valve HV-12... Open Valve HV-13... Open Pressure gauge PI-1 selector switch... Right Pressure gauge PI-2 selector switch... Right Desuperheater On/Off switch... Off Priming tank three-way valves... Pumping station three-way valves... Air distribution register (on top of the heat pump)... Open Perform the following settings on the simulated ground heat pump: Main power switch (simulated ground heat pump)... On Temperature controller set point... 3 C (5 F) below ground temperature Wait for the compressor of the simulated ground heat pump to start and then wait about 5 min for the temperature of the water in the tank to get close to its set point. a Heat pumps have several protection devices and do not start immediately when power is turned on. The blower and the ground loop pump may be running before the heat pump turns on. Festo Didactic 89952-20 25

7. Feel the temperature at the various locations identified by a circled letter in Figure 18 by touching the components with your hands. Record your observations using the terms cold, room temperature, warm, and hot in the At start up column of Table 5. Perform the following settings on the heat pump: Thermostat... Heating mode Temperature set point...5 C (9 F) above room temperature After a while, the compressor starts and the corresponding indicator light on the control panel turns on. Wait until the compressor has been running for ten minutes, and then repeat your temperature observations. Record your observations in the After 10 minutes of operation in heating mode column in Table 5. Figure 18. Locations where the temperature must be sensed. 26 Festo Didactic 89952-20

Table 5. Sensed temperatures in heating and cooling modes. Location (circled number in Figure 18) At start up After 10 minutes of operation in heating mode Temperature At the moment when the mode is set to cooling After 10 minutes of operation in cooling mode A B C D E F G 8. Using the words On or Off, record the control panel indicator light status in the Heating mode column of Table 6. Table 6. Indicator light status in heating and cooling modes. Indicator light Heating mode Cooling mode Loop pump Compressor Desuperheater pump Reversing valve Circulation pump Heat pump fault 9. Is the air temperature near the air distribution register (G) warmer than the air temperature near the heat pump air intake (F)? Festo Didactic 89952-20 27

10. Did the water in the ground simulation tank (C) change temperature after ten minutes of compressor operation? 11. Did the temperature of the water flowing through the ground loops increase or decrease after ten minutes of compressor operation? 28 Festo Didactic 89952-20

Temperature at various locations on the training system in cooling mode In this part of the job sheet, you will operate your training system in cooling mode and repeat your temperature observations. You will compare your observed temperatures in heating mode and cooling mode. 12. Perform the following settings on your training system: Main power switch... On Thermostat... Off Valve HV-1... Open Valve HV-2... Open Valve HV-3... Open Valve HV-4... Open Valve HV-5... Open Valve HV-6... Open Valve HV-7... Open Valve HV-8... Closed Valve HV-9... No adjustments required Valve HV-10... Handle in horizontal position Valve HV-11... Open Valve HV-12... Open Valve HV-13... Open Pressure gauge PI-1 selector switch... Right Pressure gauge PI-2 selector switch... Right Desuperheater On/Off switch... Off Priming tank three-way valves... Pumping station three-way valves... Air distribution register (on top of the heat pump)... Open Perform the following settings on the simulated ground heat pump: Main power switch (simulated ground heat pump)... On Temperature controller SP... 3 C (5 F) below initial ground temperature Wait for the compressor of the simulated ground heat pump to start and then wait about 5 min for the temperature of the water in the tank to get close to its set point. 13. Feel the temperature at the various locations identified by a circled letter in Figure 18 by touching the components with your hands. Record your observations using the terms cold, room temperature, warm, and hot in the At the moment when the mode is set to cooling column of Table 5. Then, perform the following settings on the heat pump: Festo Didactic 89952-20 29

Thermostat... Cooling mode Temperature set point... 5 C (9 F) below room temperature After a while, the compressor starts and the corresponding indicator light on the control panel turns on. Wait until the compressor has been running for ten minutes, and then repeat your temperature observations. Record your observations in the After 10 minutes of operation in cooling mode column in Table 5. 14. Using the words On or Off, record the control panel indicator light status in the Cooling mode column of Table 6. 15. Compare your observations in heating and cooling modes recorded in Table 5. Where did the temperature change from warm to cold, and from cold to warm? 16. When you changed the operating mode to cooling, did the reversing valve indicator light turn on or turn off? 17. Based on your answer to the previous question, would you say that the default operating mode of your training system is heating mode or cooling mode? 18. Set the thermostat operating mode to Off, then shut down your training system by setting both main power switches to Off. Name: Date: Instructor's approval: 30 Festo Didactic 89952-20