Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Similar documents
TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

SIGMADEK, LTD. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

FUNDERMAX GMBH FIRE TEST REPORT

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

ENGINEERING EVALUATION

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

We Identify and S.T.O.P. Your Noise Problems

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

Refrigerating Appliance DOE Test Report

NFPA 265 May 2002 ROP Copyright 2001, NFPA

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

REPORT 3933 US ROUTE 11, CORTLAND, NEW YORK 13045

Fire Performance of Translucent Systems

FM Approval Standard For Cavity Walls And Rainscreens

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

January 26, Mr. Larry Sunshine Bentax USA 418 Meadow Street Fairfield CT Dear Mr. Sunshine:

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

Certificate of Compliance

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

First Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

Food Service Technology Center

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Materials Testing by Gregory Havel

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

CLT Adhesive Tests in Support of Mass Timber Buildings

SOUTHWEST RESEARCH INSTITUTE

BCTC CARPET TECHNICAL CENTRE

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

REPORT 3933 US ROUTE 11 CORTLAND, NEW YORK 13045

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

REPORT Dialight, 1501 Route 34 South, Farmingdale, NJ 07727

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

REPORT 545 E. Algonquin Rd., Arlington Heights, IL 60005

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

Resolution: FR-1-NFPA Statement: When tests are conducted for fire reconstruction or research the items excluded above can be included.

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

for Walmart suppliers. About Bureauu Veritas laboratories in building and Phase 1: Pre- Assessment until the factory Phase 2: Initial Assessment

First Revision No. 6-NFPA [ Section No. 2.2 ]

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

UPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS

TABLE OF CONTENTS. 1.0 INTRODUCTION Scope References Test Specimen Description Summary 3

Report on Public Input June 2014 NFPA 101

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

Test One: The Uncontrolled Compartment Fire

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

Artificial Trees and Fire Performance

FLASHLIGHT ANSI STANDARDS

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

Heat and Smoke Release of a Ceiling-Installed Speaker

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles

CLASSIFICATION Constructional Data Report (CDR)

Sprinklers in Combustible Concealed Spaces

TECHNICAL BULLETIN Weston Parkway, Cary, North Carolina, Telephone (919) FLAMMABILITY TESTING: A REVIEW BY COTTON INCORPORATED

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

Refrigerating Appliance ErP Test Report

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

ARC MAPPING Things to Consider

Fire Suppression Performance of Manually Applied CAF and Other Water Based System

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

Copyright 2018 American Wood Council 1

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Test Report: ICL/H18/9039 Rev 1

Chapter 17, Initiating Devices

PREDICTING LARGE-SCALE FIRE PERFORMANCE FROM SMALL- SCALE FIRE TEST DATA

An experimental study of the impact of tunnel suppression on tunnel ventilation

FULL-SCALE FIRE TESTS OF A TWO-STORY CROSS-LAMINATED TIMBER STRUCTURE

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Smoke Layer Height and Heat Flow through a Door

Transcription:

Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf, TX 78112 RENDERED TO Demilec USA, LLC 2925 Galleria Drive Arlington, TX 76011 USA PRODUCT EVALUATED: SEALECTION 500 5-1/2" walls and 10" ceiling with TPR 2 Fireshell F1 OE EVALUATION PROPERTY: Heat Release, Flame Spread Report of testing SEALECTION 500 with 14 mils of TPR 2 Fireshell F1 OE for compliance with the applicable requirements of the following criteria: NFPA 286 and IBC 803.2.1. This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any 1055, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program. Page 1 of 21

Page 2 of 21 1 Table of Contents INTRODUCTION 3 TEST SAMPLES 3 TESTING AND EVALUATION METHODS 3 TESTING AND EVALUATION RESULTS 5 CONCLUSIONS 7 APPENDICES Appendix A: DATA 8 Appendix B: PHOTOGRAPHS 13 LAST PAGE 21

Demilec usa LLC Page 3 of 21 2 Introduction Intertek Testing Services NA (Intertek) has conducted testing for Demilec USA, LLC, on SEALECTION 500 spray foam covered with TPR 2 Fireshell F10E to evaluate heat release and flame spread properties when subjected to specific ignition conditions. Testing was conducted in accordance with NFPA 286. This evaluation was performed on October 16, 2008. 3 Test Sam pies 3.1. SAMPLE SELECTION The sample materials were witnessed in production by Intertek Inspector Robert Rombuck, on September 5, 2008, at the Demilec (USA) plant at 2925 Galleria Drive, Arlington TX, 76011. The sealed containers were inspected prior to the spraying of the test assembly, see Appendix B. The spray foam was applied on September 23, 2008. 3.2. SAMPLE AND ASSEMBLY DESCRIPTION The test specimen consisted of three walls with 2x8 studs, 48 inches o.c. and 2x12 joists, 24 inches o.c. with a 15/32 inch plywood backing. The final interior dimensions were 8 feet high, 8 feet wide and 12 feet deep. Ceiling joists ran parallel to the short dimension of the room. The corner was constructed such that two studs met at their edges, forming a 90 angle. On top of this substrate, the spray foam was applied to a thickness of 5-1/2 inches on the walls and 10 inches on the ceiling. There was no significant over spray outside of the cavities. The wall foam, studs, ceiling foam and joists were covered with 14 mils of TPR 2 Fireshell F10E. See Photos in Appendix B for a visual depiction of the description. 4 Testing and Evaluation Methods This standard describes a method for determining the contribution of textile wall and ceiling coverings to room fire growth during specified fire exposure conditions. This method is not intended to evaluate the fire endurance of assemblies, nor is it able to evaluate the effect of fires originating within the wall assembly. The method is not intended for the evaluation of floor finishes. This method is to be used to evaluate the flammability characteristics of finish wall and ceiling coverings when such materials constitute the exposed interior surfaces of buildings. This test method does not apply to fabric covered less than ceiling height, freestanding, prefabricated panel furniture systems or demountable, relocatable, full-height partitions used in open building interiors. Freestanding panel furniture systems include all freestanding panels that provide

Page 4 of 21 visual and/or acoustical separation and are intended to be used to divide space and may support components to form complete work stations. This fire test measures certain fire performance characteristics of finish wall and ceiling covering materials in an enclosure under specified fire exposure conditions. It determines the extent to which the finish covering materials may contribute to fire growth in a room and the potential for fire spread beyond the room under the particular conditions simulated. The test indicates the maximum extent of fire growth in a room, the rate of heat release, and if they occur, the time to flashover and the time to flame extension beyond the doorway following flashover. It does not measure the fire growth in, or the contribution of, the room contents. Time to flashover is defined herein as either the time when the radiant flux onto the floor reaches 20 kw/m 2 or the temperature of the upper air reaches 600 C. A pair of crumpled single sheets of newspaper are placed on the floor 2 feet out from the center of the rear wall and front walls to determine flashover. The spontaneous ignition of this newspaper provides the visual indication of flashover. The potential for spread of fire to other objects in the room, remote from the ignition source, is evaluated by measurements of: 1. The total heat flux incident on the center of the floor. 2. A characteristic upper-level gas temperature in the room. 3. Instantaneous net peak rate of heat release. The potential for the spread of fire to objects outside the room of origin is evaluated by the measurement of the total heat release of the fire. TEST EQUIPMENT AND INSTRUMENTATION IGNITION SOURCE The ignition source for the test is a gas burner with a nominal 12- by 12-inch porous top surface of a refractory material. The burner used at this laboratory is filled with a minimum 4-inch layer of Ottawa sand. The top surface of the burner through which the gas is applied is positioned 12 inches above the floor, and the burner enclosure is located such that the edge of the diffusion surface is located 1 inch from both walls in the left corner of the room opposite from the door. The gas supply to the burner is C.P. grade propane (99 percent purity). The burner is capable of producing a gross heat output of 40±1 for five minutes followed by a 160±5 kw for ten minutes. The flow rate is metered throughout the test. The design of the burner controls is such that when one quarter-turn ball valve is opened, the flow of gas to the burner produces 40 kwand when a second quarter-turn valve is opened the combined flow produces 160 kw. COMPARTMENT GEOMETRY AND CONSTRUCTION The interior dimensions of the floor of the fire room, when the specimens are in place, measures 8 feet, by 12 feet. The finished ceiling is 8 feet ± 0.5 inches above the floor. The four walls are at right angles defining the compartment. The compartment contains a 30 ± 0.25 by 80 ± 0.25

Demilec USA LLC Project No. 3161466SAT-00S Page 5 of 21 inch doorway in the center of one of the 8' by 6' 11" walls. No other openings are present to allow ventilation. The test room is lined with 5/8" type X gypsum wallboard. PROCEDURE SUMMARY OF METHOD A calibration test is run within 30 days of testing any material as specified in the standard. All instrumentation is zeroed, spanned and calibrated prior to testing. The specimen is installed and the diffusion burner is placed. The collection hood exhaust duct blower is turned on and an initial flow is established. The gas sampling pump is turned on and the flow rate is adjusted. When all instruments are reading steady state conditions, the computer data acquisition system and video equipment is started. Ambient data is taken then the burner is ignited at a fuel flow rate that is known to produce 40 kw of heat output. This level is maintained for five minutes at which time the fuel flow is increased to the 160 kw level for a 10-minute period. During the burn period, all temperature, heat release and heat flux data is being recorded every 6 seconds. At the end of the fifteen minute burn period, the burner is shut off and all instrument readings are stopped. Post test observations are made and this concludes the test. All damage is documented after the test is over, using descriptions, photographs and drawings, as is appropriate. 4.1. TEST STANDARD NFPA 286. 5 Testing and Evaluation Results 5.1. RESULTS AND OBSERVATIONS FIRE TESTS The test was started at 11 :55 am on October 16, 2008. The ambient temperature was 7rF with a relative humidity of 52%. The data acquisition system was started and the burner was ignited. Events during the test are described below: TIME (min:sec) OBSERVATION 0:00 Ignition of burner. Heat output set to 40 kw. 0:37 The walls began to discolor. No ignition. 0:52 The walls began to smoke. 2:00 The ceiling became obscured by smoke. 2:21 Transient ignition on the back wall. 2:50 Transient ignition on the left side wall. 4:00 Still no steady ignition 5:00 The burner was increased to 160 kw. 6:00 The walls were burning 6-7 feet from the floor. Intertek

Page 6 of 21 9:00 Smoke opacity began to decrease. The corner stud ignited. 15:00 The flow of propane was deactivated. Test terminated. Observations continued at customer request. 15:16 The wall foam self extinguished. 15:46 The wood stud self extinguished. Post Test Observations: The intumescent and foam were heavily charred and showed signs of receding in the area adjacent to the burner on the back wall, and on the left side wall. For additional details, see the post-test photographs later in this report.

Demilec USA. LLC Page 7 of 21 6 Conclusion The sample submitted, installed, and tested as described in this report displayed low levels of heat release, low upper level temperatures, and no flames exited the test chamber. The heat flux on the floor did not reach flashover levels. The sample did not spread flames to the ceiling during the 40 kwexposure. NFPA 286 does not publish pass/fail criteria. One must consult the codes to determine pass fail. This specimen MET the criteria set forth in the 2003 and 2006 IBC Section 803.2.1 INTERTEK TESTING SERVICES NA Reported by: ;#-~/ C. Anthony Penaloza Flammability Testing Team Leader Reviewed by: Javier. Trevino Senior Project Engineer

Oemilec USA, LLC Page 8 of 21 APPENDIX A Test Data

Oem ilee USA, LLC Page 9 of 21 Thermocouple Data 1200 1000 800 Ii:' - ~ j... l.': 600 Q) c.. E Q) I 400 I 1 I I I - Center of Room - Ceiling Over Burner Back Left Quad Back Right Quad - Front Left Quad - Front Right Quad - Doorway I - - -_. --- I j 200 ~- ------=::::::::------J o o 2 4 6 8 10 12 14 16 time (minutes) an

Page 10 of 21 Smoke Release 2.5 800 -.!!!... E -; 1.5 -III 0::: Q) CIl III Q) a; 0::: Q) ~ 0 E en 2 -. 1 - -~f- - - l- SRR(mA2/sec) -: TSR ~ma2) I ra 700 600 '"- - 500.s Q) CIl iii 0:: 400 Q) ~ 0 E CI) - ---- - 300 S 0 I 200 0.5 - -~-- 100 o L--~~~~~~------~--------~~--~----:! O -- 16 o 2 4 6 8 10 12 14 time (minutes)

Page 11 of 21 Heat Release 400 350 -- 7- -~-- 200 180 300 250..-. ~ ~ 0 ~ 200... (I) ~ 0 a.. 150 ------- --- ----- --- --------- Af\~ II / --.L 1\, ---I' 160 r- 140 (j) cu 120 ~ ::l 0 """) 100 g' ~... >- Cl (I) 80 c: w 100 1 t-- 50 ~. /,/ [ 60 - HRR(kW) ~ ' ~r 40 l= THR(MJ) ------- A.. 0 0 0 2 4 6 8 10 12 14 16 time (minutes) 20..

Page12of21 Heatflux 3.5 3 2.5 2 N E 3: 1.5. 0.5 o r 2 4 -, r 6 8 10 T 12 14 T -0.5 time (minutes) -

Page 13 of 21 APPENDIX B Photographs

Page 14 of 21 SEALECTION A 500, Sealed Sample SEALECTION B 500 Sealed Sample

Page 15 of 21 Pre-test photo back wall Pre-test photo ceiling

Page 16 of 21 Pre-test photo corner.

Demijec USA, LLC Page 17 of 21 Test photo discoloration Intertek

Page 18of21 160kW and smoke ceiling

Page 190f21 Post-test photo

Page 20 of 21 Detail of corner

Project No. 3161466SAT -005 Page 21 of 21 LAST PAGE OF TEST REPORT REVISION SUMMARY DATE SUMMARY Removed extra space in product name, SEALECTION, throughout Corrected product application thickness Amended test sample information to include sampling details and photographs of sealed containers. Revised TPR z Fireshell product name, throughout Post-test observations amended. Corrected tyqographical errors in conclusions Corrected typographical error in heat release rate graph. Revised Table of Contents as needed.,."