ANSI/ASHRAE/IES

Similar documents
ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Code Compliance Commercial Application Guide

lighting control Flexible control every step of the way Simple, scalable, wireless DESIGN INSTALL MAINTAIN

Vive wireless hub. BACnet Integration. Demand Response

Light control solutions

Retrofit Solutions NEW. Energy-saving products for single rooms. Lutron energy-saving products. Patient Rooms. Office Spaces. Affordable Solutions

lighting control Simple and scalable Flexible control every step of the way DESIGN INSTALL MAINTAIN

Quick Install Energy Solutions

RA2 Select. Whole home lighting control made simple. Lutron.com/ra2select. Lutron Electronics Co., Inc Suter Road Coopersburg, PA

lighting control Simple and scalable Flexible control every step of the way DESIGN INSTALL MAINTAIN

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

Quick Install Energy Solutions Featuring Energi TriPak

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

lighting control Simple, scalable, wireless Transform existing buildings with wireless lighting controls Wireless controls and sensors

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

FCSENS0R Occupancy Sensor. Long Description. Manufacturer Information. Taxonomies, Classifications, and Categories

Application Note #407 Revision F March 2019

Vive PowPak Fixture Controls

Lutron Sensor Solutions. Lutron energy-saving light controls for your home or office. simple. affordable. energy-saving.

Volume 1: Basic devices and single-space systems

Spaces are over lighted by 10-20% designed for worst-case interiors and fabrics, adjustable systems can tune-out waste

GRAFIK RA 2. Convenient, wireless light and blind control Integrates with leading smart home brands

Maestro Wireless dimmers, switches and sensors

Wireless Indoor Lighting Control System

ASHRAE October 18, 2013

Wireless Wall-Mount Sensor

Fixture Controller. Applications. Features. Specifications. Certifications & Affiliations. Catalog #: ALC/ALCE Part #: /

Maestro 0 10 V Dimmer Sensor

LIGHTING CONTROLS

WSA120: New Energy Codes and Lighting Controls

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

Quick Install Energy Solutions Featuring Energi TriPak

Application Note #106 Revision D June Emergency Lighting. Overview

RadioRA 2 PRELIMINARY COPY 68 F 70 F. Wall-mounted seetemp display for temperature control Coming soon!

Control your lights, shades, and temperature from anywhere. Motorized shade. Smart Bridge

Lighting Control Strategies. to meet code requirements save energy and improve building performance

Energy Codes. Connected Lighting simplified by Eaton. design and application guide

Energi Savr NodeTM. A versatile, energy saving lighting control solution that is easy to install and easy to expand

Wireless Lighting Control Made Easy

Meeting RF Performance Criteria...7 Background...7 Expectations...7 End-of-Line Testing...7 Fixture Control Self-Test...7 Basic Functionality...

Code Review TITLE PRESENTED BY POURIA NIKNAM

LightSweep. Lighting Control System

Discover the power of smart lighting

Mini Product Guide.

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Reduce lighting energy costs with controls

visual environment technologies etcconnect.com

Lutron In-Fixture Solutions Deliver a Beautiful Lighting Experience

visual environment technologies etcconnect.com

Education Title Solutions

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

Office Title Solutions

Lutron LED Drivers. Take control of the LED opportunity

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

design guide for wireless l i g h t i n g c o n t r o l

Hospitality Title Solutions

RA2 Select. Whole home lighting control made simple

RA2 Select. Whole home lighting control made simple

Healthcare Title Solutions

Lighting Control Solutions for Parking Facilities

ESL-IC Smart Room Control

Restaurants ASHRAE Solutions

TITLE 24 ICONOGRAPHY. Iconography System

2015 IECC. Design Guide for Smart Lighting Control and Energy Solutions

PRELIMINARY COPY. RadioRA 2. Save energy with wireless total home control from Lutron

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

Lutron Wireless. Adjust your lights, shades, and temperature from anywhere. Motorized shade. Remote control

Sivoia QS. Triathlon Shading Solutions. The most fashionable, flexible, and affordable motorized shading system available today. Pico Wireless Control

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

Restaurants IECC 2015 Solutions

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

A Guide for Applicants and Lighting Designers

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Hi-lume 3D Overview. Fluorescent Dimming Ballasts

Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

IECC. nlight Applications Guide.

Advanced Lighting Control for High Building Performance

Discover the power of smart lighting

Aesthetic, energyefficient. control solutions for hospitality facilities QUICK GUIDE TO LIGHTING CONTROL FOR HOTELS

Product Specifications Dialog Room Controller* (*patent pending)

Wireless Wall-Mount Sensor

Applied Lighting Controls

Indoor Controls. SpaceWise SWZG2. Wireless technology

Balance LC. classroom light control fixture solution. simple to order simple to install simple to use

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS

California Title Design Guide for Smart Lighting Control and Energy Solutions

Wireless Wall-Mount Sensor

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Lighting is typically one of the

EcoSystem H-Series Ballasts

Ever evolving energy code requirements and the large demand for energy

SECTION LIGHTING CONTROLS

VESICA LINEAR SUSPENDED VES L

Ceiling-Mounted Wireless Occupancy/Vacancy Sensor

Lighting Application Guide for K-12 Classrooms

Hi-lume 3D Overview. Fluorescent Dimming Ballasts Hi-lume 3D Architectural Dimming

simplicity. convenience. control.

Transcription:

Vive Solutions Commercial Application Guide Code Compliance Lighting Controls ANSI/ASHRAE/IES 90. 200

Table of Contents ASHRAE ASHRAE 90.-200 90.-200 Introduction Solutions Overview... 2 Summary of Code Requirements... 4 Daylight Zone Requirements... 5 Suggested Code Compliant Solutions... 6 How to Use this Guide... 8 Vive Local Solutions Layout... 0 Applications Atrium Retrofit (Switching)... 2 New Construction (Dimming 0-0 V)... 4 Private Office Retrofit (Switching)... 42 New Construction (Dimming 0-0 V)... 44 Restroom (Multi-Stall) Retrofit (Switching)... 46 New Construction (Dimming 0-0 V)... 48 Egress Stairwell Retrofit (Fixture Control)... 50 New Construction (Fixture Control)... 52 Break Room Retrofit (Switching)... 6 New Construction (Dimming 0-0 V)... 8 Classroom Retrofit (Switching)... 20 New Construction (Dimming 0-0 V)... 22 Recommended (Fixture Control)... 24 Conference Room Retrofit (Switching)... 26 New Construction (Dimming 0-0 V)... 28 Recommended (Fixture Control)... 30 Egress Corridor Retrofit (Switching)... 32 New Construction (Dimming 0-0 V)... 34 Open Office Retrofit (Switching)... 36 New Construction (Dimming 0-0 V)... 38 Recommended (Fixture Control)... 40 This document summarizes the lighting and receptacle control requirements for commercial buildings. It is for information purposes only. It is not meant to replace your state s or local jurisdiction s official energy code. The recommendations presented in this guide are based on the originally published code prior to addenda. Please refer to your local building energy code or authority having jurisdiction for your precise requirements. Only the authority having jurisdiction can guarantee code compliance.

Solutions Overview Energy-saving lighting control strategies Strategy 80% High-end trim/tuning sets the maximum light level based on customer requirements in each space. * Max: 00% Max: 80% Potential savings 0 30% Lighting Codes can sometimes be complicated and difficult to navigate. This commercial application guide provides examples of how Lutron products can be used to meet or exceed code requirements. This guide focuses on Vive and Vive compatible solutions, but our other control systems offer similar features. Lutron Product Capabilities: Commercial Applications Auto On Auto Off Occupancy/vacancy sensing turns lights on when occupants are in a space and off when they vacate the space.* 20 60% Lighting Full On Dim Daylight harvesting dims electric lights when daylight is available to light the space.* 25 60% Lighting Local Solutions Panel Solutions Full On Dim Personal dimming control gives occupants the ability to set the light level.* 0 20% Lighting Wallbox Vive Vive with wireless hub* Energi Savr Node Quantum Shade Open Shade Closed Controllable window shading moves shades to reduce glare and solar heat gain. * 0 20% Cooling Occupancy sensing 7am: Dim Full On Appliance On Heating 7pm: Off Dim Appliance Off Cooling Scheduling provides scheduled changes in light levels based on the time of day.* Demand response automatically reduces lighting loads during peak electricity usage times. * Plug load control automatically turns off loads after occupants leave a space.* HVAC integration controls heating, ventilation, and air conditioning systems through a contact closure.* * Go to lutron.com/references for more information 0 20% Lighting 30 50% During peak period 5 50% of Controlled loads 5 5% HVAC Strategies for code/standards compliance Multi-level lighting control Daylight harvesting Receptacle control Timeclock ** Demand response Energy monitoring BACnet integration To learn more about these products and their specifications, go to lutron.com/catalogs * For the latest information on products compatible with the Vive wireless hub go to lutron.com/vive ** Requires QS Timeclock Automated Demand Response capability requires signal from a third-party device 2 3

Summary of Requirements for Lighting and Receptacle Controls Daylight Zone Requirements The requirements listed below are summarized for simplicity and may have other exceptions that were omited. Local Control Minimum control type Switching Multi-level or dimming Description Lighting shall be capable of turning ON and OFF. There shall be at least one manual device for control of the lighting within a space. See code for spaces that allow remote location of control. Lighting shall be capable of providing at least one level between 30% and 70% of full power, in addition to ON and OFF. There shall be at least one manual device for control of the lighting within a space. See code for spaces that allow remote location of control. Code provision 9.4..2 (a) Exceptions 9.4..2 (a) Daylight Zone Requirements: Fixtures in primary side-light or skylight zones must be controlled by a daylight sensor. Fixtures in daylight zone must be controlled separately from fixtures in the rest of the space. Sidelighting (Window) Daylight Exceptions: Daylight control is not required in primary sidelighted areas less than 250 sq. ft. and in areas under skylights less than 900 sq. ft. Timeclock 2 Interior: Scheduled control, based on time-of-day, turns lighting ON or OFF based on typical occupancy. Occupancy sensors also comply as an alternate to using a timeclock. Exterior & parking garages: Scheduled control, based on time-of-day and sunrise/sunset, turns lighting ON or OFF based on typical occupancy and daylight (requires astronomical timeclock). 9.4.. (a) 9.4..3 (a) & (c) 9.4..7 (a), (b), & (c) WINDOW HEAD HEIGHT (HW) 2 ft 2 ft Automatic Control 3 Occupancy sensor Full ON Partial ON Automatic control turns lighting ON upon occupancy or OFF after a vacancy of 30 minutes or less. When initiated by a timeclock or, lighting is automatically turned ON to maximum lighting power. When initiated by a timeclock or, lighting is automatically turned ON to 50% or less of maximum lighting power. 9.4..2 (b) 9.4..3 (b) 9.4. Exceptions 9.4. Section View NOT TO SCALE DAYLIGHT ZONE Plan View NOT TO SCALE.0 x HW Full OFF When initiated by a timeclock or, lighting is automatically turned OFF. 9.4..2 (b) Partial OFF When initiated by a timeclock or, lighting is automatically reduced by at least 50% of maximum lighting power (30% for enclosed parking garages and exterior). Automatic full OFF also complies. 9.4..3 (b) 9.4..6 (g) 9.4..7 (c) Toplighting (Skylight) Other Daylight responsive control Interior: A sensor which adjusts lighting in response to available daylight is required for sidelight and skylight zones. There must be at least two light levels between ON and OFF. See the Daylight Zone Requirements diagrams for more information. Exterior and parking garages: A photosensor can be used as an alternate to the dawn/dusk operation of an astronomical timeclock. The perimeter 20 ft. of parking garages with access to daylight must automatically reduce lighting power in response to daylight. 9.4..3 (d) 9.4..4 9.4..5 9.4..7 (a) SKYLIGHT AVERAGE CEILING HEIGHT (HC) 0.7 x HC Receptacle control At least 50% of the receptacles in the space shall automatically turn OFF based on typical occupancy or after a vacancy of 30 minutes or less. Plug-in devices do not comply. 8.4.2 SKYLIGHT ZONE For areas being used as a path of egress or fixtures being used for emergency, verify compliance with your local authority having jurisdiction. Acceptance (functional) testing is required for all new construction applications to ensure that control hardware and software are calibrated, programmed and functioning properly (Code provision 9.4.4). When multi-level lighting control and/or daylight responsive control is required, Lutron recommends using continuous dimming to allow for smooth light level adjustment and maximize energy savings. 2 Lutron recommends using s to achieve automatic on/off requirements in place of a timeclock to maximize energy savings and optimize user experience. 3 Manual ON is always permitted for interior applications. Provide manual ON control when no automatic ON is indicated. Section View NOT TO SCALE Plan View NOT TO SCALE 4 5

Suggested Code Compliant Solutions Suggested Code Compliant Solutions The compliant solutions listed below are suggested based on total installed cost, simplicity of design, and basic functional needs for the space. These solutions do not represent the only compliant options to meet lighting and receptacle control requirements. Applications in this guide will illustrate these solutions and/or alternate solutions for advanced functionality. Diagram key: = New construction = Lighting retrofit = New construction and retrofit Atrium Break Room Classroom, Lecture Hall, Training Room Conference, Multi-purpose Room Egress Corridor 4 Lobby Open Office (>250 sq. ft.) Private Office (<250 sq. ft) Restroom Egress Stairwell 4 Storage Room Facade/ Landscape Parking Garage (Not Roof) 3 Other Exterior 5 Local Control Switching Multi-level or dimming 6 Timeclock Occupancy sensor Automatic Control 2 Full ON Partial ON Full OFF Partial OFF Other Daylight responsive control Receptacle control Retrofit requirements indicated are for lighting alterations greater than 0% of the connected load in a space. 2 Manual ON is always permitted for interior applications. Provide manual ON control when no automatic ON is indicated. 3 When typically occupied, the sensor provides Partial OFF functionality. When typically unoccupied, the sensor provides Full OFF functionality. For entrances and exits, lights are scheduled to Full OFF when typically unoccupied and at night; daylighting and occupancy sensing are not required. 4 For areas not designated as a path of egress, the must turn lights to full OFF. 5 Astronomical timeclock shall ensure all lights are off during daylight hours. Lights should be scheduled to Partial OFF during night hours. See section 9.4..4 for scheduling times. 6 Multi-level or dimming capability is not required in non-daylit lobbies. 6 7

How to Use this Guide Room type Type of solution This guide offers up to three solutions per space type. The Retrofit Solutions are simple and inexpensive solutions, generally suited for a basic retrofit. The New Construction Solutions are value driven, generally best suited for new construction. The Recommended Solutions have advanced functionality for greater comfort and energy savings. This application guide is designed to help specifiers and contractors understand codes and Lutron controls in a simple manner. Each of the pages will lay out different spaces, the corresponding lighting control products and the way the system is setup in the space. For Specifiers Use this application guide for design suggestions, the way the system operates and to specify the relevant products for each space. For Contractors Use this application guide to understand how the system is installed, the way the system must operate and to order the correct products for each application. Understand how the products are laid out in the space Classroom New Construction ASHRAE 90.-203 2 DZ DZ DZ 2 2 2 DZ 2 DZ 2 DZ 2 2 2 2 2 2 2 RMJS-8T-DV-B PowPak dimming module with 0-0 V 4 $ 50.00 RMJS-20R-DV-B 20 A PowPak relay module $ 39.00 LRF2-DCRB-WH wireless daylight sensor $ 20.00 LRF2-VKLB-P-WH Low-voltage wireless corner-mount vacancy sensor DZ & DZ 2 = Daylight Zones $ 85.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control 2 $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 Code Notes: For non-daylit classrooms, all general lighting can be connected to a single 0-0 V dimming module. This solution requires 0-0 V enabled ballasts and drivers by others. Classroom New Construction ASHRAE 90.-203 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Controlled receptacles automatically regain power when occupant enters. Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights. All lights automatically turn off 5 minutes after all 50% of all receptacles automatically turn off 5 minutes after all 22 23 Learn more about the products used in the space Pico wireless control wireless corner-mount vacancy sensor and daylight sensor Manual On Auto Off Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning Appliance On Appliance Off Plug Load Control 65% Type of solution Learn about the products visible in the space and the different options available for these. Learn what strategies are implemented in the space Learn what energy savings you achieve over manual shut off Understand how the space functions with the installed system 8 9

Vive Local Solutions Layout This is a high-level overview of the local solutions layout. For individual room requirements refer to the detailed room type solutions in this guide. A single PowPak module can control a single or multiple fixtures. The products shown here are representative of local solutions. Multiple product options are available to meet the needs of the space. Vive wireless hub* PowPak module Occupancy sensor Pico wireless remote control Daylight sensor Vive wireless hub Features: Central control, management, and monitoring of Vive devices via web browser Supports astronomic and time-of-day events Two contact closure inputs for 3rd party integration such as Automatic Demand Response WiFi access for easy commissioning Control up to 0,000 sq. ft. with a single hub Optional BACnet integration * Go to lutron.com/vive for complete compatibility and design details 0

Atrium Retrofit Atrium Retrofit Pico wireless control RMJS-6R-DV-B PowPak switching module 2 $ 29.00 PJ2-2B-GWH-L0 Pico wireless 2-button control 2 $ 2.00 Manual: Occupant uses wall switches to turn on and turn off general lighting. Timeclock: Timeclock turns lights on during normally occupied hours. Timeclock turns lights off during normally unoccupied hours. 7am: Dim 7pm: Off Scheduling PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 HJS--FM Vive wireless Hub Shared Consult your local rep for Hub pricing and service options. Code Notes: Requirements specified for atriums 20-40 ft. in height. Go to lutron.com/vive for complete compatibility and design details. 0% 2 3

Atrium New Construction Atrium New Construction DZ Low-voltage DZ DZ & DZ 2 = Daylight Zones DZ DZ Pico wireless 4-button scene control wireless daylight sensor DZ 2 DZ 2 DZ 2 DZ 2 DZ 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Full On Dim Daylight Harvesting RMJS-8T-DV-B PowPak dimming module with 0-0 V 4 $ 50.00 LRF2-DCRB-WH wireless daylight sensor 2 $ 20.00 PJ2-4B-GWH-L3 Pico wireless 4-button scene control $ 39.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant selects scenes to set desired light levels for all lights. Timeclock: Timeclock turns lights off during normally unoccupied hours. 85% Max: 00% Max: 85% High-end Trim/Tuning 7am: Dim 7pm: Off Scheduling Scene Scene Scene 2 Scene 2 Scene Scene 2 Scene Control HJS--FM Vive wireless Hub Shared Consult your local rep for Hub pricing and service options. Code Notes: Requirements specified for 20-40 ft. atriums. Go to lutron.com/vive for complete compatibility and design details. This solution requires 0-0 V enabled ballasts and drivers by others. 60% 4 5

Break Room Retrofit Break Room Retrofit Maestro vacancy sensing switch Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Manual On Auto Off MS-VPS6M2-DV-WH Maestro vacancy sensing switch* $ 53.00 Manual: Occupant uses wall switch to turn all lights off. All lights automatically turn off 5 minutes after all * Maestro MS-VPS6M2 is not compatible with Vive wireless hub. 30% 6 7

Break Room New Construction Break Room New Construction Low-voltage Pico wireless control wireless corner-mount vacancy sensor Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Manual On Auto Off RMJS-8T-DV-B PowPak dimming module with 0-0 V $ 50.00 Manual: Occupant uses wall dimmer to set desired light levels for all lights. 85% Max: 00% Max: 85% High-end Trim/Tuning LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 All lights automatically turn off 5 minutes after all PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 Code Notes: For break rooms with daylight, include a 0-0 V dimming module per zone and a daylight sensor. This solution requires 0-0 V enabled ballasts and drivers by others. 45% 8 9

Classroom Retrofit Classroom Retrofit 2 2 2 2 2 2 Pico wireless control wireless corner-mount vacancy sensor 2 2 2 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Manual On Auto Off RMJS-6R-DV-B PowPak switching module 2 $ 29.00 Manual: Occupant uses wall switches to turn on and turn off general and white-board lighting. LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 All lights automatically turn off 5 minutes after all PJ2-2B-GWH-L0 Pico wireless 2-button control 2 $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 45% 20 2

Classroom New Construction Classroom New Construction DZ DZ DZ 2 2 2 Low-voltage DZ = Daylight Zone 2 2 2 Pico wireless control wireless corner-mount vacancy sensor and daylight sensor 2 2 2 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Manual On Auto Off RMJS-8T-DV-B PowPak dimming module with 0-0 V 3 $ 50.00 LRF2-DCRB-WH wireless daylight sensor $ 20.00 LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control 2 $ 2.00 Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone. Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights. All lights automatically turn off 5 minutes after all Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 Code Notes: For non-daylight classrooms, all general lighting can be connected to a single 0-0 V dimming module. Receptacle Control is required for Shop and Laboratory classrooms. This solution requires 0-0 V enabled ballasts and drivers by others. 60% 22 23

Classroom Recommended Classroom Recommended 2 2 2 integrated into each light fixture 2 2 2 Pico wireless control Pico wireless 4-button scene control Integral fixture control with sensor 2 2 2 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Manual On Auto Off Integral to fixture Integral fixture control with sensor 2 $ 70.00 2 PJ2-4B-GWH-L3 Pico wireless 4-button scene control $ 39.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control 2 $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter 3 $ 8.00. Fixture control comes pre-installed in fixture. Look for the Wireless symbol for fixtures containing this module. Go to lutron.com/findafixture for a complete list of compatible fixtures and drivers. 2. Fixture adder for the control module may vary. Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant selects scenes or uses dimmers to set desired light levels for all lights. Entry scene controller has 3 user preferred presets and all off button. All lights automatically turn off 5 minutes after all Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning Scene Scene Scene 2 Scene 2 Scene Scene 2 Scene Control Receptacle control is required for shop and laboratory classrooms. This solution requires digitally enabled ballasts and drivers by others. 65% 24 25

Conference Room Retrofit Conference Room Retrofit Pico wireless control wireless corner-mount vacancy sensor Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Manual On Auto Off RMJS-6R-DV-B PowPak switching module $ 29.00 Manual: Occupant uses wall switch to turn all lights off. LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 All lights automatically turn off 5 minutes after all PJ2-2B-GWH-L0 Pico wireless 2-button control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 40% 26 27

Conference Room New Construction Conference Room New Construction DZ DZ DZ Low-voltage DZ & DZ 2 = Daylight Zones DZ 2 DZ 2 DZ 2 Pico wireless control wireless corner-mount vacancy sensor and daylight sensor RMJS-8T-DV-B PowPak dimming module with 0-0 V 2 $ 50.00 LRF2-DCRB-WH wireless daylight sensor $ 20.00 LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control 2 $ 2.00 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant uses wall dimmer to set desired light levels for all lights. All lights automatically turn off 5 minutes after all Manual On Auto Off Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 For non-daylight conference rooms the lighting can be connected to a single 0-0 V dimming module. This solution requires 0-0 V enabled ballasts and drivers by others. 60% 28 29

Conference Room Recommended Conference Room Recommended DZ DZ DZ DZ & DZ 2 = Daylight Zones DZ 2 DZ 2 required for each light fixture required for each light fixture Pico wireless 4-button scene control wireless corner-mount vacancy sensor and daylight sensor DZ 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Manual On Auto Off Multiple EcoSystem-enabled Hi-Lume soft-on, fade-to-black series ballasts/drivers 0 $ 67.00 - $ 8.00 FCJS-ECO Wireless fixture control with EcoSystem 0 $ 75.00 LRF2-DCRB-WH wireless daylight sensor $ 20.00 LRF2-VKLB-P-WH wireless corner-mount vacancy sensor $ 85.00 Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant uses wall dimmer to set desired light levels for all lights. All lights automatically turn off 5 minutes after all Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning PJ2-4B-GWH-L3 Pico wireless 4-button scene control 2 $ 39.00 PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 Scene Scene Scene 2 Scene 2 Scene Scene 2 Scene Control Go to lutron.com/ballasttool or lutron.com/findafixture to identify the correct ballast or LED fixture for your project. 60% 30 3

Egress Corridor Retrofit Egress Corridor Retrofit To emergency power Pico wireless control wireless hallway RMJS-6R-DV-B PowPak switching module $ 29.00 LRF2-OHLB-P-WH wireless hallway $ 85.00 All non-emergency lights automatically turn on to maximum light level. Manual: Occupant uses wall switch to turn all non-emergency lights off. All non-emergency lights automatically turn off 5 minutes after all Auto On Auto Off PJ2-2B-GWH-L0 Pico wireless 2-button control 2 $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 40% 32 33

Egress Corridor New Construction Egress Corridor New Construction To emergency power Pico wireless control wireless hallway Low-voltage RMJS-8T-DV-B PowPak dimming module with 0-0 V $ 50.00 All lights automatically turn on to maximum light level. Maximum light level is set to 80%. Manual: Occupant uses wall dimmer to set desired levels for all lights. Manual control cannot fully shut off the lights. Minimum light level is set to 0%. Auto On Partial Off 85% Max: 00% Max: 85% High-end Trim/Tuning LRF2-OHLB-P-WH wireless hallway $ 85.00 All lights automatically go to minimum light level 5 minutes after all PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control 2 $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter 2 $ 8.00 Emergency Mode: Lighting connected to emergency power turns on to full output. Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for corridors with daylight zones. This solution requires 0-0 V enabled ballasts and drivers by others. Code Note: For non-egress corridors, set the minimum light level to full off. 60% 34 35

Open Office Retrofit Open Office Retrofit Pico wireless control wireless ceiling-mount RMJS-6R-DV-B PowPak switching module $ 29.00 LRF2-OCR2B-P-WH wireless ceiling-mount 4 $ 85.00 PJ2-2B-GWH-L0 Pico wireless 2-button control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 All lights automatically turn on to maximum light level. Manual: Occupant uses wall switch to turn all lights off. All lights automatically turn off 5 minutes after all Auto On Auto Off 35% 36 37

Open Office New Construction Open Office New Construction Low-voltage DZ DZ DZ DZ DZ = Daylight Zone Pico wireless control wireless ceiling-mount and daylight sensor RMJS-8T-DV-B PowPak dimming module with 0-0 V 2 $ 50.00 RMJS-20R-DV-B 20 A PowPak relay module $ 39.00 LRF2-DCRB-WH wireless daylight sensor $ 20.00 LRF2-OCR2B-P-WH wireless ceiling-mount 4 $ 85.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 All lights automatically turn on to 50% light level. Occupant turns on lights to maximum level manually. Maximum light level is set to 80%. Controlled receptacles automatically regain power when occupant enters. Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone. Manual: Occupant uses wall dimmers to set desired light levels for all lights. All lights automatically turn off 5 minutes after all 50% of all receptacles automatically turn off 5 minutes after all Partial On Auto Off Full On Dim Daylight Harvesting 85% Max: 00% Max: 85% High-end Trim/Tuning Appliance On Appliance Off Plug Load Control Code Notes: For non-daylight open offices, all general lighting can be connected to a single 0-0 V dimming module. This solution requires 0-0 V enabled ballasts and drivers by others. 50% 38 39

Open Office Recommended Open Office Recommended integrated into each light fixture Pico wireless control Integral fixture control with sensor Integral to fixture Integral fixture control with sensor 6 $ 70.00 2 RMJS-20R-DV-B 20 A PowPak relay module $ 39.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00. Fixture control comes pre-installed in fixture. Look for the Wireless symbol for fixtures containing this module. Go to lutron.com/findafixture for a complete list of compatible fixtures and drivers. 2. Fixture adder for the control module may vary. Each individual light automatically turns on to 50% light level as occupant approaches fixture proximity. Controlled receptacles automatically regain power when occupant enters. Automatic: Each individual overhead light dims/ brightens based on local daylight availability. Manual: Occupant uses wall dimmer to set desired light levels for all lights. Maximum light level is set to 80%. Each individual light automatically turns off 5 minutes after all occupants exit fixture proximity. 50% of all receptacles automatically turn off 5 minutes after all Partial On Auto Off Full On Dim Daylight Harvesting 85% Max: 00% Max: 85% High-end Trim/Tuning Appliance On Appliance Off Plug Load Control This solution requires digitally enabled ballasts and drivers by others. 60% 40 4

Private Office Retrofit Private Office Retrofit Pico wireless control wireless ceiling-mount vacancy sensor Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Manual On Auto Off RMJS-6R-DV-B PowPak switching module $ 29.00 Manual: Occupant uses wall switch to turn all lights off. LRF2-VCR2B-P-WH wireless ceiling-mount vacancy sensor $ 85.00 All lights automatically turn off 5 minutes after all PJ2-2B-GWH-L0 Pico wireless 2-button control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 30% 42 43

Private Office New Construction Private Office New Construction DZ DZ Low-voltage DZ & DZ 2 = Daylight Zones required for each light fixture Pico wireless control PowPak fixture sensor DZ 2 DZ 2 Lights do not automatically turn on when an occupant enters the space; lights must be turned on manually. Maximum light level is set to 80%. Manual On Auto Off FCJS-00 Wireless Fixture Control with 0-0 V 2 $ 75.00 RMJS-20R-DV-B 20 A PowPak relay module $ 39.00 FC-SENSOR PowPak Fixture Sensor 2 $ 35.00 PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 Controlled receptacles automatically regain power when occupant enters. Automatic: Overhead lights dim/brighten based on daylight availability. There are two perimeter daylight zones. Manual: Occupant uses wall dimmer to set desired light levels for all lights. All lights automatically turn off 5 minutes after all 50% of all receptacles automatically turn off 5 minutes after all Full On Dim Daylight Harvesting Full On Dim Personal Dimming 85% Max: 00% Max: 85% High-end Trim/Tuning Appliance On Appliance Off Plug Load Control FCJS models are capable of controlling up to 3 ballasts or drivers. Review the Vive PowPak Fixture Controls submittal document for more design details. This solution requires 0-0 V enabled ballasts and drivers by others. 60% 44 45

Multi-Stall Restroom Retrofit Multi-Stall Restroom Retrofit Pico wireless control wireless ceiling-mount RMJS-6R-DV-B PowPak switching module $ 29.00 LRF2-OCR2B-P-WH wireless ceiling-mount 2 $ 85.00 All lights automatically turn on to maximum light level. Manual: Occupant uses wall switch to turn all lights off. All lights automatically turn off 5 minutes after all Auto On Auto Off PJ2-2B-GWH-L0 Pico wireless 2-button control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 50% 46 47

Multi-Stall Restroom New Construction Multi-Stall Restroom New Construction Low-voltage Pico wireless control wireless ceiling-mount RMJS-8T-DV-B PowPak dimming module with 0-0 V $ 50.00 LRF2-OCR2B-P-WH wireless ceiling-mount 2 $ 85.00 All lights automatically turn on to maximum light level. Maximum light level is set to 80%. Manual: Occupant uses wall dimmer to set desired light levels for all lights. All lights automatically turn off 5 minutes after all Auto On Auto Off 85% Max: 00% Max: 85% High-end Trim/Tuning PJ2-3BRL-GWH-L0 Pico wireless 3-button with raise/lower control $ 2.00 PICO-WBX-ADAPT Pico wallbox adapter $ 8.00 Code Notes: Add a daylight sensor for restrooms with daylight zones. This solution requires 0-0 V enabled ballasts and drivers by others. 60% 48 49

Egress Stairwell New Construction Egress Stairwell New Construction To emergency power To emergency power wireless corner-mount A section of the floor is shown A floor cross-section is shown. One fixture per landing is suggested. FXSWLX4H Lutron 4 ft. stairwell LED fixture 2 (per floor) $ 540.00 All lights automatically turn on to maximum light level. Maximum light level is set to 80%. All lights dim to the minimum light level 5 minutes after all Minimum light level is set to 0%. Auto On Partial Off 85% Max: 00% Max: 85% High-end Trim/Tuning LRF2-OKLB-P-WH wireless corner-mount (per floor) $ 85.00 Emergency Mode: Lighting connected to emergency power turns on to full output. Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for stairwells with daylight zones. Lutron Stairwell Fixture (FXSWLX44) is not currently compatible with Vive wireless hub. A new model number is coming soon that will include Vive compatibility. Go to lutron.com/vive for the latest compatibility details. Code Notes: For non-egress stairwells, see the recommended solution and set the minimum light level to full off. 80% 50 5

Egress Stairwell Recommended Egress Stairwell Recommended To emergency power To emergency power Integrated into each light fixture wireless corner-mount Integral fixture control A section of the floor is shown A floor cross-section is shown. One fixture per landing is suggested. Integral to fixture Integral fixture control 2 (per floor) $ 60.00 2 All lights automatically turn on to maximum light level. Maximum light level is set to 80%. All lights dim to the minimum light level 5 minutes after all Minimum light level is set to 0%. Auto On Partial Off 85% Max: 00% Max: 85% High-end Trim/Tuning LRF2-OKLB-P-WH wireless corner-mount (per floor) $ 85.00 Emergency Mode: Lighting connected to emergency power turns on to full output.. Fixture control comes pre-installed in fixture. Look for the Wireless symbol for fixtures containing this module. Go to lutron.com/findafixture for a complete list of compatible fixtures and drivers. 2. Fixture adder for the control module may vary. Code Notes: Verify that the egress fixtures go to full output upon loss of control signal. For projects that require UL 924 compliance, provide an automatic load control relay (ALCR) per load controller connected to emergency fixtures. Add a daylight sensor for stairwells with daylight zones. This solution requires digitally enabled ballasts and drivers by others. Code Notes: For non-egress stairwells, set the low end to full off. 80% 52 53

, EcoSystem, Hi-Lume, Lutron, Maestro, Pico, PowPak, and Quantum are registered trademarks of Lutron Electronics Co., Inc. Energi Savr Node,, and Vive are trademarks of Lutron Electronics Co., Inc. lutron.com Lutron Electronics Co., Inc., 7200 Suter Road, Coopersburg, PA 8036-299 Customer Assistance Online: lutron.com/help Email: support@lutron.com Phone:.844.LUTRON (588.766) includes 24/7 technical support /206 Lutron Electronics Co., Inc. I P/N 367-2556 REV F