Frost Units for air temperature monitoring

Similar documents
QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Duct Temperature Sensors

Frost Protection Thermostat

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

1592P01. for liquids in piping DN

Room Temperature Controllers

Room thermostat with 24-hour time switch and large LCD

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Room thermostats with LCD RDD100..

Room Temperature Controller

Electronic timeswitch

Room Temperature Sensors

Room thermostat with independent DHW control

Wireless room thermostat with LCD

Use. For 2-pipe fan coils

Duct Temperature Sensors

Wall-mounted room thermostat with LCD

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

Room thermostat with Auto Timer, independent DHW

Flush-mounted room thermostat

Output module (230 V)

RAB21 RAB21.1. For two-pipe fan coils

RVL479. Heating Controller. for use with a partner unit

Manual call point. Sinteso Cerberus PRO FDM223H, FDM224H. 'Heavy Duty' manual call point addressed (FDnet/C-NET)

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

Semi flush-mount room thermostats

Multi line separator module

Flush-mounted room thermostats

Mimic display driver, LED ribbon cable

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

QAW70. Room Unit. Building Technologies. for use with heating controllers

Input module, input/output modules

Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

Room thermostat with Auto Timer, Option External Input

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Room thermostat with Auto Timer, Option External Input

OH720, OP720, HI720, HI722

13 tones to choose from, 2 programmable alarm levels Adjustable sound levels up to 93 dba

Input module, input/output module

DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

Manual call points. Sinteso / Cerberus PRO FDM225, FDM226

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

DM1101 / DM1103 / DM1104 DM1103-L / DM1103-S Manual call points Manual release button and emergency stop button

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

DM1131 / DM1133 / DM1134 Manual call points

Call stations and extensions

ASA linear smoke detector

Room thermostat with Auto Timer, Option External Input

Interbases. Sinteso FDSB221, FDSB228, FDSB229

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

SOL-LX-W, SOL-LX-C, RoLP-LX, RoLP Sounder, beacon, and sounderbeacon

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

FT2080 Fire terminal (Touch) Mounting Installation

FT2080 Fire terminal (Touch) Mounting Installation

Radio fire detection system

Application Sheet Fan coil unit with staged fan, heating and cooling coil (4 pipe) on triac output including lighting and blinds operation

Type 5347 (TR/STL), Type 5348 (TR/ST) and Type 5349 (STM/STL) Double Thermostats

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

Micro/Ultra Filtration System StamoClean CAT 430

Smart Thermostat RDS110

Application Sheet Chilled/heated ceiling (4 pipe) with 6-way valve on analog output

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

FDBZ290 Air sampling smoke detection kit

Room thermostat with Auto Timer, Option External Input

FDCW241 Radio gateway Mounting

REA22 Room Temperature Controller

FDA241, FDA221 Siemens ASD

FDBZ290 Air sampling smoke detection kit

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

FDOOT221, FDO221, FDT221

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

Digital Room Thermostat for Heating Applications with 7-Day Time Program

Fire control panels FC360

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure.

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Control Products & Systems OEM

Powers Controls ET 134 Low Temperature Detection Thermostat

DOW1171 / DCW1151 Radio fire detection system

DT1101A / DT1102A / DO110xA Automatic fire detectors

FDOOT241-9, FDOOT241-A, FDO241, FDT241

Heating and D.h.w. Controller RVL482 Basic Documentation

TC-5231 Series, TC-5232, & TC-5241 Series

DC1192 Input /Output module

Aquastats. Aquatrol Indoor/Outdoor Control. Automatic Changeover Switch 16/05/08

FDA241, FDA221 Siemens ASD

DM1153H-Ex / DM1154H-Ex Manual call point 'Heavy Duty'-Ex

for relative humidity and temperature

THERMASREG TR 040 THERMASREG TR 060

FDCL221-M Multi line separator module

Indoor Air Quality Controller

Capillary & Bulb Thermostatic Control & Fail-Safe Limit

Use. Functions. Key function. Other functions

RVL480. Heating Controller

Installation, operating and servicing instructions

Transcription:

284 284P0 Frost Units for air temperature monitoring QAF8... Robust aluminium die-cast housing Responds to temperature change sensed over any 30 cm length of capillary Small switching differential Good repeatability Setpoint adjustment ( 5... 5 C) Protection standard IP54 (65) Use The frost unit QAF8... for air-side monitoring of the temperature of LTHW heating coils in ventilation and air conditioning systems is used to prevent frost damage. It has a small switching differential and good repeatability. The reset occurs automatically (manual reset required with QAF8.6M). Typical applications The frost unit can be used to initiate the following frost protection functions: Stop fan Close outside air dampers Open heating coil valve 00 % Start heating coil pump Switch off chiller (condenser) and humidifier Trip visual and/or audible frost alarm CAN284en 206-02-09 Building Technologies

Type summary Typ reference Reset Capillary length QAF8.3 automatic reset 3 m QAF8.6 automatic reset 6 m QAF8.6M with lock-out and manual reset 6 m Accessories Name Capillary tube clamp (6 pieces) Typ reference FK-TZ Ordering and delivery When ordering, please give name and type reference, e.g. frost unit QAF8.6M. The QAF8... frost unit is supplied complete with FK-TZ (capillary tube clamps). If necessary a M20 cable gland for cable entry of the M20x.5 type can be fitted to achieve class IP65. This cable gland is not supplied with the delivery. Technical design The frost unit QAF8... trips when the temperature drops below the selected setpoint over a capillary length of 30 cm. An automatic reset occurs when the temperature rises above the setpoint again (manual reset required with QAF8.6M). The (R34a) gas-filled capillary and the diaphragm assembly together form the measuring element, which is mechanically linked to the micro-switch. The temperature is measured over the full length of the capillary. Normal position SD 2 4 284D0 Frost alarm 0 Cold w Warm T 2 4 Legend. SD Switching differential T Air temperature w Preselected setpoint Mechanical design The frost unit QAF8... has the following parts: Die-cast aluminium housing with removable cover Mechanical setpoint adjuster with scale in Celsius and Fahrenheit (setpoint adjustment screw can be locked mechanically) Micro-switch for change-over contact Sensor unit with diaphragm assembly and copper capillary Capillary filled with R34a gas The QAF8.6M has a manual reset button 2/6

Engineering notes Withdrawable tray: It is recommended that the frost unit QAF8... should be installed on a purpose-built withdrawable tray directly downstream of the heating coil. The connecting cable must be long enough to enable the tray to be inserted and removed without difficulty. For heating coils with very large cross-sections, a number of frost units can be fitted and connected in series. In this case, the setpoint must be set individually on each frost unit. Fitting notes Frost thermostat Capillary The ambient temperature affecting the frost unit housing (with the test loop) must be at least 2 C above the pre-selected setpoint. If this cannot be guaranteed (e.g. outdoors or in exposed spaces), the housing and test loop must be installed inside the supply air unit. The capillary must be mounted on the downstream side of the heating coil (and on the upstream side in the case of coiling coils). It should be looped diagonally across the heat exchanger pipes at a distance of approximately 5 cm, and should cover the entire area evenly. For test purposes, it is advisable to leave a loop of approximately 20 cm directly beneath the housing outside the entry to the duct. To prevent damage to the capillary it should be protected by grommets or similar where it passes through metal walls. To prevent damage to the capillary, a minimum bending radius of 20 mm must be ensured. Mounting is easier if the capillary tube clamps (FK-TZ or AQM63.3) are used. Commissioning notes After removal of the locking screw (under the housing cover) the setpoint can be adjusted from above with a screwdriver. Frost simulation To simulate frost conditions, the test loop can be immersed in a vessel of iced water. To simulate frost with the frost unit QAF8.6M, push in the reset button (on the housing base). 3/6

Maintenance notes The frost unit is maintenance-free. Correct operation of the device can be checked by immersing the test loop in a vessel of iced water. Disposal notes The devices are considered electronics devices for disposal in terms of European Directive 202/9/EU and may not be disposed of as domestic waste. Dispose of the device via the channels provided for this purpose. Comply with all local and currently applicable laws and regulations. Technical data Setpoint adjustment range W h Factory setting w Switching differential SD Repeatability Responsive length of sensor Capillary length Type of switch Contact rating Reset mechanism External supply line protection (EU) 5... 5 C (23...59 F) 5 C (4 F) 2 C (3.6.8 F) 0.5 C ( 0.9 F) Approx. 0.3 m refer to "Type summary" Single pole change-over AC 250 V, 5(.2) A DC 30 V, 5(.5) A QAF8.3, QAF8.6 Automatic QAF8.6M Manual Fuse slow max. 0 A or Circuit breaker max. 3 A Characteristic B, C, D according to EN 60898 Admissible medium Orientation Air Any Electrical connection Screw terminals for.5 mm2 Cable entry Threaded M 20 x.5 Protection class I to EN 60 730- Protection degree of housing IP54 to EN 60 529 with cable gland (M20x.5 IP65) IP65 to EN 60 529 (not included as standard) Product standard EN 60730- EU Conformity (CE) Environmental compatibility Ambient temperature Max. operating temperature Min. operating temperature Storage Destruction limit t smax Materials Housing Bellows housing Capillary Capillary contents Contacts Weight (including packaging) Maintenance CAT284xx*) The product environmental declarations OE-T-99.4767d and 07_OE-T-99.4767e *) contain data on RoHS compliance, materials composition, packaging, environmental benefit and disposal 70 C (58 F) w + min. 2 C (min. 3.6 F) 30... 70 C ( 22... 58 F) 40 C (284 F) Die-cast aluminium Copper Copper Freon R34a Ag (Silver) 0.9 kg None required *) The documents can be downloaded from http://siemens.com/bt/download. 4/6

Connection terminals 2 4 T 284G0 Legend 2 Frost alarm / sensor short circuit 4 Normal operation Dimensions (dimensions in mm) QAF8... 06 9 37 284M0 AQM63.3 4,2 25 69 3 85 62 284M0 50 3,7 ø3 6000 (3ooo) or FK-TZ 5/6

Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 630 Zug Switzerland Tel. +4 4-724 24 24 www.siemens.com/buildingtechnologies Siemens Switzerland Ltd, 2005 Technical specifications and availability subject to change without notice. 6/6