GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

Similar documents
GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

BK 46. Installation Instructions Steam Trap BK 46

GESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45

TRG 5-6x. GESTRA Steam Systems. Installation Instructions

MK 45 A. Stainless Steel Design. Installation Instructions Steam Trap MK 45 A

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

GESTRA Steam Systems NRGS 11-2, NRGS Installation Instructions Level Electrode Types

SMK 22 SMK SMK SMK 22-82

BK 45 BK 45-U BK 45-LT BK 46

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

NRG NRG NRG NRG

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld

GESTRA. Program for Universal Connections. The Smart Solutions

Temperature Sensor TRG Original Installation Instructions English

Level Electrode NRG NRG Original Installation Instructions English

Level Electrode NRG Original Installation Instructions English

Conductivity Electrode LRG Original Installation Instructions English

Installation & Operating Instructions

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

GESTRA Steam Systems OR Installation Instructions Oil & Turbidity Detector OR 52-7

Steam Traps and Steam Trap Testing

Model: 1100 Float-Controlled Condensate Trap, PN 25

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100

GESTRA Information A 1.5

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

Mechanical seals external, single or double, to DIN EN 12756

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

1592P01. for liquids in piping DN

Flow switch. Operating Manual. English manual page Page 1 of 15 Fax:

GESTRA Information A 1.7

GESTRA. Steam Traps and Steam Trap Testing. For all applications

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Operating and installation instructions

Ball Float Steam Trap with Integral Spiratec Sensor and Flanged Connections

FLOAT AND THERMOSTATIC STEAM TRAPS FLT17 (DN 1/2 to 1 ; DN15 to DN25)

1592P01. for liquids in piping DN max. DC 48 V, 1 A, 20 W

GESTRA. Product Overview. The optimum components for every application

INSTRUCTIONS CertoClav EL

Water level controller and limiter

GESTRA. Product Overview. The optimum components for every application

Product overview. the optimum components for every application

Care and Maintenance

THERMODYNAMIC STEAM TRAP

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

Installation and Maintenance Manual

FSW300 Series Flow Switch

Installation, operating and servicing instructions

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

MFP14 Automatic pumps. for condensate and other industrial fluids

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

FT14 Ball Float Steam Trap (Screwed)

! WARNING. Before using product, read and understand instructions.

Installation and Maintenance Manual Forbes Marshall Bucket Trap FMBT50

INSTALLATION, OPERATION

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

FT14 and FT14HC. SG Iron Ball Float Steam Traps (1" HC, 1¼", 1½" and 2")

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

VC-1, VC-1-SL, VC-2-L, VC-2-SL

MFP14 Automatic pumps for condensate and other industrial fluids

Installation manual extra-low-voltage socket outlets for panel- and surface-mounting

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

GESTRA. Steam traps and monitoring equipment. The right choice in every case

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Water Safety Shut-Off Valve HON 790. Product information. serving the gas industry worldwide

SCHMIDT Flow Sensor SS Ex - Supplementary instructions for use in explosive atmospheres ATEX

TECHNICAL DATA. Wet 26a. February 22, 2009

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Quick Start Guide , Rev. BB February Rosemount 1495 Orifice Plate Rosemount 1496 Orifice Flange Union

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

AIC Series Float & Thermostatic Steam Trap Installation and Maintenance Instructions

Mechanical Seal RG-4 stationary, double, liquid sealed

Inverted Bucket Steam Traps

Friwa Compact. Operating instructions EN

Series 1140 and 1141 Temperature Regulators

Rosemount 1595 Conditioning Orifice Plate

Installation and maintenance instructions

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

Self-operated Temperature Regulators Series 43 Temperature Regulators Type 43-1 Type 43-2

HKF 8180 Operating instructions

Catalog. Self-operated Regulators Volume 2 Temperature Regulators

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER

Bedienungsanleitung. Fass-, Behälter- und Containerpumpen. F dichtungslos. F ,98% Fassentleerung. F

CalMag Filter Installation Instructions

Zip Econoboil. On wall boiling water. Installation instructions & user manual. Model number: ,

Safety. Operating instructions Ionization pilot burners ZAI, ZMI, ZKIH DANGER. Contents WARNING CAUTION Edition 12.11

Supplementary Installation and Operating Instructions. Category II2G

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Betriebsanleitung Operating Instructions

205 Control Installation and Maintenance Instructions

Transcription:

GESTRA Steam Systems BK 15 Installation Instructions 810682-02 Steam Trap BK 15, DN 40-50

Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 PED (Pressure Equipment Directive)...4 ATEX (Atmosphère Explosible)...4 Explanatory Notes Scope of supply...5 Description...5 Function...5 Design...5 Technical Data Pressure / temperature ratings...6 Corrosion resistance...6 Sizing...6 Name plate / Marking...6 Design Component parts BK 15...7 Key...8 Installation BK 15...9 Flanged design...9 Socket-weld design...9 Butt-weld design...9 Attention...10 Heat treatment of welds...10 Commissioning BK 15...11 Danger...11 Adjusting regulator (undercooling, controlled steam flowrate)...11 Restoring factory setting...11 Tools...11

Contents continued Operation Page BK 15...12 Maintenance Checking steam trap...12 Cleaning / replacing regulator and strainer...12 Tools...12 Torques...13 Spare Parts Spare parts list...13 Annex Declaration of Conformity...14

Important Notes Usage for the intended purpose Use steam trap BK 15 only for the discharge of condensate in steam lines or for air venting. Use this equipment only within the specified pressure and temperature ratings and check corrosion resistance and chemical suitability for the application in question. Safety Note The equipment must only be installed and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who through adequate training have achieved a recognised level of competence. Danger The steam trap is under pressure during operation. When loosening flanged connections, sealing plugs or the regulator hot water or steam may escape. This presents the danger of severe scalds to the whole body. Installation and maintenance work should only be carried out when the system is depressurized: isolate the trap from both upstream and downstream pressure. The steam trap becomes hot during operation. This presents the risk of severe burns to hands and arms. Installation and maintenance work should only be carried out at room temperatures. Sharp edges on internals present a danger of cuts to hands. Always wear industrial gloves for installation and maintenance work. Attention The name plate indicates the technical specification of the equipment. Do not commission or operate a steam trap without a name plate. PED (Pressure Equipment Directive) The equipment fulfills the requirements of the Pressure Equipment Directive PED 97/23/EC. Applicable with fluids of group 2. According to section 3.3 the equipment is excluded from the scope of this directive and must therefore not be CE marked. ATEX (Atmosphère Explosible) The equipment does not have its own potential source of ignition and is therefore not subject to the ATEX Directive 94/9/EC. The equipment can be used in potentially explosive areas 0, 1, 2, 20, 21, 22 (1999/92/EC). The equipment is not Ex marked. 4

Explanatory Notes Scope of supply BK 15 1 Steam trap type BK 15 1 Installation manual Description Thermostatic/thermodynamic steam trap with corrosion-resistant regulator unaffected by waterhammer. The Duo stainless steel regulator is externally adjustable. With integral strainer and nonreturn valve action. Asbestos-free cover gasket (graphite). Installation in any position. The steam trap is adjusted at our factory to discharge condensate with virtually no banking-up. More undercooling (banking-up of condensate) can be manually adjusted during operation from the outside. Function During start-up of the plant the Duo stainless steel plates are flat. The service pressure acts in the opening direction, the valve is completely open. As the condensate temperature rises, the plates deflect, drawing the stage nozzle towards the closed position. As the condensate temperature sinks, the deflection of the Duo stainless steel plates decreases and the steam trap opens at the adjusted opening temperature. The thermostatic and spring characteristics of the stack of plates are balanced such that condensate is always discharged at a given undercooling temperature. The trap provides automatic air-venting at start-up and during operation. The correct functioning of the BK 15 is neither affected by upstream pressure variations nor by back pressure. The BK 15 can also be used for thermal air-venting in steam systems. Design BK 15 Version for installation in horizontal and vertical lines. 5

Technical Data Pressure/temperature ratings BK 15 For pressure/temperature ratings see specification on trap body or name plate: Pressure class PN/Class, material number, max. temperature, max. pressure, max. differential pressure. Corrosion resistance When used for its intended purpose the safe functioning of the steam trap will not be impaired by corrosion. Sizing The valve body must not be subjected to pulsating loads. The dimensional allowances for corrosion reflect the latest state of technology. Name plate / Marking The pressure / temperature ratings are indicated on the trap body / the name plate. For more information see GESTRA data sheets and Technical Information. According to EN 19 the name plate and the valve body indicate the type and design: Name / logo of the manufacturer Type designation Pressure class PN or Class Material number Max. temperature Max. pressure Flow direction 3 Stamp on trap body, e. g. specifies the quarter and the year of production 05 (Example: 3 rd quarter 2005). Nominal size Ratings acc. to EN ISO 26552 Thermovit regulator Standard design U 30 K undercooling Fig. 1 6

Design Component parts BK 15 N A B C D E F G H I J K Fig. 2 M L 7

Design continued Key A Union nut ¾" BSP B Gland ring C Packing 9 x 14 x 7 D Cover E Adjusting screw F Guide ring G Thermovit regulator H Strainer I Bush (force-fit, no spare part) J Cover gasket 92.7 x 102 x 1 K Body L Name plate M Hexagon nut M 12 N Hexagon bolt M 12 8

Installation BK 15 The steam trap BK 15 can be installed in any position, taking the flow arrow into account. In the case of a horizontal installation, make sure that the cover is on top. Flanged design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 90 mm is required for removing cover D. 4. Remove plastic plugs. They are only used as transit protection. 5. Clean seating surfaces of both flanges. 6. Install steam trap. Socket-weld design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 90 mm is required for removing the cover D. 4. Remove plastic plugs. They are only used as transit protection. 5. Remove regulator as described under Maintenance. 6. Clean socket-weld ends. 7. Arc-weld trap (welding process 111 and 141 in accordance with DIN EN 24063) in place. Butt-weld design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 90 mm is required for removing the cover D. 4. Remove plastic plugs. They are only used as transit protection. 5. Clean butt-weld ends. 6. Arc-weld trap in place (welding process 111 and 141 in accordance with DIN EN 24063) or use gas-welding process (welding process 3 in accordance with DIN EN 24063). 9

Installation continued Attention Heat treatment of welds n Only qualified welders certified e. g. according to DIN EN 287 may weld the steam trap into pressurized lines. n Do not insulate the steam trap. A subsequent heat treatment of the welds is not required provided that the pipe is made from a material that is similar to that used for the trap body. If a particular pipe material makes a heat treatment necessary make sure the heat treatment is restricted to the close vicinity of the weld. Should this not be possible remove the Thermovit regulator before carrying out the heat treatment. 10

Commissioning BK 15 Make sure that all flange bolts are firmly fastened, ensuring tight shut-off. Danger The steam trap is under pressure at start-up and during operation. When loosening the union nut A hot water or steam may escape. This presents the danger of severe burns and scalds to the whole body. The steam trap becomes hot during operation. This presents the risk of severe burns to hands and arms. Installation and maintenance work should only be carried out at room temperatures. Always wear industrial gloves when adjusting the regulator. Adjusting regulator (undercooling, controlled steam flowrate) The regulator of the BK 15 is adjusted at our factory to close steam-tight and open as soon as condensate is formed. If a certain undercooling and, consequently, banking-up of condensate is required for e. g. a heating process, the trap setting can be modified at start-up and during operation: 1. Take notice of the danger note. Slacken union nut A (one turn) and turn adjustment screw E clockwise with a screwdriver. 1/8 turn corresponds to approx. 4 K (degc) change in discharge temperature. Starting from factory setting you can turn the adjustment screw E up to 1.5 turns to the right. 2. If required you can also adjust a controlled steam flowrate. Starting from factory setting turn the adjustment screw E for this purpose 1.5 turns to the left. 3. Tighten union nut A with the torque indicated in the table Torques on page 13. Restoring factory setting The regulator of the BK 15 is adjusted at our factory to close steam-tight and open as soon as condensate is formed. If necessary, the factory setting can be restored as follows: 1. To depressurize the steam trap cut off steam and in the case of back pressure condensate line(s). Let the trap cool down to room temperature. 2. Undo union nut A and turn adjustment screw E with a screwdriver clockwise until a resistance is felt. 3. Turn adjustment screw E 3 turns anticlockwise. The steam trap will now discharge condensate with virtually no banking-up (factory setting). 4. Tighten union nut A with the torque indicated in the table Torques on page 13. Tools n Screwdriver 5.5/100 mm to DIN 5265, form A n Spanner A.F. 36 mm to DIN 3113, form B n Torque spanner 20 160 Nm to DIN ISO 6789 11

Operation BK 15 The BK 15 can be serviced (see Maintenance). Maintenance GESTRA steam traps type BK 15 do not require any special maintenance. However, if used in new installations which have not been rinsed it may be necessary to check and clean the trap. Checking steam trap You can check the steam trap BK 15 for steam loss during operation using the ultrasonic measuring unit VAPOPHONE or the test unit TRAPtest. Should you detect any loss of live steam clean the trap and/or replace the regulator. Cleaning / replacing regulator and strainer 1. Take notice of the note Danger on page 4. 2. Undo hexagon bolts N. Remove cover D from the body K. 3. Remove and clean regulator G. 4. Remove and clean strainer H. 5. Clean body K, internals and all gasket surfaces. 6. Replace regulator G in case of visible signs of wear or damage. 7. Apply heat-resistant lubricant to all threads and the seating surface of the nozzle insert and the cover (use for instance WINIX 2150). 8. Insert new gasket J. 9. Insert strainer H. 10. Screw in regulator G and tighten with the torque indicated in the table Torques. 11. Place cover D onto the body K. Tighten hexagon bolts N with hexagon nuts M in diagonally opposite pairs to the torque indicated in the table Torques. Tools n Spanner A. F. 32 mm to DIN 3113, form B n Spanner A. F. 18 mm to DIN 3113, form B n Torque spanner 20 120 Nm to DIN ISO 6789 WINIX 2150 is a registered trademark of WINIX GmbH, Norderstedt 12

Maintenance continued Torques Item Designation Torque [Nm] G Thermovit regulator 140 N M Hexagon bolts / nuts 45 A Union nuts 30 All torques given in the table are based at a room temperature of 20 C. Threads without lubricant. Spare Parts Spare parts list Item Designation Stock code Stock code C Packing*) 9 x 14 x 7 376552 376552 C G J Thermovit regulator, gasket kit 098847 098847 H J Strainer, body gasket 375698 375698 J Body gasket*) 92.7 x 102 x 1, graphite 375699 375699 *) Minimum purchasing quantity 20 pcs. For smaller quantities please contact your local dealer. 13

Annex Declaration of Conformity We hereby declare that the pressure equipment BK 15 conforms to the following European Directive: n EC Pressure Equipment Directive (PED) No. 97/23 of 29 May 1997, unless excluded from the scope of the Directive acc. to section 3.3. n Applied conformity assessment procedure: Annex III, module H, verified by the Notified Body 0525. This declaration is no longer valid if modifications are made to the equipment without consultation with us. Bremen, 26 th September 2006 GESTRA AG Head of the Design Dept. Uwe Bledschun Academically qualified engineer Quality Assurance Representative Lars Bohl Academically qualified engineer 14

For your notes 15

GESTRA Agencies all over the world: www.gestra.de España GESTRA ESPAÑOLA S.A. Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 34 91 / 5 15 20 32 Fax 00 34 91 / 4 13 67 47; 5 15 20 36 E-mail: aromero@flowserve.com Polska GESTRA Polonia Spolka z.o.o. Ul. Schuberta 104 PL - 80-172 Gdansk Tel. 00 48 58 / 3 06 10-02 od 10 Fax 00 48 58 / 3 06 33 00 E-mail: gestra@gestra.pl Great Britain Flowserve Flow Control (UK) Ltd. Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 57 E-mail: gestraukinfo@flowserve.com Portugal Flowserve Portuguesa, Lda. Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0 03 51 22 / 6 19 87 70 Fax 0 03 51 22 / 6 10 75 75 E-mail: jtavares@flowserve.com Italia Flowserve S.p.A. Flow Control Division Via Prealpi, 30 l-20032 Cormano (MI) Tel. 00 39 02 / 66 32 51 Fax 00 39 02 / 66 32 55 60 E-mail: infoitaly@flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel.: 00 15 02 / 267 2205 Fax: 00 15 02 / 266 5397 E-mail: dgoodwin@flowserve.com GESTRA AG P. O. Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Telephone +49 (0) 421 35 03-0 Fax +49 (0) 421 35 03-393 E-Mail gestra.ag@flowserve.com Internet www.gestra.de 810682-02/407cm 2001 GESTRA AG Bremen Printed in Germany 16