Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

Similar documents
TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

SELECT-A-HORN/STROBE SERIES

CSH24CH. Colored Light Strobe/Horn Series High Candela. Description. Features. Ceiling/Wall Mount Patent Pending. Ordering Information

TrueAlert Multi-Candela Notification Appliances

Field Configurable Horns and Strobes

Field Configurable Horns and Strobes

TrueAlert Notification Appliances

Addressable Detectors & Bases

Dimensions of the Optional Mounting Box (BB-400R/W)

Genesis LED G1 Series

s Notification Appliances

L-Series, Emergency Communication Devices

L-Series, Indoor Strobes and Horn Strobes

MEA. SpectrAlert Series Horns, Strobes, and Horn/Strobes GENERAL

SIGA-CC1 Single Input Signal Module Installation Sheet

TrueAlert Addressable Notification Appliances

SpectrAlert Advance. Field-Selectable Mass Notification Devices. Description. An ISO Company SIGNALING. MEA Approved E

Print Specification. Publication. Instructions. Specific requirements. General requirements

L-Series, Indoor Strobes and Horn Strobes

FX-PDD Duct Smoke Detector Installation Sheet

TrueAlert Addressable Notification Appliances

1 Watt Supervised Self-Amplified Strobe Speakers Round Flush Grille with 75cd Strobe

TrueAlert Multi-Candela Notification Appliances

ELECTRONIC SOUNDER STROBE Model : AVD-C407

*15cd models are Listed at 15cd and meet 75cd on axis

Potter Wall Mount Select-A-Strobe

TrueAlert Addressable Notification Appliances

08 Series Notification Appliances AS / AH & AS Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

Selectable Output Chimes and Chime/Strobes

'08 Series Notification A liances

Installation Instructions Model ABHW-4S

Signature Series Auto-Sync Output Module (CC1S)

Wheelock RSS & RSSP Series

LifeAlarm Fire Alarm Control Panels

Booster Power Supply Manual

SECTION FIRE ALARM SYSTEMS

Speakers and Speaker Strobes

The Advance You ve Been Looking For

LifeAlarm Fire Alarm Controls

Fire Safety. Installation Instructions. Model ADBX-11. Audible Base INTRODUCTION. Model ADBX-11

Installation Instructions for 116DEGEX-FJ-(R) AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations

WARNING WARNING. Installation Instructions for 116DEXSTC-FJ AdaptaBeacon Fire Alarm Strobe Lights for Use in Hazardous Locations.

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Table 1: dba Ratings for AMT Multitone Signal Typical Anechoic dba at 10 Feet per CAN/ULC S525-07

TrueAlert ES Addressable Notification Appliances

INSTRUCTION & SERVICE MANUAL

Addressable NAC Output Module D327A

L-Series Audible Visible Notification PRODUCTS. Accessories Chimes Chime Strobes ECS and MNS Horns Horn Strobes Speakers Speakers Strobes Strobes

Life safety notification

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

Conventional Smoke Detectors KFAPO

Agent Release Control Panel

TrueAlarm ES Analog Sensing

R-Series Remote Annunciators and Expanders Installation and Operation Guide

GEC Low-frequency Horn Strobes

Signaling Devices. Acoustic Signaling Devices 298. Optical Signaling Devices 309. Bosch Security Systems B.V.

EVA-SCM-SCI Sounder Control Module

good things in small packages

30.45 Electric Release PDRP-2001

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Notification Appliance Circuit Module

1. POWERPATH Operation

ESL 500N Series Smoke Detector Installation Sheet

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

TrueAlert Addressable Notification Appliances

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Addendum for STI-6406 with Dual Access Control

Exit Stopper. STI-6400 Series

FIRE ALARM Submittal DR. PECK FHM DAYTONA 4TH FL 125 MEMORIAL MEDICAL PARKWAY DAYTONA BEACH, FL 32117

RCR-REX Request-to-Exit Dual Technology Motion Sensor Installation Guide

Multiple Input and Output Modules

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

July 14, 1999 DF C-100.

AL800ULADA. NAC Power Extender. Installation Guide

ANNUNCIATOR FIXED MODULE

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

D7052. Installation Instructions Multiplex Dual Input Module

advancedsolutions Advanced Design. We have engineered all SpectrAlert products to meet or exceed code today and tomorrow. We ve worked to standardize

Exit Stopper. STI-6400 Series

TrueAlert Addressable Notification

Addressable Fire Alarm Control Panel

Signature Series Component

MR-2602 Two Zone Fire Alarm Control Panel

AL600ULADA. NAC Power Extender. Installation Guide

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

Yodalarm. Sounders. Pg Y03 Y04/YL4 Y05/YL5 Y08/YL8/Y08 SUPER/ YL8 SUPER V4 V6/Y06/YL6 Carillon

E-FSC. Conventional Fire Alarm Control Panels. Standard Features. Overview

TECHNICAL DATA OBSOLETE

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

X10 Mini, Midi & Maxi

(EN) RevC AS610-AS630 Outdoor Siren Installation Sheet.pdf. Remark: Rev. Date: Modif. no.

Specification/ Data Sheet

GE Security Fire & Life Safety F-DACT(F) Digital Alarm Communicator Transmitter Installation Sheet

Remote Booster Power Supply Technical Reference Manual

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

System Sensor L-series indoor horn/ strobes

PSN-1000 & PSN 1000(E) Installation Manual

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Transcription:

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet Table 1: Models Description Low frequency (520 Hz) horn, white housing, no FIRE marking, standard output clear strobe light Low frequency (520 Hz) horn, white housing, with FIRE marking, standard output clear strobe light Low frequency (520 Hz) horn, red housing, no FIRE marking, standard output clear strobe light Low frequency (520 Hz) horn, red housing, with FIRE marking, standard output clear strobe light Surface wall mount box, white housing Surface wall mount box, red housing Number G4LFWN-HVM G4LFWF-HVM G4LFRN-HVM G4LFRF-HVM G4B G4RB This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971. Synchronized operation requires a separately installed synchronization device. See the control panel or power supply compatibility list for compatible synchronization devices. Description The Genesis Low Frequency (520 Hz) Horn-Strobe can be used for applications where a low frequency alarm notification appliance with strobe light output is required. The device is designed for wall mounting and indoor use only. See Table 1 for a list of model numbers. When this device is used as a low frequency sounder in sleeping quarters, the strobe's candela switch (Figure 1) must be set to 110 cd. The horn-strobe includes field-configurable jumper options for selecting: Temporal or steady horn output Low db or high db output Temporal or continuous pattern strobe The horn-strobe also includes a field-configurable switch for setting the strobe candela level. This setting is locked in place and is visible after final installation. Installation Install and wire this device in accordance with applicable national and local codes, ordinances, and regulations. The horn-strobe should be mounted so that the entire lens is not less than 80 in. (2.03 m) and not greater than 96 in. (2.44 m) above the finished floor. The entire lens should also be 24 in. (61 cm) or more from the finished ceiling. WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment. Note: Electrical supervision requires that you break the wire run at each terminal. Do not loop wires around the terminals. 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 3102149-EN REV 02 ISS 25MAR14

To install the horn-strobe: Figure 1: Horn-strobe settings 1. Remove the cover by using a screwdriver to depress and slightly twist both tabs on top of the unit. 2. Set the horn signal, sound output level, and strobe signal to the desired settings. See Figure 1. To change the horn output level from high db to low db, cut jumper JP3. To change the horn signal from temporal to steady, cut jumper JP2. To change the strobe pattern from continuous to temporal (private mode), cut jumper JP1. 3. Set the candela output. Slide the candela switch to the desired candela output by aligning it with the indicator notch below the switch. See Figure 1. 4. Mount the horn-strobe as follows. Note: Route the signal circuit field wiring through the cutout in the center of the horn-strobe. Flush mount: Mount the horn-strobe and flush mount spacer onto a compatible electrical box (Figure 2), making sure not to overtighten the mounting screws. See Specifications for compatible electrical boxes. Surface mount: Mount the G4B or G4RB surface mount box on the wall (Figure 3), and then secure the appliance to the box using the fasteners provided with the box. 5. Connect the signal circuit field wiring to the horn-strobe terminals (Figure 4). Observe polarity for the unit to function properly. 6. Replace the cover by aligning it at the bottom, and then snapping it in at the top. 7. Test the unit for proper operation. Maintenance Caution: To maintain the required agency listings, do not change factory-applied finishes. (1) Jumper JP3 (2) Jumper JP2 Figure 2: Flush mount (3) Jumper JP1 (4) Candela switch indicator notch This unit is not serviceable or repairable. Should the unit fail to operate, contact the supplier for a replacement. Perform a visual inspection and an operational test twice a year or as directed by the local authority having jurisdiction. (1) Compatible electrical box (2) Flush mount spacer (3) Horn-strobe (4) 8-32 x 1 in. screw, provided (2X) (5) Cover 2 / 6 P/N 3102149-EN REV 02 ISS 25MAR14

Figure 3: Surface mount (1) Surface mount box (G4B or G4RB) (2) Horn-strobe Figure 4: Wiring diagram (3) Screw (4X provided with G4B or G4RB box) (4) Cover Specifications Operating voltage 24 VDC or 24 VFWR [1] Operating horn-strobe current See Table 6 Sound level output See Table 2 and Table 3 Audible directional characteristics Light output Synchronization Default settings Wire size Compatible electrical boxes Operating environment Temperature Relative humidity See Table 4 and Table 5 Selectable at 15, 30, 75, and 110 cd (see Figure 5, Figure 6, and Figure 7) [2] Maximum allowed resistance between any two devices is 20 Ω. Refer to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire resistance. 1 flash per second (fps) 12 to 18 AWG (1.0 to 4.0 mm²) Standard 4 in. square box 1-1/2 in. (38 mm), 2-1/8 in. (54 mm) deep, or G4B/G4RB surface mount box 32 to 120 F (0 to 49 C) 0 to 93% noncondensing [1] This device was tested to the Regulated 24 DC/FWR operating voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these values for system operation. [2] When this device is used as a low frequency sounder in sleeping quarters, the strobe's candela switch (Figure 1) must be set to 110 cd. Table 2: UL sound level output (dba) [1] Signal and voltage Low High Temporal 16 VDC 72.4 76.0 24 VDC 72.3 75.7 33 VDC 73.3 75.4 Continuous 16 VDC 75.7 79.8 24 VDC 76.1 78.6 33 VDC 75.4 78.8 [1] UL 464: Sound level output at 10 ft. (3.05 m) measured in a reverberant room. (1) From NAC output (2) To next device or EOL Note: Polarity is shown in the active condition. Table 3: Nominal sound level output (dba, temporal tone) [1] Voltage Low High 16 VDC 84.0 85.5 24 VDC 83.9 85.4 33 VDC 83.7 85.5 16 VFWR 83.7 86.1 24 VFWR 83.9 85.9 33 VFWR 84.0 85.9 [1] Measured in an anechoic chamber at 10 ft. (3.05 m). P/N 3102149-EN REV 02 ISS 25MAR14 3 / 6

Table 4: Audible directional characteristics (horizontal pattern) Angle ( ) [1] Output (db) [2] 0 85 +90 82-90 82 Figure 5: UL 1971 minimum light output (% of rating vs. angle) [1] Angles are measured from a perpendicular axis; positive angles to the right. [2] Peak output at 16 VDC, set for steady tone. Table 5: Audible directional characteristics (vertical pattern) Angle ( ) [1] Output (db) [2] 0 85 +90 82-90 82 [1] Angles are measured from a perpendicular axis; positive angles are up. [2] Peak output at 16 VDC, set for steady tone. Table 6: Nominal operating horn-strobe current in RMS (ma) Voltage Strobe output (cd) 15 30 75 110 Temporal 16 VDC 219 266 381 437 16 VFWR 308 362 510 579 24 VDC 151 176 243 278 24 VFWR 228 258 349 395 33 VDC 112 132 177 199 33 VFWR 186 208 267 291 Continuous 16 VDC 221 258 371 433 16 VFWR 305 358 514 576 24 VDC 147 171 239 274 24 VFWR 211 247 335 377 33 VDC 110 129 175 196 33 VFWR 178 199 257 287 (1) Angle (2) Minimum UL required candela light output % of rated candela vertical specification - - - - % of rated candela horizontal specification Figure 6: Typical horizontal light output profile, 110 cd setting VDC = Volts direct current, regulated and filtered VFWR = Volts full wave rectified (1) Intensity (cd) (2) UL minimum requirement (cd) 4 / 6 P/N 3102149-EN REV 02 ISS 25MAR14

Figure 7: Typical vertical light output profile, 110 cd setting (1) Intensity (cd) (2) UL minimum requirement (cd) Regulatory information Manufacturer Year of manufacture UL rating North American standards Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA The first two digits of the date code (located on the product identification label) are the year of manufacture. Regulated 24 DC and 24 FWR Meets UL requirements for standards UL 464, UL 1638, and UL 1971 Contact information For contact information, see www.edwardsutcfs.com. P/N 3102149-EN REV 02 ISS 25MAR14 5 / 6

6 / 6 P/N 3102149-EN REV 02 ISS 25MAR14