Raychem Heating System

Similar documents
Gardian W51. Approvals

JBM-100-LBTV2 Power Connection, Powered Splice, Dual Power Connection, or Splice with Junction Box

C A Heating Cable Gland Kit

RayClic Connection System

C Electrical Connection Kit

HHS-WWH HOPPER HEATING SYSTEM WRAP-WOUND HEATER INSTALLATION INSTRUCTIONS DESCRIPTION. HHS-WWH PRODUCT SPECIfICATIONS

1SC-SSC Splice Connection Kit Installation Instructions

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

FlexiPanel INSTALLATION PROCEDURES WITH MAINTENANCE AND TROUBLE SHOOTING GUIDE INSPECTION REPORT FORMS

Frost Heave Protection System Installation and Operation Manual

SEALING FIBER SEALING COMPOUND

XAGA 550/550-L. Aerial Splice Closure. 1. General Description. 2. Warnings. 3. Cautions

Retro-DWS Other Methods Internal Heating Cable System for Sewer Pipe and Waste Drain Applications

QuickStat-TC Installation & Operation Manual

HVS S 15kV Class

TraceTek TT1000 Modular Sensing Cable

Side Entry Bushing (SEB) High Temperature Cable Clamp Bushing Installation Instructions

HVS S Splice Series

Consignes d installation

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1

C910 Series. Single-point heat-tracing control system

HWAT -ECO. Installation and Operation Manual. Electronic controller for hot water temperature maintenance systems

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Commercial and Residential Self-Regulating Heating Products

XL-Trace System Installation and Operation Manual

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

HOTFOIL HB MODULE HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL HB.IOM.R3

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

The DEF-System by BRUGG. The Best Way to defeat the problem of DEF heat Installation Instructions

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

COPPER FREESTANDING TUB

ACCS-30. Multipoint commercial heat-tracing control system

breeze easytm model # F100-1W

Installation Manual PS-225 & PS-275

Silicone Rubber Heating Tape with Adjustable Thermostat Control (HSTAT Series) Instruction Manual

QuickNet System Installation Manual Manuel d installation du système QuickNet Manual de instalación del sistema QuickNet

Installation Manual PS-200 & PS-201

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

Electric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

FloorHeat Installation Manual

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

Small Box for Cable Termination. 3.1 Preparation of box 3.3 Mounting of the box on the wall

Industrial Strength Leak Detection

OCH-SS series Direct Wired Units Indoor * and Outdoor Comfort Heaters

Please Read and Save These Instructions.

DATASHEET PolySwitch RKEF Devices

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

Retro-DWS Internal Heating Cable System for Non-Pressurized Sewer and Waste Drain Pipes

DHCSR Series Drum / Pail Heaters

Installation Instructions

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

Tyco Thermal Controls provides complete heat tracing and speciality. wiring solutions for the industrial, commercial, and residential markets.

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Foil Heaters. Installation Manual: TECHNICAL HELPLINE

EasyWire Between Joists Installation Instructions

FTC-HST WARNING: CAUTION:

RESIN FREESTANDING TUB

(HSTAT Series) Instruction Manual

aquilar - leak detection solutions

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

TE Connectivity's AMP NETCONNECT Cable Management

Silverware Pre-washing System INSTALLATION

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

FIND LEAKS BEFORE THEY FIND YOU. Leak Detection and Location Systems

H908 WinterGard Plug-in Power Connection Kit with End Seal

NELSON HEAT TRACING SYSTEMS

e Bath Fan with Light User s Guide

Installation and Operation Instructions. Versa. Screw Plug Oil & Water Immersion Heater. PD January 2018

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

Gas Connector Installation Instructions

NELSON HEAT TRACING SYSTEMS INSTALLATION

Installation, Operation and Maintenance Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

OPERATION MANUAL Model 8011 & mA

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Top Control Dishwasher

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

OCH-SSE series Direct Wired Units Indoor * and Outdoor Comfort Heaters

MAYFIELD CEILING FAN LISTED E ITEM # MODEL #BTH44ABZC5C BTH44BNK5C Español p. 20 ATTACH YOUR RECEIPT HERE.

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

Self Regulating Trace Heating Systems Installation and Maintenance. Non-Hazardous Area Installations

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

NELSON HEAT TRACING SYSTEMS ALT-BC STANDARD POWER CONNECTION KIT

OPERATION MANUAL MODEL & ACCELEROMETER

KE-Series Constant-Wattage Heating Cable

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

Dishwasher Installation Instructions DW 24XT/DW 24XV

G Series SAVE THESE INSTRUCTIONS. (Model B) Convector Heater for Hazardous Locations GENERAL! INSTALLATION


HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

Installation Instructions

SELF-REGULATING PIPE TRACING HEATER CABLE

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

Installation Instructions

Transcription:

Raychem Heating System Tank Heater (H55207) Approvals F M APPROVED Ordinary and Hazardous Locations lass I, Div. 2, Groups B,, D lass II, Div. 1 & 2, Groups E, F, G lass III All hazardous location applications must be engineered by Raychem. T-ratings: Low-watt heaters: T4A High-watt heaters (lass I): T2 High-watt heaters (lass II & III): ontact Raychem Description Raychem Heating System (RHS) tank heaters are designed for applications ranging from freeze protection to process maintenance of tanks. The RHS-H heaters are only for use on unlined metal tanks with maintain temperatures up to 200 F. The RHS-L heaters are for use on polypropylene, fiber-reinforced plastic (FRP), or metal tanks with fluid maintain temperatures not exceeding 120 F, or lined metal tanks. RHS heaters must be used in conjunction with a primary control thermostat. RHS heaters have an integrated thermostat which may be used only for over-temperature protection in the event of failure of the primary thermostat. These instructions describe the procedure for installation of RHS tank heaters. Storage and handling instructions are also provided. arefully follow all directions. RHS heaters come with a factory-supplied, liquid-tight conduit and fitting to transition heater cold-lead wires into the conduit. The cold lead wires are 14 AWG copper conductors with Teflon insulation. For technical assistance, contact Raychem at (800) 545-6258. Additional Materials Required Raychem RHS Installation Kit (P/N 844869) Raychem thermostat or equivalent Raychem BK-35 clamp kit (P/N 77215) or equivalent Thomas and Betts 5232 conduit fitting and 5302 sealing ring or agency approved equivalent RHS storage 1. Keep each heater in its box until you are ready to install it. 2. Store the box in a cool, dry environment. 3. Avoid stacking heavy objects on the box, which could damage the RHS heater. Tank preparation 1. Inspect the tank surface. The installation area must be free of Sharp protrusions (weld splatter, rough seams, etc.) Rust and corrosion Grease, oil, moisture Obstructions, such as instrument lines, electrical wiring or conduit, tank support, or reinforcements. Handling Important: This heater is an electrical device. Handle it with the same care you would use with any electrical device and carefully follow these instructions. 1. In the field, keep the heater in its box until you are ready to install it on the tank. 2. File, sand, or sandblast the tank surface as required to provide a smooth, rust-free paintable mounting area large enough for the heater you are using plus 3 inches beyond the heater outline. For polypropylene or fiber-reinforced plastic (FRP) tanks, use 60-grit sandpaper to roughen the 2. To avoid mechanical damage, do not lay the heater where it can be stepped on or struck by tools or equipment. 3. Do not fold or twist the heater, or allow it to be bent smaller than the 17-inch minimum bend radius. tank surface, going a minimum of 3 inches beyond the heater outline. 3. The tank surface must be free of grease, oil, and moisture. 4. The tank surface and the RHS heater must be clean and dry until adhesive has fully cured. WARNING: The RHS heater must be installed correctly to ensure proper operation and to prevent shock or fire. Read these important warnings and carefully follow all the installation instructions. To minimize the danger of fire if the heater is damaged or improperly installed, and to comply with the 1996 National Electrical ode, ground-fault equipment protection must be used on each heater branch circuit. Damaged heaters and connections must be replaced. Do not attempt to repair or energize if damaged. Approvals and performance are based on the use of specified parts only. Do not use substitute parts or vinyl electrical tape. Leave these installation instructions with the user for future reference. AUTION: Uncured adhesive can irritate eyes. Read warnings on tube. onsult MSDS VEN/0004 for additional information.

Preparation 1. Perform an insulation resistance megohmmeter (Megger) test on the heater immediately after removing the heater from the shipping carton. Instructions on how to perform the Megger test are in the Testing and maintenance section. 2. Using an ohmmeter, measure the heater resistance using the white and black cold leads. If the resistance is greater than 450 ohms, call your Raychem representative. 3. Install the tank heater below the typical minimum fluid level. If this level is unknown, install heater on the lower 1 3 of the tank. This will ensure proper heat to the liquid. 4. Do not attach the flexible conduit to the heater at this time, as the weight will make the installation to the tank more difficult. 5. Before proceeding with the installation, make sure that you have sufficient RHS Installation Kits (P/N844869). Note: RHS-H-500 and RHS-L-150 heaters will each require approximately one adhesive tube; RHS-H-1000 and RHS-L-300 heaters will each require approximately one and one half tubes; RHS-H-1400 and RHS-L-420 heaters will each require two tubes. 6. Hold the RHS heater against the tank and, using a marking pen, outline the heater perimeter. 7. The tank surface must be prepared as stated under Tank preparation on the previous page and be free of grease, oil, and moisture. The tank surface temperature should be between 0 F ( 18 ) and 150 F (65 ) for proper installation. Heater preparation 8. Place the heater on a flat surface with the metal ground plate facing up. Using the aluminum tape included with the mounting kit, place two strips along both vertical ends. Half the tape should overlap the heater's edge and the ends of tape should extend 3 inches beyond the heater. 9. Place two more strips of aluminum tape horizontally across the heater, one inch in from the heater's edge. 10. Turn the heater over so that the red silicone rubber surface is facing up. Wipe the silicone surface with a soft cloth to remove any dirt or debris. 11. Unscrew the cap from the adhesive tube. ut off the end of the adhesive tube at the first thread. ut one inch off the cap and screw it back on the tube. Note: The adhesive working time is approximately 10 minutes. Application and spreading of adhesive must be done qickly, without interruptions. Do not attempt to install the heater if adhesive is tack free to the touch. Note health warnings on adhesive tube. 12. Apply the adhesive only on the red silicone rubber portion of the heater. The adhesive bead should be approximately 1/4" in diameter and spaced approximately 1/2" apart placed in a serpentine pattern across the width of the heater. 13. Using the straight edge of the trowel, distribute the adhesive evenly on the red silicone rubber portion of the heater. Fill in voids or gaps with additional adhesive. Once smoothed, the adhesive thickness should be no more than 1/16" thick. Heater installation on tank Important: The tank heater must be installed with good contact to the tank wall. Inadequate contact, excessive adhesive, or voids in the adhesive may result in lower tank heater efficiency. 14. Holding the heater by the terminal box and the opposite end, place the heater on the prepared tank surface. While still holding the terminal box, use the wedge to smooth the aluminum tape to the tank surface. Remove all ripples from the tape to ensure it will hold securely. 15. Using the wedge, starting from the center of the heater and working out to the perimeter, ensure you spread the adhesive evenly and remove any trapped air. 16. Place three more vertical strips of aluminum tape on the heater. The first strip should be located next to the terminal box. The second strip should be placed 6 inches in from the opposite end. The third strip should be placed at the heater centerline. Use the wedge to smooth the aluminum tape. 17. The adhesive must be allowed 24 hours to fully cure before you install the flexible conduit and thermal insulation. After 24 hours, the two exposed horizontal edges must be sealed with aluminum tape. This will prevent contaminants from getting under the heater. The tape should extend approximately 1.5 inches beyond the edges of the heater.

Flexible conduit installation 1. After the adhesive has been allowed to cure for 24 hours and the heater horizontal edges sealed with aluminum tape, you may attach the flexible conduit. A 4-foot length of flexible conduit is provided with the heater. 2. Measure the distance between the heater terminal box and power junction box. Use standard industry practice to cut conduit to appropriate length. 3. onnect the conduit to the power junction box first. Use a Thomas and Betts 5232 conduit fitting and 5302 sealing ring (or agency approved equivalent) to keep the enclosure water-tight and dust-tight. 4. onnect the conduit to the heater terminal box. Make sure the blue nylon bushing is seated on the heater terminal box fitting. Place one wrench on the hexagonal nut located on the heater terminal box. This nut must not rotate during installation. Hand tighten the cap nut and then use a second wrench to completely tighten. The fitting manufacturer recommends 25 foot pounds of torque to be applied. 5. Fully insulate tank. Place identification labels on insulation, showing the location of the heater beneath. Thermostat installation and connection 1. Install and connect the primary thermostat(s) as shown in the thermostat installation instructions. The wiring diagrams provided on the next page are for reference only. 2. Install the primary thermostat bulb midway between two RHS heaters or heater and heat sink at the same level as the heaters. The bulb should be placed horizontally around the tank using a Raychem BK-35 (P/77215) clamp kit or equivalent. 3. onnect the primary thermostat(s) and heater cold leads as shown in the thermostat installation instructions. The heater ground is the cold lead wire with green insulation. 4. Use the GFEPD circuit breaker specified on the design or installation drawing. Ground-Fault protection The 1996 NE, Section 427-22, and Raychem requires 30-mA ground-fault protection on all electrical equipment branches. All RHS heater circuits are required to be protected with a 30-mA ground-fault protection device (GFPD). This device will minimize the risk of fire or shorting by shutting off the power to the circuit whenever a significant ground-fault current is detected. Suitable circuit breakers with ground-fault protection can be purchased through Raychem.

Typical wiring diagrams onnecting a single RHS heater Ø Ø 208-V or 240-V supply or N Ø 120-V or 277-V supply RHS Phase-phase or phase-neutral, no contactor onnecting RHS heaters in parallel N ØA ØB Ø 208-V supply N ØA ØB 208-V or 240-V supply N Ø 120-V or 277-V supply ontactor ontactor 120-V coil RHS #1 120-V coil RHS #2 RHS #1 RHS #1 RHS #3 RHS #2 RHS #2 4-wire, 3-phase with contactor 3-wire, phase-phase with contactor Phase-neutral, no contactor

Testing and maintenance Insulation resistance (Megger) test The megohmmeter (Megger) test verifies that the heater has not been damaged during installation or operation. Perform this test with both power leads disconnected from the distribution system. Also disconnect the thermostat. We recommend making the Megger connections at the junction or splice box where the RHS cold leads are connected to power. When performing this test during normal maintenance, disconnect the cold leads before testing the heater. Raychem recommends performing the Megger test at 2500 Vdc; 500 Vdc is the minimum (acceptable) test voltage. 1. onnect the positive lead of the Megger to both power leads of the heater. onnect the negative lead to the ground (green) wire of the heater. 2. Set the voltage at 2500 Vdc (500 Vdc minimum) and turn the Megger on. 3. Apply voltage for one minute. Minimum insulation-resistance value should be greater than 20 megohms. 4. Turn the Megger off and discharge the heater to the ground, if not automatically done by the Megger. Go to Step 5 if the heater is installed on a metal surface. If the heater is on plastic, the Megger test is complete at this point. 5. Move the negative lead of the Megger from the heater ground wire to the metal tank surface. 6. Repeat Steps 2, 3, and 4 to test the integrity of the insulating layer attached to the tank surface. Note: If the Megger value is less than 20 megohms in either Step 3 or Step 6, find and remedy the cause. Some things to look for include the following: Were the Megger leads connected correctly? Was the thermostat bypassed? Are connections in the junction box correctly made? Is there water in the junction box? Is there damage to the RHS or its power cord? (aution: Do not attempt to repair a damaged heater. It must be replaced.) Performance test This test checks that the system including thermostat, contactor, and connections is working properly. 1. When the heaters and controls are installed and connected to power,and the tank or vessel is thermally insulated, fill the tank with fluid to a level above the heater locations. 2. Measure the temperature of the tank fluid. 3. Turn the circuit breaker on. 4. Set the primary thermostat at a temperature about 20 F higher than the fluid temperature measured in Step 2. This action energizes the heaters. 5. Allow the heater(s) to be powered for about five minutes, then measure the voltage and current. Note these values in the maintenance log as a reference for future maintenance checks. 6. Lower primary thermostat set point to ensure that the heater shuts off. 7. Set primary thermostat to desired set point. Maintenance We recommend that the Megger test be performed on each RHS heater once a year. Where multiple heaters are connected in parallel, disconnect and individually test each heater. A performance test should also be done once a year. heck control thermostats at that time. Things to look for include the following: ontrol switching at the proper temperature. Signs of corrosion inside the thermostat housing. Mechanical damage or corrosion to the capillary or temperature sensor. orrosion of the microswitch inside the housing.

Worldwide Headquarters Tyco Thermal ontrols 300 onstitution Drive Menlo Park, A 94025-1164 USA Tel: (800) 545-6258 Fax: (800) 596-5004 info@tycothermal.com www.tycothermal.com Important:All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their application. Tyco Thermal ontrols makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal ontrols only obligations are those in the Tyco Thermal ontrols Standard Terms and onditions of Sale for this product, and in no case will Tyco Thermal ontrols or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, or use or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal ontrols reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification. Tyco, Raychem are trademarks of Tyco Thermal ontrols LL or its affiliates. Megger is a trademark of Thorne EMI Plc. of London. Teflon is a trademark of E. I. DuPont de Nemours and ompany. anada Tyco Thermal ontrols 250 West ST. Trenton, Ontario anada K8V 5S2 Tel: (800) 545-6258 Fax: (800) 596-5004 2006 Tyco Thermal ontrols LL Printed in USA P/N 797471 H55207 04/06