SUPER T WALL FANS. Installation and Wiring Instructions

Similar documents
Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz

READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Centrif Duo & Centrif Duo Plus

Lo-Carbon Quadra Centrifugal Fan

T-SERIES. Wall & Panel Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Lo-Carbon Quadra SELV

Silhouette Installation and Wiring Instructions

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

Lo-Carbon SELV Tempra

T-SERIES. Window & Roof Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

Lo-Carbon Quadra Centrifugal Fan

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

VA 150 A, VA 150 P WINDOW EXTRACT FAN. Installation and Wiring Instructions V/1/50Hz

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

Installation and Wiring Instructions

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH THE ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS

DUCT AIR HEATER WITH BUILT-IN CONTROLS. Installation & User Instructions. Stock Ref T T T3

Lo-Carbon SOLO Plus SELV Centrifugal Bathroom/Toilet Fan

Lo-Carbon T-series Window & Roof Models

EXTRACTOR HOOD. Please read all the instructions carefully before starting the installation. 230 / 240V 50Hz

VA100 SELV 12 RANGE. Installation and Wiring Instructions IPX7

Vent-Axia Svara Multifunctional app controlled fan. Important Information 2 Installation and Wiring Instructions 3-11 Accessories 12 Pin Code 12

HR200WK Through the wall Heat Recovery Ventilator

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

INTEGRA PLUS ABC. 230V~ 50Hz. Stock Ref. N. Installation and Wiring Instructions IPX2

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

100 FLUEBOOST

Sentinel Kinetic MVHR RANGE

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

FLUEBOOST. flueboost 350 gas fire model

Lo-Carbon PoziDry Pro

CI/SfB (57.7) 2nd edition. Lo-Carbon Quadra

Purge Ventilation Unit. Product Manual. ventilation systems TP625

Warnings, Safety Information and Guidance

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

INSTALLATION, OPERATION & MAINTENANCE MANUAL

PUREAIR SENSE. Instruction Manual. A product by. B at hroom Fan wi t h O dour Sen se Tec h n ology Vent-Axia PureAir Sense F&W Manual.

THESE INSTRUCTIONS MUST BE READ FULLY BEFORE COMMENCING INSTALLATION.

Trimbox Mixed Flow Fans. Product Manual. ventilation systems TP220T TP221T TP222T TP223T

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

Manual Comfort Air Curtain

hp Dust Collector With Vacuum Attachment

Bathroom Exhaust Fan

ELTA FANS IN-LINE MIXED FLOW FAN IMF100 / 125 / 150 / 200 INCLUDING MODELS WITH BUILT-IN-RUN-ON TIMERS T

Ceiling Sweep Fan Assembly Instructions

HIT Centrifugal In-Line Fan

e Bath Fan with Light User s Guide

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING

USER S MANUAL. Heat Recovery Ventilator. Vents Brig HRV 200 Vents Brig HRV 300

Installation instructions. Designer series wall canopy. and User guide NZ AU GB IE. HC90DXB1, HC90DMB1 models

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

SUNCOURT INSTALLATION INSTRUCTIONS RADON FAN MODEL: RDKO4, RDK04-3, RDN04 & RDN04-3

CI/SfB (57.7) 1st Edition. Lo-Carbon Response/SELV dmev Unit. A new generation of Lo-Carbon continuous running fans

e Bath Fan with Light User s Guide

750MM INDUSTRIAL PEDESTAL DRUM FAN

Simply Silent Contour 4 (100mm) Axial Extraction Fan

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

Gas Fire Patio Heater Q9

Installation & Operating Instructions

LV100 Standard LV100PC Pull Cord LV100T Timer LV100H Humidistat LV100HP Humidistat and Pull Cord LV100PIR

3MAVR60XX Series Fan. Owner s Guide and Installation Manual. UL Model NO. : 3MAVR60XX

e Bath Fan with Light User s Guide

Panel Fan Series Operators Manual (Galvanized and Polymer)

Model pictured: RPA3CI6SS/WH

"Microbox" DC Models MBOX 125/2DC MBOX 125/2DC204

Xpelair Simply Silent TM Contour Fan

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

irconcentre.co.uk airooncentre.co.uk

TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive. Installation & Operator s Instruction Manual

Instruction Manual. Vapour Pump Thermal Snap-Switches. Cooling-Fail Thermal Snap-Switch

CENTRIFUGAL PUMPS OPERATING INSTRUCTIONS

Corn Flame Energy Corn Stove Model 3000

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Xpelair Simply Silent DX150

Wet/Dry Vacuum Kit

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

INSTRUCTION MANUAL FOR OIL BURNER MODELS

Sentinel. Kinetic Advance MVHR. Installation & Commissioning. Stock Ref. N Advance S Advance SX

PLEASE READ AND SAVE THESE INSTRUCTIONS

FP005) CHARCOAL SPIT ROASTER (HS-F SAFETY INSTRUCTIONS FOR OUTDOOR USE ONLY IMPORTANT! PLEASE AD THESE INSTRUCTIONS CAREFU REA

3MAVR60XXD Series Fan. Owner s Guide and Installation Manual. CUL Model NO. : 3MAVR60XXD

HEAVY DUTY BRASS SHOWER PUMPS

Aqueous Thermostatic Surface Mounted Bar Shower Valve With Fast Fit Connections

INSTALLATION INSTRUCTIONS FOR DUCTED WHOLE HOUSE FANS

TWIN-FLOIII HEATER INSPECT THE SHIPMENT IMMEDIATELY WHEN RECEIVED TO DETERMINE IF ANY DAMAGE HAS OCCURRED DURING SHIPMENT.

Owner s Manual READ AND SAVE THESE INSTRUCTIONS

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

THE BARCLAY HUGGER CEILING FAN INSTALLATION INSTRUCTIONS

PANEL FAN SERIES OPERATORS MANUAL (Galvanized and Polymer)

Humidity and Thermostat control box for Attic Fan

Please tape down. NewTeam Ltd. Customer Service Dept. Brunel Road Earlstrees Industrial Estate Corby Northants NN17 4JW

THE DAVENPORT CEILING FAN INSTALLATION INSTRUCTIONS

Xpelair Simply Silent TM DX100 Fan

Transcription:

SUPR T WALL FANS Installation and Wiring Instructions Stock Ref. N 16 10 16 6 10 16 7 10 16 8 10 - Gravity Shutter Version (6 Pole) 16 7 10 16 67 10 16 77 10 16 87 10 - lectric Shutter Version (6 Pole) 16 6 20 16 66 20 - Grease Filter Version (4 Pole) 220-240V/1/0Hz RAD INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS RAD AND SAV THS INSTRUCTIONS

Installation and Wiring Instructions for the Super T Wall Fans. IMPORTANT: RAD THS INSTRUCTIONS BFOR COMMNCING TH INSTALLATION DO NOT install this product in areas where the following may be present or occur: xcessive oil or a grease-laden atmosphere. Corrosive or flammable gases, liquids or vapours. Ambient air temperatures of less than C or higher than 70 C. Possible obstructions which would hinder the access or removal of the Fan. SAFTY AND GUIDANC NOTS A. All wiring to be in accordance with the current I... Regulations, or the appropriate standards of your country and MUST be installed by a suitably qualified person. B. The Fan should be provided with a local double pole isolator switch having a contact separation of at least 3mm. C. nsure that the mains supply (Voltage, Frequency, and Phase) complies with the rating label. D. The Fan should only be used in conjunction with the appropriate Vent-Axia products.. It is recommended that the connection to the terminal box is made with flexible cable/conduit. F. When the Fan is used to remove air from a room containing a fuel-burning appliance, ensure that the air replacement is adequate for both the fan and the fuel-burning appliance. G. If the Fan is used to supply air into a room, the installer must ensure that the fan intake is located a minimum of 600mm from any flue outlet. H. If your Super T Wall Fan is to be mounted at a height of less than 2.m from the floor level and is accessible, protective Discharge / Intake grilles MUST B FITTD to the fan unit. I. Super T wall fans are designed as a through the wall unit and should always be installed with the internal / external grilles and louvres / meshes provided. J. This Fan should not be used where it is liable to be subject to direct water spray from hoses etc. K. Certain applications may require the installation of sound attenuation material to achieve the sound levels required and an Auto Transformer speed controller is also recommended. L. Due to the weight of the Unit it is recommended that two persons are involved in the installation. 1 TYPICAL INSTALLATION OF SUPR T FANS a) Form / Cut the correct size hole in the wall (Fig. 1.) where the fan unit is to be installed. VNT-AXIA recommends the use of the correct size of Lintel(s) above the Super T Wall Unit. Fig 1. 280 (min) - 312 (max) 'A' Sq. Hole through the Wall 'B' Sq. Grille Impeller Weight Dia. A B (Approx) 3 470 0 17 Kg 400 20 97 22 Kg 40 80 67 28 Kg 00 60 727 33 Kg 2

b) Remove the Plate Fan from the telescopic liner by removing the four Nyloc M8 nuts, leaving the anti-vibration mounts fastened to the bracing bars (Note the position of internal wall label when fitting the liner). c) nsure that suitable wiring arrangements have been made to the fan the wiring is recommended to come into the fan wall liner from either side as indicated in Fig. 2. Fig 2. lectric Shutter ( Model) Telescopic Wall Liner Lintels (various). M cage nuts Anti-Vibration Mounts Plate Fan Finger Guard M6 Locknut Mesh Flexible conduit Conduit Glands Internal Wall positioning label Louvre / Back Draught Shutter M8 nyloc nuts and washers. Internal Grille d) Remove the sidewall knockout to suit the installation, fit conduit adapter (supplied) through hole and secure with nut on external side of liner. e) Place the wall liner into the hole, feed the cable or flex through to inside of liner and extend the liner to correct wall depth and cement both ends into position flush with the wall surfaces. f) The wall sleeves should be angled downwards to the outside and secured into the wall by the screws. g) Tighten the M6 locking nuts at the top and base of the unit. h) nsure that the four M Cage Nuts in the front and rear of the unit that locate the grille and louvre fixings (see Fig. 2) are free from debris and remain clear. i) Fit the Plate Fan into the Wall Liner (ensuring the terminal box outlet is positioned in the correct orientation) and fix into position using the M8 nyloc nuts and washers. j) Fit the other conduit adapter to the appropriate hole in the Fan terminal box. Fix the length of flexible conduit to the conduit adapter in the metal liner. k) Feed cable or flex through conduit adapter nut and flexible conduit. Remove nut from conduit adapter in terminal box and place over conduit feed cable or flex. Feed cable or flex into terminal box. Connect flexible conduit into terminal box adapter and tighten nut. l) Select and follow the appropriate wiring diagram in Section 2 Wiring. m) Fix the Internal Grille onto the liner using a screwdriver (ensuring the Grille blades are pointing upwards). n) Loosely tighten all four screws, move grille until horizontal, then fully tighten. o) nsure that the Fan blade rotates freely. p) Fix the xternal Louvre / Back draught Shutter onto the liner (follow the same procedure for the Internal grille). q) Switch the mains power supply on and check that the Fan is operating correctly. (lectric Shutter) Model Notes. A. The lectric Shutter must be provided with an unregulated (230V) supply. B. The W102 03 102M 2.A lectronic speed controller has a shutter terminal (L3). Refer to the Controller Installation and Wiring Instructions. 3

2 WIRING WARNING: TH FAN AND ANCILLARY CONTROL QUIPMNT MUST B ISOLATD FROM TH POWR SUPPLY DURING TH INSTALLATION / OR MAINTNANC. TH QUIPMNT MUST B ARTHD. Note: The thermal protection device fitted is of an automatic resetting type and is rated at A. It is recommended that this protection device is always included in the circuit. If manual resetting is required, an ancillary circuit will be required with the TP switch connected into the circuit. nsure that the earth/ground connection has been made inside the terminal box. WIRING DIAGRAMS Fig 3. Super T Wall Fan connected to a 240V Coil D.O.L. Starter and an lectric Shutter (if applicable). xtract Only. ST 3 16W/L and ST 400 16W/L. STGF 3 and STGF 400 xtract or Intake 3 and 400 (220-240V 0 Hz). L ~ N (220-240V 0 Hz). L ~ N 9 23 9 23 2 4 6 96 24 2 4 6 96 24 FAN TRMINAL W Y V X U Z FAN TRMINAL W V U Y X Z N L N L SHUTTR TRMINAL SHUTTR TRMINAL Form 'A' (xtract). Form 'B' (Intake). 4

Fig 4. Super T Wall Fan connected to a 240V Coil D.O.L. Starter and an lectric Shutter (if applicable). xtract Only. ST 40 16W/L and ST 00 16W/L. xtract or Intake 40 and 00 (220-240V 0 Hz). L~N (220-240V 0 Hz). L~ N 9 23 9 23 2 4 6 96 24 2 4 6 96 24 W V U W V U Y X Z Y X Z FAN TRMINAL N L N L SHUTTR TRMINAL Form 'A' (xtract). SHUTTR TRMINAL Form 'B' (Intake). 3 CLANING AND MAINTNANC WIRING a) Before servicing or cleaning the unit, switch power off at mains terminal box or service panel and lock service panel to prevent power being switched on accidentally. b) We recommend that that at intervals appropriate to the installation the internal grille should be removed from the liner and the impeller and motor fins cleaned. c) nsure fixing and locking washers are secure. d) Check that all assembly and mounting screws and mounts are secure and tight. e) Vent-Axia fan motors are fitted with sealed for life bearings and therefore do not require lubrication. SPD CONTROL The following controllers are recommended for use with the Vent-Axia Super T range: Vent-Axia 240V coil D.O.L. starter Vent-Axia 2.A electronic controller Vent-Axia 3A auto transformer

VNT-AXIA SALS CNTRS NGLAND & WALS NATIONAL CALL CNTR SCOTLAND Newton Road, Crawley West Sussex Telephone: 0141 429 1166 RH10 9JA Fax: 01293 6169 Telephone: 01293 30202 RPUBLIC OF IRLAND Fax: 01293 6169 Vent-Axia Ventilation Ltd. 921 Western Road Industrial state NORTHRN IRLAND Naas Road, Dublin 12. Telephone: 02890 402220 Telephone: (01) 40 4133 Fax: 01293 6169 Fax: (01) 40 470 Did you find these instructions easy to use? We value your comments, contact us via: mail: info@vent-axia.com The Vent-Axia Guarantee Applicable only to products installed and used in the United Kingdom. For details of the Guarantee outside of the United Kingdom contact your local supplier. Vent-Axia guarantees this product for two years from the date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company s discretion the product will be replaced without charge, provided that the product: 1). Has been installed and used in accordance with the instruction given with each unit. 2). The electricity supply complies with the rating label. 3). Has not been misused, neglected or damaged. 4). Has not been modified or repaired by any person not authorised to do so by Vent-Axia. IF CLAIMING UNDR TH TRMS OF TH GUARANT Please return the complete product, carriage paid to your original supplier by post or in person. Please ensure that it is adequately packed and accompanied by a letter clearly marked Guarantee Claim stating the nature of the fault and providing proof of the date and source of purchase. As part of the policy of continuous product improvement Vent-Axia reserve the right to alter specifications without notice Head Office: Fleming Way, Crawley, West Sussex RH10 9YX Tel: 01293 26062 Fax: 01293 1188 Internet site at: www.vent-axia.com 468382 0603