Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International

Similar documents
Engineered for flexibility and performance

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Your Chiller Solution For Efficiency And Reliability. McQuay Dual Compressor Centrifugal Chillers 160 to 2500 Tons

Presented By: John Dolan, P.E.

Technical Development Program

Method to test HVAC equipment at part load conditions

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

Magnetic Bearing Technology: Achievements in Higher Efficiency

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

Mechanical Systems Design

Midea VFD Centrifugal Chiller Technology

Centrifugal Compressor Water Chillers Catalog 605 Models WSC, WDC, WCC, HSC

Agenda and Objectives

Welcome To. System Benefits With ECM PUMPS

Description of All Alternatives Considered-

Centrifugal Compressor Water Chillers

Redesign of Bennett Hall HVAC System

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Water-Cooled Screw Compressor Chillers

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

How to Select and Size a Chiller

THERMAL ICE STORAGE: Application & Design Guide

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

Trailblazer air cooled scroll chillers

The McQuay DISTINCTION SERIES. Single/Dual Compressor Centrifugal Chillers. Installation and Maintenance Manual

HVAC Clinic. Helical Rotary & Centrifugal Water Chillers

NET ENERGY WATER LOOPS A clear path to net zero energy buildings

The Electronic Newsletter of The Industrial Refrigeration Consortium Vol. 11 No. 1, 2011

ENGINEERING. Edition No. 13 October 2002

Therefore check, who will be eternally bound

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

LL Series Chillers and Outdoor Mechanical Rooms. Engineering Catalog

CTI Sponsored Educational Program

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Binoe E. ABUAN, Menandro S. BERANA, Ruben A. BONGAT. University of the Philippines Diliman, Quezon City, Philippines

EarthWise System Seminar

Daikin Blueprint: Delivering Hot Water with a Chiller

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Commercial Refrigeration

Call us today! (800)

Call us today! (800)

Centrifugal, Magnetic Bearing, Compressor Water Chiller Model WMC-035T, 110 to 175 Tons

Water-cooled chillers with High Speed Centrifugal Compressors

DIGI-CRAC DIGI-CRAH South 59 th Street Omaha, NE bes- tech.net

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

RECORD SUBMITTAL COVER SHEET

Water-Cooled Screw Compressor Chillers

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Smardt Oil-Free Chillers

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

On Balance: Heat Rejection Control a Packaged Solution

Understanding Head Pressure Control. Walter H Langille, M.A.Sc., P.Eng Sales Engineer KeepRite Refrigeration

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

DISTRIBUTION SYSTEMS. Water Piping and Pumps

June Copyright Climatec

Call us today! (800)

Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.

MTW Series Modular Oil Free Centrifugal Chillers

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

PACKAGED REFRIGERATION EQUIPMENT

Air conditioning 23XRV

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Packaged Ammonia Chillers with Variable Frequency Drives powerpac

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

Smardt vs. McQuay Comparison of Standard Options and Other Benefits < 400 tons

CVGF. Water Cooled Centrifugal Chillers

HVAC Myths and Realities Trane Engineers Newsletter Live Series

Richard Hiles ClimateMaster

Heat Transfer Products. Product Line Update

Water-Cooled Dual Compressor Screw Chiller

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

HYBRID ADIABATIC Cooling System

Development of centrifugal chiller and heat pump using low GWP refrigerant

How to Cut Chiller Energy Costs by 30%

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Water-Cooled Screw Compressor Chillers

Fans and Pumps I. Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong

5. ASSESSMENT RECOMMENDATIONS

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

MicroTech Series-200 Flooded Screw Chiller

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

Centrifugal Compressor Water Chillers THE DISTINCTION SERIES

GWP Alternative Refrigerants

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Energy-Efficiency Measures List

Transcription:

Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International

Equipment Using Different Kinds Of Equipment Or Different Performance Equipment Can Improve Cost Difficult Part Is To Evaluate Life Cycle Analysis

Air Cooled Vs. Water Cooled Water Cooled Will Be More Energy Efficient It Usually Costs Less To Operate Maintenance And Water Costs For Optimization Go Water Cooled

Water Cooled - Optimizing Selections Enter Design Data Into The Program Start The Process Choose The Chiller After A Large Vertical Drop Not Good Good Selection Look At The Number Of Selections And Prioritize Analyze Options Cost

Review Components In Selecting The Chiller Look At: Vessel Length Changes Vessel Diameter Changes Vessel Tube Count Compressor / Gear Selection-If Appropriate Motor Size Number Of Passes

Optimizing Performance Conditions Of Service: Use Lower Entering Condenser Water Temp Use Higher Leaving Chilled Water Temp 1/2 Degree Anywhere Makes a BIG Difference!! MINIMIZE LIFT

Range Vs. Supply Water Temperature Declining Supply Water Temperature (44 To 38F) Increase Chilled Water Range From 10 To 24F Annual Energy Analysis Run C.W. Range C.W. S.T. Chiller Pumps Tower Fan S.A. Fan Total ( F) ( F) ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) 1 10 44 26,074 15,175 1,591 28,275 71,115 2 12 44 26,096 13,784 1,593 28,560 70,033 3 16 44 26,211 12,055 1,597 29,350 69,213 3 14 42 27,733 12,790 1,593 28,573 70,689 4 16 42 27,779 12,039 1,593 28,570 69,981 5 18 40 29,371 11,462 1,594 28,584 71,011 6 20 40 29,351 11,002 1,596 28,872 70,081 7 22 38 30,365 10,623 1,596 28,881 71,465

99% Of All Operating Hours Are At Part Load

The New Industry ARI Standard -1998 Part Load Analysis (IPLV) % Load Old % Hrs New % Hrs 100 17 1 75 39 42 50 33 45 25 11 12 Systems Solution

Optimizing Selections- Glycol! High Glycol = Low Heat Transfer: Propylene Glycol Has Really Bad Heat Transfer Properties Increases Head On Compressor Utilize Less % Of Glycol - Even 0.5% Can Make A Difference ASHRAE Fundamentals: Physical Properties Of Secondary Coolants Don t Limit Input Values Run Selections Multiple Ways

Vessels High Pressure Drops? Look At 1 Pass Vessels Look At Reducing Evaporator Or Condenser Length Tube Thickness Can Increase Pressure Drop Single Pass Conversely - High Temperature Difference? Look At (3) Pass Look At Series Flow With 1, 2, Or 3 Pass Two Pass Three Pass

Optimizing Selections- F.L. Vs. IPLV Low NPLV Or IPLV: Look At Multiple Compressor Or VFD Sort By NPLV/IPLV Lowest NPLV Is Not Normally The Lowest Full Load kw/ton Slight Decrease In Full Load KW/TR Can Dramatically Increase Cost And Actually Increase NPLV/IPLV!

Various 500 Ton Chillers.6.5.505 IPLV.4.403.365.337.3 WSC WDC WSC w/vfd WDC w/vfd Notes: WSC = Single Compressor Centrifugal Chiller WDC = Dual Compressor Centrifugal Chiller VFD = Variable Frequency Drive

System Considerations Multiple Chillers On A Job? High Temperature Difference Across The Evaporator? Look At Series / Counterflow Arrangements 1 Multiple Compressor Instead Of 2 Singles

Cooling Tower Considerations Oversize Tower To Lower Condenser Water Supply Temperature Chiller Stays Same Price, Efficiency Improves 11% Tower Capital And Operating Cost Up Slightly 3% Annual Savings Run Cond.W.S.T. Chiller Chiller Pumps Tower Fan S.A. Fan Total ( F) kw/ton ($/yr) ($/yr) ($/yr) ($/yr) ($/yr) 1 85 0.547 24,435 15,209 1,441 24,512 65,597 2 84 0.535 23,842 15,207 1,463 24,508 65,020 3 83 0.524 23,425 15,205 1,482 24,505 64,617 4 82 0.514 23,055 15,203 1,501 24,502 64,261 5 81 0.492 22,147 15,199 1,526 24,496 63,368 6 80 0.483 21,848 15,197 1,548 24,942 63,535

Annual WB In Major US Cities 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 Strong Candidates For VFD Chillers - January February March April May June July August September October November December Los Angeles Washington DC Atlanta Chicago Miami

Optimizing Starter Selections Try Different Starters Solid State Starters Have Different Size Breaks Than Wye Delta Starters Solid State Starters Are Now Cheaper In Most Cases - Try Both Ways Depending Upon Size Breaks Try Unit Mounted And Free Standing - Size Breaks Can Make Different Selections Appear Check VFD Sizing Expensive At Very Bottom Of Amp Rating

Variable Flow Vs. Constant Flow 500000 450000 400000 Pump Work Cut In Half 350000 kwh 300000 250000 200000 150000 Notice Pump Work Half Chiller Work! 100000 50000 0 Chillers Pumps Towers Fans Variable Primary Flow 2 Chiller Primary/Secondary Flow 2 Chiller Parallel Flow

Wrap-up Many Ways To Solve An Application Selection Is Only As Good As The Data Given Optimize Your Selections