ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

Similar documents
ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

Digital Precise Air Control - DPAC

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Your Home. Jacco & Assoc.

Reference Guide for Microprocessor Controller

I/O ZONE 560/583 USERS GUIDE

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Reference Guide for Microprocessor Controller

Pioneer Gold Controller Technical Guide

Verasys System Operation Overview Technical Bulletin

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only


Long lasting unit provided by heavy-duty, corrosion-resistant, galvanized steel construction.

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

1.0 Digital Controller

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Feature Summary. I. System

HVAC Controls Upgrades: Requirement Details ( )

Installation and Maintenance Manual OM

SEQUENCE OF OPERATIONS

HVAC Controls Upgrades: Requirement Details ( )


American University Design Standards

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

York 25-Ton VAV Rooftop Unit

Your Home. Jacco & Assoc. Fan on with call for heating or cooling Heating on with call from space thermostat Stage as

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Table of Contents. WSHP Open v3

1.0 Digital Controller

Reference Guide for Microprocessor Controller

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

MicroTech Rooftop/RMC

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

SINGLE-PACKAGE ROOFTOP HEAT PUMP UNITS INDEX. VOLTAGE (3 Ph, 60 Hz) ACCESSORIES

DX-9100 Applications from Engineering Services

VCM-X Controller Technical Guide

Product Data. Features/Benefits. AirManager Control. 33AM Comfort System

Sequence of Operations (excerpt)

ENERVEX ADC100 DRAFT CONTROL

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

Tri-Stack Smart System

Job Name Control Systems Description Date

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Controls Lite. Controls Instruction, Operation, and Maintenance. IOM-C Part Number

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

RSMSD Technical Guide

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

CONTROL PANEL INSTRUCTIONS RSQ-4

Safety & Installation Instructions

HEAT COOL. Meets Commercial California Title 24

Honeywell ENERGY SAVINGS KIT

User s Manual

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

MicroTech Self-Contained Air Conditioning System

L SERIES UNITS 504,908M. 10/2004 Supersedes 9/2004

VCM-X Modular E-BUS Controller Technical Guide

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

T7300F Multistage Conventional or Heat Pump Programmable Commercial Thermostat

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

INSTALLATION INSTRUCTIONS

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

Advanced Installation and Configuration Instructions

- Data Brochure Boiler Control 274

HEAT HEAT HEAT COOL COOL

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

Marvel S MICROPROCESSOR CONTROLLER. Installation, Operation and Maintenance Manual Effective October 2018 DISCONTINUED. For Reference Only

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

WHITE-RODGERS COMFORT-SET 90 SERIES

Siemens Thermostats. RDY2000BN Thermostat

Table of Contents. W2W Open

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Helps reduce cycle time and increase productivity with advanced SPRAY-CURE technology.

Heat Pump Defrost Board Replacement Kit

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

CONTENTS. Installation Guide. VT7200 Series

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

CP CP

Wiring Diagrams. NOTE: This literature applies to units produced after 11/3/96 (software version 2.0 or greater) DIAGRAM INDEX

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIT DIGITAL CONTROLS APPLICATION, OPERATION & MAINTENANCE

INSTALLATION, OPERATION & QUICK START GUIDE

Installer Guide. WARNING Important Safety Information. 1 Specifications

- Data Brochure Addendum

MODEL AC-SCC-5 INSTALLATION, OPERATION & MAINTENANCE MANUAL

ADC150 Automatic Draft Control

Reciprocating Chiller

Table of Contents. Unit Ventilator

Energy Recovery with Cooling and Heating Model ERCH

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

OPERATING MANUAL Enertronic Control System 2

SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE

Transcription:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1

2 OCCUPIED MODE: When the program control source calls for the start of the Occupied Mode, the ALC controller verifies that there are no fault or shutdown conditions, a delay timer begins after which the unit goes into Occupied Mode: 1. Outdoor Air Damper (OD): After the unit goes into Occupied Mode, the OA damper will open. As the OA damper opens, the Outdoor Air Damper Actuator (OADA) auxiliary switches close. The OA damper stays open until the system reaches the end of the Occupied Mode period. It will remain open for an additional 2 minutes before closing. 2. Supply Fan (SF): As the OA damper opens, the OADA auxiliary switch (adjustable) will close and the SF will turn on. The SF shall operate continuously while the unit is in the Occupied Mode. When the system reaches the end of the Occupied Mode period, the SF will continue to run for an additional 2 minutes before turning off. SF-VFD: Supply Fan Variable Frequency Drive. The SF-VFD will modulate its speed based upon the differential pressure transmitter (SF-DPT) signal to maintain the supply duct static pressure set point. For constant air volume (CAV), select Manual Override in the BACview keypad and input the required speed (Hz) per field test and balance. 3. Exhaust Fan (EF): At the same time the SF turns on, the EF, if included, will turn on. The EF shall operate continuously while the unit is in the Occupied Mode. When the system reaches the end of the Occupied Mode period, the EF will continue to run for an additional 2 minutes before turning off. EF-VFD: Exhaust Fan Variable Frequency Drive. The EF-VFD will modulate its speed based upon the differential pressure transmitter (EF-DPT) signal to maintain the building static pressure set point. For constant air volume (CAV), select Manual Override in the BACview keypad and put the required speed (Hz) per field test and balance. 4. Energy Conservation Wheel (ECW): As the OA damper opens, the OADA auxiliary switch (fixed) closes which enables the Johnson Controls C450 controller. At this point, the ECW operates as an independently controlled component. Separate Outdoor Air Temperature (OAT) and Return Air Temperature (RAT) sensors are wired directly to the Johnson Control C450. SEQUENCE OF OPERATION The ALC controller is turned on by a switch located on its front upper left corner. Several options exist for starting the unit, such as the Resident Program Scheduler or the Building Automation System. These control source options can be selected from the BACview display pad on the Configuration Set-Up screen (requires Admin password). The Resident Program has an adjustable scheduler that uses the internal time clock to allow for separate Sequences for Occupied and Unoccupied periods. This can be accessed from the BACview display pad on the Schedules screen (requires user password). NOTE: Some temperature-related events have an additional delay on make to allow temperatures to settle. ECW Standard Operation: When the OAT is above or below an adjustable differential (3 F [1.7 C]) of the return RAT, the ECW will be on, otherwise it is off. ECW with On/Off Defrost: When the OAT is above or below an adjustable differential (3 F [1.7 C]) of the RAT, the ECW will be on. It will be off if the OAT is within the differential range or below an adjustable set point to allow for wheel defrosting (default is 15 F [-9.4 C]). ECW with VFD Controlled Defrost (WM-VFD): When the OAT is above or below an adjustable differential (3 F [1.7 C]) of the RAT, the ECW will be on. It will slow its speed or stop if the OAT is below an adjustable set point to allow for defrosting default is 15 F [-9.4 C). It will be off if the OAT is within the RAT differential range. 5. Cooling Mode: Reversing Valve is OFF in Cooling Mode. When the OAT (Entering Coil Air Temperature, ECAT, if wheel exists) is above the leaving air temperature (LAT) cooling set point (72 F [22.2 C], adjustable) plus an adjustable differential, compressor #1 turns on. For systems with two compressors, when the LAT is above the LAT cooling set point (72 F [22.2 C], adjustable) plus an adjustable differential, compressor #2 turns on. Compressor enabling logic includes a 4-minute (fixed) minimum run-time and a 5-minute (fixed) minimum time-off delay. Digital Compressor(s): The digital compressor is controlled by the Digital Compressor Module (DCM). The ALC controller will send an analog signal to the DCM and modulate capacity by rapidly loading and unloading the digital compressor in 15 second intervals. HGRH is included: The DCM will modulate based on the suction line temperature (SLT) set point (45 F [7.2 C], adjustable). HGRH is not included: The DCM will modulate based on the LAT cooling set point. If the SLT drops to 32 F (0.0 C) or less, the digital compressor will run fixed at 10%. For systems with two digital compressors, when there is a call for 1st stage cooling, 2nd stage cooling will also be enabled 10 seconds later. Both compressors will modulate to maintain the set point. If the SLT drops to 28 F (-2.2 C) or less for 15 minutes, the ALC controller will issue an alarm and compressor #1 stops. When the SLT warms back up to 50 F (10.0 C) or more, compressor #1 turns back on.

For systems with two compressors, if there is a current call for 1st stage cooling and compressor #1 is shutdown due to an alarm (HP1, LP1, or SLT1), compressor #2 will be turned on to take its place until it returns. Hot Gas Reheat (HGRH) On/Off: differential, HGRH turns on and cycles to maintain the LAT cooling set point (72 F [22.2 C], adjustable). Hot Gas Reheat (HGRH) Modulating: differential, HGRH turns on and modulates to maintain the LAT cooling set point (72 F [22.2 C], adjustable). 6. Dehumidification Mode: Reversing Valve is OFF in Dehumidification Mode. When OAT (ECAT, if wheel exists) is more than 60 F (15.6 C) (adjustable) and the zone relative humidity (Z-RH) is 1%RH (adjustable) above the Z-RH set point (55%RH, adjustable), and there is no call for heating, Dehumidification Mode is enabled. After the minimum time-off delay, compressor #1 turns on. For systems with two compressors, when the Z-RH is 2%RH (adjustable) above the Z-RH set point (55%RH, adjustable), after the minimum time-off delay, compressor #2 turns on. Both compressors will respond in sequence and run at full cooling. HGRH is enabled to operate as necessary to maintain the LAT cooling set point (72 F (22.2 C), adjustable). When the Z-RH is 2%RH (adjustable) below the Z-RH set point, the Dehumidification Mode is disabled. Digital Compressor(s): The digital compressor(s) run at 100% capacity when there is a call for dehumidification. During dehumidification mode, if the SLT drops to 38 F (3.3 C) or less, the DCM will modulate from 100% (for SLT of 38 F [3.3 C]) down to 10% (for SLT of 32 F [0.0 C]). Operation at 32 F (0.0 C) or less will be the same as during normal cooling mode operation. For systems with two digital compressors, both compressors will turn on and run at 100% capacity. Hot Gas Reheat (HGRH) On/Off: differential, HGRH turns on and cycles to maintain the LAT cooling set point (72 F [22.2 C], adjustable). Hot Gas Reheat (HGRH) Modulating: differential, HGRH turns on and modulates to maintain the LAT cooling set point (72 F [22.2 C], adjustable). 7. Room Temperature Reheat Override (RTRHO) Optional: Room Temperature Reheat Override mode is selectable using the BACview display pad or BAS, and operates in cooling mode and dehumidification mode when HGRH is included (default is OFF ). When HGRH is on and the zone air temperature (ZAT) is above the ZAT cooling set point (72 F [22.2 C], adjustable), the LAT cooling set point (72 F [22.2 C], adjustable) will decrease by a ratio and decrease HGRH modulation (or turn off HGRH, if On/Off control) in order to lower the ZAT. When the ZAT equals the ZAT cooling set point (72 F [22.2 C], adjustable), the unit will go back to normal cooling mode with LAT control. When the ZAT is below the ZAT cooling set point (72 F [22.2 C], adjustable), the LAT cooling set point (72 F [22.2 C], adjustable) will increase by a ratio, turn on HGRH (if off), and increase HGRH modulation (if included) in order to raise the ZAT. When the ZAT equals the ZAT cooling set point (72 F [22.2 C], adjustable), the unit will go back to normal cooling mode with LAT control. 8. Heating Mode: Reversing Valve is ON in Heating Mode. When the OAT (ECAT, if wheel exists) is below the OAT (ECAT, if wheel exists) heating set point (55 F [12.8 C], adjustable) minus an adjustable differential, compressor #1 turns on. For systems with two compressors, when the LAT is below the LAT heating set point (72 F [22.2 C], adjustable) minus an adjustable differential, compressor #2 turns on. Compressor enabling logic includes a 4-minute (fixed) minimum run-time as well as the 5-minute (fixed) minimum time-off delay. If there is a current call for 1st stage heating and compressor #1 is shut down due to an alarm (HP1, LP1, or SLT1), compressor #2 will be turned on to take its place until it returns. Digital Compressor(s): The digital compressor is controlled by the Digital Compressor Module (DCM). The ALC controller will send an analog signal to the DCM and modulate capacity by rapidly loading and unloading the digital compressor in 15 second intervals. The Digital compressor will load and unload based on the LAT heating set point. When the OAT is at or below the OAT compressor heating lock-out set point, 28 F (-2.2 C) (adjustable, minimum 20 F [-6.7 C]), both compressors will turn off. After the compressors are off, the auxiliary heat will be enabled. Defrost Mode: On defrost mode, the reversing valve will switch to cooling for the condenser coil to defrost the built-up ice on the condenser coil. 3

4 The unit is equipped with a Defrost Timer. The defrost timer provides a selectable time interval between defrost cycles. It will allow a 10 minute defrost every 30/60/90 minutes as long as the defrost thermostat is closed. The timer is factory set at 60 minutes. The time interval may be changed to 30 or 90 minutes if desired (disconnect power to the unit before moving the jumper). The hold input on the defrost timer allows the timer to accumulate time while the compressor is running in heating mode. A warm outdoor coil causes the defrost thermostat to open which will prevent time accumulation or end the Defrost period. The defrost timer allows up to a 10 minutes defrost cycle if the defrost thermostat is closed. When the Defrost period ends, either by opening of the defrost thermostat or after the 10 minutes defrost period has elapsed, the timer is reset. Shorting the two test terminals together on the defrost timer, a 60 minute delay is reduced to 14 seconds and a 10 minute delay is reduced to 2.3 seconds. During defrost cycle, when the LAT goes 5 F (2.8 C) below the LAT heating set point the ALC controller will run the auxiliary heat to try to maintain the LAT heating set point. Auxiliary Heat: After both heat pumps have been enabled, when the LAT is below the LAT heating set point (72 F [22.2 C], adjustable) minus an adjustable differential, and after an adjustable delay period, auxiliary heating will be enabled. When the LAT is above the LAT heating set point (72 F [22.2 C], adjustable) plus an adjustable differential, auxiliary heating will be disabled. Staged Auxiliary Heat (Electric Heat or Gas Furnace): 2-Stage Heat: The ALC controller will enable the 1 st stage of auxiliary heat using an analog heat relay module (HARM). As the LAT goes further below the LAT heating set point (72 F [22.2 C], adjustable), second-stage auxiliary heating is enabled. As the LAT rises, second-stage auxiliary heating turns off. As the LAT goes above the LAT heating set point (72 F [22.2 C], adjustable), first-stage auxiliary heating turns off. 4-Stage Heat: The ALC controller will send an analog signal (0-10vdc) to the analog relay module (HARM) on the control panel which activates the different stages of auxiliary heating. As the LAT goes further below the LAT heating set point (72 F [22.2 C], adjustable), the different stages will turn on. As the LAT goes further above the LAT heating set point (72 F [22.2 C], adjustable), the different stages will turn off. Modulating Auxiliary Heat: SCR Electric Heat: On demand for auxiliary heating, the electric heating SCR will modulate in order to maintain the LAT heating set point (72 F [22.2 C], adjustable). Modulating Gas Heat: On demand for auxiliary heating, the gas furnace controller will modulate to control the gas flow in order to maintain the LAT heating set point (72 F [22.2 C], adjustable). Room Temperature Heating Override Optional: Room Temperature Heating Override mode is selectable using the BACview display pad or BAS, and operates in heating mode when included (default is OFF ). When the zone air temperature (ZAT) is 2 F (1.1 C) (adjustable) below the ZAT heating set point, the LAT heating set point will increase by a ratio and increase heat modulation in order to raise the ZAT. When the ZAT is equal to or more than the ZAT heating set point, the unit will go back to normal heating operation. When the ZAT is 2 F (1.1 C) (adjustable) above the ZAT heating set point, the LAT heating set point will decrease by a ratio and decrease heat modulation in order to lower the ZAT. When the ZAT is equal to or less than the ZAT heating set point, the unit will go back to normal heating operation. 9. Emergency Heating Mode: Compressors are off in Emergency Heating Mode. Emergency Heating mode is selectable using the BACview display pad or BAS (default is OFF ). When the OAT (ECAT, if wheel exists) is below the OAT (ECAT, if wheel exists) emergency heating set point (50 F [10.0 C], adjustable) minus an adjustable differential, emergency heating is enabled and modulates to maintain LAT heating set point (72 F [22.2 C], adjustable). When the OAT (ECAT, if wheel exists) is above the OAT (ECAT, if wheel exists) emergency heating set point (50 F [10.0 C], adjustable) plus an adjustable differential, emergency heating is disabled. Staged Emergency Heat (Electric Heat or Gas Furnace): 2-Stage Heat: Terminal W1 turning on enables first-stage emergency heating. As the LAT goes further below the LAT heating set point (72 F [22.2 C], adjustable), terminal W2 energizes and second-stage emergency heating is enabled. As the LAT rises, terminal W2 turns off and second-stage emergency heating turns off. As the LAT goes above the LAT heating set point (72 F [22.2 C], adjustable), terminal W1 turns off and first-stage emergency heating turns off. 4-Stage Heat: Terminal W1 turning on enables the heating analog relay module (HARM) on the control panel which activates the different stages of emergency heating. As the LAT goes further below the LAT heating set point (72 F [22.2 C], adjustable), the different stages will turn on. As the LAT goes further above the LAT heating set point (72 F [22.2 C], adjustable), the different stages will turn off. Modulating Emergency Heat: SCR Electric Heat: On demand for emergency heating, the electric heating SCR will modulate in order to maintain the LAT heating set point (72 F [22.2 C], adjustable). Modulating Gas Heat: On demand for emergency heating, the gas furnace controller will modulate to control the gas flow in order to maintain the LAT heating set point (72 F [22.2 C], adjustable).

UNOCCUPIED MODE: When the system has reached the end of its Occupied Mode, the compressor(s) and outdoor fan(s) (subject to minimum run-time) or heating system will turn off. The SF and EF (if existing) will continue to run for 2 minutes before turning off. After this, the ECW (if existing) will turn off and the OA damper will close. Unit is now off. Safety Switches: High Pressure Switch (HP): If HP1 is open, the ALC controller will issue an alarm and compressor #1 is turned off and locked out. After resetting HP1, the compressor lock-out can be reset in the BACview display pad or by cycling the power of the ALC controller. For systems with two compressors, this sequence is the same for compressor #2, Y2 and HP2. Low Pressure Switch (LP1): If LP1 is open after the LP1 by-pass time, the ALC controller will issue an alarm and compressor #1 turns off. After 30 seconds (fixed), the LP1 alarm will reset. Following a minimum time off delay, compressor #1 will turn on. If the ALC controller records 3 low pressure start/restart failure incidents within 1 hour, compressor #1 is locked out and the ALC controller will issue an alarm. The compressor lock-out can be reset in the BACview display pad or by cycling the power of the ALC controller. For systems with two compressors, this sequence is the same for compressor #2, Y2 and LP2. Safety Shutdown: Smoke Detector: When a smoke detector (SD) is provided, it is wired directly to the ALC controller. If smoke is detected, the ALC controller will shut down the unit. The alarm can be reset in the BACview display pad or by cycling the power of the ALC controller. If a compressor fails to start 3 times in an hour due to low pressure switch lock out. The alarm can be reset in the BACview display pad or by cycling the power of the ALC controller. If the SLT drops to 28 F (-2.2 C) or less for 15 minutes, the ALC controller will issue an alarm and compressor stops. When the SLT warms back to 50 F (10.0 C) or more, compressor turns back on. If a compressor fails to start 3 times in an hour due to low suction line temperature, compressor will be locked out. The alarm can be reset in the BACview display pad or by cycling the power of the ALC controller. If the ALC controller detects an LAT sensor failure. The alarm can be reset in the BACview display pad or by cycling the power of the ALC controller. The ALC controller has a digital input for Emergency Shutdown (EMR Energy Management Relay). The default is off (disabled) unless it is part of the order. When enabled, the digital input should be field wired to a normally close (N.C.) switch. When the contact opens, the unit will shut down and the ALC controller will send an alarm to the BAS. When the contact closes, the alarm resets automatically. Standard Alarms: (alarms require reset in the BACview or cycling the power of the ALC controller unless noted) 1. Supply Fan Alarm: If the SF fails to start and the SF-APS (air proving switch) does not confirm air flow to ALC; following 60 second (adjustable) delay. Unit will automatically shut down. 2. Exhaust Fan Alarm: If the EF fails to start and the EF-APS (air proving switch) does not confirm air flow to ALC; following 60 second (adjustable) delay. 3. Compressor #1/#2 Fault: Compressor stops due to HP1/HP2 open; following 30 second (fixed) delay. Requires HP1/HP2 manual reset. 4. Low Pressure Switch #1/#2 Alarm: Compressor stops due to LP1/LP2 open; following 90 second (adjustable) delay. Compressor lock out occurs if alarm happens 3 times in 1 hour (Low Pressure Switch #1/#2 STOP). 5. SLT #1/#2 Alarm: Compressor stops due to SLT1/ SLT2 freeze condition; following 15 minute (adjustable) delay. Compressor lock out occurs if alarm happens 3 times in 1 hour (SLT #1/#2 STOP). 6. Sensors readings exceeding limits, following 2 minute (fixed) delay. Alarms reset automatically. a. ECAT Sensor Failure if wheel exists; Open: -60.2 F (-51.2 C), Short: 296 F (146.7 C). b. EC-RH Sensor Failure if wheel exists; Open: 0%, Short: > 100%). c. SLT1 Sensor Failure Open: -60.2 F (-51.2 C), Short: 296 F (146.7 C). d. SLT2 Sensor Failure Open: -60.2 F (-51.2 C), Short: 296 F (146.7 C). e. OAT Sensor Failure if no wheel exists; Open: -60.2 F (-51.2 C), Short: 296 F (146.7 C). f. OA-RH Sensor Failure if no wheel exists; Open: 0%, Short: > 100%. g. ZAT Sensor Failure Open: < 45.1 F (7.3 C), Short: > 98 F (36.7 C). h. Z-RH Sensor Failure Open: 0%, Short: > 100%. 7. LAT Sensor Failure: Open: -60.2 F (-51.2 C), Short: 296 F (146.7 C). Unit will automatically shut down. 8. High LAT Alarm: LAT high limit, 120 F (48.9 C) (adjustable) with Electric Heat. Alarm resets automatically. 9. High LAT Alarm: LAT high limit, 130 F (54.4 C) (adjustable) with Gas Furnace Heat. Alarm resets automatically. 10. Low LAT Alarm: LAT low limit, 40 F (4.4 C) (adjustable), following 15 minute (adjustable) delay. Unit will automatically shut down. 11. Clogged Filter Alarm: Clogged filter indicator (CFI), following 2 minute (fixed) delay. Alarm resets automatically. 12. Heat Failure: In heating mode and the LAT falls below 50 F (10.0 C) (adjustable), following 15 minute (adjustable) delay. Alarm resets automatically. 13. Smoke Detector Alarm: If smoke is detected, following 30 second (fixed) delay. Unit will automatically shut down. 14. Set Point Overlap Alarm: If OAT cooling and heating set points are selected such that the ranges overlap. Alarm logic will reset modified set points to previous value. Alarm resets automatically. 5

THANK YOU FOR YOUR BUSINESS 7050 Overland Road Orlando, FL 32810 U.S.A. Telephone: +1.407.292.4400 Fax: +1.407.290.1329 www.addison-hvac.com Installation Code and Quarterly Inspections: All installation and service of ADDISON equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Addison and conform to all requirements set forth in the ADDISON manuals and all applicable governmental authorities pertaining to the installation, service, operation and labeling of the equipment. To help facilitate optimum performance and safety, Addison recommends that a qualified contractor conduct quarterly inspections of your ADDISON equipment and perform service where necessary, using only replacement parts sold and supplied by Addison. Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ADDISON representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual. This product is not for residential use. This document is intended to assist licensed professionals in the exercise of their professional judgment. 2013 Addison Printed in the USA All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form or by any means - graphic, electronic, or mechanical, including photocopying, recording, taping or information storage and retrieval systems - without the written permission of Addison. ADSOOASHPBNA 1013 Orig