SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

Similar documents
SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA OUTDOOR UNIT. No. OBH543. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-EF25VE MUZ-EF25VEH MUZ-EF35VE MUZ-EF35VEH MUZ-EF42VE MUZ-EF50VE. No. OBH590 REVISED EDITION-F. Models HFC

SERVICE MANUAL MUZ-SF25VE MUZ-SF25VEH MUZ-SF35VE MUZ-SF35VEH MUZ-SF42VE MUZ-SF42VEH MUZ-SF50VE MUZ-SF50VEH OUTDOOR UNIT. No. OBH629 REVISED EDITION-E

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH629 REVISED EDITION-A. Models HFC. Revision A: MUZ-SF25/35/42VE - E2 have been added. Please void OBH629.

SERVICE MANUAL MUZ-HJ50VA - E1, E2, ER1, ER2, ET1, ET2 MUZ-HJ35VA - E1, E3, ER1, ER3, ET1, ET2

SERVICE MANUAL MUZ-GE50VA - E1 MUZ-GE50VAH - E1 MUZ-GE60VA - E1 MUZ-GE71VA - E1

MUZ-EF25VE - E1 MUZ-EF25VEH - E1 MUZ-EF35VE - E1 MUZ-EF35VEH - E1 MUZ-EF42VE - E1 MUZ-EF50VE - E1 Indoor unit service manual MSZ-EF VE Series (OBH589)

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

1 TECHNICAL CHANGES. MUZ-A09NA MUZ-A09NA - 1 MUZ-A09NA - U1 MUZ-A09NA - U2 1. Refrigerant system diagram has been changed.

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

1. INDOOR UNITS... MSZ-FH-3 2. OUTDOOR UNITS... MSZ-FH-4 3. SYSTEM... MSZ-FH-5

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL INDOOR UNIT. No. OBH788

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MUZ-LN25VG MUZ-LN35VG MUZ-LN50VG MUZ-LN60VG OUTDOOR UNIT. No. OBH767. Models HFC R32

SERVICE MANUAL OUTDOOR UNIT. No. OBH789

Submittal Data: LIVS09HP230V1B. Job Name Location Date. Submitted To. Cool Quiet Comfort & more 9,000 BTU/H (208/230V) Wall Mounted Heat Pump System

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

Submittal Data: VIR09HP115V1B Job Name Location Date. Submitted To. Innovative Ductless solutions 9,000 BTU/H (115V) Wall Mounted Heat Pump System

Submittal Data: VIR12HP230V1B. Job Name Location Date. Submitted To

Submittal Data: VIR24HP230V1B. Job Name Location Date. Submitted To

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy MUZ-GA35VAH - E1

Power Input (Max) 1,500 W Dehumidification 1.7 pt/hr HSPF 10.5 COP 4.2 Compressor Type DC Inverter Driven 2-Stage Rotary Heating at 17 F FLA 8.

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models

Revision C: Specification has been corrected. The value of "Moisture removal" for MSZ-GE24NA and MSY-GE24NA has been corrected. [2.7 pt.

DESIGN & TECHNICAL MANUAL

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DESIGN & TECHNICAL MANUAL

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models

15A 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

13 SEER HEAT PUMPS. Featuring Earth-Friendly R-410A Refrigerant 13PJL SERIES. Features Coils constructed with copper tubing and enhanced aluminum

Submittal Data: UMAT48HP230V1AF. Job Name Location Date. Submitted To

15A Operating Range Communication Wire Size 18-2 AWG / 300V THHN Cooling (Max) 118 F (48 C)

DESIGN & TECHNICAL MANUAL

SERVICE MANUAL MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. OB368 R410A CONTENTS

13 SEER CONDENSING UNITS

18-2 AWG / 300V THHN Operating Range MCA 2.0A Cooling (Max) 118 F (48 C) MOCP/Breaker Size 15A (Min) 0 F (-18 C)

TECHNICAL & SERVICE MANUAL

Innovative Ductless Mini Split Solution Submittal Data: GUHD24ND3FO/GKH24D3FI Job Name Location Date

Air Conditioner CONTENTS

16 SEER TWO-STAGE AIR CONDITIONERS

DESIGN & TECHNICAL MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

TZPL SERIES. Applications Thermal Zone remote heat pumps offer comfort and dependability for single, multi-family and light commercial applications.

Single Zone Air Conditioner SVC MANUAL (Exploded View)

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

DESIGN & TECHNICAL MANUAL

SERVICE MANUAL. Inverter Wall Mounted Single Split. MODELS Cooling Only. Heatpump SM-5WM-Y-NA-B1

SUBMITTAL DATA: MSY-GL12NA & MUY-GL12NA 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL

13 SEER CONDENSING UNITS & AIR HANDLERS

TECHNICAL GUIDE MODELS: DCPM/DHPM PREMIUM SERIES DUCTLESS SINGLE-SPLIT AIR CONDITIONERS AND HEAT PUMPS 22 SEER 1 PHASE 3/4 THRU 3 NOMINAL TONS

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SUBMITTAL DATA: MSY-GL24NA & MUY-GL24NA 24,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM. System Reference:

Air Conditioners. Technical Data RZQG-L

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

PAJ3. Product Specifications

Product Data INDUSTRY LEADING FEATURES / BENEFITS

SERVICE MANUAL. Wireless type Models MSZ-A09RV - (WH) MUZ-A09RV - MSZ-A12RV - (WH) MUZ-A12RV - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

14.5 SEER HEAT PUMPS. Featuring New Industry Standard R-410A Refrigerant 14PJM SERIES

CS-E18NKUA CS-E24NKUA CU-E18NKUA CU-E24NKUA TABLE OF CONTENTS WARNING

Part 3 Troubleshooting

DESIGN & TECHNICAL MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DESIGN & TECHNICAL MANUAL

Transcription:

Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH747 REVISED EDITION-A Models MUZ-HM09NA - U8 MUZ-HM18NA - U1 MUZ-HM09NA2 - U8 MUZ-HM18NA2 - U1 MUZ-HM12NA - U8 MUZ-HM24NA- U1 MUZ-HM12NA2 - U8 MUZ-HM24NA2 - U1 MUZ-HM15NA - U1 MUZ-HM15NA2 - U1 Indoor unit service manual MSZ-HM NA Series (OBH746) MUZ-HM24NA CONTENTS 1. TECHNICAL CHANGES 3 2. PART NAMES AND FUNCTIONS 4 3. SPECIFICATION 5 4. OUTLINES AND DIMENSIONS 9 5. WIRING DIAGRAM 11 6. REFRIGERANT SYSTEM DIAGRAM 13 7. DATA 16 8. ACTUATOR CONTROL 28 9. SERVICE FUNCTIONS 29 10. TROUBLESHOOTING 30 11. DISASSEMBLY INSTRUCTIONS 54 PARTS CATALOG (OBB747) NOTE: RoHS compliant products have <G> mark on the spec name plate.

Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions. Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. 2

1 TECHNICAL CHANGES MUZ-HM24NA - U1 1. New model MUZ-HM09NA - U8 MUZ-HM09NA2 - U8 MUZ-HM12NA - U8 MUZ-HM12NA2 - U8 MUZ-HM15NA - U1 MUZ-HM15NA2 - U1 MUZ-HM18NA - U1 MUZ-HM18NA2 - U1 MUZ-HM24NA2 - U1 1. New model 3

2 PART NAMES AND FUNCTIONS MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 Air inlet (back and side) Piping Air outlet Drain hose Drain outlet MUZ-HM24NA MUZ-HM24NA2 Air inlet (back and side) Piping Drain hose Air outlet Drain outlet 4

3 SPECIFICATION Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Rated (Maximum) Power consumption Rated (Minimum~Maximum) MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 Cooling 1 Btu/h 9,000 ( 3,800 ~ 10,000 ) 12,000 ( 3,800 ~ 12,200 ) Heating 47 1 Btu/h 10,900 ( 4,500 ~ 11,800 ) 12,200 ( 5,500 ~ 14,500 ) Heating 17 2 Btu/h 6,700 (7,200) 7,600 (9,000) Cooling 1 W 728 (201-828) 1,188 (201-1,278) Heating 47 1 W 877 (251-977) 967 (336-1,197) Power consumption Rated (Maximum) Heating 17 2 W 677 (757) 777 (967) EER 1 [SEER] 3 Cooling 12.0 [ 18.0 ] 9.9 [ 18.0 ] HSPF IV 4 Heating 10.0 [NA] / 8.5 [NA2] 10.0 [NA] / 8.5 [NA2] COP Heating 1 3.55 3.61 Power factor Cooling (208/230) % Heating (208/230) % Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 12 Fan motor F.L.A A 0.50 Model KNB073FQDHC KNB092FQAHC Compressor R.L.A A 6.6 L.R.A A 8.2 Refrigeration oil L (Model) 0.32 (NEO22) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) 46 49 Heating db(a) 50 51 Airfl ow High - Med. - Low Fan speed High - Med. - Low Defrost method Dimensions Cooling CFM 1,063 1,102-639 Heating CFM 1,240-1,105 1,186-1,116-1,045 Cooling rpm 740 810-490 Heating rpm 860-770 870-820 - 770 Reverse cycle W in. 31-1/2 D in. 11-1/4 H in. 21-5/8 Weight Ib. 73 73 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping t supplied Refrigerant pipe size (Min. wall thickness) Connection method Between the indoor & outdoor units Liquid in. 1/4 (0.0315) Gas in. 3/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 40 Piping length ft. 65 Refrigerant charge (R410A) 1 lb. 12 oz. 2 lb. 9 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 3: Test condition (Refer to page 6.) 4: Test condition (Refer to page 6.) 5

Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Rated (Maximum) Power consumption Rated (Minimum~Maximum) Power consumption Rated (Maximum) MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 Cooling 1 Btu/h 14,000 (3,100-16,000) 17,200 (5,800-18,000) Heating 47 1 Btu/h 18,000 (4,800-18,500) 18,000 (5,400-20,900) Heating 17 2 Btu/h 11,500 (14,000) 11,500 (15,000) Cooling 1 W 1,127 (187-1,957) 1,598 (308-2,028) Heating 47 1 W 1,570 (190-1,980) 1,548 (288-2,208) Heating 17 2 W 1,290 (1,820) 1,258 (1,908) EER 1 [SEER] 3 Cooling 12.0 [18.0] 10.5 [18.0] HSPF IV 4 Heating 10.0 [NA] / 8.5 [NA2] 10.0 [NA] / 8.5 [NA2] COP Heating 1 3.30 3.32 Power factor Cooling (208/230) % 98/98 98/98 Heating (208/230) % 98/98 97/97 Power supply V, phase, Hz 208/230, 1, 60 208/230, 1, 60 Max. fuse size (time delay) A 15 15 Min. circuit ampacity A 10 10 Fan motor F.L.A A 0.50 0.50 Model SNB130FQBMT SNB130FQBMT Compressor R.L.A A 7.4 7.4 L.R.A A 9.3 9.3 Refrigeration oil L (Model) 0.35 (FV50S) 0.35 (FV50S) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) 49 49 Heating db(a) 51 51 Airfl ow High - Med. - Low Fan speed High - Med. - Low Defrost method Dimensions Cooling CFM 1,102-639 1,102-639 Heating CFM 1,186-1,045-1,045 1,186-1,045-1,045 Cooling rpm 810-490 810-490 Heating rpm 870-770 - 770 870-770 - 770 Reverse cycle W in. 31-1/2 31-1/2 D in. 11-1/4 11-1/4 H in. 21-5/8 21-5/8 Weight Ib. 81 81 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping t supplied Refrigerant pipe size (Min. wall thickness) Connection method Between the indoor & outdoor units Liquid in. 1/4 (0.0315) 1/4 (0.0315) Gas in. 1/2 (0.0315) 1/2 (0.0315) Indoor Flared Flared Outdoor Flared Flared Height difference ft. 40 40 Piping length ft. 65 65 Refrigerant charge (R410A) 2 lb. 9 oz. 2 lb. 10 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 3: Test condition (Refer to page 6.) 4: Test condition (Refer to page 6.) 6

Outdoor unit model Capacity Rated (Minimum~Maximum) Capacity Rated (Maximum) Power consumption Rated (Minimum~Maximum) MUZ-HM24NA MUZ-HM24NA2 Cooling 1 Btu/h 22,500 (5,800 ~ 22,500) Heating 47 1 Btu/h 26,000 (5,400 ~ 26,000) Heating 17 2 Btu/h 18,500 (18,500) Cooling 1 W 2,575 (275 ~ 2,575) Heating 47 1 W 2,445 (265 ~ 2,445) Power consumption Rated (Maximum) Heating 17 2 W 2,245 (2,245) EER 1 [SEER] 3 Cooling 8.6 [18.0] HSPF IV 4 Heating 10.0 [NA] / 8.5 [NA2] COP Heating 1 3.05 Power factor Cooling (208/230) % 99/99 Heating (208/230) % 99/99 Power supply V, phase, Hz 208/230, 1, 60 Max. fuse size (time delay) A 15 Min. circuit ampacity A 14 Fan motor F.L.A 0.93 Model SNB130FQBMT Compressor R.L.A 10 L.R.A 12.5 Refrigeration oil L (Model) 0.35 (FV50S) Refrigerant control Linear expansion valve Sound level 1 Cooling db(a) 54 Heating db(a) 55 Airfl ow High - Med. - Low Fan speed High - Med. - Low Defrost method Dimensions COOL CFM 1,742-922 HEAT CFM 1,691-1,691-1,372 Cooling rpm 840-450 Heating rpm 810-810 - 650 Reverse cycle W in. 33-1/16 D in. 13 H in. 34-5/8 Weight Ib. 121 External fi nish Munsell 3Y 7.8/1.1 Refrigerant piping t supplied Refrigerant pipe size (Min. wall thickness) Connection method Between the indoor & outdoor units Refrigerant charge (R410A) Liquid in. 3/8 (0.0315) Gas in. 5/8 (0.0315) Indoor Flared Outdoor Flared Height difference ft. 50 Piping length ft. 100 3 lb. 9 oz. NOTE: Test conditions are based on AHRI 210/240. 1: Rating conditions (Cooling) Indoor: 80 FDB, 67 FWB, Outdoor: 95 FDB, (75 FWB) (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 47 FDB, 43 FWB 2: (Heating) Indoor: 70 FDB, 60 FWB, Outdoor: 17 FDB, 15 FWB 7

Test condition 3, 4 ARI Mode Test SEER (Cooling) HSPF (Heating) "A-2" Cooling Steady State at rated compressor Speed "B-2" Cooling Steady State at rated compressor Speed "B-1" Cooling Steady State at minimum compressor Speed "F-1" Cooling Steady State at minimum compressor Speed "E-V" Cooling Steady State at Intermediate compressor Speed 5 "H1-2" Heating Steady State at rated compressor Speed "H3-2" Heating at rated compressor Speed "H0-1" Heating Steady State at minimum compressor Speed "H1-1" Heating Steady State at minimum compressor Speed "H2-V" Heating at Intermediate compressor Speed 5 Indoor air condition ( F) Outdoor air condition ( F) Dry bulb Wet bulb Dry bulb Wet bulb 80 67 95 (75) 80 67 82 (65) 80 67 82 (65) 80 67 67 (53.5) 80 67 87 (69) 70 60 47 43 70 60 17 15 70 60 62 56.5 70 60 47 43 70 60 35 33 5: At Intermediate compressor Speed = ("Rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed". OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed voltage (V) Outdoor unit 208/230 V 1 phase 60 Hz Min. 187 208 230 Max. 253 (2) OPERATION Intake air temperature ( F) Mode Condition Indoor Outdoor DB WB DB WB Standard temperature 80 67 95 Cooling Maximum temperature 90 73 115 Minimum temperature 67 57 14 Maximum humidity 78 % Standard temperature 70 60 47 43 Heating Maximum temperature 80 67 75 65 Minimum temperature 70 60-4 -5 8

4 OUTLINES AND DIMENSIONS MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 Unit: inch REQUIRED SPACE *1 4 in. (100 mm) or more when front and sides of the unit are clear 4 in. (100 mm) or more clear *1 4 in. (100 mm) or more 8 in. (200 mm) or more *2 14 in. (350 mm) or more *2 When any 2 sides of left, right and rear of the unit are clear holes Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 1/4 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 3/8 (HM09/12) Ø 1/2 (HM15/18) 9

MUZ-HM24NA MUZ-HM24NA2 Unit: inch REQUIRED SPACE *1 20 in. (500 mm) or more when front and sides of the unit are clear Clear *1 16-7/16 Air in Drain hole 1-9/16 1-5/8 4 in. (100 mm) or more 4 in. (100 mm) or more 13 2 Air in 14-3/16 Air out 6-7/8 19-11/16 33-1/16 4-5/16 2-holes 13/32 13/16 3-3/16 20 in. (500 mm) or more *2 Service panel 14 in. (350 mm) or more *2 When any 2 sides of left, right and rear of the unit are clear Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 3/8 17-25/32 34-5/8 44 35 6-1/2 3-29/32 7-11/16 Gas refrigerant pipe joint Refrigerant pipe (flared) Ø 5/8 10

5 WIRING DIAGRAM MUZ-HM09NA - U8 MUZ-HM09NA2 - U8 MUZ-HM12NA - U8 MUZ-HM12NA2 - U8 MUZ-HM15NA - U1 MUZ-HM15NA2 - U1 MUZ-HM18NA - U1 MUZ-HM18NA2 - U1 11

MUZ-HM24NA - U1 MUZ-HM24NA2 - U1 12

6 REFRIGERANT SYSTEM DIAGRAM MUZ-HM09NA MUZ-HM09NA2 Refrigerant pipe ø3/8 (ø9.52) (with heat insulator) Flared connection Muffler Stop valve (with service port) Service port 4-way valve Discharge temperature thermistor RT62 Muffler Service port Compressor Defrost thermistor RT61 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Unit: Inch (mm) Flared connection Stop valve (with strainer) Refrigerant pipe ø1/4 (ø6.35) (with heat insulator) Capillary tube O.D. 0.118 I.D. 0.079 9-7/16 LEV (ø3.0 ø2.0 240) Strainer #100 R.V. coil heating ON cooling Refrigerant flow in cooling Refrigerant flow in heating MUZ-HM12NA MUZ-HM12NA2 Refrigerant pipe ø3/8 (ø9.52) (with heat insulator) 4-way valve Flared connection Muffler Stop valve (with service port) Service port Discharge temperature thermistor RT62 Muffler Service port Compressor Defrost thermistor RT61 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Flared connection Stop valve (with strainer) Refrigerant pipe ø1/4 (ø6.35) (with heat insulator) Capillary tube O.D. 0.118 I.D. 0.071 23-5/8 Capillary tube (ø3.0 ø1.8 600) ( 2) O.D. 0.118 I.D. 0.079 9-7/16 LEV (ø3.0 ø2.0 240) Strainer #100 R.V. coil heating ON cooling Refrigerant flow in cooling Refrigerant flow in heating 13

MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 Unit: Inch (mm) Refrigerant pipe ø1/2 (ø12.7) (with heat insulator) 4-way valve Flared connection Muffler Stop valve (with service port) Service port Discharge temperature thermistor RT62 Muffler Service port Compressor Defrost thermistor RT61 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Flared connection Stop valve (with strainer) Refrigerant pipe ø1/4 (ø6.35) (with heat insulator) MUZ-HM24NA MUZ-HM24NA2 Capillary tube O.D. 0.157 I.D. 0.094 9-7/16 (ø4.0 ø2.4 240) LEV Capillary tube O.D. 0.118 I.D. 0.079 8-9/32 (ø3.0 ø2.0 210) Strainer #100 R.V. coil heating ON cooling Refrigerant flow in cooling Refrigerant flow in heating Refrigerant pipe ø5/8 (ø15.88) (with heat insulator) 4-way valve Muffler with #100 mesh strainer Service port Flared connection Stop valve (with service port) Service port Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Flared connection Stop valve Refrigerant pipe ø3/8 (ø9.52) (with heat insulator) Strainer #100 Muffler Compressor Capillary tube O.D. 0.157 I.D. 0.094 3-15/16 (ø4.0 ø2.4 100) Capillary tube O.D. 0.118 I.D. 0.079 7-7/8 (ø3.0 ø2.0 200( 4)) LEV Strainer #100 Capillary tube O.D. 0.157 I.D. 0.094 7-7/8 (ø4.0 ø2.4 200) Outdoor heat exchanger temperature thermistor RT68 R.V. coil heating ON cooling Refrigerant flow in cooling Refrigerant flow in heating 14

MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Model MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 Max. Length A Refrigerant piping: ft. Max. Height difference B 65 40 Gas 3/8 Piping size O.D: in. Liquid 100 50 5/8 3/8 1/2 1/4 Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: oz.) NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation. Model MUZ-HM09NA MUZ-HM09NA2 Outdoor unit precharged 1 lb. 12 oz. Refrigerant piping length (one way): ft. 25 30 40 50 60 65 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 2 lb. 9 oz. 0 1.08 3.24 5.40 7.56 8.64 MUZ-HM18NA MUZ-HM18NA2 Model MUZ-HM24NA MUZ-HM24NA2 2 lb. 10 oz. Outdoor unit precharged Calculation: X oz. = 1.08/5 oz./ft. (Refrigerant piping length (ft.) - 25) Refrigerant piping length (one way): ft. 25 30 40 50 60 70 80 90 100 3 lb. 9 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20 Calculation: X oz. = 1.08/5 oz./ft. (Refrigerant piping length (ft.) - 25) 15

7 DATA MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 7-1. PERFORMANCE DATA 1) COOLING CAPACITY Model MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 Indoor air Outdoor intake air DB temperature ( F) IWB ( F) 75 85 95 105 115 TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC 71 11.0 7.6 0.67 10.3 7.1 0.73 9.7 6.6 0.79 9.0 6.2 0.83 8.3 5.7 0.86 67 10.4 8.6 0.63 9.7 8.0 0.69 9.0 7.4 0.75 8.4 6.9 0.80 7.7 6.3 0.83 63 9.8 9.4 0.60 9.1 8.7 0.66 8.5 8.1 0.72 7.7 7.3 0.77 7.0 6.7 0.80 71 14.7 9.4 1.08 13.7 8.7 1.18 12.9 8.2 1.27 12.0 7.6 1.34 11.0 7.0 1.39 67 13.9 10.7 1.02 13.0 10.0 1.12 12.0 9.2 1.21 11.2 8.6 1.28 10.3 7.9 1.34 63 13.1 11.8 0.97 12.1 10.9 1.07 11.3 10.2 1.16 10.3 9.3 1.23 9.4 8.5 1.28 71 17.2 11.1 1.04 16.0 10.4 1.14 15.1 9.7 1.23 14.0 9.1 1.29 12.9 8.3 1.35 67 16.2 12.7 0.98 15.1 11.8 1.08 14.0 10.9 1.17 13.0 10.2 1.24 12.0 9.3 1.30 63 15.3 13.9 0.94 14.1 12.9 1.04 13.2 12.0 1.12 12.0 10.9 1.19 10.9 10.0 1.24 71 21.1 15.3 1.46 19.7 14.3 1.60 18.5 13.4 1.72 17.2 12.5 1.81 15.8 11.5 1.89 67 20.0 17.2 1.38 18.6 16.0 1.52 17.2 14.8 1.64 16.0 13.8 1.74 14.7 12.6 1.82 63 18.7 18.6 1.31 17.4 17.3 1.45 16.2 16.1 1.57 14.7 14.6 1.67 13.4 13.3 1.74 71 27.6 20.9 2.34 25.8 19.5 2.56 24.2 18.3 2.76 22.5 17.0 2.91 20.7 15.7 3.02 67 26.1 23.2 2.21 24.3 21.6 2.43 22.5 20.0 2.63 20.9 18.6 2.79 19.2 17.1 2.92 63 24.5 25.1 2.10 22.7 23.3 2.33 21.2 21.6 2.51 19.2 19.7 2.68 17.6 18.0 2.79 NOTE: 1. IWB : Intake air wet-bulb temperature TC : Total Capacity (x10 3 Btu/h) SHC : Sensible Heat Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. SHC is based on 80 F of indoor Intake air DB temperature. 2) COOLING CAPACITY CORRECTIONS Refrigerant piping length (one way: ft.) Model 25 (std.) 40 65 100 MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 1.0 0.954 0.878 1.0 0.954 0.878 0.771 16

3) HEATING CAPACITY Indoor air Outdoor intake air WB temperature ( F) Model 5 15 25 35 43 45 55 IDB ( F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC 75 4.8 0.53 6.3 0.67 7.9 0.79 9.4 0.88 10.6 0.92 11.0 0.94 12.4 0.97 MUZ-HM09NA 70 5.2 0.51 6.7 0.65 8.2 0.77 9.6 0.86 10.9 0.90 11.2 0.92 12.7 0.95 MUZ-HM09NA2 65 5.5 0.49 6.9 0.62 8.6 0.74 10.0 0.83 11.2 0.88 11.6 0.89 13.0 0.94 75 5.4 0.58 7.1 0.74 8.8 0.87 10.6 0.97 11.9 1.01 12.3 1.03 13.9 1.07 MUZ-HM12NA 70 5.8 0.56 7.5 0.71 9.2 0.85 10.8 0.94 12.2 0.99 12.6 1.01 14.2 1.05 MUZ-HM12NA2 65 6.1 0.53 7.7 0.68 9.6 0.82 11.2 0.92 12.6 0.97 12.9 0.98 14.5 1.03 75 7.9 0.94 10.4 1.19 13.1 1.40 15.6 1.56 17.6 1.64 18.1 1.66 20.5 1.73 MUZ-HM15NA 70 8.6 0.90 11.1 1.15 13.5 1.37 15.9 1.52 18.0 1.60 18.5 1.63 21.0 1.70 MUZ-HM15NA2 65 9.0 0.86 11.3 1.10 14.1 1.32 16.5 1.48 18.5 1.56 19.1 1.58 21.4 1.66 75 7.9 0.94 10.4 1.18 13.1 1.39 15.6 1.55 17.6 1.63 18.1 1.65 20.5 1.72 MUZ-HM18NA 70 8.6 0.90 11.1 1.14 13.5 1.36 15.9 1.51 18.0 1.59 18.5 1.62 21.0 1.69 MUZ-HM18NA2 65 9.0 0.86 11.3 1.10 14.1 1.31 16.5 1.47 18.5 1.55 19.1 1.57 21.4 1.65 75 11.4 1.48 15.1 1.86 18.9 2.19 22.5 2.44 25.4 2.56 26.1 2.60 29.6 2.70 MUZ-HM24NA 70 12.4 1.41 16.0 1.80 19.5 2.14 23.0 2.38 26.0 2.50 26.8 2.55 30.3 2.65 MUZ-HM24NA2 65 13.0 1.35 16.4 1.73 20.4 2.06 23.8 2.31 26.8 2.44 27.6 2.48 30.9 2.60 NOTE: 1. IDB : Intake air dry-bulb temperature TC : Total Capacity (x10 3 Btu/h) TPC : Total Power Consumption (kw) 2. Above data is for heating operation without any frost. How to operate with fixed operational frequency of the compressor. 1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner. 2. The compressor starts with operational frequency. 3. The fan speed of the indoor unit is High. 4. This operation continues for 30 minutes. 5. In order to release this operation, press the EMERGENCY OPERATION switch or press any button on the remote controller. 17

7-2. PERFORMANCE CURVE Cooling Indoor air Wet-bulb temperature difference ( F) Total power consumption (kw) Capacity correction factors 1.0 0.9 0.8 0.7 0.6 0.5 1.5 1.4 1.3 1.2 1.1 1.0 Cooling capacity (at Rated frequency) 0.9 72 68 64 14 23 32 41 50 59 68 77 86 95 104 113 MUZ-HM09NA MUZ-HM09NA2 Outdoor intake air DB temperature( F) SHF at rating condition = 0.82 Airflow = 367 CFM Indoor intake air WB temperature ( F) 0.4 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) MUZ-HM15NA MUZ-HM15NA2 71 67 63 Indoor intake air Wet-bulb temperature( F) 79 75 MUZ-HM12NA MUZ-HM12NA2 Total power consumption (kw) 1.5 1.4 1.3 1.2 1.1 1.0 SHF at rating condition = 0.74 Airflow = 367 CFM Indoor intake air WB temperature ( F) 0.9 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) MUZ-HM18NA MUZ-HM18NA2 71 67 63 Total power consumption (kw) SHF at rating condition = 0.78 Airflow = 533 CFM 1.5 1.4 1.3 1.2 1.1 1.0 0.9 0.8 0.7 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) Indoor intake air WB temperature ( F) 71 67 63 Total power consumption (kw) 2.0 1.8 1.6 1.4 SHF at rating condition = 0.86 Airflow = 625 CFM Indoor intake air WB temperature ( F) 1.2 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) 71 67 63 MUZ-HM24NA MUZ-HM24NA2 Total power consumption (kw) 3.2 3.0 2.8 2.6 2.4 2.2 2.0 1.8 SHF at rating condition = 0.89 Airflow = 702 CFM Indoor intake air WB temperature ( F) 65 75 85 95 105 115 Outdoor intake air DB temperature ( F) 71 67 63 This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. 18

Heating Indoor air Dry-bulb temperature difference ( F) Capacity correction factor 1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 Heating capacity (at Rated frequency) Indoor intake air Dry-bulb temperature ( F) 59 68 79-4 5 14 23 32 41 50 59 Outdoor intake air WB temperature ( F) MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 Total power consumption (kw) MUZ-HM24NA MUZ-HM24NA2 Total power consumption (kw) 1.1 0.9 0.7 0.5 0.3 0 10 20 30 40 50 60 70 Outdoor intake air WB temperature ( F) 3.2 2.9 2.6 2.3 2.0 1.7 1.4 1.1 Indoor intake air DB temperature ( F) MUZ-HM15NA MUZ-HM15NA2 Total power consumption (kw) 2.0 1.7 1.4 1.1 0.8 Airflow = 413 CFM Indoor intake air DB temperature ( F) Indoor intake air DB temperature ( F) 75 70 65 Airflow = 463 CFM 0.5-5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) Airflow = 702 CFM 0.8-5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) 75 70 65 75 70 65 0.5 0.4 0 10 20 30 40 50 60 70 Outdoor intake air WB temperature ( F) This value of frequency is not the same as the actual frequency in operating. Refer to 7-5 and 7-6 for the relationships between frequency and capacity. Total power consumption (kw) 1.2 1.1 1.0 0.9 0.8 0.7 0.6 Indoor intake air DB temperature ( F) MUZ-HM18NA MUZ-HM18NA2 Total power consumption (kw) 2.0 1.7 1.4 1.1 0.8 Airflow = 413 CFM Indoor intake air DB temperature ( F) 75 70 65 Airflow = 625 CFM 0.5-5 5 15 25 35 45 55 65 Outdoor intake air WB temperature ( F) 75 70 65 19

7-3. CONDENSING PRESSURE Cooling Data are based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-HM09NA MUZ-HM09NA2 Condensing pressure (PSIG) 440 400 360 320 Indoor DB temperature ( F) 86 80 75 70 Suction pressure (PSIG) 200 180 160 140 Indoor DB temperature ( F) 86 80 75 70 280 6870 75 80 85 90 95 100 105( F) Outdoor ambient temperature 120 68 70 75 80 85 90 95 100 105( F) Outdoor ambient temperature MUZ-HM12NA MUZ-HM12NA2 (PSIG) 420 86 80 75 70 (PSIG) 190 86 Condensing pressure 380 340 300 Indoor DB temperature ( F) Suction pressure 170 150 130 Indoor DB temperature ( F) 80 75 70 260 6870 75 80 85 90 95 100 105( F) Outdoor ambient temperature 110 6870 75 80 85 90 95 100 105( F) Outdoor ambient temperature MUZ-HM15NA MUZ-HM15NA2 (PSIG) 500 Condensing pressure 450 400 350 300 250 Indoor DB temperature ( F) 86 80 75 70 200 65 70 75 80 85 90 95 100 105 ( F) Outdoor ambient temperature (PSIG) 180 Suction pressure 160 140 120 100 80 Indoor DB temperature ( F) 60 65 70 75 80 85 90 95 100 105 Outdoor ambient temperature 86 80 75 70 ( F) 20

MUZ-HM18NA MUZ-HM18NA2 (PSIG) 550 Condensing pressure 500 450 400 350 300 Indoor DB temperature ( F) 86 80 75 70 250 65 70 75 80 85 90 95 100 105 ( F) Outdoor ambient temperature (PSIG) 200 Suction pressure 180 160 140 120 100 Indoor DB temperature ( F) 80 65 70 75 80 85 90 95 100 105 Outdoor ambient temperature 86 80 75 70 ( F) MUZ-HM24NA MUZ-HM24NA2 (PSIG) 510 Condensing pressure 470 430 390 350 310 Indoor DB temperature ( F) 86 80 75 70 (PSIG) 180 Suction pressure 165 150 135 120 105 Indoor DB temperature ( F) 86 80 75 70 270 70 75 80 85 90 95 100 105 ( F) Outdoor ambient temperature 90 70 75 80 85 90 95 100 105 Outdoor ambient temperature ( F) Heating Data are based on the condition of outdoor humidity 75%. Air flow should be set to High speed. Data are for heating operation without any frost. MUZ-HM09NA MUZ-HM09NA2 Condensing pressure (PSIG) 370 345 320 295 270 Indoor DB temperature ( F) 75 70 65 Suction pressure (PSIG) 210 185 160 135 110 Indoor DB temperature ( F) 75 70 65 245 58Hz 85 58Hz 220 60 5 15 25 35 45 55 65 75( F) 5 15 25 35 45 55 65 75( F) Outdoor ambient temperature Outdoor ambient temperature 21

MUZ-HM12NA MUZ-HM12NA2 Condensing pressure (PSIG) 460 420 380 340 Indoor DB temperature ( F) 58Hz 75 70 65 Suction pressure (PSIG) 210 185 160 135 110 Indoor DB temperature ( F) 75 70 65 300 85 58Hz 260 60 5 15 25 35 45 55 65 75( F) 5 15 25 35 45 55 65 75( F) Outdoor ambient temperature Outdoor ambient temperature MUZ-HM15NA MUZ-HM15NA2 Condensing pressure (PSIG) 500 450 400 350 Indoor DB temperature ( F) 75 70 65 (PSIG) 190 Suction pressure 165 140 115 90 Indoor DB temperature ( F) 75 70 65 300 58Hz 65 58Hz Condensing pressure 250 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature MUZ-HM18NA MUZ-HM18NA2 (PSIG) 500 450 400 350 300 Indoor DB temperature ( F) 58Hz 75 70 65 40 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature (PSIG) 200 Suction pressure 175 150 125 100 75 Indoor DB temperature ( F) 58Hz 75 70 65 250 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature 50 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature 22

MUZ-HM24NA MUZ-HM24NA2 Condensing pressure (PSIG) 550 500 450 400 350 Indoor DB temperature ( F) 75 70 65 (PSIG) 200 Suction pressure 175 150 125 100 Indoor DB temperature ( F) 75 70 65 300 81Hz 75 81Hz 250 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature 50 5 15 25 35 45 55 65 75 ( F) Outdoor ambient temperature 23

7-4. STANDARD OPERATION DATA Total Electrical circuit Refrigerant circuit Indoor unit Outdoor unit Model MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA Item Unit Cooling Heating Cooling Heating Cooling Heating Capacity Btu/h 9,000 10,900 12,000 14,400 14,000 18,000 SHF 0.82 0.77 0.78 Input kw 0.750 0.900 1.210 0.990 1.17 1.60 Rated frequency Hz 59.5 77.5 69.0 77.0 56.5 74 Indoor unit MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA V, Power supply phase, 208/230, 1, 60 Hz Input kw 0.022 0.023 0.022 0.023 0.043 0.030 Fan motor current A 0.24/0.22 0.25/0.23 0.24/0.22 0.25/0.23 0.43/0.39 0.34/0.31 Outdoor unit MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 Power supply V, phase, Hz 208/230, 1, 60 Input kw 0.728 0.877 1.188 0.967 1.127 1.570 Comp. current A 3.32/3.00 3.66/3.31 4.39/3.97 5.41/4.89 4.91/4.44 7.11/6.43 Fan motor current A 0.27/0.24 0.30/0.27 0.34/0.31 0.31/0.28 0.41/0.37 0.40/0.36 Condensing pressure PSIG 389 331 389 397 396 427 Suction pressure PSIG 151 103 133 104 138 98 Discharge temperature F 154 152 163 162 168 178 Condensing temperature F 115 103 115 116 115 120 Suction temperature F 59 39 56 35 61 31 Comp. shell bottom temperature F 151 149 158 158 152 158 Ref. pipe length ft. 25 Refrigerant charge (R410A) 1 lb. 12 oz. 2 lb. 9 oz. Intake air temperature DB F 80 70 80 70 80 70 WB F 67 60 67 60 67 60 Discharge air temperature DB F 60 97 56 108 58 114 WB F 58 55 56 Fan speed (High) rpm 1,020 1,040 1,020 1,040 1,280 1,140 Airfl ow (High) CFM 367 (Wet) 413 367 (Wet) 413 498 (Wet) 463 Intake air temperature DB F 95 47 95 47 95 47 WB F 43 43 43 Fan speed rpm 800 850 900 860 910 900 Airfl ow CFM 1151 1225 1229 1172 1,243 1,229 24

7-4. STANDARD OPERATION DATA Total Electrical circuit Refrigerant circuit Indoor unit Outdoor unit Model MSZ-HM18NA MSZ-HM24NA Item Unit Cooling Heating Cooling Heating Capacity Btu/h 17,200 18,000 22,500 26,000 SHF 0.86 0.89 Input kw 1.64 1.59 2.63 2.5 Rated frequency Hz 68 74 98 108 Indoor unit MSZ-HM18NA MSZ-HM24NA Power supply V, phase, Hz 208/230, 1, 60 Input kw 0.042 0.042 0.055 Fan motor current A 0.44/0.40 0.44/0.40 0.55/0.50 Outdoor unit MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 Power supply V, phase, Hz 208/230, 1, 60 Input kw 1.598 1.548 2.575 2.445 Comp. current A 7.22/6.53 7.11/6.43 11.11/10.05 10.56/9.55 Fan motor current A 0.41/0.37 0.40/0.36 1.05/0.95 1.05/0.95 Condensing pressure PSIG 423 361 404 403 Suction pressure PSIG 144 99 127 94 Discharge temperature F 165 161 174 194 Condensing temperature F 120 108 116 116 Suction temperature F 54 35 54 44 Comp. shell bottom temperature F 149 143 173 192 Ref. pipe length ft. 25 Refrigerant charge (R410A) 2 lb. 10 oz. 3 lb 9 oz. Intake air temperature DB F 80 70 80 70 WB F 67 60 67 60 Discharge air temperature DB F 58 114 57 108 WB F 56 56 Fan speed (High) rpm 1,140 1,140 1,250 1,250 Airfl ow (High) CFM 562 (Wet) 625 632 (Wet) 702 Intake air temperature DB F 95 47 95 47 WB F 43 43 Fan speed rpm 910 900 810 810 Airfl ow CFM 1,243 1,229 1,691 1,691 25

7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY 1.5 MUZ-HM09NA MUZ-HM09NA2 Correction of Cooling capacity Correction of Cooling total input 1.5 1.5 Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors 1.0 0.5 1.0 0.5 1.0 0.5 1.5 1.0 0.5 0 50 100(Hz) 0 50 100(Hz) 0 50 100 150(Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 1.5 MUZ-HM12NA MUZ-HM12NA2 Correction of Cooling capacity Correction of Cooling total input 1.5 Correction of Heating capacity 1.5 0 50 100 150(Hz) The operational frequency of compressor Correction of Heating total input 2.0 Capacity correction factors 1.0 0.5 1.0 0.5 1.0 0.5 1.5 1.0 0.5 0 50 100(Hz) The operational frequency of compressor 0 50 100(Hz) 0 50 100 150(Hz) The operational frequency of compressor The operational frequency of compressor 0 50 100 150(Hz) The operational frequency of compressor 2.0 MUZ-HM15NA MUZ-HM15NA2 Correction of Cooling capacity Correction of Cooling total input 2.0 2.0 Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 0 25 50 75 100 (Hz) 0 25 50 75 100(Hz) 0 50 100 150 (Hz) 0 50 100 150(Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 2.0 MUZ-HM18NA MUZ-HM18NA2 Correction of Cooling capacity Correction of Cooling total input 2.0 2.0 Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 0 25 50 75 100 (Hz) 0 25 50 75 100(Hz) 0 50 100 150 (Hz) 0 50 100 150(Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 26

MUZ-HM24NA MUZ-HM24NA2 2.0 Correction of Cooling capacity Correction of Cooling total input 2.0 2.0 Correction of Heating capacity Correction of Heating total input 2.0 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 Capacity correction factors 1.5 1.0 0.5 Input correction factors 1.5 1.0 0.5 0 30 60 90 120 150 (Hz) 0 30 60 90 120 150 (Hz) 0 30 60 90 120 150 (Hz) 0 30 60 90 120 150(Hz) The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor The operational frequency of compressor 7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller. 27

8 ACTUATOR CONTROL MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 8-1. OUTDOOR FAN MOTOR CONTROL The fan motor turns ON/, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [] The fan motor turns 15 seconds after the compressor has stopped running. Compressor Outdoor fan motor ON ON 5 seconds 15 seconds 8-2. R.V. COIL CONTROL Heating................. ON Cooling................. Dry.................... NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor. <COOL> 5 seconds <HEAT> 5 seconds ON Compressor R.V.coil ON Outdoor fan ON motor 8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Purpose Compressor LEV Actuator Outdoor fan motor R.V. coil Indoor fan motor Discharge temperature Protection thermistor Cooling: Coil frost prevention Indoor coil temperature thermistor Heating: High pressure protection Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection Cooling: Low ambient temperature operation Ambient temperature thermistor Outdoor heat exchanger temperature thermistor Optional parts Heating: Defrosting (Heater) Cooling: Low ambient temperature operation Cooling: High pressure protection Defrost heater 28

9 SERVICE FUNCTIONS MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board (Refer to 10-6.1.). Defrost finish temperature Jumper MUZ-HM09 MUZ-HM12 MUZ-HM15/18 MUZ-HM24 Soldered (Initial setting) 41 F (5 C) 50 F (10 C) 41 F (5 C) 50 F (10 C) JS ne (Cut) 46 F (8 C) 55 F (13 C) 50 F (10 C) 64 F (18 C) 9-2. PRE-HEAT CONTROL SETTING When moisture gets into the refrigerant cycle, it may interfere with the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermistor is 68 F (20 C) or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W) Pre-heat control setting <JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. : To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 10-6.1) JK Jumper Soldered Cut Pre-heat control setting Deactivated (Factory setting) Activated NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary. 29

10 TROUBLESHOOTING MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 10-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn the main unit first with the remote controller, then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug. 2) Be sure to turn the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor. 4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. <Incorrect> <Correct> Lead wiring Connector housing 5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires. 3. Troubleshooting procedure 1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting service work. (See the service manual of the indoor unit for a description of those failure codes.) 2) Before servicing, check that the connector and terminal are connected properly. 3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 4) Refer to 10-2 and 10-3. 30

10-2. FAILURE MODE RECALL FUNCTION Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 1. Flow chart of failure mode recall function for the indoor/outdoor unit Operational procedure The cause of abnormality cannot be found because the abnormality does not recur. Setting up the failure mode recall function Turn ON the power supply. <Preparation of the remote controller> While pressing OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. Press STOP/OPERATE (/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp. 2 Judgment of indoor/outdoor abnormality (Blinks) Before blinking, does the upper lamp of the OPERATION INDICATOR lamp stay ON for 3 seconds? When it stays ON for 3 seconds (without beep): The outdoor unit is abnormal. () Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnormalities that cannot be recalled with this way. Check if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2) The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least 2 consecutive blinking cycles. 2 The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table. (Refer to 10-2.3) Make sure to check at least 2 consecutive blinking cycles. 3 Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn the power supply and turn it ON again. Press RESET button of the remote controller. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above. Press STOP/OPERATE (/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2. Blinking pattern when the indoor unit is abnormal: 2.5-second Blinking at 0.5- second interval 2.5-second Blinking at 0.5- second interval ON Beeps Repeated cycle Beeps Repeated cycle Beeps Repeated cycle 3.Blinking pattern when the outdoor unit is abnormal: Blinking at 0.5-2.5-second 3-second ON second interval 2.5-second 3-second ON Blinking at 0.5- second interval ON beep Repeated cycle Beeps 31 beep Repeated cycle Beeps Repeated cycle

2. Flow chart of the detailed outdoor unit failure mode recall function Operational procedure The outdoor unit might be abnormal. Check if outdoor unit is abnormal according to the following procedures. Make sure that the remote controller is set to the failure mode recall function. With the remote controller headed towards the indoor unit, press TOO COOL button to adjust the set temperature to 77 F (25 C). 1 1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of the OPERATION INDICATOR lamp. 2 () (Blinks) The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table (10-2.3.). Make sure to check at least 2 consecutive blinking cycles. 2 The outdoor unit is normal. Releasing the failure mode recall function Release the failure mode recall function by the following procedures. Turn the power supply and turn it ON again. Press RESET button of the remote controller. Release the failure mode recall function according to the left mentioned procedure. Repair the failure parts. Deleting the memorized abnormal condition After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" (10-2.1.). Press STOP/OPERATE (/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above. NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized. 2.Blinking pattern when outdoor unit is abnormal: 2.5-second 3-second ON Blinking at 0.5- second interval 2.5-second 3-second ON Blinking at 0.5- second interval ON beep Repeated cycle Beeps beep Repeated cycle Beeps Repeated cycle 32

3. Outdoor unit failure recall mode table MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 OPERATION INDICATOR upper lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P.C. board) Condition Remedy Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function ne (rmal) 2-time fl ash Outdoor power system Overcurrent protection cut-out operates Reconnect connectors. 2.5 seconds 3 consecutive times within 1 minute Refer to 10-5. "How after the compressor gets started. to check inverter/ compressor". Check the stop valve. 3-time fl ash Discharge temperature 1-time fl ash every Thermistor shorts or opens during Refer to 10-5. "Check 2.5 seconds thermistor Defrost thermistor 2.5 seconds compressor running. of outdoor thermistors". Defective outdoor thermistors can be Fin temperature thermistor 3-time fl ash identifi ed by checking the blinking pattern of P.C. board temperature 4-time fl ash LED. thermistor Ambient temperature thermistor 2-time fl ash 4-time fl ash 2.5 seconds Overcurrent 11-time fl ash Large current fl ows into intelligent power module/ power module 1. Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check the stop valve. Compressor synchronous 12-time fl ash of compressor current is Waveform Reconnect compressor compressor". abnormality (Compressor startup failure protection) Refer to 10-5. "How distorted. connector. to check inverter/ 5-time fl ash 2.5 seconds Discharge temperature Temperature of discharge temperature thermistor exceeds 241 F (116 C), Check the refrigerant circuit and the compressor stops. refrigerant amount. Compressor can restart if discharge Refer to 10-5. "Check temperature thermistor reads 212 F of LEV". (100 C) or less 3 minutes later. 6-time fl ash 2.5 seconds 7-time fl ash 2.5 seconds 8-time fl ash 2.5 seconds 9-time fl ash 2.5 seconds 10-time fl ash 2.5 seconds High pressure Fin temperature/ P.C. board temperature Outdoor fan motor nvolatile memory data Discharge temperature 7-time fl ash 5-time fl ash NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.). Temperature of indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Temperature of outdoor heat exchanger temperature thermistor exceeds 158 F (70 C) in COOL mode. Temperature of fin temperature thermistor on the inverter P.C. board exceeds 167-176 F (75-80 C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158-167 F (70-75 C). Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. nvolatile memory data cannot be read properly. Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. Check the refrigerant circuit and the refrigerant amount. Check the stop valve. Check around the outdoor unit. Check the outdoor unit air passage. Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of inverter P.C. board". Replace the inverter P.C. board. Refer to 10-5. "Check of LEV". Check the refrigerant circuit and the refrigerant amount. 33

OPERATION INDICATOR upper lamp (Indoor unit) 11-time fl ash 2.5 seconds 12-time fl ash 2.5 seconds 14-time fl ash 2.5 seconds Abnormal point (Failure mode / protection) DC voltage Each phase current of compressor Overcurrent Compressor openphase Stop valve (Closed valve) 4-way valve/ Pipe temperature LED indication (Outdoor P.C. board) 8-time fl ash 9-time fl ash 10-time fl ash 14-time fl ash 16-time fl ash Condition Remedy Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function DC voltage of inverter cannot be Refer to 10-5. "How detected normally. to check inverter/ compressor". Each phase current of compressor cannot be detected normally. Large current fl ows into intelligent Reconnect compressor power module (IPM)/power module connector. (IPM) 1. Refer to 10-5. "How The open-phase operation of to check inverter/ compressor is detected. compressor". The interphase short circuit occurs in the output of the intelligent power module (IPM)/power module (IPM) 1. The compressor winding shorts circuit. Closed valve is detected by compressor Check the stop valve current. The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature. Check the 4-way valve. Replace the inverter P.C. board. 34

MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 The upper lamp of the OPERATION INDICATOR lamp (Indoor unit) Abnormal point (Failure mode/protection) LED indication (Outdoor P.C. board) Condition Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function ne (rmal) 1-time fl ash Indoor/outdoor Any signals from the inverter P.C. Refer to 10-5. How 2.5 seconds communication, receiving error board cannot be received normally for 3 minutes. to check miswiring and serial signal error. Indoor/outdoor Although the inverter P.C. board Refer to 10-5. How error communication, receiving received 30 consecutive times. sends signal "0", signal "1" has been serial signal error. to check miswiring and 2-time fl ash 2.5 seconds Outdoor power system Reconnect connectors. Refer to 10-5. "How 3-time fl ash 2.5 seconds 4-time fl ash 2.5 seconds 5-time fl ash 2.5 seconds 6-time fl ash 2.5 seconds 7-time fl ash 2.5 seconds 8-time fl ash 2.5 seconds 9-time fl ash 2.5 seconds Discharge temperature thermistor Defrost thermistor Fin temperature thermistor P.C. board temperature thermistor Ambient temperature thermistor Outdoor heat exchanger temperature thermistor Overcurrent Compressor synchronous abnormality (Compressor start-up failure protection) Discharge temperature High pressure Fin temperature/ P.C. board temperature Outdoor fan motor nvolatile memory data Power module (IPM) (MUZ- HM09/12NA(2))/(IC700) (MUZ-HM15/18/24NA(2)) 1-time fl ash every 2.5 seconds 3-time fl ash 4-time fl ash 2-time fl ash 11-time fl ash 12-time fl ash 7-time fl ash 5-time fl ash 6-time fl ash NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.). Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Thermistor shorts or opens during compressor running. Large current fl ows into the power module (IPM) (MUZ-HM09/12NA(2))/ (IC700) (MUZ-HM15/18/24NA(2)). Waveform of compressor current is distorted. Temperature of discharge temperature thermistor exceeds 241 F (116 C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 F (100 C) or less 3 minutes later. Temperature indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Temperature defrost thermistor exceeds 158 F (70 C) in COOL mode. Temperature of the fin temperature thermistor on the inverter P.C. board exceeds 167-187 F (75-86 C), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 162-185 F (72-85 C). Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. nvolatile memory data cannot be read properly. The interface short circuit occurs in the output of the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ- HM15/18/24NA(2)). The compressor winding shorts circuit. to check inverter/ compressor". Check stop valve. Refer to 10-5. "Check of outdoor thermistors". Defective outdoor thermistors can be identifi ed by checking the blinking pattern of LED. Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check stop valve. Reconnect compressor connector. Refer to 10-5. "How to check inverter/ compressor". Check refrigerant circuit and refrigerant amount. Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. Check stop valve. Check around outdoor unit. Check outdoor unit air passage. Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of outdoor fan motor". Refer to 10-5. "Check of inverter P.C. board". Replace the inverter P.C. board. Refer to 10-5. to check inverter/ compressor". "How 35

The upper lamp of the OPERATION INDICATOR lamp (Indoor unit) 10-time fl ash 2.5 seconds 11-time fl ash 2.5 seconds 14-time fl ash or more 2.5 seconds Abnormal point (Failure mode/protection) Discharge temperature DC voltage Each phase current of compressor Stop valve (Closed valve) 4-way valve/ Pipe temperature Outdoor refrigerant system abnormality LED indication (Outdoor P.C. board) 8-time fl ash 9-time fl ash 14-time fl ash 16-time fl ash 17-time fl ash Condition Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. DC voltage of inverter cannot be detected normally. Each phase current of compressor cannot be detected normally. Closed valve is detected by compressor current. The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature. Remedy Indoor/outdoor unit failure mode recall function Outdoor unit failure mode recall function Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. Refer to 10-5. "How to check inverter/ compressor". Check stop valve. Check the 4-way valve. Replace the inverter P.C. board. A closed valve and air trapped in the Check for a gas leak refrigerant circuit are detected based in a connecting piping on the temperature sensed by the etc. indoor and outdoor thermistors and the Check the stop valve. current of the compressor. Refer to 10-5. Check of outdoor refrigerant circuit. NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-3.). 36

10-3. TROUBLESHOOTING CHECK TABLE. Symptom LED indication 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Outdoor unit does not operate. 'Outdoor unit stops and restarts 3 minutes later' is repeated. 1-time fl ash every 2.5 seconds Abnormal point/ Condition Outdoor power system Condition Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started. Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient temperature thermistor shorts or opens during compressor running. Outdoor control system 6-time fl ash Serial signal 11-time fl ash Stop valve/ Closed valve 16-time fl ash 4-way valve/ Pipe temperature 17-time fl ash (MUZ-HM15/18/ 24NA(2)) 2-time fl ash 3-time fl ash 4-time fl ash 5-time fl ash 8-time fl ash 10-time fl ash Outdoor refrigerant system abnormality Overcurrent protection Discharge temperature overheat protection Fin temperature / P.C. board temperature thermistor overheat protection High pressure protection Compressor synchronous abnormality Outdoor fan motor 12-time fl ash Each phase current of compressor 13-time fl ash nvolatile memory data cannot be read properly. (The upper lamp of the OPERATION INDICATOR lamp on the indoor unit lights up or fl ashes 7-time.) The communication fails between the indoor and outdoor unit for 3 minutes. Closed valve is detected by compressor current. The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature. A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor. Large current fl ows into the power module (IPM) (MUZ- HM09/12NA(2))/(IC700) (MUZ-HM15/18/24NA(2)). When overcurrent protection occurs within 10 seconds after compressor starts, compressor restarts after 15 seconds (MUZ-HM09/12NA). Temperature of discharge temperature thermistor exceeds 241 F (116 C), compressor stops. Compressor can restart if discharge temperature thermistor reads 212 F (100 C) or less 3 minutes later. Temperature of the fin temperature thermistor on the heat sink exceeds 167-176 F (75-80 C) (MUZ-HM09/12NA(2))/167-187 F (75-86 C) (MUZ-HM15/18/24NA(2)) or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 158-167 F (70-75 C) (MUZ-HM09/12NA(2))/162-185 F (72-85 C) (MUZ-HM15/18/24NA(2)). Indoor coil thermistor exceeds 158 F (70 C) in HEAT mode. Defrost thermistor exceeds 158 F (70 C) in COOL mode. The waveform of compressor current is distorted. Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up. Remedy Reconnect connector of compressor. Refer to 10-5. "How to check inverter/compressor". Check stop valve. Refer to 10-5. "Check of outdoor thermistors". Replace inverter P.C. board. Refer to 10-5. "How to check miswiring and serial signal error. Check stop valve. Refer to 10-5. "Check of R.V. coil". Replace the inverter P.C. board. Check for a gas leak in a connecting piping etc. Check the stop valve. Refer to 10-5. Check of outdoor refrigerant circuit. Reconnect connector of compressor. Refer to 10-5. "How to check inverter/compressor". Check stop valve. Check refrigerant circuit and refrigerant amount. Refer to 10-5. "Check of LEV". Check around outdoor unit. Check outdoor unit air passage. Refer to 10-5. "Check of outdoor fan motor". Check refrigerant circuit and refrigerant amount. Check stop valve. Reconnect connector of compressor. Refer to 10-5. "How to check inverter/compressor". Refer to 10-5. "Check of outdoor fan motor. Refer to 10-5. "Check of inverter P.C. board. Refer to 10-5. "How to check inverter/compressor". Each phase current of compressor cannot be detected normally. DC voltage DC voltage of inverter cannot be detected normally. Refer to 10-5. "How to check inverter/compressor". NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1. 2. LED is lighted during normal operation. 3. Blinking patterns of this mode differ from the ones of the failure recall mode. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second. (Example) When the fl ashing frequency is 2. 0.5-second ON 0.5-second ON Inverter P.C. board MUZ-HM09/12NA(2) LED Flashing ON 2.5-second 2.5-second MUZ-HM15/18/24NA(2) Flashing LED 37

. Symptom LED indication 16 16 18 19 20 21 22 Outdoor unit operates. Outdoor unit operates. 1-time fl ash 3-time fl ash 4-time fl ash 5-time fl ash 7-time fl ash 8-time fl ash 9-time fl ash Abnormal point/ Condition Frequency drop by current protection Frequency drop by high pressure protection Frequency drop by defrosting in COOL mode Frequency drop by discharge temperature protection Outside temperature thermistor protection Low discharge temperature protection PAM protection PAM: Pulse Amplitude Modulation Zero cross detecting circuit (MUZ-HM09/12NA(2)) Inverter check mode NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1. 2. LED is lighted during normal operation. 3. Blinking patterns of this mode differ from the ones of the failure recall mode. Condition MUZ-HM Current from power outlet is nearing Max. fuse 09/12NA(2) size. MUZ-HM15/ When the input current exceeds approximately 18/24NA(2) 10.5 A, compressor frequency lowers. Temperature of indoor coil thermistor exceeds 131 F (55 C) in HEAT mode, compressor frequency lowers. Indoor coil thermistor reads 46 F (8 C) or less in COOL mode, compressor frequency lowers. Temperature of discharge temperature thermistor exceeds 232 F (111 C), compressor frequency lowers. When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed. Temperature of discharge temperature thermistor has been 122 F (50 C) or less for 20 minutes. The overcurrent flows into IGBT (Insulated Gate Bipolar transistor: TR821) (MUZ-HM09/12NA(2))/PFC (Power factor correction: IC820) (MUZ-HM15/18/24NA(2)) or the DC voltage reaches 320 V (MUZ-HM09/12NA(2))/394 V (MUZ- HM15/18/24NA(2)) or more, PAM stops and restarts. Zero cross signal for PAM control cannot be detected. The connector of compressor is disconnected, inverter check mode starts. The fl ashing frequency shows the number of times the LED blinks after every 2.5-second. (Example) When the fl ashing frequency is 2. 0.5-second ON 0.5-second ON Remedy The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled. Check refrigerant circuit and refrigerant amount. Refer to 10-5. "Check of LEV". Refer to 10-5. "Check of outdoor thermistors". Refer to 10-5. Check of outdoor thermistors. Refer to 10-5. "Check of LEV". Check refrigerant circuit and refrigerant amount. This is not malfunction. PAM protection will be activated in the following cases: 1 Instantaneous power voltage drop. (Short time power failure) 2 When the power supply voltage is high. Check if the connector of the compressor is correctly connected. Refer to 10-5. "How to check inverter/compressor". Inverter P.C. board MUZ-HM09/12NA(2) LED Flashing ON 2.5-second 2.5-second MUZ-HM15/18/24NA(2) Flashing LED 38

10-4. TROUBLE CRITERION OF MAIN PARTS MUZ-HM09NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM12NA2 MUZ-HM15NA MUZ-HM15NA2 MUZ-HM18NA MUZ-HM18NA2 MUZ-HM24NA MUZ-HM24NA2 Part name Check method and criterion Figure Defrost thermistor (RT61) Fin temperature thermistor (RT64) Measure the resistance with a tester. Ambient temperature thermistor (RT65) Refer to 10-6. Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Outdoor heat exchanger temperature thermistor (RT68) Discharge temperature thermistor (RT62) Compressor Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Refer to 10-6. Test point diagram and voltage, 1. Inverter P.C. board, for the chart of thermistor. Measure the resistance between terminals using a tester. [Temperature: 14-104 F (-10-40 C)] rmal (Ω) HM09 HM12 HM15/18/24 U-V U-W 1.36-1.93 1.52-2.17 0.82-1.11 V-W WHT V RED BLK W U Outdoor fan motor Measure the resistance between lead wires using a tester. [Temperature: 14-104 F (-10-40 C)] Color of lead wire rmal (Ω) HM09/12/15/18 HM24 RED BLK BLK WHT WHT RED 29-40 12-16 WHT V RED BLK W U R. V. coil (21S4) Measure the resistance using a tester. [Temperature: 14-104 F (-10-40 C)] rmal (kω) 0.97-1.38 Expansion valve coil (LEV) Measure the resistance using a tester. [Temperature: 14-104 F (-10-40 C)] Color of lead wire rmal (Ω) RED ORN RED WHT 37-54 RED BLU RED YLW WHT ORN RED (+12V) LEV YLW BLU Defrost heater (Optional parts) Measure the resistance using a tester. [Temperature: 14-104 F (-10-40 C)] rmal (Ω) 349-428 39

10-5. TROUBLESHOOTING FLOW A How to check inverter/compressor Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/ (IC700) (MUZ-HM15/18/24NA(2)) Check the voltage between terminals. See 10-5. Check of open phase. Are the voltages balanced? Replace the inverter P.C. board. Check the compressor. See 10-5. Check of compressor. B Check of open phase With the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ- HM15/18/24NA(2)) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the terminals. Output voltage is 50-130 V. (The voltage may differ according to the tester.) << Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA- TION: Refer to 7-6.) <<Measurement point>> At 3 points BLK (U)-WHT (V) Measure AC voltage between the lead wires at 3 points. BLK (U)-RED (W) WHT(V)-RED (W) NOTE: 1. Output voltage varies according to power supply voltage. 2. Measure the voltage by analog type tester. 3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 10-6.1.) C Check of compressor Refer to 10-5. Check of compressor winding. Is the compressor normal? Refer to 10-5. Check of compressor operation time. Does the compressor operate continuously? OK Replace the compressor. Refer to 10-5. Check of compressor start failure. 40

D Check of compressor winding Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ- HM15/18/24NA(2)), and measure the resistance between the compressor terminals. <<Measurement point>> At 3 points BLK-WHT Measure the resistance between the lead wires at 3 points. BLK-RED WHT-RED <<Judgement>> Refer to 10-4. 0 [Ω] Abnormal [short] Infinite [Ω] Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement. E Check of compressor operation time Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to overcurrent. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 7-6.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent. F Check of compressor start failure <<Judgement>> 0 second 1 second 2 seconds 10 seconds 10 minutes Compressor starts Abnormal ((IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ-HM15/18/24NA(2)) failure) (Compressor winding short) Abnormal (Compressor lock out) (Starting defect) Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector) Abnormal (Refrigerant circuit defect) (Closed valve) rmal Confi rm that ~ is normal. Electrical circuit check. Contact of the compressor connector. Output voltage of inverter P.C. board and balance of them (See 10-5. ). Direct current voltage between DB61(+) and (-) on the inverter P.C. board. Voltage between outdoor terminal block S1-S2 Does the compressor run for 10 seconds or more after it starts? Check the refrigerant circuit. Check the stop valve. After the compressor is heated with a drier, does the compressor start? 1 Compressor start failure. Activate pre-heat control. (Refer to 9-2. "PRE-HEAT CONTROL SETTING") Replace the compressor. 1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating. 41 Heating part

G Check of outdoor thermistors Disconnect the connector of thermistor in the inverter P.C. board (see below table), and measure the resistance of thermistor. Is the resistance of thermistor normal? (Refer to 10-6.1.) Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch. Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK (Cause is poor contact.) Replace the inverter P.C. board. Thermistor Symbol Connector, Pin. Board Defrost RT61 Between CN641 pin1 and pin2 Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Inverter P.C. board Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3 H Check of R.V. coil First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4. Check if there is 208/230 VAC at L1 - L2. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no signal is being transmitted to R.V. coil. Check if CN721 is connected. Unit operates COOL mode even if it is set to HEAT mode. Disconnect connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ- HM15/18/24NA(2)). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode). Is there 208/230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the inverter P.C. board. Replace the 4-way valve. Unit operates HEAT mode even if it is set to COOL mode. Disconnect connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ- HM15/18/24NA(2)). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode). Is there 208/230 VAC between CN721 and on the inverter P.C. board 3 minutes after the power supply is turned ON? Replace the inverter P.C. board. Replace the 4-way valve. 42

I Check of outdoor fan motor Check the connection between the connector CN931 and CN932. Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Is the resistance between each terminal of outdoor fan motor normal? (Refer to 10-4.) Disconnect CN932 from the inverter P.C. board, and turn on the power supply. Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-) Replace the outdoor fan motor. (Fixed to either 5 or 0 VDC) Does the voltage between each terminal become 5 and 0 VDC repeatedly? Does the outdoor fan motor rotate smoothly? Replace the inverter P.C. board. 43

J Check of power supply Disconnect the connector between the compressor and the power module (IPM) (MUZ-HM09/12NA(2))/(IC700) (MUZ-HM15/18/24NA(2)). Turn ON power supply and press EMERGENCY OPERATION switch. Rectify indoor/outdoor connecting wire. Does the upper lamp of the OPERATION INDICATOR lamp on the indoor unit light up? Is there voltage 208/230 VAC between the indoor terminal block S1 and S2? Replace the indoor electronic control P.C. board. Is there DC voltage 260-325 VDC (MUZ-HM09/12NA(2))/260-370 VDC (MUZ-HM15/18/24NA(2)) between DB61 (+) and DB61 ( ) on the inverter P.C. board? (Refer to 10-6.1.) Does LED on the inverter P.C. board light up or fl ash? (Refer to 10-6.1.) Replace the inverter P.C. board. Check the electric parts in main circuit. If lights up, OK. If fl ashes, refer to 10-3. 260-325 VDC (MUZ-HM09/12NA(2)) 260-370 VDC (MUZ-HM15/18/24NA(2)) DB61 Inverter P.C. board (Solder side) 44

K Check of LEV (Expansion valve) Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. Hold down the other 2 buttons for another 3 seconds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then release the buttons. Press STOP/OPERATE (/ON) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. Do you hear the expansion valve "click, click "? Do you feel the expansion valve vibrate when touching it? OK 1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received. Is LEV coil properly fi xed to the expansion valve? Does the resistance of LEV coil have the characteristics? (Refer to 10-4.) Replace the LEV coil. Properly fi x the LEV coil to the expansion valve. Measure each voltage between connector pins of CN724 on the inverter P.C. board. 1. Pin (-) Pin (+) 2. Pin (-) Pin (+) 3. Pin (-) Pin (+) 4. Pin (-) Pin (+) Is there about 3-5 VAC between each? NOTE: Measure the voltage by an analog tester. Replace the inverter P.C. board. Replace the expansion valve. NOTE: After check of LEV, do the undermentioned operations. 1. Turn the power supply and turn it ON again. 2. Press RESET button on the remote controller. 45

L Check of inverter P.C. board Check the outdoor fan motor. (Refer to 10-5..) Is the fuse (F901) blown on the inverter P.C. board? Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct. Operate the outdoor unit by starting EMERGENCY OPERATION. Check the LED indication on the inverter P.C. board. Does the LED flash 10 times? (10-time fl ash) Check the corresponding parts following LED indication. (Refer to 10-3.) Replace the inverter P.C. board. 46

M How to check miswiring and serial signal error MUZ-HM09/12NA(2) Turn the power supply. Is there rated voltage in the power supply? Check the power supply. Turn ON the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Check the wiring. Press EMERGENCY OPERATION switch once. Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit> Is serial signal error indicated 6 minutes later? Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? Correct them. B A Turn the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Bridge the outdoor terminal block S2 and S3. 1 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confi rm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board is normal, LED blinks 6 times after 3 minutes. Turn ON the power supply. Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.) Check of power supply. (Refer to 10-5..) Does the LED on the inverter P.C. board repeat "3.6-second- and 0.8-second-ON quick blinking"? 3 Turn the power supply. Remove the bidge between the outdoor terminal block S2 and S3. Turn ON the power supply. (Lighted or not lighted) Replace the inverter P.C. board. 2 2. Be careful of the residual voltage of smoothing capacitor. Is there rated voltage between the indoor terminal block S1 and S2? <Confi rmation of power voltage> Check the wiring If there are any error of the indoor/outdoor connecting wire: such as the damage of the wire, intermediate connection, and/or poor contact to the terminal block, replace the indoor/ outdoor connecting wire. Turn inverter-controlled lighting equipment. Turn the power supply and then turn ON again. Press EMERGENCY OPERATION switch. Is serial signal error indicated 6 minutes later? B Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal> A Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit. Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board? Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board? Replace the indoor power P.C. board and the indoor terminal P.C. board Replace the indoor electronic control P.C. board. Is there 2 VDC or less between CN10A (+) and JPG (GND)(-) on the indoor electronic control P.C. board? 47

MUZ-HM15/18/24NA(2) Turn the power supply. NOTE: Refer to the indoor unit service manual. Is there rated voltage in the power supply? Turn ON the power supply. Check the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Press EMERGENCY OPERATION switch once. Check the wiring. Does the OPERATION INDICATOR lamp light up? <Confi rmation of the power to the indoor unit> Is serial signal error indicated 6 minutes later? Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire? Correct them. B A Turn the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Bridge the outdoor terminal block S2 and S3. 1 Turn ON the power supply. 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confi rm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type) Is the bus-bar voltage of the inverter P.C. board normal? (Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.) Does the LED on the inverter P.C. board repeat "3.6-second- and 0.8-second-ON quick blinking"? 3 Turn the power supply. Remove the bridge between outdoor terminal block S2 and S3. (Lighted or not lighted) Replace the inverter P.C. board. 2 2. Be careful of the residual voltage of smoothing capacitor. Turn on the power supply. Turn inverter-controlled lighting equipment. Turn the power supply and then turn ON again. Press EMERGENCY OPERATION switch. Is serial signal error indicated 6 minutes later? B Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3? <Confi rmation of serial signal> A Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit. Is there 2 VDC or less between CN10A (+) and GND (-) on the indoor electronic control P.C. board? Is there 2 VDC or less between Is there 2 VDC or less between CN10A (+) and GND (-) on CN10A (+) and GND (-) on the indoor electronic control P.C. board? the indoor electronic control P.C. board? Replace the indoor power P.C. board. 48 Replace the indoor electronic control P.C. board.

N Check of defrost heater (Optional parts) Check the following points before checking electric continuity. 1. Does the resistance of ambient temperature thermistor have the characteristics? Refer to 10-6.1. 2. Is the resistance of defrost heater normal? Refer to 10-4. 3. Does the heater protector remain conducted (not open)? 4. Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors? In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 32 F (0 C) or below, and let the defrost thermistor continue to read 30 F (-1 C) or below. NOTE: In case both thermistors are more than the above temperature, cool them with cold water etc... Is there 208/230 VAC between CN722 and on the inverter P.C. board? Refer to 10-6.1. t the problem of the inverter P.C. board. Replace the inverter P.C. board. O Check of outdoor refrigerant circuit (Optional parts) Has the operation stopped during pump down? Was the operation started with the stop valve closed, and was it opened during operation? The unit occasionally stops when the stop valve is opened or closed during operation. Open the stop valve and start the cooling operation again. The operation has stopped to prevent the diesel explosion caused by air trapped in the refrigerant circuit. Close the stop valve, and disconnect the power plug or turn the breaker. The refrigerant gas amount may be 60% or less than the normal amount. Identify where the gas is leaking from, and fi x the leak. CAUTION : Do not start the operation again to prevent hazards. 49

P Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas and the indoor unit within 9.91 ft. (3m), or is the distance between the antennas and the outdoor unit within 9.91 ft. (3m)? Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit. Is the distance between the TV sets or radios and the indoor unit within 3.28 ft. (1m), or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft. (3m)? Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit. Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring? Replace or repair the antenna. Replace or repair the coaxial cable. Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close? Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas. Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service. 1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave) 2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, ground wire, antennas, wiring from antennas, receiver 5. Electric field intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifi er such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in 1) Turn the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2) Within 3 minutes after turning ON the power supply, press STOP/OPERATE (/ON) button on the remote controller for power ON, and check for the electromagnetic noise. 3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise. 4) Press STOP/OPERATE (/ON) button on the remote controller for power, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise. 50

10-6. TEST POINT DIAGRAM AND VOLTAGE 1. Inverter P.C. board MUZ-HM09NA MUZ-HM12NA MUZ-HM09NA2 MUZ-HM12NA2 Back side of unit 208/230 VAC Bus-bar voltage DB61 260-325 VDC (-) (+) Smoothing capacitor (C63) Smoothing capacitor (C62) Fuse (F801) T3.15AL250V Smoothing capacitor (C61) Fuse (F701) T3.15AL250V R.V.coil (CN721) 208/230 VAC Fuse (F901) T3.15AL250V Output to drive compressor (LDU, LDV, LDW) Signal of outdoor fan motor (CN931) 208/230 VAC Front side of unit Output to drive outdoor fan motor (CN932) Fin temperature thermistor/rt64 (CN642) Outdoor heat exchanger temperature thermistor /RT68 (CN644) LED Discharge temperature thermistor/rt62 (CN641) Defrost thermistor /RT61(CN641) Ambient temperature thermistor/rt65 (CN643) LEV connector (CN724) Jumper wire for changing defrost setting (JS) Jumper wire for pre-heat control setting (JK) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) 100 90 80 70 60 50 40 30 20 10 0-4 14 32 50 68 86 104 Temperature( F) Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100 0 32 50 68 86 104 122 140 158 176 194 212 230 248 Temperature ( F) 51 Fin temperature thermistor(rt64) 200 180 160 140 120 100 80 60 40 20 0 32 50 68 86 104 122 140 158 176 Temperature( F)

1. Inverter P.C. board MUZ-HM15NA MUZ-HM18NA MUZ-HM15NA2 MUZ-HM18NA2 Back side of unit 208/230 VAC DB61 260-370 VDC (-) (+) Smoothing capacitor (C63) Smoothing capacitor (C62) Fuse (F801) T3.15AL250V Smoothing capacitor (C61) R.V.coil (CN721) 208/230 VAC Fuse (F701) T3.15AL250V Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932) Output to drive compressor (LDU, LDV, LDW) Front side of unit 90 80 70 60 50 40 30 20 10 LED Fin temperature thermistor/rt64 (CN642) 0-4 14 32 50 68 86 104 Temperature( F) Signal of outdoor fan motor (CN931) Ambient temperature thermistor/rt65 (CN643) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) 100 Defrost thermistor /RT61(CN641) 52 Discharge temperature thermistor/rt62 (CN641) Outdoor heat exchanger temperature thermistor /RT68 (CN644) Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100 0 32 50 68 86 104 122 140 158 176 194 212 230 248 Temperature ( F) LEV connector (CN724) 180 160 140 120 100 80 60 40 20 208/230 VAC Jumper wire for preheat control setting (JK) Jumper wire for changing defrost setting (JS) Fin temperature thermistor(rt64) 200 0 32 50 68 86 104 122 140 158 176 Temperature( F)

1. Inverter P.C. board MUZ-HM24NA MUZ-HM24NA2 Back side of unit 208/230 VAC DB61 260-370 VDC (-) (+) Smoothing capacitor (C63) Smoothing capacitor (C62) Smoothing capacitor (C61) Fuse (F801) T3.15AL250V R.V.coil (CN721) 208/230 VAC Heater connector (CN722) (Optional parts) Fuse (F701) T3.15AL250V Fuse (F901) T3.15AL250V Output to drive outdoor fan motor (CN932) Output to drive compressor (LDU, LDV, LDW) Front side of unit 90 80 70 60 50 40 30 20 10 LED Fin temperature thermistor/rt64 (CN642) 0-4 14 32 50 68 86 104 Temperature( F) Signal of outdoor fan motor (CN931) Ambient temperature thermistor/rt65 (CN643) Defrost thermistor(rt61) Ambient temperature thermistor(rt65) Outdoor heat exchanger temperature thermistor(rt68) 100 Defrost thermistor /RT61(CN641) 53 Discharge temperature thermistor/rt62 (CN641) Outdoor heat exchanger temperature thermistor /RT68 (CN644) Discharge temperature thermistor (RT62) 800 700 600 500 400 300 200 100 0 32 50 68 86 104 122 140 158 176 194 212 230 248 Temperature ( F) LEV connector (CN724) 180 160 140 120 100 80 60 40 20 208/230 VAC Jumper wire for preheat control setting (JK) Jumper wire for changing defrost setting (JS) Fin temperature thermistor(rt64) 200 0 32 50 68 86 104 122 140 158 176 Temperature( F)

11 DISASSEMBLY INSTRUCTIONS <"Terminal with locking mechanism" Detaching points> The terminal which has the locking mechanism can be detached as shown below. There are 2 types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching. (1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism. Sleeve Locking lever 11-1. MUZ-HM09NA MUZ-HM12NA MUZ-HM09NA2 MUZ-HM12NA MUZ-HM15NA MUZ-HM18NA MUZ-HM15NA2 MUZ-HM18NA2 NOTE: Turn the power supply before disassembly. OPERATING PROCEDURE Slide the sleeve. Pull the terminal while pushing the locking lever. 1. Removing the cabinet (1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Remove the screws fixing the conduit cover. (4) Remove the conduit cover. (Photo 4) (5) Remove the screw fixing the conduit plate. (Photo 5) (6) Remove the conduit plate. (7) Disconnect the power supply wire and indoor/outdoor connecting wire. (8) Remove the screws fixing the top panel. (9) Remove the top panel. (10) Remove the screws fixing the cabinet. (11) Remove the cabinet. (12) Remove the screws fixing the back panel. (13) Remove the back panel. Photo 1 Connector Hold the sleeve, and pull out the terminal slowly. PHOTOS Screws of the top panel Back panel Screws of the back panel Photo 2 Screws of the cabinet Service panel Screws of the top panel Photo 3 Screw of the cabinet Screws of the terminal block support and the back panel Direction to remove Screws of the cabinet Screws of the cabinet Hooks 54

OPERATING PROCEDURE Photo 4 Photo 5 Screws of the conduit cover PHOTOS Screw of the conduit plate 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV) (3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the separator. (5) Remove the fixing screws of the terminal block support and the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire and screw of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the inverter P.C. board from the P.C. board support. Photo 6 Screws of the heat sink support and the separator Screws of the terminal block support and the back panel 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN721 (R.V. coil) (3) Remove the R.V. coil. Photo 7 Heat sink Heat sink support P.C. board support Screw of the Terminal block support Terminal block support Screw of the inverter P.C. board Screw of the ground wire 55

OPERATING PROCEDURE 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 8 PHOTOS Screw of the R.V. coil Discharge temperature thermistor Photo 9 Ambient temperature thermistor Outdoor heat exchanger temperature thermistor Defrost thermistor 56

OPERATING PROCEDURE 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931, CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. NOTE: The propeller fan nut is a revers thread. Photo 10 PHOTOS Screws of the outdoor fan motor Propeller fan Propeller fan nut 6. Removing the compressor and 4-way valve (1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Remove the screws fixing the reactor. (4) Remove the reactor. (5) Remove the soundproof felt. (6) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (7) Detach the brazed part of the suction and the discharge pipe connected with compressor. (8) Remove the nuts fixing the compressor. (9) Remove the compressor. (10) Detach the brazed part of pipes connected with 4-way valve. Photo 11 Screws of the reactor Photo 12 Soundproof felt Suction pipe brazed part Discharge pipe brazed part Brazed parts of 4-way valve 57

11-2. MUZ-HM24NA MUZ-HM24NA2 OPERATING PROCEDURE 1. Removing the cabinet (1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the screws fixing the conduit cover. (6) Remove the conduit cover. (7) Remove the screw of fixing the conduit plate. (8) Remove the conduit plate. (9) Remove the top panel. (10) Remove the valve cover. (11) Disconnect the power supply and indoor/outdoor connecting wire. (12) Remove the screws of the cabinet. (13) Remove the cabinet. (14) Remove the screws of the back panel. (15) Remove the back panel. NOTE: Turn the power supply before disassembly. Photo 1 Screws of the cabinet PHOTOS Screws of the top panel Photo 3 Screws of the conduit cover Screws of the cabinet Screws of the cabinet Photo 2 Screws of the top panel Screw of the valve cover Screw of the back panel Screws of the cabinet Photo 4 Screw of the conduit plate Screws of the back panel Screws of the cabinet Screws of the service panel 58

OPERATING PROCEDURE 2. Removing the inverter assembly, inverter P.C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV) (3) Remove the compressor connector. (4) Remove the screw fixing the heat sink support and the separator. (5) Remove the fixing screws of the terminal block support and the back panel. (6) Remove the inverter assembly. (7) Remove the screw of the ground wire, screw of the P.C. board cover and screws of the terminal block support. (8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter P.C. board from the P.C. board support. Photo 5 Screw of the heat sink support and the separator Photo 6 Heat sink PHOTOS Heat sink support Screws of the terminal block support and the back panel 3. Removing R.V. coil (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board> CN721 (R.V. coil) (3) Remove the R.V. coil. Photo 7 Screw of the R.V. coil P.C. board support Screw of the inverter P.C. board Screw of the ground wire Screw of the P.C. board cover Screws of the terminal block support Brazed parts of 4-way valve 59

OPERATING PROCEDURE PHOTOS 4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger temperature thermistor and ambient temperature thermistor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature thermistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) (3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor from its holder. (6) Pull out the ambient temperature thermistor from its holder. Photo 8 Outdoor heat exchanger temperature thermistor Ambient temperature thermistor 5. Removing outdoor fan motor (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board> CN931 and CN932 (Fan motor) (3) Remove the propeller fan nut. (4) Remove the propeller fan. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor. NOTE: The propeller fan nut is a reverse thread. Photo 9 Defrost thermistor Propeller fan nut 6. Removing the compressor and 4-way valve (1) Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit. NOTE: Recover gas from the pipes until the pressure gauge shows 0 PSIG. (5) Detach the brazed part of the suction and the discharge pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 7) Photo 10 Brazed part of the discharge pipe Screws of the outdoor fan motor Discharge temperature thermistor Brazed part of the suction pipe 60