Precept Marine Control Panel Application Guide

Similar documents
Excel-EN Conventional Fire Control Panel

System 800 Addressable Fire Detection & Alarm System

Intelligent Security & Fire Ltd

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

Installation, Operating and Maintenance Manual

Discovery 1-4 Loop 32 Zone, 40 Character Analogue Addressable Control Panel. Application Guide

Technical Data Sheet

FIREBETA EXTINGUISHING CONTROL PANEL (ECP)

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Discovery 1-4 Loop 96 Zone, 40-Character Analogue Addressable Control Panel. Application Guide

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Application, Installation, Operation & Maintenance Manual

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

OPERATION AND INSTALLATION MANUAL

Control Panel Engineering and Commissioning Instructions

Surveyor Envoy-MINI 4

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

CONVENTIONAL CONTROL PANEL FL2/4/8/12 LT-XP

Doc. No.: OMPII.DOC Rev. 2 Written By: Raj Patel Checked By: AJC Approved By: JBJ Date: 03/05/05

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

Surveyor Excel. Fire Alarm Control Equipment Network version. Programming Manual MASTER MANUAL. VERSION 14.0 and Above

FIREPRO INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL. Approved Document No. GLT Issue: 1. 8 Author: NRPJ Date: 7/ 3/201 4

MAG2/4. AL MAG2 Soft. Version 2.1 MAG4 Soft.Version 2.0 USER MANUAL

User Operation Manual

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

FIRE ALARM CONTROL PANEL. COMPLIES WITH EN54 part 2 & part 4 MEETS THE FUNCTIONAL REQUIREMENT OF BS:EN 5839 part 1 INSTALLATION MANUAL

2018 Johnson Controls. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland DUO-CEL

Conventional Fire Alarm System 2014 V1.2

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

Sigma CP (K and T Series)

Conventional Leaflets

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

EX8. Instruction Manual: COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 AND EN54 PARTS 2 & 4

Fire Alarm Control Panel. System Maintenance and Log Book

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Discovery 4 Loop Analogue Addressable Control Panel (NVI & NVA series Protocols)

Sigma XT+ Extinguishant Control Panel. Operation and Maintenance Manual

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

DECKMA. GmbH. Decksmaschinen und Automation Vertriebs GmbH BEDIENUNGSANLEITUNG FÜR FEUERMELDEANLAGE USER MANUAL FOR FIRE ALARM SYSTEM

Conventional Fire Control Panel

4 wire conventional alarm system

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

FEC400 Series. Installation Manual

SALES SUPPORT DOCUMENT

Menvier Fire System MF9300

Installation, Commissioning & Operating Manual

Conventional Fire Detection

ZXSe Range Data Sheet

Conventional Fire Control Panel with Extinguishant Control Unit. Operation and Maintenance Manual SIGMA-2-M3-ECU SIGMA-4-M3-ECU SIGMA-8-M3-ECU

MR-2602 Two Zone Fire Alarm Control Panel

SOLO Single Loop Addressable Fire Control Panel

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Conventional Fire Control Panel (FKEP2, FKEP4, FKEP8) Operation and Maintenance Manual. Man-1078EL Issue 01 February 2014

Intelligent Security & Fire Ltd

Control Panel Engineering and Commissioning Manual (TO BE RETAINED BY THE COMMISSIONING ENGINEER)

The EN54 Part 2 & 4 Fire System

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

The complete conventional fire warning system

ZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features

Operation and Maintenance Manual

FIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF

FireNET Plus Wiring Instructions

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Xenex Conventional Fire Detection & Alarm System

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

5000 INSTALLATION GUIDE

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Control Panel User Guide

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

Fire Control Panel. Installation & Programming Manual TABLE OF CONTENTS

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Installation and user manual for the BiWire / Conventional Repeater Panel

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F

VSN PLUS VSN 4 PLUS ; VSN 8 PLUS ; VSN 12 PLUS

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FSTP4-2-wire 4 Zone Conventional Fire Control Panel Operation and Maintenance Manual. Man-1078FS4 Issue 01 April 2012

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Installation and Operating Instructions

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

TECHNICAL DATA OBSOLETE

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

installation & maintenance manual LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL approved document no. DFU rev 5

The EN54 Part 2, 4 and 13 Fire System

The EN54 Part 2 and 4 Fire System

DL-250 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

EXTINGUISHING AGENT RELEASE MODULE

Product Catalogue. Intelligent Control Equipment for Life Safety. Issue 1

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

GAS SUPRESSION CONTROL PANEL:

Transcription:

Precept Marine Control Panel Application Guide Contents Page 1.0 Cabinet Specifications 2 2.0 Panel Hardware Specifications 5 3.0 Panel Configuration 8 4.0 Technical Specifications 8 5.0 Battery Sizes 10 6.0 Precept Marine Panel Compatible Zone Devices 11 Appendix i Other Relevant Documentation 12 The Precept Marine range of panels are approved to BS5839 Part 4 1988 by Lloyd s Register for marine and offshore applications in environment categories ENV1 and ENV2. [Certificate number 99/00089]. The Precept range of panels are approved to BS5839 Part 4 1988 by the Loss Prevention Certification Board, certificate numbers 018a, 018b and 018s. For full details, refer to the current edition of the Loss Prevention Certification Board List of Approved Products and Services. Docment Ref: Precmapp.doc/Rev2 17.04.02 Page 1 of 12 Originator MC Checked by _RP Approved by _JBJ

1.0 Cabinet Specifications 1.1 Surface Cabinet All cabinets are manufactured from 18 SWG sheet steel and finished in satin texture epoxy powder stove paint. Top entry grommets and rear entry knockouts are provided. Cabinet colour: RAL7035 Textured (light grey) 2-4 zone 8 zone 16 zone 32 zone Repeaters* Protection Plugs 7 off 13 off 13 off 27 off 13 off a 310mm 370mm 445mm 445mm 370mm b 290mm 325mm 405mm 811mm 325mm c 106mm 106mm 109mm 109mm 106mm *Note: Repeater Panel Is Not Approved. 1.1.1 Surface Panel Order Codes & Descriptions Part No Description 2500/774 Precept Marine 2 zone control panel - Lloyd s/lpcb approved; size - 310h x 290w x 100d 2500/775 Precept Marine 4 zone control panel - Lloyd s/lpcb approved; size - 310h x 290w x 100d 2500/776 Precept Marine 8 zone control panel - Lloyd s/lpcb approved; size - 370h x 325w x 100d 2500/777 Precept Marine 16 zone control panel - Lloyd s/lpcb approved; size - 445h x 405w x 105d 2500/778 Precept Marine 32 zone control panel - Lloyd s/ LPCB approved; size - 445h x 810w x 105d Document Ref: Precmapp.doc/Rev2 17.04.02 Page 2 of 12 Originator MC Checked by _RP

1.2 Semi Flush Bezels The semi flush bezel locates to the rear of the bevelled edge of the back box, leaving the bevelled edge and door raised out from the wall. It is finished in the same colour as the back box and is fitted by means of pinch bolts, thus avoiding the need to drill the cabinet. 2-4 zone 8 zone 16 zone 32 zone Repeaters* Hole height a 315mm 375mm 450mm 450mm 375mm Hole width b 295mm 330mm 410mm 815mm 330mm Hole depth c 76mm 76mm 79mm 79mm 76mm Max bezel height d 375mm 435mm 510mm 510mm 435mm Max bezel width e 353mm 388mm 468mm 874mm 388mm Bezel overlap f 30mm 30mm 30mm 30mm 30mm Bezel depth g 30mm 30mm 30mm 30mm 30mm Door protrusion h 30mm 30mm 30mm 30mm 30mm *Note: Repeater Panel Is Not Approved. 1.2.1 Semi-flush Bezel Order Codes & Descriptions Part No Description 2501/120 Semi-flush bezel to fit Precept Marine 2 / 4 zone control panels 2501/121 Semi-flush bezel to fit Precept Marine 8 zone control panel 2501/122 Semi-flush bezel to fit Precept Marine 16 zone control panel 2501/123 Semi-flush bezel to fit Precept Marine 32 zone control panel Document Ref: Precmapp.doc/Rev2 17.04.02 Page 3 of 12 Originator MC Checked by _RP

1.3 Fully Flush Bezels The fully flush option is achieved by fixing a flat bezel/door assembly to the standard back box, replacing the standard door. Available in brass, stainless steel (polished or brushed), or painted to specifications. The panel comes with assembly already fitted (preferred) but can if necessary be supplied for later site fitting. 2-4 zone 8 zone 16 zone 32 zone Hole height a 315mm 375mm 450mm 450mm Hole width b 320mm 345mm 425mm 851mm Hole depth c 106mm 106mm 109mm 109mm Bezel height d 349mm 411mm 485mm 483mm Bezel width e 388mm 423mm 507mm 887mm Hinge protrusion f 20mm 20mm 20mm 20mm 1.3.1 Fully-flush Bezel Order Codes & Descriptions Part No Description 2501/130 Fully-flush painted bezel to fit 2/4 zone panels (painted to customer's specification) 2501/131 Fully-flush stainless steel bezel to fit 2/4 zone panels (brushed or polished) 2501/132 Fully-flush brass bezel to fit 2/4 zone panels (brushed or polished) 2501/133 Fully-flush painted bezel to fit 8/12 zone panels (painted to customer's specification) 2501/134 Fully-flush stainless steel bezel to fit 8/12 zone panels (brushed or polished) 2501/135 Fully-flush brass bezel to fit 8/12 zone panels (brushed or polished) 2501/136 Fully-flush painted bezel to fit 16 zone panel (painted to customer's specification) 2501/137 Fully-flush stainless steel bezel to fit 16 zone panel (brushed or polished) 2501/138 Fully-flush brass bezel to fit 16 zone panel (brushed or polished) 2501/139 Fully-flush painted bezel to fit 32 zone panel (painted to customer's specification) 2501/140 Fully-flush stainless steel bezel to fit 32 zone panel (brushed or polished) 2501/141 Fully-flush brass bezel to fit 32 zone panel (brushed or polished) Document Ref: Precmapp.doc/Rev2 17.04.02 Page 4 of 12 Originator MC Checked by _RP

2.0 Panel Hardware Specifications 2.1 User Controls and Indications Lloyd s approval label Illuminate flashing when a zone has been triggered into fire. Illuminate steady after silence alarms has been pressed. Illuminate flashing with any zone fault or device removed. Illuminates steady when zone isolated. LPCB approved label. Illuminates when mains supply is on. Zone identification label. Illuminates when relays or zones are isolated. Illuminates when a general system fault has occurred. Refers to engineer s LEDs on panel motherboard. Illuminates when processor fault has occurred. Press to isolate / de-isolate. Causes zone fault LED to illuminate steady. Press to reset system after silence alarms has been pressed. Press to isolate/ de-isolate auxiliary relays. Press to silence buzzer in fault condition. Press to silence alarm circuits. Press to test all LEDs & panel buzzer. User operating instructions. Press to operate alarm circuits & fire relays. Press again to stop. Document Ref: Precmapp.doc/Rev2 17.04.02 Page 5 of 12 Originator MC Checked by _RP

2.2 Engineer Facilities 2.2.1 Mechanical Assembly Illustration (door not shown for clarity) Document Ref: Precmapp.doc/Rev2 17.04.02 Page 6 of 12 Originator MC Checked by _RP

2.2.2 Motherboards Showing Essential Engineering Components 3.0 Panel Configuration Document Ref: Precmapp.doc/Rev2 17.04.02 Page 7 of 12 Originator MC Checked by _RP

The Engineer s Controls are located on the bottom of the control board. They are in the form of a four way DIL switch. The function of the switches is described below: Switch 1 Switch 2 Switch 3 Switch 4 - Pulsing or continuous alarms - Non-latching zone (zone 1) (Disallowed under BS5839 part 4) Does not operate fire relays - One man test facility - Operates the processor fault counter in accordance with BS5839 part 4 (8, 16 and 32 zone panels only) or Disable aux. fire relay on evacuate (4 zone panel only) Switch 2 & 4 - Shop Unit Specification (4 zone panel only) With switches 2 & 4 ON together, operation of zone 1 will be non-latching - indication only (i.e. no alarm sounding). Fire buzzer will operate and the aux. fire relays will function as above. 3.1 Processor Program Changes NOTE: Processor programme changes will invalidate approval status. The microprocessor can be re-programmed to provide special functions. All the functions available, either via the user controls or the terminal connections can be accessed or ignored by the main processor. Some typical examples are listed below: - Zone 1 non-latch indication only, no alarms to operate Auxiliary fire relays to reset upon Silence Alarms Zones 7-19 no alarms but latching inputs Extended reset delay - 15 seconds All zones non-latching - pulsed alarms, auxiliary relays to operate Zones 1,2 non-latching - auxiliary relays to operate but no alarms Zones 1,2,3 non-latching - no alarms or auxiliary relays to operate 4.0 Technical Specifications 4.1 Precept Marine 2 zone control panel Max. power supply output 1.5A Mains failed current - alarm 175mA (plus alarm load) Mains failed current - standby 65mA Integral charger output 500mA Auxiliary 24V supply 250mA Alarm circuit output 2 at 500mA each Battery size 2 x 12V 3.2AH sealed lead acid Weight (excluding batteries) 5 kg 4.2 Precept Marine 4 zone control panel Max. power supply output 1.5A Mains failed current - alarm 190mA (plus alarm load) Mains failed current - standby 80mA Integral charger output 500mA Auxiliary 24V supply 250mA Alarm circuit output 2 at 500mA each Battery size 2 x 12V 3.2AH sealed lead acid Weight (excluding batteries) 5 kg 4.3 Precept Marine 8 zone control panel Max. power supply output 3.0A Mains failed current - alarm 270mA (plus alarm load) Document Ref: Precmapp.doc/Rev2 17.04.02 Page 8 of 12 Originator MC Checked by _RP

Mains failed current - standby Integral charger output Auxiliary 24V supply Alarm circuit output Battery size Weight (excluding batteries) 150mA 1A 500mA 2 at 800mA each 2 x 12V 6.2AH sealed lead acid 8kg 4.4 Precept Marine 16 zone control panel Max. power supply output Mains failed current - alarm Mains failed current - standby Integral charger output Auxiliary 24V supply Alarm circuit output Battery size Weight (excluding batteries) 5A 355mA (plus alarm load) 230mA 1A 800mA 2 at 1A each 2 x 12V 6.2AH sealed lead acid 11kg 4.5 Precept Marine 32 zone control panel Max. power supply output Mains failed current - alarm Mains failed current - standby Integral charger output Auxiliary 24V supply Alarm circuit output Battery size Weight (excluding batteries) 10.0A (2 transformers) 710mA (plus alarm load) 460mA 2 at 1A each 2 at 800mA each 4 at 1A each 4 x 12V 6.2AH sealed lead acid 22kg Document Ref: Precmapp.doc/Rev2 17.04.02 Page 9 of 12 Originator MC Checked by _RP

4.6 Typical Terminal Wiring Schematic Sounder EOL 3K9 RESISTOR - - + + Marine Approved Detectors 3k9 Resistor Note: Repeater panels are not marine approved 3K9 Resistor Full function repeater with zone LED's, common fault LED and system Silence alarms, Reset, and Evacuate. Sounder - - - + + Marine Apprived Call point Remote indicator + + Auxiliary fire and fault contacts - +- + BELL CCTS PCOP COPC O FIRE FIRE FLT 1 2 +- 1 +- +- + - + - +- + - + - 12345678FESR- + 2 3 4 5 6 7 8 ZONES ZONE OUTPUTS AUX 24V BATTERIES + P: POLE C: CLOSE O: OPEN DIL SWITCH SETTINGS 1=CONTINUOUS/PULSED ALARMS 2=ZONE 1 NON LATCH 3=ONE MAN TEST 4=PROC FAIL COUNTER PRECEPT 8/16 ONLY AUX RESET RELAY OPERATED FOR 10S UPON 'SYSTEM RESET'. (PRECEPT 16 ONLY) C P O RESET AUX F: FAULT E: EVACUATE S: SILENCE R: RESET + + FUSE RATINGS 2/4 ZONE = 1A 8/16 ZONE = 3A 12V 12V N E L 230 V AC 50 HZ Mains supply Note:- This is a schematic representation only and not a PCB layout drawing. 5.0 Battery Sizes Battery Rating 3.2AH battery 12V 6.2AH battery 12V 12AH battery 12V 15AH battery 12V 38AH battery 12V 65AH battery 12V Battery Size 134 length x 67 wide x 64 high 151 length x 65 wide x 97.5 high 151 length x 98 wide x 97.5 high 181 length x 98 wide x 167 high 166 length x 175 wide x 125 high 350 length x 166 wide x 174 high Document Ref: Precmapp.doc/Rev2 17.04.02 Page 10 of 12 Originator MC Checked by _RP

6.0 Precept Panel Compatible Zone Devices Notes: For marine and offshore use, these control panels shall only be used with compatible LR Type Approved zone devices. The Precept Marine panel is designed to operate with the following devices. Manufacturer Part no. Description Maximum [Combined] Quantity Per Zone Apollo 55000-200MAR Series 60 ionisation detector 20 Apollo 55000-210MAR Series 60 integrating ion detector 20 Apollo 55000-100MAR Series 60 Grade 1 heat detector 20 Apollo 55000-101MAR Series 60 Grade 2 heat detector 20 Apollo 55000-102MAR Series 60 Grade 3 heat detector 20 Apollo 55000-103MAR Series 60 Range 1 heat detector 20 Apollo 55000-104MAR Series 60 Range 2 heat detector 20 Apollo 55000-300MAR Series 60 optical detector 20 Apollo 45681-200MAR Series 60 mounting base 20 Hochiki SLR-EM CDX marine optical smoke detector 20 Hochiki SIJ-EM CDX marine ionisation smoke detector 20 Hochiki DCD-1EM CDX marine combined heat detector Grade 1 20 Hochiki YBN-R/4M CDX marine mounting base 20 Hochiki YBO-R/5M CDX marine mounting base with Rem Ind 20 Hochiki MBB-1 CDX marine back box 20 KAC WR2061-120-470 Indoor Class Call Point with 470 Ohm series Unlimited monitoring resistor and LED KAC WR2072-470 Indoor Class Call Point with 470 Ohm series Unlimited Monitoring resistors and LED KAC WR4061-120-470 Waterproof Class Call Point with 470 Ohm Unlimited series monitoring resistor and LED KAC WR4072-470 Waterproof Class Call Point with 470 Ohm Unlimited series monitoring resistor KAC WRZ2/4072 Class 4000 for use in hazardous areas with Unlimited normally open, closing on alarm contacts with 6 Watt series monitoring resistor [470 Ohm preferred value] KAC WRZ2/4010 Class 4000 for use in hazardous areas with normally open, closing on alarm contacts with 6 Watt series monitoring resistor and 0.75 Watt end of line resistor. [3K9 Ohm preferred value] Unlimited All call points must have a 470-680 ohm resistor fitted to them. Document Ref: Precmapp.doc/Rev2 17.04.02 Page 11 of 12 Originator MC Checked by _RP

Appendix i Other Relevant Documentation Sales Literature Installation & Commissioning Manual Wiring Recommendations Fault Finding Guide User Instructions After-Sales Technical Support Booklet Document Ref: Precmapp.doc/Rev2 17.04.02 Page 12 of 12 Originator MC Checked by _RP