SECTION FM-200 FIRE SUPPRESSION SYSTEM

Similar documents
SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: ARGONITE Engineered Fire Suppression System

FM-200 In-Cabinet Series

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Hospitals and Major Medical Centers

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

D. Reference Standards (Utilize latest editions available):

Capital Projects Group Fire Extinguishers Specification

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

Design & Construction Standards, Revised January

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

SECTION FIRE-SUPPRESSION STANDPIPES

C E R T I F I C A T E O F C O M P L I A N C E

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

SECTION FIRE PUMP AND CONTROLS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

Twin-Agent Fire Fighting/Securing Systems Specifications

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Data/ Specification Sheet

SECTION WET-PIPE SPRINKLER SYSTEMS

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

GAS FLOODING SYSTEM FOR CIFF AT BASEMENT

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

Product Alert September 20, 2012

WORMALD INTERNATIONAL ELECTRIC VALVE ACTUATOR

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Carbon Dioxide Fire Suppression Systems

Gas Station & C Store SECTION CWM Job No

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

FIRE SUPPRESSION SPRINKLER SYSTEM

Industrial Dry Chemical Fire Suppression System

BOC FS125 The Fire Extinguishing Solution

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Model DDX Deluge Valve

Badger Universal Control Head

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

TECHNICAL DATA. 319a. January 27, 2012

Inert Gas Fire Extinguishing System

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Copyright 2013 Fike 12/13 SECTION CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Worldwide Contacts.

Safe, Effective, Environment-friendly

B. Section Identification for Fire Suppression Piping and Equipment.

CLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition

SECTION COMMERCIAL-KITCHEN HOODS

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

Model F3 Dry Sprinklers

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

TECHNICAL DATA OBSOLETE

SECTION AUTOMATIC SPRINKLER PIPING

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Linear Heat Detection Engineering Specifications

Residential Sprinkler For Sloped Ceilings

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Additional Bulletins applicable to all F1RES LL Sprinklers Wall Wetting - Bulletin 007 Design and Installation - Bulletin 140

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

SECTION AIR DUCT ACCESSORIES

Port of St Helens SIA Aircraft Hanger Scappoose, OR

PRODUCT MANAGEMENT BULLETIN# 171b

CONSTRUCTION REQUIREMENTS

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM

DETECT-A-FIRE Heat Detectors

TECHNICAL DATA OBSOLETE

Transcription:

SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to meet a minimum design concentration of 20 %, by volume in all designated spaces to be protected. 2. CODES/STANDARDS COMPLIANCE 2.1 The design, installation, testing and maintenance of the above stated FM-200 fire suppression system shall be in accordance to the following codes, standards and regulatory bodies: A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. B. NFPA 12A Halon 1301 Fire Extinguishing Systems C. UL 2166 Standard for Halocarbon Clean Agent Extinguishing System Units D. Factory Mutual Approval Guide E. ANSI B1.20.1 Standard for pipe threads, General Purpose, 1992 F. Design and installation practices set forth by system manufacturer G. NFPA 70 - NEC National Electrical Code H. NFPA 72 National Fire Alarm Code I. Kentucky Building Code. 2.2 The Fire suppression system must have the following listings and approvals: A. FM Approved Factory Mutual Research Center B. UL 2166 Listed Underwriters Laboratories Inc. 2.3 The manufacturer shall meet ISO 9001 requirements for the design, production and distribution of the FM-200 fire suppression systems. 3. SYSTEM DESCRIPTION 3.1 All FM-200, fire suppression equipment and accessories must be manufactured by: Kidde Fire Systems or Fike FE-25 (ECARO). 3.2 The months from date of shipment or one (1) full year from the date of installation. 3.3 The system shall be supplied and installed by a factory-authorized, Kidde Fire Systems dis- FM 200 FIRE SUPPRESSION SYSTEM 15360-1

tributor. The distributor / Installer shall be trained by the manufacturer to calculate / design, install, test and maintain the ADS, FM-200 Fire suppression system and shall be able to produce a certificate stating such on request. 3.4 The ADS system shall consist of a Kidde FM-200 Agent Storage Cylinder, Kidde Nitrogen Driver Cylinder, Kidde Nitrogen Transfer hardware, Kidde actuation hardware and Kidde ADS system distribution nozzles attached to a pipe network. 3.5 (OPTIONAL EQUIPMENT) The FM-200 Agent Cylinder shall have the option of a Liquid level indicator. This device will provide a reliable means other than weighing for determining the agent weight with the storage container during normal routine servicing. 4. COMPONENTS 4.1 FM-200 Cylinder and Valve Assembly A. FM-200 shall be stored in a Kidde ADS series Cylinders P/N 90-10022X-001 or 90-10039X- 001. Operating pressure of the FM-200 shall be at 44 psig @ 70 F. B. FM-200 Agent cylinders can be actuated pneumatically with Kidde P/N 878737. C. The FM-200 Agent cylinder shall be provided with a safety rupture disc. 4.2 Nitrogen Driver Cylinder and Valve Assembly A. Nitrogen shall be stored in a Kidde ADS series Nitrogen driver cylinder P/N 90-102300-001 for use with agent storage cylinder 90-10022X-001 B. Nitrogen shall be stored in a Kidde ADS series Nitrogen driver cylinder P/N 90-104070-001 for use with agent storage cylinder 90-10039X-001 C. Operating Pressure for Nitrogen driver cylinders, P/N 90-102300-001 and 90-104070-001 shall be 1800 psig @ 70 F. D. Nitrogen driver cylinders shall be equipped with a discharge head, Kidde P/N 872442 and shall be actuated as the primary cylinder using a Kidde electric control head, electric / cable control head or lever operated control head. E. (OPTIONAL EQUIPMENT): pneumatic actuation of Nitrogen driver cylinders can be accomplished by using a nitrogen pilot Cylinder Kidde P/N s 877940 or 06-129773-00X F. Nitrogen shall be transferred from the Nitrogen Driver Cylinder to the FM-200 Agent cylinder by using a ¾ Outlet, flexible transfer hose. Kidde P/N 06-118207-00X. G. Nitrogen Transfer to the FM-200 Agent cylinder shall be regulated by an Orifice fitting, Kidde P/N 90-194129-XXX. Size of Orifice restrictor plate to be determined using Kidde ADS flow calculation software P/N 90-190002-100. FM 200 FIRE SUPPRESSION SYSTEM 15360-2

4.3 Distribution Nozzles A. Engineered discharge nozzles for use with the Kidde ADS series system will be made of Brass or Stainless steel, Kidde P/N 90-1944XX-XXX B. Each nozzle shall be located in the space per the manufactures guidelines, Nozzles can have either a 180 or a 360-degree discharge pattern. A. Each Nozzle discharge pattern shall be available in sizes ranging from ½ NPT to 2 NPT. C. (OPTIONAL EQUIPMENT): Nozzle escutcheon plates can be used to conceal pipe entry through ceiling, Kidde P/N 06-23613X-001 4.4 Pipe Network A. Distribution piping, and fittings, shall be installed in accordance with NFPA 2001, approved piping standards and FM-200 system manufacturer s requirements. 4.5 (OPTIONAL EQUIPMENT) 3-Way Directional Ball Valves A. For selector suppression systems were multiple hazard manifold arrangements are used, a Kidde 3-Way directional ball valve for use with the ADS series system shall be used. P/N 90-22003X-00X. B. When multiple cylinders are used, each cylinder must have the same orifice fitting and drill size and be of the same cylinder size and fill density to ensure proper regulated flow of agent and nitrogen. C. 3-way directional ball valves shall be pneumatically actuated using a Kidde nitrogen pilot cylinder P/N 877940 or 06-129773-00X. D. The fire system control panel will energize an electric solenoid P/N 06-118384-001 attached to the actuator, allowing pressure to enter the actuator and turn the selected 3-way ball valve, 90 deg CCW. E. The 3-way directional ball valves shall be installed and located in the piping network per the manufacturers guidelines and design manual F. 3-Way directional ball valves must be UL system listed with the Kidde ADS. 5. WARRANTY The manufacturer shall warrant all FM-200 fire suppression system products for 36 months from the date of Substantial Completion. 6. SUBMITTALS 6.1 Engineered Design Drawings FM 200 FIRE SUPPRESSION SYSTEM 15360-3

A. The factory-authorized Kidde Fire Systems Distributor shall provide all required installation drawings per NFPA 2001. 6.2 Flow Calculation Reports A. The contractor shall provide the following information in the flow calculation report. 1. Customer Information and Project Data 2. Enclosure Information at a minimum, enclosure information is to include Minimum and adjusted design concentrations, Minimum and maximum enclosure temperatures, minimum agent required and volume of enclosures, including non-permeable volume if applicable. 3. Agent information at a minimum, agent information is to include Cylinder size and part number, quantity of cylinders, main and / or reserve cylinders, pipe take off direction, floor loading for agent cylinder and the nitrogen restrictor plate orifice area. 4. Pipe network information at a minimum, pipe network information is to include pipe type, pipe diameter, pipe length, change in direction or elevation, pipe equivalent length and any added accessory equivalent length. In addition, the following nozzle information shall be provided; number of nozzles and identification of enclosure location, flow rate of associated nozzle, nozzle nominal size, nozzle type and nozzle orifice area. 5. (OPTIONAL) 3-way ball valve information A calculation must be completed for each directional valve in the piping network. Modeling of the 3-Way ball valve must be shown in the opened and closed position. 6. Detailed list of all Pipes and Pipe Fittings designed in the pipe network 6.3 Commissioning Equipment List A. The contractor shall provide a commissioning equipment list for each installed FM-200 suppression system. The equipment list shall identify all installed equipment and configurations. 6.4 Test Plan A. The contractor / Installer shall submit a test plan which describes how the system equipment and room integrity shall be tested. This shall include a step-by-step description of all tests and shall indicate type and location of test apparatus to be used. At a minimum, the tests to be conducted shall be per NFPA 2001 and any additional supplemental tests required by the AHJ. Tests shall not be scheduled or conducted until the engineer of record approves the test plan. 6.5 Installation Drawings FM 200 FIRE SUPPRESSION SYSTEM 15360-4

A. Four (4) sets of installation drawings for each installed FM-200 suppression system and One (1) set of the calculation report, owners manual and product data sheets shall be submitted to the end-user / owner. B. Upon completion of installation and commissioning acceptance, two (2) sets of As-Built installation drawings and One (1) set of the calculation report for each installed FM-200 suppression system shall be given to the owner / end-user for use and reference. 6.6 Operation and Maintenance Manuals A. Two (2) copies of the Kidde ADS FM-200 fire suppression system, Operation and Maintenance Manual shall be submitted after complete installation. 7. SYSTEM INSTALLATION AND COMMISSIONING 7.1 FM-200 Fire Suppression System Equipment A. All work shall be completed in a high degree of workmanship and in compliance with the above referenced codes and standards. In addition, the contractor shall install the system in accordance with the manufacturer s installation, operation and maintenance manual. 7.2 Training Requirements A. The contractor shall be certified and trained by the manufacturer on installation, design and maintenance of the Kidde ADS, FM-200 fire suppression systems. 7.3 Routine Maintenance 1. Routine maintenance shall be performed as recommended by the manufacturer s installation, operation and maintenance manual. At a minimum, the routine maintenance will include the following: 2. Visual Check of Pipe network and distribution nozzles per the operation and maintenance manual. 3. Weight of FM-200 Agent cylinder and pressure of Nitrogen driver cylinder per the operation and maintenance manual. 4. Inspect all cylinders and equipment for damage per the operation and maintenance manual. 5. Pneumatic operation of 3-way directional valve. END SECTION 15360 FM 200 FIRE SUPPRESSION SYSTEM 15360-5