THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Similar documents
TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Sensor Interface Module Installation/Operation Instructions

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1 Sensor Interface Module

NGC-UIT2-ORD-R Remote User Interface Terminal for Raychem NGC Systems Installation Instructions

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

DESCRIPTION. 42 mm. 125 mm

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

910 Series Single-point heat-tracing control system

HTC-915-CONT. Heat-Trace Control system

NGC-40 Advanced Heat-Tracing Control System

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

Industrial Strength Leak Detection

Dual-point heat-tracing control system

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

Modular Sensing Cable Installation Instructions

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Above Ground Greasy Waste Disposal Lines

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

fuel leak detection find leaks before they find you

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

THERMAL MANAGEMENT SOLUTIONS

CSI Master Format 2004 Guide Specification for: Snow Melting (Mineral Insulated)

PRODUCT SELECTION GUIDE FOR WATER SENSING SYSTEMS

THERMAL MANAGEMENT SOLUTIONS

RAYCHEM NGC-30 COMPONENTS

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM. product overview

HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

Supervisor Standard Edition

HHS-WWH HOPPER HEATING SYSTEM WRAP-WOUND HEATER INSTALLATION INSTRUCTIONS DESCRIPTION. HHS-WWH PRODUCT SPECIfICATIONS

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

TT3000 and TT5000 Series

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

ECW-GF, ECW-GF-DP DIGITAL ELECTRONIC CONTROLLERS AND REMOTE DISPLAY PANEL PRODUCT OVERVIEW

FreezGard. Self-regulating crankcase heater. Product Overview

aquilar - leak detection solutions

aquilar - leak detection solutions

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM PRODUCT OVERVIEW

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

Power Supply Display Module PSDM. Installation and Operation Manual

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

Duct and Rough Service Carbon Monoxide Sensor

CSI Master Format 2012 Guide Specification for: Hot Water Temperature Maintenance (HWAT) Systems

For Raychem ACS-30 Controls Systems

INSTALLATION INSTRUCTIONS

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

4100U City and Relay Cards Installation Instructions

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

INSTALLATION INSTRUCTIONS

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Pioneer-R16 Gas Monitor Operator s Manual

Remote Relay Module (RRM)

Solid Core and Split Core Fixed Current Status Switches CSS-O,C; CSP-O,C -F (FIXED) SERIES

TT3000 and TT5000 Series

SAFETY INFORMATION AND WARNINGS

Oxygen (O2) Single-Point Gas Detection System

Multi-Gas-Controller MGC2

CR Series Command Relays

Analog Room Pressure Monitor RPC Series

1SC-SSC Splice Connection Kit Installation Instructions

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

21-light Remote Annunciator. Owner s Manual

DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Sensepoint XCL Fixed Gas Detector

/9308 External Battery Chargers Installation Instructions

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

OPTISENS TUR 2000 Technical Datasheet

FTC-HST WARNING: CAUTION:

Greentrol Automation, Inc.

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Operating Instructions. For. Alarm Control Module. Model SSR 500

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Two-Channel Gas Controller

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

HOT WATER TEMPERATURE MAINTENANCE HWAT SYSTEM

Dry Contact Probe DCP (#30008)

Longline Heating. Contents. Introduction

Dräger PointGard 2100 Detection of toxic gases and vapours

Carbon Monoxide Transmitter

Annunciator Unit SACO 16 D1. Product Guide

Designed for testing three-phase circuits up to 600V Install on line or load side of electrical disconnect Detects absence of AC and DC voltage

C910 Series. Single-point heat-tracing control system

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

Transcription:

TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For DC models use a Listed Class 2 Power Supply. Product Information TTSIM-1A TTSIM-1A-120 TTSIM-1A-230 TTSIM-1A-12VDC TTSIM-1A-24VDC Relay contacts Installation categories Storage temperature Operating temperature Enclosure 22 to 26 Vac, 50/60 Hz, 3 W (SELV level for Europe) 92 to 132 Vac, 50/60 Hz, 3 W 216 to 253 Vac, 50/60 Hz, 3 W 12 Vdc +/- 10% 2W 24 Vdc +/- 10% 2W Form C (SPDT), 250 Vac/30 Vdc at 2 Amps maximum (30 V SELV level for Europe) Overvoltage Category II Pollution Degree 2 18 C to 60 C (0 F to 140 F) 0 C to 50 C (32 F to 122 F) NEMA 1; IP20 (NEMA 4X / IP 56 with optional enclosure) General Information Please read these instructions and keep them in a safe place. These instructions must be followed carefully to ensure proper operation. The TTSIM-1A has been designed for use with TraceTek sensing cables, point sensors and normally open, dry contact devices (float switch, pressure or vacuum switch, optical probe with adapter, limit switch, etc.). Up to 150 m (500 ft) of sensor cable can be monitored by the TTSIM-1A. Contact factory for information regarding longer monitoring distance. The TTSIM-1A is designed for installation in ordinary (nonhazardous) areas. The TTSIM-1A has five small LED s to indicate power, status and communications activity, as well as a relay with SPDT contacts. The TTSIM-1A can be used as a stand-alone leak detection alarm, or connected to a host system (TraceTek TTDM- 128, computer, or control automation system) via simple, twisted pair RS-485 serial communication wiring. Tools Required Small flat blade screwdriver Small needle nose pliers Tools to mount DIN rail or enclosure Installation Items (not supplied) 35 mm DIN rail mounting strip (for wall mounts or interior of large control cabinets) and attachment hardware. TT-RS485 power and telemetry jumper cable. Optional TTSIM-ENC-4X-OUTDOORS environmental enclosure for outdoor or corrosive environments, or TTSIM-ENC-4X- INDOORS enclosure with clear cover for indoor, non-corrosive environments. Storage Keep the TTSIM-1A modules in a dry place prior to installation. Avoid damage to components. Additional Items An agency-approved zener barrier must be used where sensing cable connected to the TTSIM-1A will be located in Class1 Div 1 (Zone 0 or 1 in Europe) Hazardous Locations. 1 / 6

Installing the TTSIM-1A Note: To avoid damage to the TTSIM-1A, store the unit in it s packaging until ready to install. Selecting the mounting position Choose a location where the module will be protected from the elements, temperature extremes or heavy vibration. The TTSIM-1A is designed to be snapped onto standard 35 mm DIN rail. Existing electrical or instrumentation cabinets with spare rail space make good mounting locations. It is also possible to install a small section of DIN rail directly on a wall or cabinet surface and mount the TTSIM-1A in any location as long as it does not create a tripping hazard or expose the TTSIM-1A to impact damage. The TTSIM- 1A should be mounted within 1200 m (4000 ft) wire run from the controlling TTDM-128 or control system host. Contact the factory for methods to increase the wire run distance beyond 1200 m. Important: The TTSIM-1A is an electronic unit. Take the following precautions to avoid damage to electronic components: Handle with care and avoid mechanical shock and impact. Keep dry. Avoid exposure to static electricity by touching a nearby piece of grounded equipment or water pipe prior to handling the TTSIM-1A. Avoid contact with metal filings, grease, pipe dope and other contaminants. Mounting the TTSIM-1A module (without NEMA 4X Enclosure Figure 1) Secure a sufficient length of DIN rail to the desired mounting surface, or locate an existing DIN rail with sufficient space to install the TTSIM-1A. Remove the TTSIM-1A from it s packaging and snap onto the DIN rail with the release tab towards the bottom. TRACETEK 35 mm DIN rail Release tab Figure 1. DIN rail mount Mounting the TTSIM-1A module in the optional NEMA 4X Enclosure Figure 2 Plan conduit alignment and drill holes as necessary. A typical outdoor or harsh environment installation will require three holes in the TTSIM-ENC: one for inbound power and telemetry, one for outbound power and telemetry and one for the sensor cable leader. See Figure 2. Secure the TTSIM-ENC to any convenient vertical surface using the four corner mounting holes and hardware suitable for the selected surface. Rough-in conduit as required and pull the cables for power and telemetry. Leave approximately 20 cm (8 in) for connection to TTSIM-1A terminals. Pull in the sensor circuit leader cable. In order to provide maximum electrostatic discharge protection, and to be CE compliant, the DIN rail must be grounded. Note: Rough-in and final connections do not have to be completed at the same time, however make sure to replace the cover and tighten the cover screws if the enclosure will be left in a partially installed condition overnight or longer. TRACETEK Figure 2. NEMA 4X enclosure 2 / 6 EN-TraceTekTTSIM1A-IM-H57338 04/16 THERMAL BUILDING SOLUTIONS

Power Supply Options The TTSIM-1A has several power supply options available. Depending on the version being installed and local regulations, the wiring requirements may vary. In all cases, be sure that each TTSIM-1A receives supply voltage from one and only one source. Important: Observe polarity markings when using 12 Vdc or 24 Vdc versions. Connections for Power and Telemetry TTSIM-1A communicates all alarm and status messages via RS-485 twisted pair telemetry. Two of the four conductors in the power/ telemetry cable are used for telemetry and the other two wires may be used to provide the supply voltage. Alternatively, separate wiring may be used for the supply voltage, as shown in Figure 3. For all TTSIM-1A modules except the last one, there will be an incoming cable (from the TTDM-128 or other host system) and an outgoing cable (to the next TTSIM-1A). Strip a sufficient amount of the jacket insulation and shielding to expose about 2.5 cm (1 in) of the four wires. Strip the primary wires to expose approximately 6 mm (1/4 in) of conductor and make the following connections: (see Figure 3) Terminal Color Item 13 Shield Drain Wire [Shielded twisted pair 14 Black RS-485 ( ) from TTDM-128, Host, 15 Red RS-485 (+) or previous TTSIM] 16 Shield Drain Wire [Shielded twisted pair 17 Black RS-485 ( ) to next TTSIM] 18 Red RS-485 (+) 21 Green AC/DC Supply From source or 22 White AC/DC Supply previous TTSIM* 23 [Green] AC/DC Supply 24 [White] AC/DC Supply [To next TTSIM] * Power supply voltage must be within range specified on TTSIM-1A label. Items in square brackets [ ] are optional. When using TraceTek TT- RS485 power and telemetry cable for power supply distribution, follow the color codes indicated in brackets. Communication Cable Power Cable Figure 3. Power and Telemetry Connections Connections for Alarm Relay The software programmable TTSIM-1A relay contacts may be used for local or remote annunciation, to control a valve or other device, or for connection to a control automation system contact input. The relay can be programmed to alarm on leak only; on either leak or fault; or on leak, fault, or service required. The relay can also be programmed to be ON (coil energized) or OFF (coil deenergized) to signal an alarm (see table below). The relay can be programmed using either a TTDM-128 or a PC running TraceTek TT-SUPERVISOR software. Programmed Status at Terminals Alarm State Alarm Condition 10-11 11-12 On (default) No alarms closed open Alarm open closed Loss of power closed open Off No alarms open closed Alarm closed open Loss of power closed open 10 11 12 Figure 4. Alarm Relay Connections (shown in power off condition) 3 / 6

Place the End of Line Jumper in the correct position If the TTSIM-1A will be connected to a host for communication, it is necessary to set the End of Line Jumper in the correct position as follows: On the last TTSIM-1A in the circuit, place the jumper as shown in Figure 5a. On all other TTSIM s in the circuit, place the jumper as shown in Figure 5b. Figure 5a. End of Line Jumper for last TTSIM-1A Figure 5b. End of Line Jumper for all other TTSIM s Leader Cable Connections for Sensor The TTSIM-1A can be used with any of the TraceTek family of sensors including: TT1000, TT3000, TT5000 and TT5001 cables. Connect the TraceTek leader cable to the TTSIM-1A as shown in Figure 6. Terminal Color Item 1 Red Red / Green Sensor Cable Loop 2 Green 3 Yellow Yellow / Black Sensor Cable Loop 4 Black Red Green Yellow Black Figure 6. Sensing Cable Connections 4 / 6 EN-TraceTekTTSIM1A-IM-H57338 04/16 THERMAL BUILDING SOLUTIONS

Operating Instructions Network Address Assignment If the TTSIM-1A will be used in a TraceTek network, each module in a TraceTek network must have a unique address in the range 001 to 127. All TTSIM-1A units are shipped from the factory with their network address pre-set to a value above the range of valid addresses, in order to prevent communication conflicts during system startup and configuration. Each TTSIM must therefore be configured to a unique address before it can communicate with the TTDM-128 or other host. To set the TTSIM-1A network addresses, repeat the following procedure for each TTSIM-1A. Perform the complete procedure one module at a time: Place the TTSIM-1A configuration jumper in the CFG position, as shown in Figure 7a. Using the TTDM-128 or host system, assign the new TTSIM-1A address (refer to the TTDM-128 User Manual, H56853). Place the configuration jumper in the normal operating position, as shown in Figure 7b, or remove it completely (the jumper is not required in normal operation). Write the address in the space provided on the TTSIM-1A cover. Figure 7a. Configuration Jumper in Configuration Position Figure 7b. Configuration Jumper set for Normal Operation Other configuration settings The TTSIM-1A has a number of configurable settings, including relay mode and operations and leak sensitivity. Refer to the TTDM- 128 User Manual (H56853) for details on how to change these configurations. 5 / 6

Maintenance and Troubleshooting No user maintenance is required! There are no user adjustments or calibrations that can be performed in the field. Each TTSIM-1A is tested and calibrated at the factory. An operating TTSIM-1A runs a continuous self check routine and reports any discrepancies to the TTDM-128 or host computer. If the TTSIM-1A or the network wiring fails in such a way that the TTSIM-1A cannot communicate with the host, then the host reports the failure as a communications failure. Status Indicators There are 5 LED s on the TTSIM-1A circuit board to indicate: power, communications (RX = inbound and TX = outbound), sensor status (leak detected and trouble). See Figure 8. The green Power LED will be ON and will blink once every 5 seconds when the TTSIM-1A is powered and fuctioning correctly. Table 1 lists various sensor status conditions and possible corrective actions. Table 2 lists communication status conditions (applicable when the TTSIM-1A is used in a network system). RX (Yellow) TX (Yellow) Leak (Red) Service (Yellow) Power (Green) TRACETEK Figure 8 TTSIM-1A LED locations Table 1. TTSIM-1A LED operational status indications LEAK SERVICE INDICATION FLASH Leak detected. Check sensor for leak or spill. ON Leak alarm has been reset by operator but the leak condition still exists FLASH The sensor needs servicing. Check sensor and leadwires/jumpers for continuity or contamination. Table 2. TTSIM-1A communication status indications (only active if connected to a network) TX RX INDICATION FLASH FLASH Unit is communicating normally with TTDM-128 or host. OFF FLASH Unit is receiving communication from TTDM-128 or host, but is not responding. OFF ON RS-485 communication wires are reversed OFF OFF Unit is not communicating with TTDM-128 or host. WWW.PENTAIRTHERMAL.COM NORTH AMERICA Europe, Middle East, Africa Asia Pacific Latin America Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7215 thermal.info@pentair.com Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com Tel: +86.21.2412.1688 Fax: +86.21.5426.2937 cn.thermal.info@pentair.com Tel: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. 2003-2016 Pentair. 6 / 6