Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Similar documents
Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Common Building Code Misinterpretations

Preview of the MA Building Code (780 CMR) 9 th edition

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

The Residences at Christina Landing Wilmington, DE

Sprinklers in Wood-Frame Construction:

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

MA Electric Code Challenges for Architects

Laboratories and Hazardous Materials. Company Overview

CHAPTER 7 ALTERATIONS LEVEL

1. The provisions of paragraph (D)(1104) of this rule shall apply to all existing buildings.

Natural Ventilation A Green Smoke Control Approach

For the Florida Building Commission And the Fire Code Advisory Council

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL fpeschulte.

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Fire Rated Door Assemblies: Compliant Designs

NFPA 45 NFPA 211 NFPA 1600

Agency for Health Care Administration

Agency for Health Care Administration

PERFORMANCE COMPLIANCE METHODS

SP07: Coordinating New Door Assembly Installation with Access Control Systems

Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications. Bryant M. Kirkland Jr, PE, CCP, LEED AP

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

Life Safety - Means of Egress/Exits NFPA 101

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

FIRE SAFETY INSPECTION REPORT

Report on First Revisions with Statement June 2014 NFPA 101

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

Agency for Health Care Administration

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

Considerations in the Design of Smoke Management Systems for Atriums

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Agency for Health Care Administration

INITIAL FIRE SAFETY ASSESSMENT

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS

Code Technologies Committee Report Elevator Lobby Group A changes: Elevator Lobby

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE/SMOKE BARRIER FUNDAMENTALS

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

January 1, 2014 Mandatory Effective Date

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Fire Safety Evaluation of Existing Manufactured Educational Building Covered by Section 423 of the Florida Building Code

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

FIRE SAFETY INSPECTION REPORT

Establishing the Risk Basis of Building Size Limits

INITIAL FIRE SAFETY ASSESSMENT

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY

Date: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition

Chapter Nursing Homes

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015

Developing a Healthcare Facility Fire Door Inspection Program

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

FIRE SAFETY INSPECTION REPORT

Welcome to the AccessibilityOnline Webinar Series. Listening to the Webinar. Listening to the Webinar, continued

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

FIRE SAFETY INSPECTION REPORT

INITIAL FIRE SAFETY ASSESSMENT

2012 B.C. Building Code Compliance Review (Division B Part 3)

Statue of Liberty: A Risk Analysis

2018 International Fire Code. Add new text as follows:

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

LABELING OF FIRE-RATED GLAZING STUDY GROUP REPORT TO CTC MEETING CHICAGO, IL - OCTOBER 13-14, 2011 CODE CHANGES

FIRE SAFETY INSPECTION REPORT

Code Technologies Committee Report Fire Rated Glazing Group A changes: Fire rated glazing

Welcome to the AccessibilityOnline Webinar Series. Listening to the Webinar

/WON BuyLine 3726 WON-DOOR. FireGuard. The ORIGINAL horizontal sliding accordion fire door.

ICC CODE CORNER 2012 IFC Code & Commentary

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Agency for Health Care Administration

American Fire Sprinkler Association. An Introduction to the IBC and IFC

Objectives. To review updated IBC and fire test requirements when designing for life safety.

FIRE SAFETY INSPECTION REPORT

Agency for Health Care Administration

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

FIRE SAFETY INSPECTION REPORT

Agency for Health Care Administration

EXIT ROUTES, EMERGENCY ACTION PLANS, AND. FIRE PREVENTION PLANS. PART 1: INTRODUCTION

Module 7. Control of Smoke & Highlights of Code Requirements

An Overview to Designing Smoke-Control Systems

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

Public. Mike Free Health. State of Alabama Department of

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Public Health Fax: Web Site:

Transcription:

Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

Welcome The Boston Society of Architects/AIA is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-aia members are available on request. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Learning Objectives Every floor opening is not an atrium! 780 CMR 713.3 and 707.2 provide specific exceptions. Architectural solutions to reduce or eliminate mechanical smoke exhaust. Basic understanding of performance-based approaches to floor openings and smoke control.

R.W. Sullivan Engineering (RWS) was established in 1945 and currently has over 85 employees. RWS is a full service engineering i firm offering integrated services in the following disciplines: i HVAC Electrical Plumbing Fire Protection Code

Agenda Floor Opening Protection Codes 780 CMR: MA State Building Code, 6 th Edition (1993 BOCA) International Building Code, 2003 Edition (780 CMR 7 th Edition) International Building Code, 2009 Edition (780 CMR 8 th Edition) NFPA 101: Life Safety Code NFPA 92B: Smoke Management Systems Types of Floor Openings General 2-Story Floor Openings 3+ Story Floor Openings Atriums Other Permitted Unenclosed Openings Performance Based Approaches

General Floor Openings Shaft Enclosures 780 CMR, IBC, and NFPA 101 require floor openings comply with one of the following: 1 hour rated shaft when connecting 2 or 3 floors. 2 hour rated shaft when connecting more than 3 floors. Meet an exception for an allowed floor opening.

2-Story Floor Openings

2-Story Floor Openings Code Code Section Prohibited Uses Used for Egress Required Separation 780 CMR 713.3 6 th Edition Exception 2 IBC NFPA 101 707.2 Exception 7 None Use Group I-2 & I-3 8.6.8.1 None 8.6.8.2 Unsprinklered Assembly Not Corridors in Use Group I & R Permitted All Unsprinklered Corridors Permitted Not Permitted Not Permitted Corridors in Use Group I & R All Unsprinklered Corridors One of the Floors All Corridors

2-Story Open Exit Stairs 780 CMR (7 th Edition) Section 1019.1 & 2009 IBC Section 1016.1 Exception 8 allows for 50% of the exit stairs between any 2 stories to be unenclosed and used as an exit stair. This stair however cannot be open to more than the two connected stories. 1 Hour Wall

2-Story Open Exit Stairs 780 CMR (7 th Edition) Section 1019.1 & 2009 IBC Section 1016.1 Exception 9 allows for all exit stairs between the first 2 stories to be unenclosed and used as exit stairs in a fully sprinklered building. The connected floors must have 2 exits and are not permitted to be open to any other floors.

Multiple 2-Story Floor Openings 4 th floor 3 rd floor Rated assemblies 2 nd floor Boundaries of floor openings 1 st floor

2-Story Floor Openings Alternative Approach 3 rd floor Sprinkler Protected Glazing or Rating Equivalent to Floor 2 nd floor 1 st floor Alternative design requires approval from the Authority Having Jurisdiction or a variance. Provides smoke reservoir that performs better than a continuous floor assembly.

3+ Story Floor Openings

3+ Story Floor Openings Size Code Code Section Restrictions Required Separation Limits 780 CMR 6 th Edition 713.3 Exception 11 Business Stairs Unsprinklered Buildings Only Use Group B 6 Floors Max Draft Curtains w/ Closely Spaces 160 ft 2 Sprinklers All Corridors NFPA 101 IBC 8.6.8.6 Escalators only No more than 4 stories in Use Groups B & M w/ sprinkler option Twice the Escalator Area Draft curtains w/ closely spaced sprinklers OR Shutter at every floor opening 713.3 Exception 8 Escalator opening 780 CMR 7 th Edition & IBC 707.2 Exception 2 Escalator /Open Stair Unsprinklered Buildings 4 Floors Max in Use Groups other than B & M Twice the Stair Area Draft Curtains w/ Closely Spaces Sprinklers NFPA 101 IEBC 8.6.6 Mini-Atrium 703.2.1 Unsprinklered Educational All Healthcare Unsprinklered Apartments Lowest or Next to Lowest Level must be a Street Floor No more than 3 Floors None Smoke Barriers Adjacent spaces have access to an exit without entering the communicating space.

Escalator / Open Stair Protection ti 780 CMR 713.3 Exc. 8, IBC 707.2 Exc. 2, NFPA 101 8.6.8.6 Openings protected with a draft curtain and closely spaced sprinklers. The opening area is limited to twice the horizontal projected area of the escalator. Also, 780 CMR and IBC limit openings to not more than 4 stories in Use Groups other than B & M.

Escalator Protection for Open Stairs NFPA 101 The Manual Escalator. Same hazard as an escalator, however only 780 CMR 7 th Edition and IBC permit the use of the previously described options for protecting a standard open stair. Approval from the Authority Having Jurisdiction or a variance is required for states adopting NFPA 101.

Mini-Atrium: Configuration NFPA 101 8.6.6 & IEBC 703.2.1 Exception 3 Connects no more than 3 stories (Not Limited by IEBC) Lowest or next-to-lowest floor is street level Open and unobstructed communicating space

Mini-Atrium: Fire Protection NFPA 101 8.6.6 & IEBC 703.2.1 Exception 3 NFPA Fire Separation Options 1 hr fire barrier Smoke barrier in a fully sprinklered building No separation required for detention/correction housing IEBC Fire Separation Smoke Barrier

Mini-Atrium: Egress NFPA 101 8.6.6 Considered a single floor area for egress capacity Occupants within the mini-atrium access to at least one exit without t having to traverse another story within the mini-atrium space Occupants outside the mini-atrium access to at least one exit without having to enter the mini-atrium space

Other Permitted Unenclosed Openings Section 707.2 4 story opening within a dwelling unit (780 CMR Exception 1 & IBC Exception 1) Malls (780 CMR Exception 5 & 2003 IBC Exception 5) Mezzanines (780 CMR Exception 9 & IBC Exception 9) Ramps in parking structures (780 CMR Exception 8 & IBC Exception 8) Use Group I-3 in accordance with 780 CMR 410.5 (780 CMR Exception 7)

Atriums

Atriums 780 CMR & IBC 404, NFPA 101 8.6.7 General requirements Sprinkler Protection: Atriums must be protected with sprinklers (780 CMR 404.2, IBC 404.3, NFPA 101 8.6.7(4)). Travel Distance: Other than the lowest floor, the egress travel distance through an atrium is limited to 150 ft (780 CMR 404.7) or 200 ft (2009 IBC 404.9). Exit Discharge: Permitted within the atrium (780 CMR 404.3.1, NFPA 101 8.6.7(2)).

Enclosure of Atrium 780 CMR & IBC 404.5, NFPA 101 8.6.7(1) Atriums are required to be separated from adjacent spaces by 1 hour rated construction except: Residential guest rooms or dwelling units where egress is provided that does pass through the atrium (780 CMR only). 3 stories are permitted to be open to the atrium if the volume calculated for the design of the smoke control system includes the volume of the spaces not separated from the atrium. (No limit in NFPA 101) Sprinkler protected glass

Sprinkler Protected Glass

Atrium Smoke Control 780 CMR 404.4 & IBC 404.4 Smoke control is required in all atriums that connect more than 2 stories ( connect = opening in floor slab).

Smoke Control Design Criteria Component Interface height above highest walking surface open to the atrium 780 CMR 6 th Edition Design fire size 2000 BTU/s Fire scenarios Axisymmetric 780 CMR 7 th Edition & 2003 IBC NFPA 101 / 92B 2009 IBC 6 ft. 10 ft. 6 ft. 5000 BTU/s minimum Axisymmetric, Balcony Spill, Window Determined by Analysis Axisymmetric, Balcony Spill, Window

Example Atrium

Example Exhaust Rates Code Exhaust Requirement (cfm) 6 th Edition: Axisymmetric * 226,508 Code Exhaust Requirement (cfm) 7 th Edition: Axisymmetric ** 332,891 7 th Edition: 15 Wide Balcony Spill 636,890 7 th Edition: Window Spill Plume 158,658 7 th Edition 636,890 The same variables were used in both axisymmetric cases except for fire size. * Calculated with a 2,000 Btu/s fire as required by 6 th Edition. ** Calculated with a 5,000 Btu/s fire as required by 7 th Edition.

Exhaust Rates Exhaust Requirement (cfm) Open Floors 780 CMR 6 th 780 CMR 7 th Edition Edition & IBC 1 thru 5 195,927 667,559 1 thru 4 138,313 487,593 1 thru 3 89,269 337,603 1 thru 2 49,631 187,613 1 8,604 35,948

Performance Based Approaches Due to the large exhaust rates under IBC alternative designs will likely become more common. 780 CMR 7 th Edition permits alternative designs for smoke control systems (780 CMR 909.20.4). A 3 rd party review and variance is currently required for all alternative designs in Massachusetts (780 CMR 901.7.2.1). 2009 IBC references NFPA 92B which allows CFD modeling

Alternative Design Examples Shutters / Curtains Used to enclose the upper stories of an atrium. Activated by building fire alarm system. Egress Access to required exits outside the atrium boundary Fire Modeling Used to estimate actual smoke production and spread. Deluge Sprinkler System Used to limit the fire size.

Atrium Egress Access to required exits without entering the atrium and allowing the smoke to lower down.

Atrium Fire Modeling

Atrium Fire Modeling Plugholing Relatively shallow smoke layer depth and a high exhaust rate can lead to the entrainment of cold air from the clear layer.

Alternative Protection Example Life Sciences Laboratory Building 2-story floor open (shown in red) Designed as an atrium per NFPA 101 No smoke control provided based on analysis

Alternative Protection Example

Visibility and Smoke Movement: Floor Opening in a University Building 208 ft 154 ft

Thank you. This concludes The American Institute of Architects Continuing Education Systems program. QUESTIONS? Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph. D, P.E., LEED AP KSH@RWSullivan.com JAI@RWSullivan.com 617.337.9319 617.337.9321 Please email us for a PDF file with full-size slides of this presentation.