Duct Air Quality Sensors

Similar documents
Room Air Quality Sensors

Room air quality sensors

QPM21 Series Duct CO 2 and Air Quality Sensors

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Duct Temperature Sensors

Room Temperature Sensors

for relative humidity and temperature

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

for relative humidity and temperature

QPA63... CO 2 /VOC Sensors. Siemens Building Technologies HVAC Products

for relative humidity and temperature with calibration certificates

Use. In ventilating and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation.

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Duct Temperature Sensors

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Differential pressure sensors

Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring

Flush-mount room sensor KNX S-Mode / KNX LTE- Mode / KNX PL-Link

PRELIMINARY EDITION

Semi flush-mount room thermostat

Indoor Air Quality Controller

Room Temperature Sensor

Room Temperature Controller

Hygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

Hygro/hygrothermal transducers (hygrometric)

SIMRAD GD10 IR GAS DETECTOR

SIMRAD GD10PE IR GAS DETECTOR

No. Icon Name Function

Room Temperature Sensors

Room Temperature Controller

Room Temperature Controller with LCD

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

Immersion Temperature Controller

Hygro and Hygrothermo Transducers (capacitive) for climatic applications

RVL479. Heating Controller. for use with a partner unit

RDH10. Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

Hygro/hygrothermal transducers (hygrometric)

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

Sensor unit MC2 with analog output for Freon gases and refrigerants

Flame Safeguards LFE10. Building Technologies HVAC Products

RVL481. Heating Controller. including d.h.w. heating

Room thermostats with LCD for wall mounting

UV Flame Supervision System

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVL480. Heating Controller

LC1350 Level Controller

Frost Protection Thermostat

Preliminary Release. Room Temperature

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

Room Temperature Controllers

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

Flush-mounted room thermostat

Danfoss gas detection units

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

Flame Safeguards LFE10. Building Technologies HVAC Products

Use. For 2-pipe fan coils

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Self-learning Room Temperature Controller

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Infrared Flame Detectors

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

LAE10 LFE10. Use. Series 02

Wireless room thermostat with LCD

ECO ROOF FAN. A modern, energy-saving roof fan with a DC motor. INSTALLER Register the roof fan for an extended 5 year guarantee!

Heating Controller. Building Technologies HVAC Products. Synco 700

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

Datasheet: K-22 LO Sensor

Room thermostat with Auto Timer, Option External Input

DT1101A / DT1102A / DO110xA Automatic fire detectors

C Note! LGI16... Burner Controls. Building Technologies

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Air Quality. Sample applications 243 CO2 VOC CO2+VOC. Air Quality

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

Mounting bezel Retaining spring. Detects movement within the detection range, allowing load control in response to changes in room occupancy.

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

Gas Central with built-in Gas Detector for Nitrogen Dioxide (NO 2

Duct Humidity and Temperature Transmitter. Features. IP65 protection. Ordering

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

OH720, OP720, HI720, HI722

RVP310. Heating Controller. Building Technologies HVAC Products

RAR... Photocell Detectors. Building Technologies Division

MANDÍK MEASUREMENT AND CONTROL SYSTEM

ASA linear smoke detector

Transcription:

1 962 QPM2102D QPM2160D, QPM2162D QPM2100, QPM2102 QPM2160, QPM2162 Duct Air Quality Sensors QPM21 With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1 ) and depending on the type of sensor VOC 2) sensing element, based on a heated tin dioxide semiconductor CO 2 temperature and CO 2 humidity-temperature multisensor No recalibrations required Operating voltage AC 24 V or DC 15 3 Signal outputs DC 0...10 V 1) NDIR = Non dispersive infrared 2) VOC = volatile organic compounds (also called mixed gas) Use In air ducts of ventilation and air conditioning plant to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation. The sensor acquires: CO 2 concentrations VOC concentrations as an indication of odors in the duct air, such as tobacco smoke, body odor, or material fumes The relative humidity of the duct air The duct air temperature The QPM21 can be used as a: Control sensor in the supply or extract air duct Transmitter for building automation and control systems and / or display units Typical use: Acquisition of CO 2 and VOC concentrations: In party rooms, lounges, fair pavillions and exhibition halls, restaurants, canteens, shopping malls, sports gymnasiums, sales rooms, and conference rooms Acquisition of CO 2 concentrations: In ventilation plant of rooms with varying occupancy levels where smoking is prohib- CE1N1962en 26.08.2008 Building Technologies

ited, such as museums, theatres, movie theatres, auditoriums, office spaces and school rooms Important! The QPM21 sensors are not suited for use as safety devices, such as gas or smoke warning devices! The sensors must not be used outdoors! Type summary Type reference CO 2 measuring range VOC sensitivity Temperature measuring range Humidity measuring range Measured value display QPM2100 0 2000 ppm --- --- --- no QPM2102 0 2000 ppm Low (R1) Normal (R2) High (R3) QPM2102D 0 2000 ppm Low (R1) Normal (R2) High (R3) --- --- no --- --- yes QPM2160 0 2000 ppm --- 0...50 C / 35...+35 C --- no QPM2160D 0 2000 ppm --- 0...50 C / 35...+35 C --- yes QPM2162 0 2000 ppm --- 0...50 C / 35...+35 C 0...100 % no QPM2162D 0 2000 ppm --- 0...50 C / 35...+35 C 0...100 % yes Ordering When ordering, please give name and type reference, e.g.: Duct air quality sensor QPM2102 The sensor is supplied complete with mounting flange and cable entry gland M16. Equipment combinations The QPM21 are suited for use with all types of systems and devices capable of acquiring and handling the DC 0...10 V output signal delivered by the sensor. Mode of operation CO 2 concentrations The Symaro TM air quality sensors acquire the CO 2 concentration by infrared absorption measurement (NDIR). Owing to an additional integrated reference light source, the measurement is always accurate and no service or recalibration is needed, thus saving service costs. The resulting output signal of DC 0...10 V is proportional to the CO 2 content of the ambient air. Function diagram CO 2 (output U1) U1 [V] 1962D01 10 8 6 4 2 0 0 400 800 1200 1600 2000 CO 2 [ppm] 2/9

CO 2 /VOC concentration only with QPM2102 and QPM2102D Ventilation demand diagram (output U2) The sensor acquires and evaluates the CO 2 / VOC concentration and transforms it to a ventilation demand signal. It represents the result of maximum selection of the CO 2 measuring signal and the filtered VOC measuring signal. With maximum selection, the 2 demand signals are compared and depending on the result and the selected VOC sensitivity delivered as the common air quality demand. The ventilation demand signal is delivered via output U2 as a DC 0 10 V signal to be fed to the ventilation controller. U2 [V] Max (CO, VOC) 2 [ppm] VOC sensitivity Response time "VOC signal" Relative humidity only with QPM2162 and QPM2162D Temperature only with QPM2160, QPM2160D, QPM2162 and QPM2162D Using the shorting plug on the setting element for the measuring range, the impact of VOC ventilation demand on maximum selection against CO 2 ventilation demand can be changed. The position in the middle (R2) produces normal sensitivity of the VOC signal (factory setting). The 2 other positions are used for increasing (R3) or decreasing (R1) VOC sensitivity. Before the processor handles a change of the measured VOC value for maximum selection, a response time of 3 minutes for every Volt the signal value changes is observed. The sensor acquires the relative humidity in the air duct with a capacitive humidity sensing element whose capacitance changes as a function of the relative humidity. An electronic measuring circuit converts the signal from the sensing element to a continuous DC 0...10 V signal, corresponding to a relative humidity range of 0...100 %. The sensor acquires the temperature in the air duct with a sensing element whose electrical resistance changes as a function of the temperature. The change is converted to an active DC 0...10 V output signal ( 0...50 C or 35...+35 C). Mechanical design The duct air quality sensor consists of housing, printed circuit board, connection terminals, mounting flange and immersion rod with measuring probe. The 2-sectional housing is comprised of base and removable cover (without display: snap-on design; with display: screwed fastening). The measuring circuit and the setting elements are located on the printed circuit board inside the cover, the connection terminals on the base. The humidity and temperature sensing elements are located at the end of the measuring probe and are protected by a filter cap. Cable entry is made via the cable entry gland M16 (IP 54) supplied with the sensor, which screws into the housing. Immersion rod and housing are made of plastic and are rigidly connected. The sensor is fitted with the mounting flange supplied with the sensor. The flange is to be placed over the immersion rod and then secured in accordance with the required immersion length. 3/9

Setting elements 1 2 3 F C Measuring range R1 R2 R3 Test function active U1 U2 10 V QPM2100/2102/2160 QPM2102D/2160D Display temperature unit F C 2 4 6 0 V 10 V X17 F C Measuring range R1 R2 R3 0 V 1962Z13en * Test function active U1 U2 U3 X17 U1 U2 U3 10 V 10 V 1 2 3 X17 QPM2162 / QPM2162D Display temperature unit F C 0 V 0 V 10 V * Set either or X17 into test function, but not both at the same time. 0 V The setting elements are located inside the cover for the measuring range with QPM2100 with QPM2102/2102D with QPM2160/2160D and QPM2162/2162D for the active test function The different vertical plug positions have the following meaning: For the CO 2 measuring range: Shorting plug in the mid position (R2) = 0 2000 ppm (factory setting) For CO 2 / VOC weighting: Shorting plug in the left position (R1) = VOC sensitivity "low" Shorting plug in the mid position (R2) = VOC sensitivity "normal" (factory setting) Shorting plug in the right position (R3) = VOC sensitivity "high" For the temperature measuring range: Shorting plug in the left position (R1) = 35...+35 C Shorting plug in the mid position (R2) = 0...50 C (factory setting) Shorting plug for the measuring range in the horizontal positions: The signal output delivers the values according to table "Test function active". Behavior in the event of fault All types QPM2102/2102D QPM2160/2160D QPM2162/2162D In the event of CO 2 failure, 10 V will be present at signal output U1 (after 60 seconds) In the event of CO 2 or VOC failure, 10 V will be present at signal output U2 (after 60 seconds) Should the temperature sensor become faulty, 0 V will be present at signal output U2 Should the temperature sensor become faulty, 0 V will be present at signal output U3, and the humidity signal at signal output U2 will increase to 10 V (after 60 seconds) Should the humidity sensor become faulty, 10 V will be present at signal output U2 (after 60 seconds), and the temperature signal will remain active Display of measured values 4/9 With sensors type QPM2102D, QPM2160D and QPM2162D, the measured values can be read on an LCD. The following measured values are displayed: CO 2 : In ppm CO 2 + VOC: As a bar chart (4 bars U2 = 2 V, 20 bars U2 = 10 V) Temperature: In C or F Humidity: In %

Disposal The major plastic components bear the material references in compliance with ISO / DIS 11 469 to facilitate environment-friendly disposal. Accessories Engineering notes Name Filter cap (for replacement) Type reference AQF3101 To power the sensor, a transformer for safety extra low-voltage (SELV) with separate windings for 100 % duty is required. When sizing and protecting the transformer, local safety regulations must be compleied with. When sizing the transformer, the power consumption of the duct sensor must be taken into consideration. For correct wiring, refer to the Data Sheets of the devices with which the sensor is used. The permissible cable lengths must be observed. Cable routing and cable selection When laying the cables, it must be observed that the longer the cables run side by side and the smaller the distance between them, the greater the electrical interference. Shielded cables must be used in environments with EMC problems. Twisted pair cables are required for the secondary supply lines and the signal lines. Mounting notes Mounting location and orientation Note! Mounting instructions To ensure degree of protection IP54 resp. IP65, the sensor must be fitted with the cable entry pointing downward! The sensor should be mounted in locations where it can be easily accessed for service. If used in connection with steam humidifiers, the distance to the humidifier must be a minimum of 3 m. If permitted by the installation, the distance should be as great as possible, but no more than 10 m The sensing elements in the immersion rod are susceptible to impact and shock. Any impact or shock should therefore be avoided The sensor must not be mounted in ventilation plant on top of a building (impact of solar radiation)! To ensure correct operation, the sensor s ambient temperature must lie in the range of 5 +45 C Mounting Instructions are enclosed in the package. Commissioning notes The sensor s functions can be checked 30 minutes after applying power: Checking the CO 2 function: In well ventilated rooms, the sensor shows the CO 2 concentration of the outside air. Typically, this is 360 ppm (the sensor s measuring accuracy must be considered). Also, a basic functional check can be made by exhaling on the sensor. In that case, it must be taken into account that the sensor s rate of response has been purposely delayed (time constant t 90 = 5 min) Checking the VOC function: Touch the sensor with a cotton ball dowsed in alcohol (e.g. gas from a cigarette lighter, without lighting a flame) Ventilation should start when the preset switching level of the connected controller is reached. 5/9

Technical data Power supply Cable lengths for measuring signal Functional data "CO 2 " Functional data "Maximum selection of CO 2 and VOC" with QPM2102 and QPM2102D Functional data "r.h." with QPM2162D Functional data "Temperature" with QPM2160/ QPM2160D and QPM2162/ QPM2162D Air velocity Protective data Electrical connections Environmental conditions Operating voltage (SELV) Frequency Power consumption Perm. cable lengths Measuring range Measuring accuracy at 23 C and 1013 hpa Temperature dependency in the range of -5 45 C Long-time drift AC 24 V ±20 % or DC15 3 50/60 Hz at AC 24 V 2 VA refer to Data Sheet of the device handling the signal 0...2000 ppm MW = measured value ±(50 ppm + 2 % MW) ±2 ppm / C typically ±20 ppm p.a. Time constant t 90 <5 min Output signal, linear (terminal U1) DC 0...10 V 0...2000 ppm, max. ±1 ma Recalibration-free Measuring range "VOC" VOC sensitivity 8 years 0...2000 ppm refer to "Type summary" Output signal, linear (terminal U2) DC 0...10 V 0...2000 ppm, max. ±1 ma Response time "VOC signal" t VOC Range of use Measuring range Measuring accuracy at 23 C and AC 24 V 0 95 % r.h. 30 70 % r.h. Temperature dependency Time constant 3 min/v 0...95 % r.h. (noncondensing) 0 100 % r.h. ±5 % r.h. ±3 % r.h. (typically) 0.1 % r.h./ C approx. 20 s Output signal, linear (terminal U2) DC 0...10 V 0...100 % r.h., max. ±1 ma Range of use 5...+45 C Measuring range 0...50 C (R2, R3) or 35...+35 C (R1) Measuring element Measuring accuracy at AC 24 V in the range of 15...35 C 35...+50 C NTC 10 kω ±0.8 K ±1 K Time constant <3.5 min. in with 2 m/s moved air Output signal, linear (terminal U2 or U3) DC 0...10 V 0...50 C / 35...+35 C max. ±1 ma Max. air velocity V max. 10 m/sec. Degree of protection of housing QPM2102D, QPM2160D, QPM2162D IP 65 to IEC 60 529 in the built-in state QPM2100, QPM2102, QPM2160, QPM2162 IP 54 nach IEC 60 529 in the built-in state Safety class III to EN 60 730 Screw terminals for 1 2.5 mm 2 or 2 1.5 mm 2 Operation to Climatic conditions Temperature (housing incl. electronics) Humidity Mechanical conditions IEC 60 721-3-3 class 3K3 0...50 C 0 95 % r.h. (noncondensing) class 3M2 6/9

Materials and colors Standards Weight Transport to Climatic conditions Temperature Humidity Mechanical conditions Base Cover Immersion rod Filter cap Mounting flange Cable entry gland Sensor (complete assembly) Packaging IEC 60 721-3-2 class 2K3 25...+70 C <95 % r.h. class 2M2 polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7035 (light-grey) polycarbonate, RAL 7001 (silver-grey) polycarbonate, RAL 7001 (silver-grey) PA66 F35 (black) PA, RAL 7035 (light-grey) silicone-free corrugated cardboard Product safety Automatic electrical controls for household and similar use EN 60 730-1 Electromagnetic compatibility Immunity QPM2162 and QPM2162D EN 61 000-6-1 Immunity QPM2100, QPM2102, QPM 2101D, QPM2160 and QPM2160D EN 61 000-6-2 Emissions EN 61 000-6-3 conformity to EMC directive 2004/108/EC conformity to Australian EMC Framework Radio Interference Emission Standard Radio Communication Act 1992 AS/NZS 3548 -conformity UL 873 Incl. packaging QPM2100, QPM2102 QPM2160, QPM2162 QPM2102D QPM2160D, QPM2162D approx. 0.247 kg approx. 0.252 kg approx. 0.267 kg approx. 0.272 kg ppm = parts per million Connection terminals QPM2100 QPM2102/2102D 0 CO 2 CO 2 CO 2 / VOC U1 0 U1 U2 196201 196202 QPM2160/2160D QPM2162/2162D R1 = -35...+35 C / CO 2 R2 = 0...50 C CO 2 r.h. 0 U1 U2 0 U1 U2 196203 R1 = -35...+35 C / R2 = 0...50 C U3 196204 0 U1 U2 U3 Sytem voltage AC 24 V (SELV) or DC 15...3 System ground and measuring neutral Signal output DC 0...10 V Signal output DC 0...10 V Signal output DC 0...10 V 7/9

Dimensions QPM2160, QPM2162: 274 QPM2100, QPM2102: 243 min. 70, max. 135 min. 100, max. 165 M16 x 1,5 Drilling plan 21 60 Dimensions in mm 8/9

80 60 28 QPM2160D, QPM2162D: 276 QPM2102D: 245 25 40 ø 15 80 50 1962M02 83 77 49 55 42 min. 70. max. 135 min. 100, max. 165 56 M16 x 1,5 Drilling plan 21 60 Dimensions in mm 2005 2008 Siemens Switzerland Ltd. Object to alteration 9/9