A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

Similar documents
Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Recent Advances in Energy, Environment and Economic Development

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

K.F. Fong *, C.K. Lee, T.T. Chow

Human response to thermal environment in rooms with chilled beams

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

ω = (1) Kirby S. Chapman Ph.D.

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Experimental study of space cooling using ceiling panels equipped with capillary mats

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Modelling the Performance of a Diffusion Absorption Refrigeration System

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

A study of radiant cooling for a room with daytime application in tropical climate

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Thermal Comfort with Convective and Radiant Cooling Systems

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Mathematical Simulation of Longan Fruit Drying

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Purdue e-pubs. Purdue University

DESIGN AND FABRICATION OF A PORTABLE REFRIGERATOR BASED ON PELTIER EFFECT

Numerical study of heat pipe application in heat recovery systems

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Using Evaporative Cooling Methods for Improving Performance of an Air-cooled Condenser

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Measurement of R32 Vapor Injection Heat Pump System

OIL AND GAS INDUSTRY

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

,Chaojian He6, f. School of Guangxi University, Nanning , China.

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Global Journal of Engineering Science and Research Management

Transcritical CO2 Bottle Cooler Development

Low GWP Refrigerants for Air Conditioning Applications

How to ensure Thermal Comfort in buildings with CFD

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Effect of Heat Exchanger Configuration on the Performance of Joule-Thomson Refrigerators

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Passive Indirect Evaporative Cooler

Desiccant Cooling with Solar Energy

Optimizing energy efficiency and occupant comfort with climate specific design of the building

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

International Journal of Informative & Futuristic Research ISSN (Online):

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Compression of Fins pipe and simple Heat pipe Using CFD

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Oxyvap Evaporative Cooling Applications

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

Modified Air Cooler with Split Cooling Unit

Jurnal UMP Social Sciences and Technology Management Vol. 3, Issue. 3,2015

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Hot Reservoir Stainless-Methanol Variable Conductance Heat Pipes for Constant Evaporator Temperature in Varying Ambient Conditions

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

973 Dew Point Mirror. Portable Industrial Chilled Mirror Hygrometer. Typical applications: REFLECTING YOUR STANDARDS

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Project Number: P15441

Storage and hot and cold water in a thermocline for Space heating/cooling and domestic hot water

Transcription:

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING G. COURRET, P. W. EGOLF, O. SARI Haute école spécialisée de Suisse occidentale, Institut de Génie Thermique, Rte de Cheseaux 1, CH 1401 Yverdon-les-Bains, Switzerland Tél. :+41.24.426 44 78; Fax. : +41.24.426 44 77 ; gilles.courret@eivd.ch ABSTRACT A condensing device allows to avoid condensation on cooling ceilings in rooms with humid air. It uses thermoelectric modules in contact with the cooling panels. The pumped heat is transferred into the cooling ceiling to keep its temperature above the dew point. Tests have been performed in a full-scale chamber. A set of condensing units was mounted on a standard hydraulic cooling ceiling. The control of temperature is achieved by regulating the mass flow of the water. By this method the loss of efficiency of the cooling panels is fully compensated. Without the condensers, the temperature of the water would have to be increased. This would cause 12 % less cooling power. But with the condensers, the total cooling power is 9 % higher in comparison to panels - without condensers - which are operated in dry air. Finally, we can state that the cooling power is increased by 20 % due to the condensers. If the system is sized to replace the entire (convective) air conditioning system, the following advantages are obtained: No noise Perfect adaptation to building retrofits (no air ducts, only water piping) Less restriction on window opening. KEYWORDS Cooling ceiling, chilled panel, condensation, protection, dehumidifier, drier, thermoelectric cooling PURPOSES OF RESEARCH Nowadays it is well accepted that radiant cooling ceilings provide a better comfort and normally cause a smaller energy demand than conventional convective air conditioning systems [1, 2, 3, 4]. Furthermore, hydraulic systems require less space, because water has a much higher heat capacity than air [1]. These systems allow to cool the ambient air but not to reduce its vapor content. As long as the temperature of the air is lower than that of the skin, human beings are only weakly sensitive to humidity in a large range (30 % to 80 % relative humidity). For example, Figure 1 shows the thermal comfort calculated according to ISO 7730 [5] versus the difference of temperature between the air and the wet bulb temperature for a given enthalpy density. For all the three cases, which have been calculated, optimal comfort is achieved (PPD of 5 %). The lowest energy cost is obtained for the highest enthalpy density (60 kj/kg). This is the case where the temperature of the air - at which optimal comfort is obtained - is closest to saturation. The efficiency of cooling panels is clearly limited by avoiding an occurrence of condensation.

100% Predicted Percentage Dissatisfied 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 60 kj/kg 55 kj/kg 50 kj/kg 0 5 10 15 T - TwetBulb [ C] Figure 1 Thermal comfort versus condensation risk for different air enthalpy densities. As a consequence, cooling panels are only seldom taken into operation without a control of the air condition. The objective of this study is to obtain first experiences with a prototype of a ceiling thermoelectric condenser. THE METHOD OF APPROACH The set-up forces condensation to occur only on a limited surface area. Each condensing unit consists of a heat exchanger, which is cooled by Peltier elements. These are in contact with the ceiling panels, to keep the condensing unit at a low temperature (see Figure 2). Therefore, the pumped heat is transferred into the cooling fluid, and the units can be used to maintain the temperature of the panels above the dew point in the downstream direction. Cooling ceiling ;;;;;;;;;;;;;;; Condenser ; ;;;; ; Thermoelectric modules 12 Condenser Venturi Collector 12 cm 40 cm Exit Figure 2 Schematic drawing of a condensing unit (prototype)

Figure 3 A condensing unit in operation Condensers are aluminum radiators with fins (Figure 3). Their total area of condensation is ten times larger than the area on which they are fixed to the ceiling. A Venturi nozzle accelerates the air in a natural manner without applying any forcing of the air by ventilators. Showing no moving parts, the set-up is very reliable in operation and well-adapted to a seasonal utilization. A tray is placed underneath the device, in order to collect the condensate. A request for an European patent has been deposited, including different possible implementations, especially regarding the removal of the condensed water [6]. A prototype was built and mounted on a cooling ceiling of 12 m 2 area, composed by conventional cooling panels. Tests have been performed in a full-scale climatic chamber (4m x 4m x 3m). The system consists of two times six identical small units, which are symmetrically distributed on two lines (see Figure 4). One line is close to the water inlet and the other to the outlet of the ceiling. The units cover only 4% of the area mounted with cooling panels. 4 m Water inlet 4 m Chilled panel Condensing unit Water outlet Figure 4 The set-up in the testing chamber

RESULTS AND ASSESSMENT OF THEIR SIGNIFICANCE Six heaters, releasing a total heat of 930 W, were mounted in a test chamber in order to simulate thermal charges. The worst climatic outdoor conditions met in Lausanne (Switzerland) are reproduced: air inlet temperature 24 C and relative humidity 80 % (dew point at 20.4 C). The renewing air rate is set at six volumes per hour, which is high above the hygienic required minimum. The temperature of the water at the inlet is kept at a usual condition, namely 15 C. A control of the temperature is achieved by regulating the mass flow through the panels. The main objective - of avoiding condensation on the panels - is clearly achieved. Enough heat is transferred into the ceiling. Measurements show that the loss of efficiency of the cooling panels is compensated by the condensing units. The total cooling power of the combined system - consisting of cooling panels and condensing units - is 9 % higher, compared to the cooling power of the panels, which are operated without condensing units in dry air. Without a protection system for condensation, the temperature of the water would have to be increased. This would cause a reduction of the cooling power of 12 %. Finally, we can state that the cooling power is increased by 20 % as an advantage of the condensing system. The drying performance of each line of condensers has been measured. At the inlet the amount of condensed water is three times higher compared with the outlet. The performance of the condenser per unit of horizontal cross section is the following: TABLE 1 Flux density for a difference of ten Kelvin between the water in the unit and the chamber Pumped heat 520 W m -2 Condensation 175 g h -1 m -2 (23 % of the pumped heat) The heat pumped by each module was calculated using to the following equation: Q& C = S T I R I 2 C 2 K ( T T ) This equation has three measured inputs: - I : Injected electrical current - T C, H :Temperatures on the cold and hot sides The resting three parameters are characteristics of the thermo-electrical modules (data provided by the supplier): - S : Seebeck coefficient - R : Electrical resistance - K : Thermal conductance This model was validated experimentally by changing the number of modules per unit. The coefficient of performance (COP) is the ratio of the pumped heat to the electrical consumed power, which is assessed by measuring in add the voltage at the terminals of the two lines of units. In steady state, the obtained value for the line at inlet is COP = 2. The flux density of pumped heat is five times higher than that achieved with standard radiant panels mounted on the ceiling. This ratio is still above three when comparing to panels fitted up with fins to reinforced natural convection. H C

TABLE 2 Comparison with diverse types of panels for ceilings Type of panel Performance ratio Radiant (standard cooling ceiling) 5.7 Reinforced convective effect 3.5 In the present study the air inlet condition corresponds to an extreme weather condition in Switzerland. If the power of the device is increased, the performance of the condensing units can be further extended. VERTICAL SPACE REQUIREMENT A high vertical space requirement causes high costs. Air ducts of conventional air conditioning systems take a minimum height of 30 cm per story, which equals approximately 10% less building profitability. The present system is of greater advantage, if it completely can substitute the air conditioning system. Such a solution is shown in Figure 5. Air Inlet Zoom: Air Inlet Water ;;Chilled Blinds Blinds Zoom Drying Panels Air Inlet; Cooling Panels Blinds Figure 5 Integration of a condensing unit with an air inlet in the building façade PARTIAL DECENTRALIZATION OF COLD PRODUCTION Caused by the thermo-electrical modules, a fraction of the production of cold is performed in each room, in contrast to common installations, where a mechanical central unit provides the entire cooling. Centralized production is generally more energy and cost effective. But to make the condenser more compact, it is necessary to operate it at a lower temperature. This rises however the thermal loss and the risk of causing condensation along the piping system. A decentralization of the production of cold allows to increase the heat flux density at an equal inlet temperature. Furthermore, cooling ceilings are usually equipped with a warning sensor to indicate too high moisture contents of the air. The signal of such a sensor could also be used to switch the dehumidifier on and off. Local control would provide energy savings, because the dew point can vary significantly from one room to another (window openings, occupants, etc.).

CONCLUSION A first prototype of a ceiling condenser has been built and tested. It has to be redesigned to improve the aesthetics, so that it is ready to target the market. A full integration into the ceiling is desired. Our research efforts show that the full set-up (panels and condensing units) allows a reduction of the installed power of the air-conditioning system. The reason is the advantage of having the possibility to control the temperature of the panels in the vicinity of the dew point. This leads to an improvement of comfort: Less draughts Less risks of dry eyes or/and dry throats. Mounting the condensing units into the panels will increase the total performance (better heat sink). Then the system will be powerful enough to keep the air humidity in the room below 70 %. In numerous cases it will be even possible to replace the entire (convective) airconditioning system. The following advantages are expected: No noise Perfect adaptation of system to building retrofits (no air ducts, only water piping system) Substantial energy savings (use of low exergy sources) Less restriction on window opening. ACKNOWLEDGEMENT The building of the prototypes and their experimental and theoretical investigations have been financed by the Haute école spécialisée de Suisse occidentale. We are grateful to the Gebert Rüf Stiftung for funding work of the numerics group and the Commission for Technology and Innovation and the Federal Office for Energy of Switzerland for its support. The authors would also like to thank the firms Barcol-Air, Energie Solaire and Trox-Hesco for supplying radiant panels and for diverse other industrial support. REFERENCES [1] Sodec, F. (1999). Economic viability of cooling ceiling systems, Energy and Buildings 30 :2, 195-201. [2] Fernberg, P.M. (1989) Taming your office environment, Modern Office Technology 34 :11, 70-72. [3]Kitagawa, K. Komoda, N. Hayano, H. Tanabe, S.-I. (1999) Effect of humidity and small air movement on thermal comfort under a radiant cooling ceiling by subjective experiments, Energy and Buildings 30 :2, 185-193. [4]Antonopoulos, K.A. Vrachopoulos, M. Tzivanidis, C. (1998) Experimental evaluation of energy savings in air-conditioning using metal ceiling panels, Applied Thermal Engineering 18, 1129-1138. [5] International Standard ISO 7730 (1993), Moderate thermal environments Determination of the PMV and PPD indices and specification of the conditions for thermal comfort. [6] Gilles Courret, Peter Egolf, Déshumidificateur pour panneaux de climatisation, request for grant of a European patent n 02405026.2-2301, (priority CH 18-01-2001).