COMMITTEE ON HAZARDOUS CHEMICALS PRE-FIRST DRAFT MEETING MINUTES

Similar documents
Preliminary Agenda Technical Committee on Liquefied Petroleum Gas

Fire Code Action Committee (F-CAC) Meeting Minutes June 19-20, 2012 Chicago IL. Summary of Actions and Regional Work Group (RWG) Assignments

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

TECHNICAL COMMITTEE MEMBERS WHO PARTICIPATED

1. Call to Order. The meeting was called to order at 1:05 PM. (See Enclosure A [Agenda])

Report of the Committee on. Hazardous Chemicals

REPRESENTING. Honolulu Fire Dept., Rep. International Association of Fire Fighters. API/Petroleum Safety Consultants

Pre-First Draft Meeting Technical Committee on Wastewater Treatment Plants On line/conference Call November 20, PM EDT

ERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002

Committee on NFPA 51A

Minutes of the Pre-ROP Meeting of the T/C on Protected Premises Signaling September 22-23, 2010 Indianapolis, IN

Standards and Safety Update

Correlating Committee on Automatic Sprinklers

NFPA Technical Committee on Hybrid (Water and Inert Gas) Fire Extinguishing Systems

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

NFPA 80 Overview January 21, 2016

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

National Fire Protection Association (NFPA) Fire Service Occupational Safety and Health Technical Committee Meeting March 14 15, 2012 San Diego, CA

TECHNICAL COMMITTEE ON FINISHING PROCESSES

TECHNICAL COMMITTEE ON SAFETY AT MOTORSPORTS VENUES. NFPA 610 First Draft Meeting. October 17-18, 2016

2008 NYC Fire Code. New Laboratory Standards. Operational & Maintenance Provisions effective July 2008

NFPA Technical Committee on Fire Tests FALL 2011 ROC MEETING MINUTES

TECHNICAL COMMITTEE MEMBERS PRESENT

Dave Hague NFPA Staff Liaison 12 21,

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

Setting A Standard on Fire Safety in Laboratories

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

SEMICONDUCTOR FABRICATION FACILITIES

Fire Prevention Coffee Break Training. May 2017

TECHNICAL COMMITTEE ON FIRE CODE

CCC 2018 GROUP A PROPOSED CHANGES TO THE I-CODES COLUMBUS COMMITTEE ACTION HEARINGS. April 15 23, 2018 Columbus Convention Center Columbus, Ohio

Report on First Revision June 2014 NFPA 5000

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Hazard Communication Self Inspection Checklist

International Code Council Fire Code Action Committee Group B Topics (Revised February 2, 2015)

Laboratories and Hazardous Materials. Company Overview

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

1. The meeting was called to order by Chair James Lathrop at 8:00 AM (CDT) on Wednesday, August 26, 2015.

STANDARDS RELATED MEETING REPORT

Hydrogen Refueling Code Gap Assessment

Changes for the New Edition. Senior Engineer, NFPA NFPA

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Significant Changes to the 2012 IFC Semiconductor Fabrication Facilities. Scott Stookey Senior Technical Staff International Code Council, Austin TX

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

MEETING AGENDA High Rise Building Safety Advisory Committee

Technical Committee on Liquefied Natural Gas

Report on Comments F2006 Copyright, NFPA NFPA 560 Report of the Committee on

M E M O R A N D U M. NFPA 1 First Draft Technical Committee FINAL Ballot Results (A2017)

FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE COMMITTEE

Understanding and Applying NFPA 25

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

INTRODUCTION. Page 1 of 5

Second Revision No. 5-NFPA [ Section No ] Supplemental Information. Submitter Information Verification. Committee Statement

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

SEMICONDUCTOR FABRICATION FACILITIES

Standard Procedure s for Tenant Fire Sprinkler Work

Introductions made by the Chair, committee members, NFPA Staff Liaison, Jacqueline Wilmot and Dan Gorham of the Fire Protection Research Foundation.

SEMICONDUCTOR FABRICATION FACILITIES

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

NFPA 45 NFPA 211 NFPA 1600

SEMICONDUCTOR FABRICATION FACILITIES

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Technical Committee on Gas Process Safety

First Revision No. 20-NFPA [ Section No ]

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

NIFAD CONFERENCE 2018

University of California, Davis Laboratory Self-Inspection Checklist

NFPA 550 ROP Meeting Minutes

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

DEPARTMENT OF DEFENSE HANDBOOK COVERED STORAGE 1. THE FOLLOWING PAGES OF MIL-HDBK-1032/2 HAVE BEEN REVISED AND SUPERSEDE THE PAGES LISTED:

MINUTES BUILDING BOARD OF REVIEW 1:00 P.M., OCTOBER 1, 2012 Third Floor, Jesse Lowe Conference Room Omaha Civic Center Farnam Street

Subject: BSR Uniform Mechanical Code, 2015 Edition: Appeal on Proposal #333

Committee on 51A M E M O R A N D U M. NFPA Technical Committee on Industrial and Medical Gases

PART 2. Basic Code Requirements - Semiconductor & Microelectronic Facilities using HPM s

2015 International Fire Code

Proposed Changes to NFPA

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

NFPA Talking Points on NFPA 1 Fire Code update to the 2015 Edition:

AS/NZS :2008

Georgia Fire Sprinkler Association

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

AGENDA TECHNICAL COMMITTEE ON CARBON MONOXIDE DETECTION OCTOBER 7, 2010 TELECONFERENCE (10:00 A.M. ET)

Report on First Revisions with Statement June 2014 NFPA 101

Minutes. NFPA Technical Committee on Fire Code. NFPA First Draft Meeting

American Fire Sprinkler Association. An Introduction to the IBC and IFC

Second Revision No. 36-NFPA [ Detail ] Submitter Information Verification. Committee Statement 5/18/2015 1:01 PM

M EM O RA N D UM. NFPA 652 First Draft Correlating Committee FINAL Ballot Results (A2018)

NFPA Fire Inspector I Study Guide

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Section 5.0: HAZARDOUS MATEIRAL STORAGE TABLE OF CONTENTS. A. Regulations, Standards and References 2. B. Scope 3. C. Approvals and Listings 3

2012 International Fire Code Errata (Portions of text and tables not shown are unaffected by the errata)

AS AS Australian Standard. Installation of fire hose reels. This is a free 6 page sample. Access the full version online.

Transcription:

COMMITTEE ON HAZARDOUS CHEMICALS PRE-FIRST DRAFT MEETING MINUTES TO: COMMITTEE ON HAZARDOUS CHEMICALS FROM: Nancy Pearce and Janna Shapiro, Staff Liaison DATE: January 7, 2016 SUBJ: Minutes of NFPA 40 and 400 Pre-First Draft Meeting, December 1-2, 2015, Sheraton San Diego Hotel and Marina, San Diego, CA I. Attendance: (by web and conference call) Members and Alternates: Robert James, Chair, UL LLC, FL Elizabeth Buc, Fire & Materials Research Laboratory, LLC, MI* James Carver, El Segundo Fire Department, CA (representing CA Fire Chiefs Association) Chris Connealy, Texas Department of Insurance, State Fire Marshal, TX Edwin Cope, Cope Engineering, TX* Dirk Der Kinderen, US DOT, PHMSA, DC Mark Dossett, San Diego Fire Rescue Department, CA (representing CA Fire Chiefs Association) Robert Fash, Las Vegas Fire & Rescue, NV (representing Fire Code Committee) Henry Febo, FM Global, MA Marty Gresho, FP2 Fire, Inc., CO Noel Hsu, Orica USA Inc., CO (representing The Fertilizer Institute) Paul Iacobucci, Akzo Nobel, IL (representing SPI/Organic Peroxide Producers Safety) Lynne Kilpatrick, Sunnyvale Department of Public Safety, Fire Marshal, CA Richard Kraus, API/Petroleum Safety Consultants, VA (representing TCC on Flammable and Combustible Liquids) Kevin Kreitman, Albany Fire Department, OR Todd Laberge, Lawrence Berkeley National Laboratory, CA Kathy Landkrohn, Occupational Safety & Health Administration, DC* R. Kenneth Lee, Axiall LLC, AR Patrick McLaughlin, McLaughlin & Associates, ID (representing TC on Industrial, Storage, & Miscellaneous Occupancies) Joyce Miles, ExxonMobil Research & Engineering, TX (representing American Chemistry Council) Kirk Mitchell, Kirk Mitchell & Associates, LLC, FL (representing Isocyanurates Industry Adhoc Committee) Anthony Ordile, Haines Fire & Risk Consulting Corporation, NJ Jerald Pierrottie, Lonza Group, Ltd., GA

Jerrold Sameth, Compressed Gas Association, VA* David Shatzer, Shatzer & Associates Consulting, PA Ronald Thomas, Institute of Makers of Explosives, UT James Vigerust, CB&I, NM (representing the NFPA Industrial Fire Protection Section) Jerry Wallace, Safety Engineering Laboratories, Inc., MI Nancy Pearce, NFPA, Staff Liaison Janna Shapiro, NFPA, Staff Liaison Guests: Heather Heckman, Moving Image Research Collections, University of South Carolina* *Joined meeting remotely II. Minutes of Meeting 1. Welcome. The Chair, Bob James, called the meeting to order at 8:00 a.m., Tuesday, December 1, 2015. The Chair welcomed the members and guests and provided a brief outline of the agenda for the meeting. The Chair invited the members and guests (including those participating remotely) to introduce themselves and identify their affiliations. 2. Minutes. The Committee approved the minutes from August 5-7, 2014 Second Draft Meeting without revision. 3. Task Group Reports. The task groups established at the second draft meeting reported on the status of their work and received feedback and direction from the full Committee regarding how to move forward, as detailed below. a) AN Task Group. Noel Hsu gave a presentation covering topics currently being worked on, including ventilation, AN storage in railcars, TFI identified areas of concern, and less dangerous formulations. The presentation also covered topics for future discussion, including AN incidents and a review of NFPA 400 for consistency of requirements for existing and new structures. See details below. 1) Ventilation. There was confusion regarding which ventilation requirements the task group was proposing to remove, the conditions under which the ventilation requirements are applicable, and how the presented OSHA calculation applies to AN. The task group agreed to provide public inputs for three different situations; ventilation in fire/emergency conditions, ventilation for open storage and handling situations, and ventilation for closed storage and outdoor bin situations. 2) Railcar Storage. Noel raised the questions of: whether this is covered by NFPA 400, and if so how is it applied; whether this a function of storage time; and how it differs from trucks waiting to be unloaded. The Committee agreed that this is covered by NFPA 400. The task group agreed to provide public inputs to clarify that NFPA 400 is applicable, using the requirements in NFPA 30 and NFPA 58 (taken from ARA) as a guide. Further topics to consider in the future may include materials beyond AN, storage in vehicles other than railcars (e.g. trucks), and both indoor and outdoor storage.

3) TFI areas of concern. For existing buildings, the committee agreed that the language in Annex 11.1.5 would be difficult to move into the enforceable part of the text and is in the annex to provide options for the AHJ. For public notification, the task group agreed to come back with recommendations regarding who is responsible for the notification and for paying for it. For sprinklers in noncombustible buildings, it was noted that sprinklers are still required for new Type I and Type II buildings, and that existing Type I and Type II buildings do not require sprinklers unless they have combustible contents or construction. The task group will consider adding annex language to 11.1.5.1 to clarify sprinkler requirements. For signage, there are concerns with the security issues of AN. The task group is considering revising 11.3.2.3.7 to remove the words ammonium nitrate for security purposes and to be consistent with 11.2.16 to address the fire and explosion hazard. For spill coverage, the task group will work on language for the annex to clarify the applications of spill control, particularly that it covers any spillage and not just bag spillage. 4) The task group also agreed to 1) review the CSB West Texas Report when it is available; 2) review code requirements to compare requirements for existing construction and new construction; and 3) look further into less dangerous formulations. b) Chapter 14 Task Group. Paul Iacobucci reported that OPPSD is reviewing calculations, and the task group will look further into this over the next few weeks. There appear to be no major issues. c) Chapter 6 Extracts from NFPA 5000 Task Group. Pat McLaughlin identified 10 items where extract tags from NFPA 5000 either need to be removed or added. He and Lynne Kilpatrick will submit public inputs for these. d) Common Path. Marty Gresho noted that the terms dead end, common path, and total travel distance are covered by NFPA 101, but common path is not addressed by Protection Level 4 occupancies. NFPA 101 does not address health hazard issues. Marty submitted a public input to NFPA 5000 to address common path for all five hazard classifications, and proposes that NFPA 400 extract this information from 5000. There was concern about fully extracting this material, as Protection Level 5 is not included in NFPA 400. Marty will submit a public input to NFPA 400 on this subject. e) NFPA 40 Task Group. Heather Heckman called in to give a presentation on the changes she and the task group plan to propose for Chapters 6 (storage of nitrate film), 7 (handling of nitrate film), and 8 (motion picture projection), as well as a proposed definition for decomposition in the context of NFPA 40, and a global change to replace the term standard roll to 1000 foot roll. The task group will also be considering changes to requirements for flat film once they are able to reach out to the stakeholders in the flat film community. See details below. 1) There was concern with the impact of changing standard roll to 1000 foot roll, particularly with sections that limit the number of rolls rather than the number of feet (for example, section 4.3.1.1). The committee is ok with making the change as long as the task group considers these types of impacts and provides justification if the amounts are changed in these sections. The task group should also confirm that there is no impact on the 35mm width of the standard roll. 2) The task group will work on developing a definition for the term decomposition and submit a public input.

3) In section 6.5.5, there was discussion that changing the number of cans will change the void space on the sides of the cans, and the impact that this might have. It was noted that this might not have a significant impact, since the cubby holes themselves are not being changed. There was a suggestion to have this section limit the number of feet rather than the number of cans (for example, change the limit to 2000 ft instead of two 1000 ft cans). The task group will consider this and will look at the criteria for this section to make sure the proposed revisions are consistent throughout. The suggested revision might also make it so not all cans are able to contact the back wall (Section 6.5.5.4), so additional revisions should be considered to address this. The task group will also propose language to prohibit cans from hanging over the lip of the cubby. 4) The task group will work on language for the proposed changes to Chapter 7 and make sure to include justification for these changes. For example, to match DoT/EPA regulations the task group might propose removing the requirement to store nitrate film under water, and the justification can include a discussion on off-gassing. 5) The task group will develop language for the proposed change to include requirements for temperature and humidity control in section 8.1. Language will also be developed to clarify that openings are protected with a rated shutter (section 8.1.6) and therefore the requirement for the number of openings in section 8.1.5 is irrelevant and can be removed. The committee would like to see any relevant data supporting revisions to section 8.1.9 for the exhaust capacity to be compatible with xenon-bulb projectors. f) Separation Distance Task Group and Research Foundation Report. Ron Thomas gave a presentation to go over the work of the separation distance task group and to bring up some questions/concerns, detailed below. 1) Why is the American table of Distances of Explosives separation distance being used for AN? 2) TNT equivalency may not be appropriate for AN fertilizer grade. 3) Should this task group just be looking at AN or should other materials be addressed (peroxides, oxidizers, etc.)? What parameters should be looked at? (e.g. process to building, process to storage, etc.) 4) Large scale tests for AN are ongoing, and will likely be completed by end of summer 2016. 5) The Research Foundation project on separation distances is not useful to the committee because it is focused on explosives (industrial grade AN). This report might be more useful to the NFPA 495 committee and should be sent to them. The task group agreed that for now they will focus on AN, and will address parameters including process to building, process to storage, storage to storage, and storage to property line. g) Chapter 15 Task Group. Tony Ordile provided an update including the scope of this task group and the topics that this group plans to address. The task group agreed that their scope is limited to inside and outside storage tanks containing hazardous material liquids at atmospheric pressure, with a focus on oxidizers and corrosives for this cycle. See details below. 1) Indoor storage of tanks. The task group does not intend to revise the MAQs for inside storage as the existing MAQ tables are applicable. If the MAQ is exceeded, then the tank(s) need to be located in the appropriate Protection Level cut-off room. 2) Outdoor storage of tanks. The task group does not intend to revise MAQs for outdoor storage to accommodate tanks, but may develop annex material to clarify what becomes applicable when the outdoor storage exceeds the MAQ. The task group believes the tank(s)

can exceed the MAQ as long as spill control and separation are maintained per the Protection Level requirements. 3) Whether protected structures. The task group agreed that if a weather protected structure is provided over an outside tank farm, it shall be in accordance with Section 6.2.7.2. The task group plans to research situations involving tank farms adjacent to a building with a weather protected canopy attached to the building, and will either add or revise text for this situation or provide annex materials on how sections 6.2.7.2, 15.4.2.1, and 15.4.1.3 would be used in conjunction with each other. 4) Closed-Use System. The task group agreed that outdoor storage tanks connected to a process in a building are part of a closed-use system, however the requirements for outdoor storage are applicable to the storage tanks and do not need to be reiterated in the outdoor use section. 5) Other issues to be addressed: - Tanks storing corrosives in Chapter 12 - Spacing between multiple tanks (for oxidizers and corrosives, the distance being considered is 3 feet) - Access aisles around a group of tanks and between the tanks and building or separation walls (considering a 3 foot minimum distance, per section 24.5.6 of NFPA 30) - Minimum clearance between top of tank and ceiling or roof for tanks in a room (considering a 3 foot minimum distance, per section 24.5.7 of NFPA 30) - Requirements for the prevention of overfilling of tanks (revise section 6.3.1.2.4.1 to have similar wording to Section 5003.2.7 of the IFC), including liquid level controls and overfill pipes - Normal venting of tanks and the discharge point of the vents - Prohibiting the manifolding of vent piping - Need for emergency venting of tanks for fire exposure - Allowance of transfer pumps to be located in the same diked area containing the tanks - Requirements for remote filling of indoor tanks from outside tanker vehicles - Requirements for tank storage that could be applicable to all tanks containing hazardous materials to be included in Chapter 6 as fundamental requirements 4. Update on Research Foundation Project Proposals. Tony Ordile and Elizabeth Buc plan to resubmit a proposal on sprinklers for Class 2 oxidizers (previously submitted in November 2014). Paul Iacobucci and the task group will continue to work on a proposal to address the hazard classification of technical and fertilizer grade AN. There was discussion as to whether the focus should be on the possible classification of AN as an unstable reactive per NFPA 400 or if the focus should be determining the conditions under which AN detonates. Proposal will be submitted by end of December. 5. TSD Facilities Report and Status Update. Elizabeth Buc presented the Research Foundation Fire Code Gap Analysis which examined the TSDF fire problem, hazardous waste regulations, and the fire codes that apply to these facilities. The analysis identified two major gaps, including recognition and proper implementation of the fire codes, and classification of hazardous waste. Following Elizabeth s presentation, Janna Shapiro gave a presentation on NFPA s involvement with this issue and informed the committee that the Standard s Council is establishing a task group to determine if fire protection and life safety for TSD facilities should be addressed in NFPA 400 or if a

new standard is needed. The NFPA 400 Committee agreed to form their own task group to examine how hazardous waste is already covered by NFPA 400. Members of this task group will include Elizabeth Buc, Lynne Kilpatrick, Marty Gresho, James Vigerust, Ron Thomas, and Todd Laberge. The work of this task group may change based on the decision of the Standards Council at their April Meeting. 6. TIA for Table 5.2.1.6 and Table 5.3.7. NFPA staff drafted a TIA to correct the Class I and II repetition in table 5.2.1.6 and the extraction error from NFPA 55 in table 5.3.7. Marty Gresho agreed to submit the TIA, and James Vigerust will endorse. 7. Editorial Issues. Nancy Pearce reviewed a number of issues identified by the editorial staff with the full Committee to determine if changes as suggested by editorial staff were needed. See details below. a) Editorial suggested changing Exemptions in section 1.1.2 to Exceptions. The Committee agreed that these items are exempt from the scope of the document, and therefore the term exemptions is appropriate and should be left as is. b) Editorial suggested reorganizing the definitions is section 3.3.19.9 to be in alphabetical order. The Committee noted that these definitions were grouped to flow consecutively, as one builds upon the other. It was pointed out that the numbering for the definitions of tanks, containers, and cylinders do not currently make sense. Tanks are defined differently in NFPA 55 and NFPA 30, and the extracted definitions need to be appropriately separated in NFPA 400. A new task group will be formed to address this. c) Editorial wanted to redo the footnotes for the tables in Chapter 5. One possible suggestion was to make the footnotes the same for every table, and put reserved or not applicable if a certain footnote does not apply to a particular table. Another comment was whether some of the footnotes belong in the body of the text rather than in the footnotes. Another issue that was discussed was the need for so many tables, and whether they could be consolidated. A new task group was formed to look at possibly consolidating the tables and addressing the footnotes. Bob James noted that the occupancy tables were originally intended to solicit input for MAQs from other committees but that this never happened. If the tables were consolidated then the footnote issue would also be resolved. Dirk Der Kinderen volunteered to chair the task group. Others who volunteered to assist include Lynne Kilpatrick, James Carver, and Ed Cope (and possibly Neal Hara from NFPA 1). d) Editorial wanted to include a footnote that the value in the parentheticals in the Chapter 5 tables is in pounds. The committee agreed to add this as a footnote under the N/A and NL footnotes. e) In the heat release rate table, editorial wanted to clarify whether min is minimum or minutes. Committee agreed to clarify that it is minutes. f) In table B.3.2, the committee agreed that under the Examples heading, the text in the heading can be moved to a footnote.

g) Editorial wanted to fix the capitalization of the words in the Annex F tables. The committee decided that these should be left as is. It was also noted that a footnote needs to be added for NE: Not evaluated. h) In Annex J, Table J.1, there are parts that have an HCS definition but nothing under materials classification. These include gases under pressure, skin irritation, and self-heating chemical. It was suggested that a note be added that these definitions are not covered in NFPA 400, and that additional classification may be required. Alternatively, the words not specifically defined could be added. Will ask Kathy Landkrohn to suggest changes and submit public inputs. 8. Other Business. a) Handling. Marty Gresho brought up the need to look at the requirements associated with handling hazardous materials. A new task group will be formed to look at the protection between the point of delivery and the storage location (for example, if hazardous materials are being moved through an unprotected area into a protected storage area), and submit a public input for this. b) Footnote g in Table 5.2.1.1.3. Lynne Kilpatrick reported that in the 2010 edition of NFPA 55, the cabinets for corrosive gases are only required if the MAQ is exceeded. In table 5.2.1.1.3 of NFPA 400, it is required that corrosive gases be confined in cabinets when below the MAQ. Lynne suggests removing footnote g from the table, since currently NFPA 400 has stricter requirements than NFPA 55. It was also noted that in the 2013 edition of NFPA 55, there are other requirements for corrosive gases when below the MAQ that NFPA 400 should possibly incorporate or point to. Lynne will submit a public input, and Jerry Sameth will take this issue to the NFPA 55 committee. c) Cutoff storage. The chapter 14 task group will look at the definitions of cutoff storage and segregated storage for chapters 14 and 15, and will try to mimic what other chapters have done. d) Electrolyte in powered industrial trucks. The committee agreed that acids, gases, and propane tanks on trucks do not count towards the MAQ, and it should be clarified that industrial power trucks are not included in emergency power or uninterrupted power supply. James Vigerust agreed to submit a public input to clarify this. e) Combustible dust. Kevin Kreitman will submit a public input to change the NFPA 400 definition of combustible dust to match that in the combustible dust standards, and will evaluate the necessity of having this in the NFPA 400. f) Annex I: James Carver will look at Annex I to evaluate whether new information needs to be added or if NFPA 472 can simply be referenced. James will submit a public input for this. g) Chapter 11-21 requirements when under MAQ. Currently, there is nothing to clearly point to Chapters 11-21 when under the MAQ, even though some of these chapters contain requirements that apply when below the MAQ. Lynne Kilpatrick agreed to look at section 6.1.1.1 to see if there is a clear way to point users to chapters 11-21 when under the MAQ, and will submit a public input. Lynne and Marty Gresho will also look at the flowcharts in the annex to address this.

h) Extracts. The committee agreed that the extracts in NFPA 400 should be from the most current editions of other codes, including codes that are in the same cycle. i) Handbook/Guidance Material. It was suggested that a handbook should be developed for NFPA 400, however Nancy noted that an annotated version of the code may be more practical while use of NFPA 400 is limited. Tony suggested possibly adding an annex section to address FAQs and to provide guidance for the AHJs on how to navigate NFPA 400. Nancy suggested possibly developing a webinar that provides instruction on how to use NFPA 400. Kevin brought up that the hazardous materials chapters in the Fire and Life Safety Inspection Manual may need to be updated, and that the chapters on hazardous materials in NFPA 1 could possibly be expanded. 9. Next Meeting. The Committee and chair discussed the location and timing for the First Draft Meeting. The preferred location is Park City, possibly at the Newpark Resort. The second choice for location is Jackson Hole. The preferred timing would be the week of September 12 (travel Monday, have meeting Tuesday-Thursday). It was agreed that three days will be needed for the meeting. 10. Adjournment. There being no further business the meeting was adjourned at 12:45 PM on Wednesday, December 2, 2015.