Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

Similar documents
Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

REFRIGERANT PIPING SYSTEM

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Ratio Architects, Inc. Section Refrigerant Piping

SECTION (15530) - REFRIGERANT PIPING

WineZone Ceiling Mount Ductless Split 15

PROJ. NO SECTION REFRIGERANT PIPING

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

SECTION (15530) - REFRIGERANT PIPING

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

REFRIGERANT PIPING

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

INSTALLATION INSTRUCTIONS

Installation Owner Diagnostics

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

Condensing Unit Installation and Operating Instructions

INSTALLATION INSTRUCTIONS

Service Step by Step Trouble-Shooting Check-List

Owner s Manual Therma-Stor II Heat Recovery System

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Horizontal/Side Discharge Condensing Units

Installation Instructions

WKS 2200 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLER'S GUIDE. ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

DESIGN STANDARDS SECTION 15600

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

SERVICING AND BREAKDOWN...

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

EarthLinked HC Series Compressor Unit R-410A Quik-Start Instructions

Installation Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Series 6, Vertical Floor-Mount Units

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

User s Information and Installation Instructions

Condensing Unit Installation and Operating Instructions

INSTALLATION AND OPERATING INSTRUCTIONS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Installation Instructions

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Daikin Direct Expansion (DX) Cooling Coils

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

SECTION AIR COILS

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

SEA FROST BAITFREEZER 110-VOLT AIR-WATER Twin Valve

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

R Series Cooling Manual

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

EarthLinked AVN Series Air Handlers Installation Manual

INSTALLATION INSTRUCTIONS

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Installation Instructions

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

HEATING AND VENTILATION

Installation Instructions

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

RCM Refrigerant Module

INSTALLATION INSTRUCTIONS

ICE AIR Vertical WSHP Technical Manual INSTALLATION

Air Conditioning Operation and Troubleshooting Matt Dunham

Refrigerant Recovery Unit, Model RRU134

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Entry Level Assessment Blueprint Heating, Ventilation and Air Conditioning (HVAC)

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

EarthLinked CC Series Compressor Unit R-410A Quik-Start Instructions

R Series Cooling Modules

SECTION AIR COILS

RPI Industries, Inc.

Series 6, Vertical Floor-Mount Units

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

CENTRAL AIR CONDITIONER SPLIT SYSTEM

INSTALLATION MANUAL R-22/R-407C OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: GCGA SERIES 1.5 TO 6.3 TONS 1 & 3 PHASE LIST OF SECTIONS LIST OF FIGURES

RPI Industries, Inc.

Air Cooled Condenser Installation and Operating Instructions

EarthLinked AFN Series Air Handlers Installation Manual

INSTALLATION INSTRUCTIONS

SWIMMING POOL & SPA HEAT PUMPS OWNERS OPERATIONAL MANUAL

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

The Essentials Of Working With R-410A

Installation Instructions

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INSTALLATION INSTRUCTIONS

Liebert CSU3000 Chiller

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

Transcription:

Ocean Breeze Split System General Installation Manual Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida 34997 Tel: 772 220 0038

Warning: The Air Conditioning Unit is a pressurized system; potential hazards can cause serious injury. DO NOT ignore any warnings in this manual. Warning: It is required that trained and certified professional personnel with experience in the HVAC field to do the installation and service of this system. Warning: Never use Oxygen to pressurize a refrigeration or Air Conditioning System. Oxygen can explode on contact with oil and will cause personal injury. When using nitrogen for this purpose, use a regulation device that can control pressure down to 1 or 2 PSIG.

Pre Installation: Ocean Breeze equipment must be installed by a certified HVAC Technician. Determine installation location for each piece of equipment. Note that each condenser unit will require 2 feet of surrounding space to be free for air flow to and from the unit. Warning: Not allowing sufficient ventilation around the unit will minimize performance, and can cause potential damage to the equipment. Next, locate all needed connections going to the Condenser unit, Electrical box, Condensate Drain, etc. Make certain there is no power to any section of the installation site... Electrical installation must be performed by a license electrical contractor. It is highly recommended to use a UL Approved Outdoor Weatherproof Rated Electrical Panel Enclosure for the Unit Breaker.

Make sure the mounting surface is clean. When installing the Condenser Unit, there must be a minimum clearance to service the Condenser Coil, Electric Box. Lay out the power cables to the unit. Use conduit or seal tight flexible conduit. Lay out the Condensate Drain Piping as close to overboard as possible. If you are reclaiming condensate water run the pipe to the collection area. When the installation of the Condenser Unit Is complete, be sure to clean up the area before continuing to the Evaporator installation. Keep all interconnection pieces sealed until needed to avoid debris deposit in the tubes. If there is more than one condenser unit, repeat the above process.

INSTALLATION: Reserve space for the electrical lines. Lay a clear path for the copper refrigerant lines to and from the Condenser Unit. Mounting the Fan Coil can be done in various ways. If Ceiling Mount, make sure unit is level. Clear paths for copper refrigerant lines and condensate drain line with adequate space around the Fan Coil. If installing Filter, make certain to reserve space for easy access for intake of evaporator. Once again keep the interconnections sealed until brazing the copper refrigerant lines. ELECTRICAL INSTALLATION: Make sure all electricity is powered off to the area before installing the Fan Coil. A dedicated Circuit Breaker should be used for the Fan Coil. Install the power wires and the conduit to the fan coil(s).

When mounting is complete, and electrical connections are made, install the copper refrigerant lines between each of the systems.

Begin installing the soft seamless annealed Copper Tube between each system. Make sure a direct, obstacle free, level route exists. Inspect the run length for potential hazards such as limited space circumference, existing electrical lines, plumbing lines, emergency spaces, temporary object motion that may occupy the planned route for your system lines. Proceed on laying out the copper lines and electric lines to and from each Fan Coil to each Condenser Unit. Before Brazing on a tube end on the unit, prepare the site for high temperature brazing. Remove the seal protection on the Fan Coil. This is the area to start from. Inspect the inside of the tube for any sings of debris. Remove debris carefully by means of small tools, or vacuum. WARNING: Lose Debris in the refrigeration system will cause damage to the System. It is recommended to use same diameter tube that is on each unit. Butt connection with

coupler. Or, use a diameter slightly larger that will accommodate the end pieces. Braze with the standard soft solder blend such as Phosphorous Copper, or any brazing alloys with high tensile strength used for copper welds only. If using Flux for less braze contact time, be extremely careful that no material enters or remain in the system that can pose harm when Power to the system is turned on. Make certain the refrigerant lines are installed as level as possible from point to point. This will prevent damage to the insulation, or the copper tube, while ensuring a steady flow of refrigerant throughout the entire system. NOTE: If the Copper Tube is not set correctly and there are vibrations throughout the system, the action of pipe rubbing in its insulation or any Oscillation within can cause a leak in the copper tube. Be certain the area is clear, and the run of copper tube is secure. When this process is complete, recheck all line runs to and from each unit from each Fan Coil to Each Condenser Unit, inspecting the completed layout carefully for any potential hazards that

may pose a problem in system operation. If laying duct work, inspect surrounding space and allow ducting to be flat and straight as possible from point to point. Use UL Approved Ducting. After all of the installation process is complete, including correct connection of copper refrigerant lines, proper electrical connections, and condensate drain lines, ducting, return, proceed to the layout test.

Testing Procedure. The layout test will prove the installation is successful or if corrections need to be made. Test each wire from point to point which will provide added assurance that all the electrical connection is correct. For Single Phase, Common, Neutral and Ground are used. Note: Wiring in Common and Neutral (Single phase) can be interchangeable; however, not recommended. Wiring in 3 Phase, must be absolute: (L1 to L1, L2 to L2, L3 to L3, Ground to Ground and so forth) If Voltage Phase Monitor is installed in AC equipment, check settings (480 Volt, 240 Volt, etc). A water test in the condensate line system will prove the drain line will evacuate the water safely to its destination whether reclamation, sump, or overboard. The drain should be constructed to have a dip and an air pilot tube to maintain flow throughout.

The final test will be the refrigerant line pressure test. One method is low pressure at 175 PSI Nitrogen, a few ounces of refrigerant, and leak detection hardware. Another method is only with high pressure Nitrogen. High pressure method is used at the factory up to 600 PSI Nitrogen for One Hour with thermo graphic tools, point sensors, visual inspection (safety pressure impact attire must be worn on this test). On the field, the low pressure test is preferred. For low pressure and visual inspection, liquid detergent soap can be used to check for bubbles on all joints. If there are bubbles, a leak has been discovered. If a leak has been identified on a joint, use soft solder to seal it.

Open all Service Valves before charging. When using the low pressure testing method, the process must be done carefully and the inspection must be made at every connection point. If all the tests are satisfactory, proceed to final stages of installation. If there are any problems, correct each problem and test each solution, reinspect all problem points to make certain the correction has been made and successful. Repeat the above testing procedures on the entire system. When all tests are complete and there are absolutely no issues, installation has been complete. Clean up the work areas, and apply weather seals from both sides of throughways for lines. Condenser Tubes do not need insulation; However, it is recommended to insulate the suction line (cold line, or low side line, or liquid line) with Polyolefine-foam with a closed cellular structure insulation, such as thermaflex or other UL Approved brands. Apply to a section, or the entire length of copper line. Insulate both lines if

required, and then group the lines together with plastic wire ties. WARNING: Copper Lines must not touch each other. Direct interacting thermodynamic properties from contact between discharge line and suction line will render the cooling system inoperative. After Leak Test, relieve all the pressure in the system. If only Nitrogen was used evacuate into the air by removing the stem valve from the connection port. If you have not installed a stem valve, disconnect the hose carefully. High pressure Nitrogen is in the system and will forcefully evacuate, posing a danger to the installer (an impact of flying hose at such high pressure can cause injury) If the Low Pressure method was used, recover the refrigerant with vacuum pump. Allow time for the recovery process (20 minutes per ton) to complete. The vacuum scale should be up to 30 HG negative pressure at sea level. When ready to Power the system on for the first time, the installer must charge the system with refrigerant.

The Low Pressure Switch may have to be bypassed for this process as the compressor will most likely be shut down due to low pressure. The Thermostat will also need to be bypassed for the unit to maintain functioning until the charging process is complete. When charging the unit, the installer will meter refrigerant, check electrical characteristics, measure air temperatures, all in combination of the specified scales for this system. There is a Sight Glass installed on the unit to verify moisture in the system. If there are unrelated problems encountered, the installer is asked to contact Ocean Breeze at 772 220 0038 for available assistance to complete the installation.

When everything is functioning within operating parameters, and the critical charge has been reached, the process is complete and the Installer can Power off the system, reconnect the bypassed components, and retest the system for normal use.

Re-test the system; allow the user to operate the system to become familiar with the equipment and performance characteristics. Maintenance: Routine Maintenance of the unit is important for the performance longevity of the system. Inspect the Condensate Drain Lines, clean if necessary. Inspect the return Air Intake into each fan coil. Vacuum for dust. Inspect the discharge of the fan coil, clean areas that connect to Ducting, or, if free blowing into the room, clean the internal blower wheel. Clean every discharge vent with vacuum. Clean Digital Control with cloth. Lightly spray sanitizer solution onto the cloth, allow solution to absorb, and then wipe the face of each control. If necessary, the control panel can be quick disconnected from the wall plate by pulling the face straight out from the base. NOTE: The AC system will not function when the Thermostat Control is not present.

Batteries can be changed when control has been disconnected from the wall plate. Replace only with fresh Alkaline Batteries (Duracell, Energizer, etc). Maintenance will keep your equipment in continue working condition for many years of use. For any questions, please contact Ocean Breeze at 772 220 0038.

Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida 34997 Tel: 772 2200038 obr@oceanbreezeac.com http://www.oceanbreezeac.com