SAMPLE FIRE SAFETY PLAN. ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba. Prepared by: John Smith Last reviewed: Bill Jones 2014

Similar documents
FIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe

FIRE SAFETY PLAN For Commercial Use

FIRE SAFETY PLAN. ARTLab Fort Garry 180 Dafoe Road Winnipeg, MANITOBA. February / Prepared by: Francisco Fernandez

Fire Safety Plan FOR. Business/Property Name: Address: Phone Number: Occupancy Classification. Approved by Fire Inspector: Date:

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

Winnipeg Fire Department Fire Prevention Branch

FIRE SAFETY PLAN Revised December

FIRE EVACUATION PLAN

University of Maryland FIRE EVACUATION PLAN

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

Emergency Evacuation Plan. Tiffany Tower Plot W2 Jumeirah Lakes Towers

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

Emergency Planning and Preparedness

University of Maryland FIRE EVACUATION PLAN NATIONAL DENTAL MUSEUM POLICE FIRE MEDICAL EMERGENCY Anyone discovering excessive heat,

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

Grossmont Cuyamaca Community College District Fire Report 2014

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

St. Vincent s Health System Page 1 of 6

Date Issued: December 14, 2017 Revision: 2.1

Mulch fires, trash can fires, or other fire outside a building should be reported by the following methods:

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

FIRE EVACUATION PLAN PRATT STREET PARKING GARAGE AND ATHLETIC CENTER POLICE FIRE MEDICAL EMERGENCY

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

Name of Establishment 123 Anywhere Street Anytown, Ontario A1A-1A1 Approved By:

WINNIPEG FIRE PARAMEDIC SERVICE FIRE PREVENTION BRANCH

FIRE SAFETY PRACTICES AND PROCEDURES

British Columbia Institute of Technology. BCIT Safety Manual FIRE SAFETY

Business License Pre-inspection Checklist

NYU RESIDENTIAL FIRE SAFETY PLAN PART I - BUILDING INFORMATION SECTION

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Fire Prevention and Procedures Policy

FINLEY HALL EMERGENCY EVACUATION PLAN

Fire Evacuation Plan Davidge Hall. UMB POLICE or

FIRE SAFETY POLICY. 2.0 Under national, provincial and municipal fire regulations, the Board will ensure compliance with:

St. John s University Fire Safety Plan

University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911

Housing & Residence Life - Building Emergency Evacuation Plan

FIRE SAFETY MANAGEMENT PLANS DEVELOPMENT GUIDE A GUIDE TO DEVELOPING

FIRE PROCEDURES 1. APPOINTMENTS

Fire Safety Plan (Single-Stage Fire Alarm System):

St. John s University

Grossmont Cuyamaca Community College District Fire Report 2012

St. John s University Fire Safety Plan

EVACUATION PLAN Solvang Retirement 1202 Jacobs Drive Eugene, OR 97402

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or

Mount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION

Purpose of Emergency Response Program Emergency Response Team / Leader Evacuation Procedures Building Life Safety System Virtual Evacuation Building

FIRE SAFETY PLAN PART 1 BUILDING INFORMATION SECTION

Guideline. Fire Safety Plan

Fire Inspection & Prevention Initiative. Fire Safety Plan Documentation Guide. Part 3 (of 3) Format Guide Edition. (December 5, 2014)

Property Name & Address [ Property Name ] - [ Property Address ]

Osceola County Department of Fire Rescue and Emergency Medical Services

Woodvale Pentecostal Church

Fire Prevention Plan for Alter Hall 3743 Ledgewood Drive

Emergency Response Team Plan. Shoal Island Office

This regulation outlines procedures to be followed for fire drills and all school event decorations.

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

Principal s Guide for Fire Safety Planning in Schools. To be kept in School Administration Office

Dutchess Community College. Emergency Action Plan. Conklin Hall College Residence

Department of Biological Sciences National University of Singapore. 4. Procedures: ACTIONS TO BE TAKEN IN THE EVENT OF FIRE DURING OFFICE HOURS

Fire Evacuation Plan Bressler Research Building. UMB POLICE or

Agency for Health Care Administration

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

Take your keys, coat, and any important information with you.

COUNTY OF SACRAMENTO DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PERMITS & INSPECTION DIVISION

FIRE SAFETY FOR OFFICE WORKERS

FIRE EMERGENCY POLICY

Fire Safety Plan (Single-Stage Fire Alarm System)

JL Office Tower Emergency Action Plan

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Fire Drill Policy. Facilities Manager DCD. Statutory. Principal. Staff. REVIEW DATE 20 th August Owner. Version Number: 8 Legal Sign:

Fire Emergency Response Procedure

Fire Safety Plan (No Fire Alarm System):

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

Standard Operating Procedure Ottawa Fire Services. Fire Operations- Structural Fire Incidents SUBJECT. Fire Alarm Systems (Silence/Reset) - Revised

BCIT FIRE SAFETY PROGRAM

Fire Safety: At Home & At Work. Volunteer Annual Review 2017

Fire Safety Plan Training 2017

The blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno.

Building Emergency Policies and Procedures

DUKE CLINIC SITE-SPECIFIC FIRE PLAN Part II General Statement. Fire Procedures

HEAD, CLARA & MARIA FIRE SAFETY PLAN

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Fire Safety Plan Information. For Construction and Demolition Sites

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Lullaboo Nursery and Childcare Center Brampton Campus Queen street west, Brampton, Ontario, L6X-0B2

Annual Fire Safety Report Icahn School of Medicine at Mount Sinai Aron Hall September, 2016

FIRE SAFETY POLICY and FIRE SAFETY ARRANGMENTS

Workplace Safety North

Meagan Ray, RN Safety Director

FIRE & EVACUATION PLAN PARADISE LOST

Fire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

FIRE SAFETY PLAN FOR NAME OF BUSINESS (IF APPLICABLE) STREET ADDRESS CITY, PROVINCE POSTAL CODE BUILDING USE # OF UNITS

Fire Safety & Evacuation Plan

St. John s University

Transcription:

SAMPLE FIRE SAFETY PLAN ABC Manufacturing Ltd. 123 Main Street Steinbach, Manitoba Prepared by: John Smith 2011 Last reviewed: Bill Jones 2014 Page 1 of 19

Table of Contents 1. Building Information 2. Fire Protection Systems 3. Floor Plans 4. Human Resources 5. General Responsibilities 6. Designated Responsibilities 7. Instructions to Occupants 8. Inspection, Testing & Maintenance Schedule Page 2 of 19

1. Building Information General Description Building Area: 20,000 sq.ft. Construction Date: 1985 Basic Construction: Wood Frame, single storey Building Use: Manufacturing of Latex products Service Locations Electrical Room location(s): Mechanical Room location(s): Storage Room location(s): Laundry Room locations(s): Basement, Northwest corner Basement, Northwest corner Main Floor, South wing Main Floor, next to offices Basement, next to washrooms Main floor next to mechanical room Hazard Locations Janitor s room, Main floor end of hall Beside north overhead door, forklift battery charging station Used oil storage, Exterior near garbage bin Page 3 of 19

2. Fire Protection Systems Fire Department Access Nearest Fire Hydrant(s): Corner of First Street & Broadway Avenue Corner of Fifth Avenue & Second Street Fire Lane: Driveway on north side of building to be kept clear and maintained. Crawlspace Access: In north wing mechanical room Roof Access: In north wing mechanical room Concealed space Access: Loft access door located in meeting room. Extrusion room ceiling space access NE corner of room Lockbox: Next to Main Entrance, East side contains Master Key Alarm Panel Key Pull Station Key Mechanical Room Key Emergency Power Make/Model: Gen-o-matic 3000 Generator Location: North mechanical room Fuel Tank Location: Outside of north mechanical room Generator serves: Emergency systems only Basic lighting Emergency lighting Elevator Sump pumps Fire Alarm Emergency Lighting Manufacturer: Service Agency: Fire Alarm System Manufacturer: Service Agency: Main Panel Location: Annunciator Panels: Emergency Light Company Good Guys Electric Bill Melater (204)-555-5624 Alarms, Alarms, Alarms Sound the Alarm Ltd. B.Ping (204)777-7654 Main Entrance, East side North entrance West entrance Page 4 of 19

Special Extinguishing Systems Kitchen Suppression System Location: Servicing Agency: Halon system Location: Service Agency: Cafeteria Kitchen Supply Company Johnny Smith (204) 325-6666 Server Room XYZ Fire Protection Less Oxygen Automatic Sprinkler System Sprinkler Tree Location: North Mechanical Room Servicing Agency: FireOut Inc R.U.Whett (204)564-5640 Page 5 of 19

3. Floor Plans Page 6 of 19

4. Human Resources Call List: Otto Matic (204) 555-5568 John Q. Public (204) 555-1234 John Guy (204) 555-1111 Building Owner: TGMD Group John Guy Phone: 1 (204) 555-1111 General Manager: John Q. Public 1 (204) 555-1234 Building Security: Safe Security Hans Cuft 1 (204) 555-7654 Building Engineer: Otto Matic 1 (204) 555-5568 Fire Marshal Building Fire Marshall 1 st Floor Fire Marshall 2 nd Floor Fire Marshall 3 rd Floor O.O. Notigan I.M.Safe B.A.Friend Willie Run Page 7 of 19

5. General Responsibilities Responsibility of the Owner To ensure that the building and facilities comply with the provisions of the Manitoba Fire Code To prepare a Fire Safety Plan in accordance with the requirements of the Manitoba Fire Code. To provide alternate measures for the safety of occupants during a shutdown of fire protection equipment. To post and maintain a copy of the fire emergency procedures on each floor area. Responsibilities of Supervisory Staff Be trained in fire emergency procedures described in the Fire Safety Plan before they are given any responsibility for fire safety, Be in charge of the approved Fire Safety Plan and the specific responsibilities of the personnel (the plan should specify the responsibilities of given to individuals). Designate and train sufficient assistants to act in positions whenever and wherever an absence may Educate and train all building personnel and pccipants in the use of the existing fire safety equipment, and in the actions to be taken according to the Fire Safety Plan. Ensure that the provisions of the approved Fire Safety Plan are adhered to, updated and maintained a minimum, annually. Any fire safety procedures which apply to them shall be distributed to the occupants. Ensure that procedures are put in place in the event that a fire protection system is temporarily shut down, (fire watch, notify alarm company, etc.) In the event of any shutdown of fire protection equipment or part thereof, the Steinbach Fire Department and building occupants must be notified. Responsibilities of Building Occupants. To be familiar with o Evacuation procedures as outlined in the Fire Safety Plan or as posted. o The location of the fire alarm system manual pull stations. o The location of exits. o The location of fire hose cabinets, fire extinguishers and other fire protection systems. o The correct address of the building. To reduce the potential of fires in the building by: Page 8 of 19

o Not permitting combustible materials to accumulate in and around the building. o Be aware of dangerous sources of ignition o Report maintenance issues regarding fire and life safety equipment. o Report inoperable or blocked exit doors. o Report propped open fire doors. o Ensure all exit routes are kept clear of obstructions. o Ensure all fire lanes are kept clear. Page 9 of 19

6. Designated Responsibilities Fire Marshall for floor the fire is discovered Ensure that the alarm system has been activated Call 911 to ensure that the Fire Department has been dispatched. Floor Fire Marshalls (general) Ensures all fire codes and company safety regulations are maintained in their section. Ensures that all personnel in their section are trained in emergency procedures and have access to the company Fire Safety Plan. If applicable, ensures that provisions have been made to assists those on their section requiring help in the event of an evacuating. In the case of an emergency Sweeps their section (if it is safe to do so) to ensure all personnel has evacuated. Assembles all personnel from their section at the Muster Point and takes attendance. Reports attendance results to the Building Fire Marshall. Building Engineer Ensures ongoing maintenance and inspection of equipment Ensures that all maintenance records and inspection logs are maintained. In case of an emergency Goes to the main Fire Alarm panel and ensures the panel is not silenced or reset. Assists the Fire Department as required. Building Security Meets Fire Department upon their arrival and assists the Fire Department in any way they can. Building Fire Marshall Ensures all fire codes and company safety regulations are maintained throughout the building. Ensures that all personnel throughout the building are trained in emergency procedures and have access to the company Fire Safety Plan. If applicable, ensures that provisions have been made to assists those requiring help in the event of an evacuating. In the case of an emergency Meets the Fire Department at the designated location and give a brief incident report to the Fire Command. Page 10 of 19

7. Instructions to Occupants In the event of discovering a fire occupants will: Remain calm, Leave the area, Close & latch all doors behind you (DO NOT LOCK THE DOORS), If not already activated, activate the fire alarm using a pull station to notify all building occupants, Telephone the Steinbach Fire Department, DIAL 9-1-1. Know and give the correct building address, Use the exit stairwells to leave the building immediately, DO NOT USE ELEVATORS. They may fail to operate if power is lost. Proceed to the designated Muster Point, Report what information you have regarding the fire to your designated Fire Marshall, Do not return until it has been declared safe to do so by the Steinbach Fire Department. In the event the fire alarms sound occupants will: Leave the area, Close & latch all doors behind you (DO NOT LOCK THE DOORS), If not already activated, activate the fire alarm using a pull station to notify all building occupants, Use the exit stairwells to leave the building immediately, DO NOT USE ELEVATORS. They may fail to operate if power is lost, Proceed to the designated Muster Point, Do not return until it has been declared safe to do so by the Steinbach Fire Department. Page 11 of 19

8. Inspection, Testing & Maintenance Schedule The list in this section is designed to help identify the required inspections & tests for various systems in your building. It is the responsibility of the building owner to ensure that all requirements of the Manitoba Fire Code are met. Definitions Check Visual observation to ensure the device or system is in place an is not obviously damaged or obstructed. Inspect Physical examination to determine that the device or system will apparently perform in accordance with its intended function. Test Operation of device or system to determine that it will perform in accordance with its intended operation or function. The Manitoba Fire Code requires that inspection, test and maintenance records be kept for a period of 2 years but it is recommended that all records be kept. Page 12 of 19

EMERGENCY LIGHT UNIT MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE LOCATION OR ID# OF POWER PACK TESTED TEST TYPE DIP SWITCH POWER FAIL ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 Main entrance #356 X N/A KT FEBRUARY 02/16/15 Coffee Room #246 X Changed bulb KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER Annual Test Date: Done by: Page 13 of 19

INTRUSION ALARM MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE AUTOMATIC DIALING SYSTEM PASS FAIL ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 X N/A KT FEBRUARY 02/16/15 X N/A KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER Annual Test Date: Done by: Page 14 of 19

FIRE ALARM MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE LOCATION OR ID# OF PULL STATION TESTED CONDITION PASS FAIL ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 Reception X N/A KT FEBRUARY 02/16/15 Coffee Room X N/A KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER 02/06/15 Alarms. Alarms, Alarms Annual Test Date: Done by: Page 15 of 19

ILLUMINATED EXIT SIGN MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE CONDITION BACK-UP ILLUMINATION PASS FAIL YES NO ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 X X N/A KT FEBRUARY 02/16/15 X X N/A KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER Annual Test Date: Done by: Page 16 of 19

FIRE DAMPER MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE JANUARY 01/15/15 FEBRUARY 02/16/15 LOCATION OR ID# OF FIRE DAMPER TESTED Mech.Room SA duct Mech.Room RA duct CONDITION ACTION TAKEN/COMMENTS INITIALS PASS FAIL X N/A KT X N/A KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER Annual Test Date: Done by: Page 17 of 19

FIRE EXTINGUISHER MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE CONDITION PASS FAIL ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 X N/A KT FEBRUARY 02/16/15 X Mech. Room Extinguisher recharged KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER 01/22/15 XYZ Fire Protection Annual Test Date: Done by: Page 18 of 19

SMOKE ALARM MAINTENANCE LOG ABC MANUFACTURING LIMITED Year: 2015 123 Main Street Steinbach MB MONTH DATE LOCATION OR ID# OF SMOKE ALARM TESTED CONDITION PASS FAIL ACTION TAKEN/COMMENTS INITIALS JANUARY 01/15/15 #3-15 X N/A KT FEBRUARY 02/16/15 #2-01 X N/A KT MARCH APRIL MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER DECEMBER 02/06/15 Alarms. Alarms, Alarms Annual Test Date: Done by: Page 19 of 19