EXPERIENCES ON THE SPECIFICATION OF ALGORITHMS FOR FIRE AND SMOKE CONTROL IN ROAD TUNNELS

Similar documents
Experiences on using closed-loop control systems for smoke control

Safety Inspections of Road Tunnels.

Impact of quick incident detection on safety in terms of ventilation response

Road tunnel safety rules in Italy: the tunnel country

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

THE AUTOMATION OF THE VENTILATION RESPONSE IN THE CASE OF A FIRE IN A TUNNEL

USING A REAL TIME SIMULATOR IN A LARGE AND COMPLEX ROAD TUNNEL FOR TIME AND COST SAVINGS

AN INNOVATIVE EXPERT SYSTEM FOR REAL TIME SAFETY MANAGEMENT OF ROAD TUNNELS (ESIMAS)

The Use of Public Address System to Improve Tunnel Safety - Current Practices. Lim Hock Tay

Sprinklers Modeling for Tunnel Road Fire Fighting

OVERCOMING EVACUATION LIMITATIONS OF THE UČKA TUNNEL BY IMPROVEMENT OF FIRE SAFETY MEASURES

AUTOMATIC FIRE EXTINGUISHING and VISUAL GUIDE SYSTEMS for TUNNEL PROTECTION

FIRE RESISTANCE OF ROLLING STOCK ELEMENTS STANDARD AND SPECIAL CASE OF TUNNELS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

This document is a preview generated by EVS

Tunnels, Risks & Design Mitigation

SYSTEMS, INFRASTRUCTURE OR USERS? WHICH IS THE BEST INVESTMENT TO IMPROVE TUNNEL SAFETY?

EUROPEAN BUREAU. EuroTAP European Tunnel Assessment Programme

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

This document is a preview generated by EVS

Fire Protection and Safety in Tunnels Conference Opening Remarks. Dr Fathi Tarada Secretary, PIARC Tunnel Operations Committee

Appendix SPAIN Madrid M30-Río-TUNNEL

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

English version. Management Centre: Avenue Marnix 17, B Brussels

This document is a preview generated by EVS

VENTILATION AND SUPPRESSION SYSTEMS IN ROAD TUNNELS: SOME ISSUES REGARDING THEIR APPROPRIATE USE IN A FIRE EMERGENCY

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Thermal Comfort with Convective and Radiant Cooling Systems

2 nd European Forum of Road Tunnel Safety Officers

FIXED FIRE FIGHTING SYSTEMS IN TUNNELS INTEGRATION AND COMPENSATION

Eurocode 9 Design of aluminium structures

EMERGENCY VENTILATION FOR SMOKE CONTROL IN ROADWAY TUNNELS (NCHRP PROJECT TASK 363)

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Full-scale Experiment of Longitudinal Ventilation Smoke Control System and Central Smoke Exhaust System in City Underwater Tunnel

Appendix AUSTRIA Vienna Kaisermühlentunnel

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

ILNAS-EN 61649:2008. Weibull analysis. Analyse de Weibull. Weibull-Analyse

PHASED CONSTRUCTION AND SAFETY IN MALA KAPELA TUNNEL

SIGNALISATION AND VISUAL GUIDE INTERACTIVE SYSTEM for EVACUATION ROUTES in TUNNELS and CONFINED AREAS

COMMISSION REGULATION (EU)

Optimisation of ventilation systems costs by using fixed fire fighting systems (FFFS) in tunnels

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

THE NECESSITY OF FIRE TESTS USING THE PASSÜR TUNNEL AS AN EXAMPLE

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

English Version. This Technical Report was approved by CEN on 11 December It has been drawn up by the Technical Committee CEN/TC 135.

National foreword. Compliance with a British Standard cannot confer immunity from legal obligations.

Petralba tunnel: A case of success

This document is a preview generated by EVS

National foreword. Text affected

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

Aspirating Gas Detection CFD Modelling Predicts Application Performance

ON THE SAFETY OF SHORT ROAD TUNNELS

AUTOMATIC FIRE EXTINGUISHING SYSTEM for TUNNEL PROTECTION with SPREAD REMOTE CONTROLLED MONITORS (TUDEM-LEGIO)

EXPERIENCE WITH THE SAFETY AND VENTILATION DESIGN IN OPERATION OF THE PLABUTSCH TUNNEL

Numerical Simulation of Fluid Flow and Heat Transfer in a Water Heater

LIGHTING APPLICATIONS - TUNNEL LIGHTING IRISH STANDARD I.S. CR 14380: Price Code. Údarás um Chaighdeáin Náisiúnta na héireann

This document is a preview generated by EVS

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh

This document is a preview generated by EVS

Automated Fire Detection and Suppression in a Retrofitted Tunnel Using Fiber-Optic Linear Heat Detection

EVACUATION MODELLING IN ROAD TUNNEL FIRES

Assessment of the variable speed limits. Ruben Corthout Chris M.J. Tampère

This document is a preview generated by EVS


Machines and plants for the manufacture, treatment and processing of flat glass Safety requirements Part 11: Drilling machines

Smoke and heat control systems Part 3: Specification for powered smoke and heat exhaust ventilators

The first tunnel fire. Benefits of fire

Comparison and Review of Safety Design Guidelines for Road Tunnels

COMPENSATORY EFFECTY OF FIXED FIRE FIGHTING SYSTEMS IN TUNNELS

CLEANROOMS AND ASSOCIATED

Fire classification of construction products and building elements

English version. OPC unified architecture - Part 1: Overview and concepts (IEC/TR :2010)

1 Development and state of the art in road tunnel ventilation technology

Seminar on Standardisation in Research and Innovation Practical tools for the dissemination and implementation of research results

Experimental tests for geosynthetics anchorage trenches

This document is a preview generated by EVS

This document is a preview generated by EVS

ISO/TR TECHNICAL REPORT. Fire-safety engineering Technical information on methods for evaluating behaviour and movement of people

This document is a preview generated by EVS

HOW TO REDUCE ENERGY CONSUMPTION OF BUILT-IN REFRIGERATORS?

1. PIARC Update 2. Tunnel System

Fire protection of emergency electrical devices: effect on the level of risk a case study of a rail tunnel

Fixed Fire Fighting Systems for Road and Rail Tunnels

Tunnel Axial Flow Fan

Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

SOUTH AFRICAN NATIONAL STANDARD

COPYRIGHT Danish Standards. NOT FOR COMMERCIAL USE OR REPRODUCTION. DS/EN 12149:1998

This document is a preview generated by EVS

This document is a preview generated by EVS

ICS ; Supersedes CEN ISO/TS :2005. English Version

This document is a preview generated by EVS

Fire and Smoke Management in a Uni-Directional Road Tunnel for a Congested Traffic Condition

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

Tunnel Fire Dynamics and Evacuation Simulations

This document is a preview generated by EVS

The Mont Blanc tunnel project. Eric CESMAT, Sylvain DESANGHERE

Tokyo-wan Aqualine - Experience of Traffic and Safety

Safety Instrumented Systems

Workshop Bridge and Tunnel Safety and Security

Transcription:

- 39 - EXPERIENCES ON THE SPECIFICATION OF ALGORITHMS FOR FIRE AND SMOKE CONTROL IN ROAD TUNNELS Espinosa, I.*; Fernández, S.*; Del Rey, I. + ; Alarcón, E. 2+ * FFII - CEMIM. Madrid. Spain. + ETSII-Universidad Politécnica de Madrid. Madrid. Spain. ABSTRACT The main objective of ventilation systems in case of fire is the reduction of the possible consequences by achieving the best possible conditions for the evacuation of the users and the intervention of the emergency services. The required immediate transition, from normal to emergency functioning of the ventilation equipments, is being strengthened by the use of automatic and semi-automatic control systems, what reduces the response times through the help to the operators, and the use of pre-defined strategies. A further step consists on the use of closed-loop algorithms, which takes into account not only the initial conditions but their development (air velocity, traffic situation, etc), optimizing smoke control capacity. Key Words: Ventilation, fire safety, smoke control. 1. INTRODUCTION The transposition of the European Directive 2004/54/CE (1) to the Spanish regulation was finalized with the publication, in 2006, of the RD 635/2006 (2) on minimum safety requirements for road tunnels. One of the key aspects included in these two regulations is the necessity, in most of the tunnels, of automatic ventilation control systems, both in normal operation and fire case. The main requirements to be achieved by the use of control systems are the reduction in the response time for ventilation activation and the implementation of predefined strategies both for manual and automatic response of fire safety facilities. However, when trying to establish the criteria for the specification of predefined ventilation strategies, various aspects must be taken into account which depends on the type of ventilation system and traffic operation conditions previous to the incident development. Even, in some cases, an appropriate management of fire incidents requires complex multi-step strategies that must be predefined and implemented in the control systems. 2. BACKGROUND During the last decades, a great amount of resources have employed for the study and development of ventilation control systems during normal operation, which included the use of closed loop algorithms and fuzzy logic for the optimization and improvement of the efficiency (CETU, ref. 3). However, during the last years, the reduction of the emission levels of the vehicles is reducing the efforts involved in the development of new technologies and methods for the control of the ventilation during normal operation. On the opposite, ventilation control in case of fire is becoming of the utmost importance. Going to the past, the PIARC report on Fire and Smoke control in Road tunnels (ref. 4) in 1999 already reflected the importance, and lack of unique rules, on the use of active control systems for the operation of ventilation.

- 40 - From then, several national guidelines have included recommendations on the operation of ventilation systems in incident cases: Austria (RVS 09.03.31) (ref. 5), Germany (RABT) (ref. 6), France (Circulaire Interministérielle 20-63 dated 20th August 2000) (ref. 7) or Switzerland (FEDRO) (ref. 8). One common aspect to all of these references is the distinction between the self evacuation phase and the fire fighting phase, and the importance of the longitudinal control of the air velocity in the tunnel, with no dependence on the type of mechanical ventilation system installed, to achieve the desired goals for smoke control. Taking into account these criteria, different contributions can be found in the literature in what concern to practical application of automatic control system use in road tunnels: Pospisil et all (ref. 9), Wehner et all (ref. 10), Stroppa (ref. 11) or Bettelini et al. (ref. 12). With the intention of describing some practical experiences in Spain, in the following, the authors describe in detail the criteria and algorithms developed and implemented for the automatic control of ventilation in road tunnels. It is important to note that the criteria and tools are mainly focused on the evacuation phase, even if some considerations are made on the general approach. In addition, some results from the evaluation tests are presented as far as the authors consider that the whole process: design, implementation, test and adjustment is crucial to evaluate the reasonable performance of ventilation control system. 3. VENTILATION STRATEGIES IN CASE OF FIRE Ventilation strategies to be used in case of fire are usually dependant to the operational configuration (unidirectional or bidirectional traffic) and the traffic conditions (free flow or standstill). In case of tunnels with unidirectional traffic without congestion, a high velocity longitudinal ventilation strategy is the one most widely adopted, which consists in the generation of a longitudinal air flow in the vicinity of the fire, in the sense of the traffic flow, enough to avoid the back layering of the smoke. Figure 1: Ventilation strategy for unidirectional free flow traffic In case of unidirectional tubes with traffic congestion, a two-stages longitudinal ventilation strategy is commonly recommended which would consist in the generation of a low velocity longitudinal air flow until the vehicles stopped downstream the fire has left the tunnel. In a second stage, a high velocity longitudinal strategy would be desirable as far as no vehicles, or users, should be situated in the route invaded by the smoke (portal, intermediate exhaust point, etc). 1 2 1 2 Figure 2: Two stages longitudinal strategy for unidirectional congested traffic For bidirectional tunnels the two strategies explained before are not longer valid, as far as there will probably be vehicles at both sides of the fire location, what would recommend to adopt ventilation strategies focused on maintaining so long as possible the stratification conditions of the smoke, what is favored by the smoke extraction (if possible), the switch off of the fans that can cause turbulence, and the reduction of the air velocity inside the tunnel.

- 41 - Figure 3: Stratification strategy for bidirectional traffic 4. CHALLENGES FOR DESIGN OF VENTILATION CONTROL SYSTEMS Consequently, it is of the outmost importance to handle the quick transition from normal operation to the emergency mode, which includes from the point of view of the ventilation system, the following steps: 1. Normal operation 2. Automatic incident detection 3. Ventilation safety response 4. Location and validation of the fire 5. Predefined ventilation response plan 6. Follow-up and correction (if necessary) 7. Emergency service strategy 8. Return to normal operation All these stages must be implemented in accordance to the general emergency response plans so, coherence between the different equipments activation can be guaranteed. However, when accomplishing the design phase, even if all the steps are clearly defined into specifications documents, some practical details must be taking into account to reduce the incidence of mistakes. It has been considered interesting to describe some of them: o Reception of multiple automatic alarms: once an incident occurs, the great amount of alarms that are received from the different equipments installed in the tunnel can interfere in the activities of the operator. For example, in the case of the AID (Automatic Incident Detection) system, the queue formation upwind the traffic stop point generates multiple alarms in areas far from the fire situation. o Excessive demand of information from the operator: when designing the interface human-computer application, the excessive request of information must be avoided and, if totally necessary, priority criteria must be established. o User failure protection: even if sometimes it is not possible to guarantee that the actions taken by the operator are correct, a great amount of mistakes can be avoided without complex means (for example, the use of double confirmation messages for fire alarm cancellation as are used in standard applications) o Exhaustive and permanent training: as far as, fortunately, fire situations are not common during the operation of the tunnel, it is necessary that the operators can receive permanent training in the management of the application, general concepts, expected behavior, practical cases, etc. In some tunnels, very good experiences are being obtained with the use of training simulators, where the use of the graphic interface screens for fire situation can be used reducing the surprise of the operator to new situations. It is important to note that the development of these applications require clear criteria, detailed specifications, considerable implementation efforts and rigorous test procedures, what in practice means time and economic provisions to be considered. 5. PRACTICAL EXAMPLES The tunnel of study has two independent unidirectional traffic tubes of about 2000 meters length. The proximity of an urban area produces a highly unbalanced traffic distribution what causes standstills in the morning and evening commuting times.

- 42 - The ventilation system is longitudinal with jet fans uniformly distributed through the tunnel, although according to the new Spanish regulation in the close future the tunnel will be refurbished and the ventilation system modified. For the detection phase, an automatic algorithm has been implemented which consider (through a weighting procedure) the signal coming from different types of sensors (fire detectors, quick changes in the measures of CO and turbidity sensors or alarms generated by the DAI) to propose the operator a most probable fire location. The result of the algorithm is to provide him, for each section a detection index, ranging from 0 (no alarms) to 100 (all alarms). Depending on the detection index value for any of the sections, different predefined procedures can be activated (pre-alarm mode), i.e. stop of the ventilation in both tubes to avoid the de-stratification of the smoke during the early stages, starting of a pre-defined number of jets, etc. In addition, a closed loop air velocity control algorithm has been implemented with the objective of maintaining the control on the longitudinal air flow what should facilitate the users evacuation. The two main parameters taken into account by the algorithm are the air velocity inside the tunnel and the target air velocity. For the case study presented, the air velocity in the fire location is calculated as the average of the values given at every instant by some representative anemometers (not all the installed anemometers should be used because some of their measures can be influenced by the jet fans flow or the smoke layer around the fire). The implemented algorithm follows a predictive - corrective logic, based on the average air velocity in the tunnel and the trend shown during the control intervals. Both magnitudes are evaluated at the end of each control periods by a linear adjustment to try to avoid the random temporal fluctuations (see red line in the decision figure). The algorithm estimates the value of the velocity expected (V est ) to occur at the end of the time interval and the slope of the linear regression curve (m). Finally, from the values obtained for the control variables, the decision on the number of jet fans to be connected is taken based on pre-programmed charts with predetermine actuations (see next table) which depends on the velocity estimated comparison to the reference interval and the sign of the slope of the linear regression (m). Differential Velocidad corregida velocity (Vreal-Vobjetivo) (Vmeasured Vreference) (positiva en sentido possitive del tráfico) in the traffic flow Vest > Vref +V ref Vest = Vref Vest>0 Vest < Vref V=0 Vest = 0 Vest=0 Vest < Vref -Vref Vest = Vref Vest<0 Vest > Vref m>0 m=0 m<0 Observed tendencia tendency real medida (by en measurement) la velocidad Desired tendencia tendency deseada (from en la velocidad analysis) Figure 4: Scheme of the close-loop logic applied

- 43 - An additional tool has been implemented in the control system to evaluate the traffic conditions in the downstream area based on the information gained from the AID system. Due to the reduced reliability of the information provided by the cameras in case of fire, it was decided that this system only provides a proposal to the operator about the traffic situation during the emergency which is responsible to modify the reference velocity for the activation of the automatic control system. 6. CONCLUSIONS The research on ventilation control methodologies and algorithms, for application into road tunnels, is focusing more and more on fire situation instead of normal operation. This fact is being reflected in the national and international regulations and guidelines. However additional research and development efforts seem to be necessary to improve the design, specification, implementation and testing of ventilation control systems. 7. REFERENCES [1] EUROPEAN UNION, Directive 2004/54/EC of the European Parliament and of the Council on minimum safety requirements for tunnels in the Trans-European Road Network, Brussels, 2004. [2] Real Decreto 635/2006 sobre requisitos mínimos de seguridad en la red de carreteras del estado. BOE 27 de mayo de 2006. [3] Marsault, M-N., Apvrille, J-M., Martin, J-C. Contrôle Comande de la Ventilation. Experimentation Logique Floue. Rapport. Centre d'etudes des Tunnels (CETU), 2001. [4] PIARC TECHNICAL COMMITTEE ON TUNNEL OPERATIONS. Fire and Smoke Control in Road Tunnels, reference 05.05.B, PIARC, Paris, 1999. [5] RVS 09.02.31, "Tunnelausruestung, Belueftung Grundlagen", Oesterreichische Forschungsgesellschaft Straße, Schiene und Verkehr, Karlsgasse 5, Vienna, Austria, 2008. [6] RABT, Richtlinien für die Ausstattung und den Betrieb von Straßentunnel. Forschungsgesellschaft für das Straßen und Verkehrswesen. Germany, ISBN 3-937356- 87-8, 2006. [7] CETU, Instruction technique annexe a la Circulaire 2000-63, CETU, Bron, France, 2000 [French and English]. [8] FEDRO, Ventilation of road tunnels, Switzerland, 2004 with amendment July 2006 [German and French], 2004/2006. [9] Pospisil, P., Brandt, R. Smoke control in road tunnels. Conference Significance of Tunnels in Transport, 16-18 June 2005, Podbanské (Slowakia). [10] Wehner, M., Brandt, R., Simon, I. Optimal smoke extraction by controlling the longitudinal flow velocity using a punctual air supply or extraction. Fifth Intnal Conf. on Tunnel Fires and Escape from Tunnels, October 2004, London (U.K.). [11] Stroppa, W. Practical experience in ventilation design for longitudinal and semi transverse ventilation systems. 2nd Symp on Tunnel Safety and Ventilation, April 2004, Graz (Austria). [12] Bettelini, M., Brandt, R., Riess, I. Progress in Tunnel Ventilation-The Mont Blanc Tunnel. AITES-ITA 2001 World Tunnel Congress, 10-13 June 2001, Milano (Italy).