Residential Split System Air Conditioners and Heat Pumps Using R-22 Refrigerant

Similar documents
Residential Piping and Long Line Guideline

LONG LINE SET APPLICATION R-410A

Air Conditioners and Heat Pumps Using R-22 Refrigerant

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

Product Data PA13NA PA13PA FEATURES AND BENEFITS

Product Data. 24AHA4 Performance Series Air Conditioner with Puron Refrigerant 1-1/2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS

APPLICATION DATA SHEET

Product Data INDUSTRY LEADING FEATURES / BENEFITS. BH13NA SINGLE -STAGE HEAT PUMP WITH PURONr REFRIGERANT. Efficiency S S Reliability S

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

application guideline and service manual AIR CONDITIONERS AND HEAT PUMPS USING PURON REFRIGERANT

Product Data. 224ANS PREFERREDt SERIES HEAT PUMP WITH PURONr REFRIGERANT 1-1/2 TO 5 NOMINAL TONS INDUSTRY LEADING FEATURES / BENEFITS

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

Installation Instructions

Installation Instructions

Installation, Start-Up and Service Instructions

Product Data. 38EYX 50Hz Heat Pump With R---410a Refrigerant Single and Three Phase 2To5Tons FEATURES AND BENEFITS AVAILABLE SIZES:

Product Data PA13 AIR CONDITIONER 1 AND 3 PHASE 1-1/2-5 TONS ( ) FEATURES AND BENEFITS AVAILABLE SIZES:

R4H4. Product Specifications

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

WCH5**4. Product Specifications

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Nominal Capacity /2Ton 024 2Tons /2Tons 036 3Tons /2Tons 048 4Ton 060 5Ton

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

R4H4. Product Specifications

N4A6. Product Specifications

Installation Instructions

Installation Instructions

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

Product Data. 38CKD (60 Hz) 13 SEER Air Conditioner Sizes FEATURES AND BENEFITS AVAILABLE SIZES:

Installation Instructions

Wiring Diagrams. 38ARZ ARS ARD Air-Cooled Condensing Units 50/60 Hz

Product Data. 38CKC (60 Hz) 10 SEER Air Conditioner EXPORT MODELS. Sizes 018 thru 060 FEATURES

Product Data. 38CKS (60 Hz) 10 SEER Air Conditioner EXPORT MODELS. Sizes 018 thru 060 AVAILABLE OPTIONS

Installation, Start-Up and Service Instructions

N4H4. Product Specifications

Product Data. 25HCB6 Performancet Stage Heat Pump with Puronr Refrigerant 2to5Tons INDUSTRY LEADING FEATURES / BENEFITS.

Installation Instructions

Duct Free Systems Product Data Digest ¾ to 5 Nominal Tons

Product Data. CA13NA Base Series Air Conditioner with Puronr Refrigerant INDUSTRY LEADING FEATURES / BENEFITS.

Product Data. 24ABC6 Comfortt16 Air Conditioner with Puronr Refrigerant /2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS

Product Data. 38YCC 50 Hz Heat Pump. Sizes 024 thru 060 FEATURES/BENEFITS

Product Data INDUSTRY LEADING FEATURES / BENEFITS MODEL 126B PREFERRED SERIES AIR CONDITIONER WITH PURON REFRIGERANT 1 1/2 TO 5 NOMINAL TONS

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

SPLIT-SYSTEM HEAT PUMP UNIT. Model PH12 SS-PH12-11 FEATURES

R 410A Ducted Horizontal Air Conditioner

Advance Product Data

A 14 SEER Heat Pump with R---410A Refrigerant Series

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

Product Data INDUSTRY LEADING FEATURES / BENEFITS

Product Data. 38CKC 50 Hz Air Conditioner. Sizes 018 thru 060 FEATURES

14 AC x

Product Data INDUSTRY LEADING FEATURES / BENEFITS. 116B Legacyt Line 16 Air Conditioner with Puronr Refrigerant 1-1/2 to 5 Nominal Tons

Installation Instructions

AIR-COOLED CONDENSING UNIT UNITS PRODUCED AFTER JANUARY, 1996 INDEX SCHEMATIC DIAGRAM FIG. NO.

Product Data CF5A COILS KMABA BLOWERS. For Manufactured Homes THE CF5A INDOOR COIL

Condensing Unit Installation and Operating Instructions

4HP15L PRODUCT SPECIFICATIONS HIGH EFFICIENCY SPLIT HEAT PUMP SYSTEM UP TO 15 SEER & 9.0 HSPF COILS COMPONENTS COMPRESSOR WARRANTY CABINET DESIGN

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S

38GHP AIR-COOLED MULTI SPLIT CONDENSING UNITS

14HPX MERIT SERIES R 410A H E A T P U M P O U T D O O R U N I T S

Installation, Start-Up and Service Instructions

Commercial High-Efficiency Condensing Units

Installation Instructions

Installation Instructions

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 18,000 to 60,000 Btuh AIR CONDITIONERS ML14XC1 PRODUCT SPECIFICATIONS

Model PA10 ELECTRIC AIR CONDITIONER SS-PA10-06 FEATURES. coated for a long-lasting, rustresistant,

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Product Data. 38TXA (60 Hz) Air Conditioner with Puron (R-410A) Sizes 024 thru 060

Product Data. Efficiency

2 shp 13 lc 1 36 t - 1 a

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

PACKAGE AIR CONDITIONER

Product Data. 38QRR Performancet Series Heat Pump with Puronr Refrigerant /2 to 5 Nominal Tons INDUSTRY LEADING FEATURES / BENEFITS

Installation Instructions

Product Data. 38CKC (60 Hz) 10 SEER Air Conditioner. Sizes 018 thru 060 FEATURES

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Wiring Diagrams. 9AB4-12 Air-Cooled Remote Condenser INDEX OPERATING SEQUENCE ACCESSORIES LEGEND AND NOTES FOR FIG. 1-6

Product Data. Features/Benefits. 28CB, 28LA Direct-Expansion. evaporator coils. 7 1 / 2 and 10 Nominal Tons Cooling

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

13HPD MERIT SERIES R 22 H E A T P U M P O U T D O O R U N I T S

Commercial High-Efficiency Condensing Units

Installation Instructions

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

Advance Product Data

Installation Instruction

INDUSTRY LEADING FEATURES 2 5 / BENEFITS

Service Step by Step Trouble-Shooting Check-List

T-Class AC and HP Units Up to SEER and 9.0 HSPF. Commercial Air Conditioners and Heat Pumps. True performance and rugged durability

Product Data. Efficiency. S S Reliability

The Centurion Rooftop GAS/ELECTRIC, TONS ELECTRIC/ELECTRIC, TONS

Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

User s Information and Installation Instructions

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Installation Instructions

10 SEER SPLIT-SYSTEM HEAT PUMP UNIT. Model PH10 SS-PH10-05 FEATURES

User s Information and Installation Instructions

Advance Product Data

MERIT Series R-410A. SEER up to HSPF up to to 5 Tons Cooling Capacity - 18,000 to 61,000 Btuh Heating Capacity - 17,500 to 58,500 Btuh

Transcription:

Residential Split System Air Conditioners and Heat Pumps Using R-22 Refrigerant Visit www.carrier.com Residential Split System Long-Line Application Guideline NOTE: Read the entire instruction manual before starting any system modification. This symbol indicates a change since last issue. INDEX SECTION 1 APPROVED SYSTEMS...1 SECTION 2 REQUIRED FIELD-INSTALLED ACCESSORIES...1-2 SECTION 3 INTERCONNECTING TUBING SIZING...2 SECTION 4 METERING DEVICE SIZING...2-4 SECTION 5 LIQUID-LINE SOLENOID APPLICATIONS AND TUBING CONFIGURATION...4 SECTION 6 CHARGING INFORMATION...4 This Long-Line Application Guideline applies to all Carrier residential air conditioner and heat pump split systems that have a nominal capacity of 18,000 to 60,000 Btuh. This guideline provides required system changes and accessories necessary for any residential product having piping requirements greater than 50 ft or installations where indoor unit is located above outdoor unit. This guideline is intended to cover applications outside the standard Installation Instructions. NOTE: The presale literature for outdoor unit must be referred to in conjunction with this guideline. This guideline is for standard single-speed products. For applications involving 2-speed products, refer to their respective Installation Instructions. SECTION 1 APPROVED SYSTEMS Any residential indoor/outdoor unit combination listed in the outdoor unit presale literature is an approved system, EXCEPT the following: Indoor coils with capillary metering devices All equipment less than nominal 18,000 Btuh All 1/4-in. liquid line applications Any indoor furnace coil/fan coil not listed in outdoor unit presale literature Any application which has interconnecting tubing with an equivalent length greater than 175 ft SECTION 2 REQUIRED FIELD-INSTALLED ACCESSORIES Step 1 General Some required field-installed accessories may be standard features on certain outdoor units. Refer to outdoor unit presale literature. The following accessories may or may not be required depending on application: Compressor crankcase heater Liquid-line filter drier Start components, start capacitor and relay Liquid-line solenoid or hard shutoff thermostatic expansion valve (TXV) Outdoor unit cycle protector (5 minute) Wind baffles Step 2 Accessory Explanations CRANKCASE HEATER Due to the increased system charge level of a long-line application, a crankcase heater must be installed. Since system charge level is greater than a normal application, refrigerant migration during off-cycle is a greater risk. LIQUID-LINE FILTER DRIER Long-line applications consist of many field-fabricated joints. Due to the increased risk of system contamination, an adequately sized liquid-line filter drier must be installed. START COMPONENTS Start components required for this guideline consist of a start capacitor and relay. Refer to outdoor unit presale literature for correct accessory kit. The presale literature indicates if a start capacitor and relay is a standard feature. Start components are required due to increased charge level and application of the liquid-line solenoid or hard shutoff TXV. When a liquid-line solenoid or hard shutoff TXV is applied to system, the unit must have the ability to start against a higher liquid pressure. (See Section 5.) During off-cycle, the solenoid or hard shutoff TXV closes, trapping high pressure liquid in liquid line. At next on-cycle, the start components provide extra starting torque to overcome the higher liquid pressure. The only outdoor units that do not require start components in any application are 3-phase units. LIQUID-LINE SOLENOID The liquid-line solenoid is required to minimize off-cycle refrigerant migration. Migration is more apparent in long-line applications due to increased charge level and indoor and outdoor units being installed at different elevations. There are 2 types of liquid-line solenoids: single flow and bi-flow. Section 5 covers particular applications, as well as accessory part numbers. The accessory solenoid part numbers are provided in outdoor unit presale literature. HARD SHUTOFF TXV A hard shutoff TXV may be substituted for a liquid-line solenoid in some applications. (See Section 5.) There are 2 types of hard shutoff TXVs: single flow for air conditioners and bi-flow for heat pumps. Accessory TXVs should be sized to the nominal tonnage of outdoor unit. Refer to outdoor unit presale literature for accessory TXV part numbers. OUTDOOR UNIT CYCLE PROTECTOR (5 MINUTE) The cycle protector is an optional accessory, but highly recommended. The purpose of cycle protection is to protect the compressor from short cycling and to ensure a longer run cycle. Long-line applications are frequently installed in apartments and condominiums where short cycles may occur due to equipment oversizing, tenants, and/or load swings. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 1 2 PC 101 Catalog No. 513-890 Printed in U.S.A. Form 38-16XA Pg 1 9-97 Replaces: 38-11XA Tab 3a 5a 1a

If system on-cycle is too short, the cycle may not be long enough to ensure oil return. The cycle protector ensures that if a short cycle occurs, the next on-cycle will be increased. This is due to the load increasing during the 5-minute off-cycle. Refer to outdoor unit presale literature for accessory 5 minute cycle protector part number. WIND BAFFLES The use of wind baffles is required if strong prevailing winds are apparent at installation site. Strong prevailing winds reduce the ability of a heat pump to defrost. Rooftop installations are most likely to experience strong prevailing winds. Wind baffles are usually applied on low-ambient kit installations. Refer to specified unit low-ambient kit instruction for detailed information on wind baffle construction. SECTION 3 INTERCONNECTING TUBING SIZING Table 1 lists recommended interconnecting vapor line diameters for equivalent total line lengths. All residential split systems installed in long-line applications must use only 3/8-in. liquid lines. Equivalent line length equals the linear length (measured) of interconnecting vapor tubing plus losses due to elbows. (See Table 2 and Fig. 1.) Liquid lines larger than 3/8-in. OD greatly increase charge quantity of the system. Excessive charge increases risk of migration and compressor damage. Table 1 provides the estimated percentage of nominal cooling capacity losses based on the standard required vapor line size versus what is selected for the long-line application. Since the vapor line is the discharge line in heating mode, losses are minimal. Calculate the linear length of vapor tube required, adding any losses for the total number of elbows for application. (See Table 2.) Using this equivalent length, select desired vapor line size from Table 1. Subtract the nominal percentage loss from outdoor unit presale literature Detailed Cooling Capacities data for the given indoor/outdoor combination. Reference all notes of Table 1. NOTE: When specifying vapor line insulation, be aware of the following standard practice: All standard accessory tubing kits are supplied with 3/8-in. insulation on vapor line. UNIT NOMINAL SIZE (BTUH) 18,000 24,000 30,000 36,000 42,000 48,000 60,000 For minimal capacity loss in long-line application, 1/2-in. insulation should be specified. For reference only, the close cell insulation material specified for accessory tubing kits is a compound of vinyl, neoprene, or nitrile blends of these polymers. Performance requirements include thermal range of 0 F to 200 F (-17.8 C to 93 C) and a maximum thermal conductivity of 0.28. NOTE: Special consideration must be given to isolating interconnecting tubing from building structure. Isolate tubing so that vibration or noise is not transmitted into structure. SECTION 4 METERING DEVICE SIZING The metering device for a long-line application must be flexible enough to compensate for frictional losses due to long refrigerant lines and installed system design (indoor coil above or below outdoor unit.) The piston or TXV provides such flexibility. The piston should be changed for both indoor coil and outdoor heat pump unit, depending on system configuration and line length. Tables 3 and 4 provide necessary changes for a given application. Use Tables 3 and 4 when selecting correct piston size. Outdoor unit presale literature must be consulted to determine metering devices specified for standard applications. After determining standard application piston size(s), refer to Tables 3 and 4 as they relate to system design (outdoor unit above or below indoor unit) per equivalent length of tubing. NOTE: If total equivalent horizontal length is 100 ft or longer, both indoor and outdoor pistons must be increased 1 full piston size, in addition to changes required by Tables 3 and 4. After finding appropriate change in piston size, add or subtract the change from original piston number. If piston size in decreased, round new piston number down to nearest common piston number found in Table 5. If piston size is increased, round new piston number up to nearest common piston number found in Table 5. Table 1 Estimated Percentage of Nominal Cooling Capacity Losses* LONG-LINE VAPOR LINE EQUIVALENT LINE LENGTH (FT) DIAMETER (IN.) 50 75 100 125 150 175 5/8 5 7 9 12 12 14 3/4 1 3 4 5 5 7 5/8 6 9 13 16 19 22 3/4 0 1 1 2 3 4 5/8 6 8 10 13 15 17 3/4 2 3 4 5 6 7 3/4 7 10 14 17 21 NR 7/8 2 4 6 8 10 11 3/4 7 10 13 17 20 23 7/8 3 4 6 7 8 10 1-1/8 0 0 1 1 2 2 3/4 10 14 18 22 NR NR 7/8 4 6 7 9 11 13 1-1/8 0 0 1 1 2 2 7/8 7 9 11 14 16 19 1-1/8 1 2 2 3 3 4 * The estimated percentage of cooling capacity that must be subtracted from the Detailed Cooling Capacities data specified in outdoor unit presale literature for any given indoor/ outdoor combination. Vapor line diameter that may be selected for a long-line application. If smaller vapor lines are selected but not specified within the table, large capacity losses will occur and defrost capabilities will be reduced. If larger vapor lines are selected but not specified within the table, refrigerant oil return will be impaired due to velocity losses. N/R Not recommended due to excessive loss of capacity. 2

90 STD A Table 3 Calculation of Indoor Piston No. OUTDOOR UNIT ABOVE INDOOR FT PISTON CHANGE 0 25 0 26 50-3 51 75-5 76 100-7 101 125-9 126 150-10 OUTDOOR UNIT BELOW INDOOR FT PISTON CHANGE 0 25 0 26 50 +4 90 LONG RAD B C EXAMPLE: An 042 size heat pump is 75 ft above an 042 size fan coil. The 042 size heat pump presale literature specifies a size 80 indoor piston and size 63 outdoor piston. To establish correct indoor piston size for a 75 ft vertical separation, refer to Table 3. For a 75 ft equivalent line length, the piston change is -5. Therefore subtract 5 from the original indoor piston size of 80: 80-5 = 75 Table 5 provides common piston sizes. In this instance, 75 is not listed, therefore round DOWN to next piston size, which would be 74. To establish correct outdoor piston size for a 75 ft vertical separation, refer to Table 4. For a 75 ft equivalent line length, the piston change is +4. Therefore add 4 to the original outdoor piston size of 63: 63 + 4 = 67 Since 67 is listed in Table 5, that is the piston which should be used. If a 67 size piston were not listed, it would be necessary to round UP to next piston size. 45 STD Fig. 1 Tube Bend Losses Table 2 Fitting Losses in Equivalent Ft TUBE SIZE OD REFERENCE DIAGRAM IN FIG. 1 (IN.) A B C 5/8 1.6 1.0 0.8 3/4 1.8 1.2 0.9 7/8 2.0 1.4 1.0 1-1/8 2.6 1.7 1.3 A92498 TXVs may be used instead of pistons for indoor metering devices. Some fan coils are equipped with a hard shutoff bi-flow TXV standard, and no change is required. When sizing an accessory TXV for long-line applications, TXV should be the same nominal tonnage as outdoor unit. Refer to presale literature for kit part numbers. Table 4 Calculation of Outdoor Piston No. OUTDOOR UNIT ABOVE INDOOR FT PISTON CHANGE 0 50 0 51 75 +4 76 100 +6 101 125 +8 126 150 +10 OUTDOOR UNIT BELOW INDOOR FT PISTON CHANGE 0 50 0 3

Table 5 Common Piston Sizes ACCURATER CHATLEFF ACCURATER CHATLEFF 32 65 65 33 67 67 35 35 68 36 70 70 37 71 38 38 73 73 39 74 40 40 76 76 41 78 78 42 42 80 80 43 81 45 82 82 46 84 84 47 86 86 49 49 88 88 51 51 89 52 52 90 90 53 92 55 55 93 93 57 57 96 96 59 59 98 98 61 61 101 101 62 104 104 63 63 109 SECTION 5 LIQUID-LINE SOLENOID AND TUBING CONFIGURATION As noted in Section 2, there are 2 types of liquid-line solenoids: 1 for single-flow applications and the other for bi-flow applications. The purpose of having 2 solenoids is to minimize the valves internal pressure drop in accordance with refrigerant flow direction. The bi-flow solenoid is designed to have minimal refrigerant pressure drop in either flow direction, which makes it suitable for heat pump usage. Refer to Table 6 for liquid-line solenoid kit part numbers. NOTE: When installing a liquid-line solenoid, the system may require a minimum 60-va low-voltage transformer. Each type of solenoid has an indicator flow arrow stamped on the valve body. When solenoid is closed (not energized) and pressure is applied in direction of flow arrow, complete shutoff occurs. If Table 6 Liquid-Line Solenoid Kit Part Numbers TYPE OF VALVE Single Flow Bi-Flow PART NO. KAALS0101LLS KHALS0101LLS pressure is applied against direction of flow arrow, leakage through valve occurs. When determining proper installation of valve within liquid line, 2 considerations must be made: 1. Direction of flow arrow 2. Where solenoid is installed in system. TXVs can only be substituted for liquid-line solenoids in singleflow air conditioning systems. Bi-flow TXVs allow liquid migration to coldest point during off cycles which could allow liquid into compressor. Fig. 2 through 5 detail proper installation of liquid-line solenoid and provide applications where TXVs may be substituted. Reference all notes of the appropriate figures. SECTION 6 CHARGING INFORMATION Weigh in appropriate refrigerant charge, then use the standard practices of superheat charging method for piston applications and subcooling charging method for TXV applications to confirm correct charge. The standard charging methods can be found on outdoor unit information plate, in unit Installation Instructions, or in the Service Manual. Since total system charge is increased for long-line application, it may be necessary to calculate the additional refrigerant charge. Since long-line applications only involve 3/8-in. liquid lines, the additional refrigerant charge required is 0.6 oz of Refrigerant 22 (R-22) per ft of 3/8-in. liquid line over 15 ft. EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/ft =6ozofadditional charge The rating plate charge of a given outdoor unit is for a standard application of 15 ft of interconnecting tubing. The rating plate charge can be found on outdoor unit rating plate or in outdoor unit presale literature. Long-line applications do not require additional oil charge. 4

175' MAX. GROUND LEVEL BASEMENT A90074 A liquid-line (single-flow) solenoid or hard shutoff TXV must be installed at indoor unit. The solenoid must be within 2 ft of indoor unit with flow arrow pointing toward indoor unit. Vapor line should slope toward indoor unit. The above requirements provide refrigerant migration protection during off-cycle due to temperature or slight elevation differences between indoor and outdoor units. Maximum equivalent line length is 175 ft between indoor and outdoor units. Fig. 2 Application with Air Conditioner Installed in a Horizontal Configuration 5

175' MAX. GROUND LEVEL BASEMENT A90075 A liquid-line solenoid must be installed within 2 ft of outdoor unit with flow arrow pointing toward outdoor unit. Vapor line should slope toward indoor unit. The above requirements provide refrigerant migration protection during off-cycle due to temperature or slight elevation differences between indoor and outdoor units. Maximum equivalent total line length is 175 ft between indoor and outdoor units. Fig. 3 Application with Heat Pump Installed in a Horizontal Configuration 6

TRAP 50' MAX. HEAT PUMP ONLY GROUND LEVEL A90076 Heat pump A liquid-line (bi-flow) solenoid must be installed within 2 ft of outdoor unit with flow arrow pointing toward outdoor unit. Air conditioner No solenoid required. An inverted vapor line trap must be installed at indoor unit. The top peak of trap must be greater than height of indoor coil. The above requirements provide protection against condensed refrigerant collecting in vapor line and maintain a solid liquid line during off-cycle. Maximum elevation between units is 50 ft. Maximum equivalent total line length is 175 ft. Fig. 4 Application with Air Conditioner or Heat Pump Installed with Indoor Unit Above Outdoor Unit 7

HEAT PUMP ONLY 150' MAX. A90077 Heat pump A liquid-line (bi-flow) solenoid must be installed within 2 ft of outdoor unit. Air conditioner No solenoid is required. The above requirements provide protection against refrigerant migration to compressor when outdoor temperature is lower than indoor temperature. Maximum elevation between units is 150 ft. Maximum equivalent total line length is 175 ft. Fig. 5 Application with Air Conditioner or Heat Pump Installed Above Indoor Unit Copyright 1997 CARRIER Corp. 7310 W. Morris St. Indianapolis, IN 46231 3816xa Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 1 2 PC 101 Catalog No. 513-890 Printed in U.S.A. Form 38-16XA Pg 8 9-97 Replaces: 38-11XA Tab 3a 5a 1a