DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System

Similar documents
Series 4302 & FILE NO: 43d.12 DATE: June 1, 2004 SUPERSEDES: 43d.12 DATE: July 15, dualarm Vertical In-Line Pumps

dualarm Vertical In-Line Pumps

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

VSA SEWAGE PUMP. Capacities to 1600 gpm, Heads to 120, Horsepower range 3/4 thru 40, 3 thru 6 discharge, 1750 and 1150 operation.

FEATURES. Other Fed-Flush Arrangements

Instantaneous Water Heaters (IWH)

Vent-Rite. Cast Iron And Steel Receivers. Simplex, Duplex, Triplex And Quadruplex Units. Pump Capacities To 150 GPM. Discharge Pressure To 75 PSI

Domestic. Pump Series CB and CBE Condensate Units SINGLE OR DUPLEX 1,000 THRU 140,000 SQ. FT. EDR-250 THRU 34,748 LB./HR.

Astro Express 2 - Hot Water Delivery System

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

6800 Design Envelope Booster. Technical overview

TECHNICAL. Series 18. Pump Packages

SECTION PLUMBING EQUIPMENT

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION STEAM CONDENSATE PUMPS

Installation and operating instructions. E.2 Series high efficiency circulator

POULTRY MARKET CATALOG

BuildingName The Description of the Project P DOCUMENTS

SECTION PLUMBING EQUIPMENT Piping (Plumbing). 2. Division 16 - Electrical Wiring and Connections.

E.2 series high efficiency circulator. Installation and operating instructions

MARLOW PUMPS RECIRCULATION

SECTION FIRE PUMP AND CONTROLS

SECTION STEAM CONDENSATE PUMPS

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

Wilo IL Vertical Split-Coupled Inline Pumps

Direct Fired Heater Model AD Specification

.2 Section Waste Management and Disposal..5 Section Motors, Drives and Guards for Mechanical Systems.

Electric Pumps. Introduction. W4100, W4200 & W4300 Condensate Pumps. Typical Condensate Pump Features

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

FLANGE-MOUNT CENTRIFUGAL PUMPS

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

1900 Series In-Line Pump

Astro 2 circulator models. Installation and operating instructions

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

YOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE.

Hoffman Specialty Pump Products

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

VERTICAL FAN COIL UNITS

Taco 00 Series Cartridge Circulators

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

5. CONDENSATE PUMPS/UNITS

Submersible Pumps. Series BERS

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Condensate Boiler Feed Water Make-Up

SECTION FIRE PUMPS 1.00 PART 1 & GENERAL Description of Work. A. Provide pumps for fire suppression Section Includes

AIRPORT PLUMBING DESIGN STANDARDS REV. 2 11/02/2015

Flow Control for Fire Protection

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

INDIRECT FIRED, SEMI-INSTANTANEOUS STEAM & BOILER WATER HEATER. Compact Design. High Recovery. Energy Efficient. Stainless Alloy Construction

ECONOBOOST EB II & EB III Compact Water Booster

Flow Control for Fire Protection

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

AM-14/AM-14C DISHWASHERS

PACKAGED AIR COOLED Product Data Catalog

DNJ SERIES PUMPS END SUCTION CLOSE COUPLED

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent

SECTION STEAM CONDENSATE PUMPS

GIRTON CABINET WASHER MODEL 794A

SECTION DOMESTIC WATER PIPING SPECIALTIES

AccuBrine automated brine maker Technical Specifications

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton

Commercial, Residential & Institutional Pumps, Tanks, & Accessories

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

.2 Section Waste Management and Disposal.

GIANT. Little. Guidelines for Sizing. Pump Company. Sewage Pumps & Systems. Sewage Pumps & Systems

Direct Gas-Fired Make-Up Air

INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT

SYSTEM DESIGN REQUIREMENTS

4VH and 4VHX. 4" Non-Clog Wastewater Pumps Standard (4VH) and Explosion-Proof (4VHX) Construction

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

SECTION PACKAGED HEAT TRANSFER SYSTEM

Indirect Gas-Fired Make-Up Air

Domestic Pump Condensate Transfer Equipment

Wastewater. Guidelines for Sizing mscdirect.com. Call MSC today to learn about the latest LittleGiant products.

DUPLEX CONDENSATE TANK SYSTEM

AIRPORT PLUMBING DESIGN STANDARDS REV. 3 3/18/2016

Industrial. Solutions brands you trust. Product Overview

DIVISION FINNED WATER-TUBE WATER HEATERS

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

.03 ATMOSPHERIC DEAERATOR

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

SERIES: WT SELF-PRIMING CENTRIFUGAL PUMPS

Domestic Pump Series VCMD TM Combination Vacuum & Boiler Feed Unit

N N O V A T I O N E F F I C I E N C Y Q U A L I T Y

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

Pumps SELECTION OF A PUMP

GRUNDFOS PLUMBING & HVAC PRODUCTS

End-Suction Centrifugal Pump

End-Suction Centrifugal Pump

Full-line Product Overview

Transcription:

DualPak Series 6900 FILE NO: 62.11 DATE: Feb. 15, 1999 SUPERSEDES: 62.11 DATE: Sept. 28, 1995 DualPak 6900 Series Booster System

D U A L P A K 6 9 0 0 Armstrong proudly presents the Series 6900 DualPak Booster. Offering the highest GPM per square foot of floorspace, Armstrong s DualPak is the most compact duplex domestic water booster system available today! FEATURES Fits through a standard 30" doorway. Less than half the footprint of conventional horizontal systems. Lightweight design allows for ceiling suspension of unit. Armstrong single source responsibility. Factory fabricated, tested and calibrated. WHAT IS THE DUALPAK 6900 SERIES BOOSTER? The DualPak is a space saving system which is ideally suited for retrofit applications, new construction, and projects with minimal available floor space. WHY USE THE DUALPAK? In an age where mechanical room space is at a premium and continues to shrink, Armstrong pumping innovations offer the space saving solutions required. The selection process is simple and quick. Armstrong takes the guesswork out of your design. All systems are factory tested at simulated jobsite conditions prior to shipment from the factory, avoiding any potential on-site problems. Systems are backed by Armstrong s extensive representative and service dealer network. Designed for popular Mid-Rise construction projects, the DualPak incorporates the model 4382 dualarm in only two sizes of pumps to cover flow ranges from 100 350 GPM, and pressure ranges between 20 and 100 PSI. The DualPak is available in 3 different configurations, offering the flexibility required to meet users needs. The unique design of the dualarm pump incorporates a check valve and individual pump isolation valves. Pump manifolding is eliminated, reducing the overall weight of the system and allowing the DualPak to be suspended from the ceiling, if required.

DUALPAK SERIES 6900 BOOSTER MODEL SERIES CONFIGURATION PUMP SIZE BOOSTER COMPONENTS DualPak 6900 ECONO SERIES DualPak 6900 EDITION SERIES DualPak 6900 ULTRA SERIES 6901 3x3x6 DUAL 6902 3x3x8 6911 3x3x6 6912 3x3x8 6921 3x3x6 6922 3x3x8 1 dualarm PUMP 2 MAIN PRV 3 DUAL PUMP CONTROLLER 4 TEMPERATURE PROBE 5 SOLENOID VALVE 6 BASE & PANEL SUPPORT 7 GAUGES 1 dualarm PUMP 2 MAIN PRV 3 DUAL PUMP CONTROLLER 4 TEMPERATURE PROBE 5 SOLENOID VALVE 6 BASE & PANEL SUPPORT 7 GAUGES 8 BY-PASS SPOOL 9 ISOLATION BUTTERFLY VALVES 10 BY-PASS ISOLATION BALL VALVE 1 dualarm PUMP 2 MAIN PRV 3 DUAL PUMP CONTROLLER 4 TEMPERATURE PROBE 5 SOLENOID VALVE 6 BASE & PANEL SUPPORT 7 GAUGES 8 BY-PASS SPOOL 9 ISOLATION BUTTERFLY VALVES 10 BY-PASS ISOLATION BALL VALVE 11 1.5 BY-PASS PILOT OPERATED PRV Model Designation 69 1 2 100 10 50 DualPak DualPak PUMP SIZE SYSTEM MOTOR PUMP SERIES CONFIGURATION (1) 3x3x6 CAPACITY (HP) BOOST DESIGNATION (0) econo OR (GPM) PRESSURE (1) edition (2) 3x3x8 (PSI) (2) ultra Typical Applications Hotels, Large Motels, Resorts Condominiums, Apartments Schools and Small Office Buildings Retirement Homes & Hospitals

DUALPAK SIZING &SELECTION SHEET Step 1: Pressure Calculation PAK This calculation will determine pump pressure required. A negative value in step F indicates that a booster pump is not required. A. STATIC HEAD (BUILDING HEIGHT) PSI = Feet x 0.431 B. FRICTION HEAD (FRICTION LOSS) (Estimated at 10% of static head) C. HIGHEST OUTLET PRESSURE REQUIRED (Average estimated value = 40 PSI) D. SYSTEM REQUIRED PRESSURE (A + B + C) E. MINIMUM SUCTION PRESSURE (SUBTRACT) F. SYSTEM BOOST PRESSURE (D E) G. PRV LOSSES (Estimate 5 Psi) H. PUMP BOOST PRESSURE (F+G) Step 2: Building Water Requirement Feet This calculation will determine the total water requirement based on fixtures in the building. PSI FIXTURE QTY OF TOTAL FIXTURE UNIT FIXTURES UNITS BATHROOM GROUP F.V. 8 BATHROOM GROUP F.T. 8 BATHTUB 4 WATER CLOSET F.V. 7 WATER CLOSET F.T. 5 URINAL 5 LAVATORY 2 KITCHEN SINK 2 SERVICE SINK 3 CLOTHES WASHER 4 DISHWASHER (Domestic) 2 HOSE BIB (1/2 PIPE) 3 DRINKING FOUNTAIN 1 SHOWER 2 TOTAL FIXTURE UNITS F.V. = FLUSH VALVE F.T. = FLUSH TANKS Project: Step 3: System Capacity Calculation To obtain the total water requirement convert total fixture units calculated to corresponding GPM. WATER DEMAND TABLE FLUSH TANKS FLUSH VALVES FIXTURE UNITS DEMAND GPM DEMAND GPM 100 44 68 200 65 91 300 85 110 400 105 125 500 125 140 750 170 175 1000 210 218 1250 240 240 1500 270 270 1750 300 300 2000 325 325 2500 380 380 Step 4: Continuous Services Services which are a continuous load on domestic water services (ie: cooling, laundry, irrigation) have to be added separately to the total fixture load previously calculated. SERVICE 1. REGULAR BUILDING SERVICES (Value obtained from Step 3) 2. EXTRA SERVICES 3. BOOSTER SYSTEM TOTAL CAPACITY (1 + 2) Step 5. Pump Selection GPM Select pump and motor horsepower from DualPak selection table based on the pressure calculation from Step 1 and the capacity calculation from Step 4. Step 6. Model Configuration Based on customer needs and application, select either an Econo, Edition or Ultra configuration. (See details inside brochure) Step 7. DUALPAK Model Selection 69 (SEE MODEL NUMBER DESIGNATION)

DUALPAK 6900 SELECTION TABLE 50% 50% Equal Capacity Split BOOST PRESSURE PSI/FT TOTAL 20 30 40 50 60 70 80 90 100 DUALPSI FT FLOW 46,2 69,3 92 115 140 162 185 208 231 100 *3x3x8 1.5 *3x3x8 3 3x3x6 5 3x3x6 5 3x3x6 7.5 3x3x6 7.5 3x3x8 10 3x3x8 10 3x3x8 15 150 *3x3x8 2 *3x3x8 3 3x3x6 5 3x3x6 5 3x3x6 7.5 3x3x6 7.5 3x3x8 10 3x3x8 15 3x3x8 15 200 *3x3x8 2 3x3x6 5 3x3x6 5 3x3x6 7.5 3x3x6 7.5 3x3x8 10 3x3x8 10 3x3x8 15 3x3x8 15 250 *3x3x8 3 3x3x6 5 3x3x6 7.5 3x3x6 7.5 3x3x6 7.5 3x3x8 10 3x3x8 15 3x3x8 15 3x3x8 15 300 *3x3x8 3 3x3x6 5 3x3x6 7.5 3x3x6 7.5 3x3x6 10 3x3x8 15 3x3x8 15 3x3x8 15 3x3x8 20 350 *3x3x8 5 3x3x6 7.5 3x3x6 7.5 3x3x6 10 3x3x6 10 3x3x8 15 3x3x8 15 3x3x8 20 3x3x8 20 *Selections marked with an asterisk are 1800 rpm, Standard selection is 3600 rpm Boost pressures do not include drop across PRV s. (Add Approximately 5 psi) DUALPAK STANDARD COMPONENTS PUMPS: Armstrong Series 4382 close coupled Vertical In-Line twin pumps in a single casing. Pumps include individual seal flush lines, suction and discharge pump isolation valves, and discharge check valve. epoxy coated inside and out, with stainless steel cover bolts to ensure long lasting protection against corrosion and mineral attack. Critical internal valve components, such as valve seat and stem, are made of stainless steel to provide long and reliable service. DUAL PUMP CONTROL PANEL: Pump Control Panel is UL or CSA labeled industrial control panel. Control Panel enclosure is Nema 1 rated, complete with main disconnect, fuseless motor protectors with thermal and shortcircuit protection. Control panel includes internal circuit breakers to enable individual pump motor isolation. Control panel includes current sensing relays with on delay timers and minimum run timers to eliminate unnecessary pump cycling. Current relay cut-in and cut-out setpoints are factory set and can be field adjusted if necessary. Control panel is complete with power on light, pump running light and low suction pressure alarm light. A lead pump alternator, designed to ensure the equal running life of pumps, is included as a standard feature. PRESSURE REDUCING VALVES: Pressure reducing valves supplied are of the highest quality available on the market today. Valve bodies are fused ISOLATION VALVES: When supplied shall be lug type, lever operated, for sizes over 2 and shall be bronze full port isolation ball valves for all smaller sizes. ACCESSORIES: Every DualPak booster is complete with suction and discharge pressure gauges with 4 dial. Pumps are complete with high temperature protection circuit to protect pumps from overheating. This circuit consists of pump mounted temperature probe and panel mounted solenoid valve for purging of water to drain. OPTIONS: Systems are available with drawdown tank for adjacent mounting, or remote mounting, to allow pumps to shutdown during periods of no-demand. System is available with other control and fabrication options. Contact your local representative for more details.

TYPICAL SPECIFICATIONS 1.0 General Furnish and install, as shown on the plans and specifications, an PAK Armstrong Series 6900 DualPak duplex booster. System design based on a total system capacity of: GPM with a pump boost pressure of: PSI and a minimum suction pressure of: PSI. 1.1 Pumps The pumps shall be Armstrong Series 4382 close coupled type Vertical In-Line centrifugal pumping unit. The cast casing with equal size suction and discharge flanges, having separate tapped flush line and pressure gauge connections, shall incorporate two radially split, single stage centrifugal rotating assemblies. Each pump shall have a cast bronze dynamically balanced impeller, bronze shaft sleeve and inside type single spring mechanical seal. Each pump shall be complete with all factory furnished flush and vent line. Each driving motor shall be an industry standard vertical solid shaft, squirrel cage induction type, built to Nema standards (Premium efficiency motors may be specified). The motor shall be HP with dripproof enclosure and be suitable for Volts Phase, 60 Hz RPM. Each port shall be fitted with a stainless steel isolation valve that allow the units to operate in parallel or standby mode, yet may be used to isolate one pumping unit for servicing or pump removal, with the other pump still operating. 1.2 Assembly All DualPak assemblies shall include pump high temperature protection including a pump casing mounted temperature probe and panel mounted solenoid valve for purging of water to drain. Every system shall include 4 dial suction and discharge gauges mounted on system inlet and outlet. ECONO SERIES: Includes pilot operated epoxy coated main pressure reducing valve, bolted to pump discharge and mounted on common base. Pump shall be wired to dual pump controller with waterproof sealtight conduit. EDITION SERIES: Includes pilot operated epoxy coated main pressure reducing valve with isolation lug type butterfly valves. By-pass spools with 1.5 by-pass line and isolation ball valve to provide water in case of servicing of main PRV. All the above are bolted to pump discharge and mounted on common base. Pump shall be wired to dual pump controller with waterproof sealtight conduit. ULTRA SERIES: Includes pilot operated epoxy coated main pressure reducing valve with isolation lug type butterfly valves. Bypass spools with 1.5 pilot operated PRV and isolation ball valve to provide water and maintain constant pressure in case of servicing of main PRV. All the above are bolted to pump discharge and mounted on common base. Pump shall be wired to dual pump controller with waterproof sealtight conduit. 1.4 Control Panel The control panel shall be of the current sensing relay sequencing type. (Pressure sequencing or flow sequencing is not acceptable). The complete panel assembly shall be UL508 labeled or CSA approved. The control panel enclosure shall be Nema 1 and include door interlocked main disconnect and magnetic motor starters with fuseless motor starters. Motor protectors shall include short circuit and overload protection. (Fused protection is not acceptable). Control panel shall include internal circuit breakers for isolation of pump motors in case of servicing. The following alarm features shall be included: power on light, low suction pressure protection and pilot light, pump running light and individual pump Hand-Off- Auto switches. Control panel shall include automatic alternation of lead pump. 1.5 Testing Unit to be factory tested for hydraulic performance and calibrated to job site conditions. No on-site adjustments will be required. Unit to be ready to accept incoming power connection and supply piping. Armstrong Pumps Inc. 93 East Avenue North Tonawanda, New York U.S.A. 14120-6594 Tel: (716) 693-8813 Fax: (716) 693-8970 Armstrong Holden Brooke Pullen Wenlock Way Manchester United Kingdom, M12 5JL Tel: +44 (0) 1612 232223 Fax: +44 (0) 1612 209660 ARMSTRONG S.A. Armstrong Limited 23 Bertrand Avenue Toronto, Ontario Canada, M1L 2P3 Tel: (416) 755-2291 Fax: (416) 759-9101 Armstrong Darling 9001 De L'Innovation, Suite 200 Montreal (Anjou), Quebec Canada, H1J 2X9 Tel: (514) 352-2424 Fax: (514) 352-2425 www.armstrongpumps.com S.A. Armstrong Limited, 1995, 1999.