Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

Similar documents
Element D Services Electrical ODG010107

In the Eye of the Beholder: Electrical Codes from the View of the AHJ and the Designer

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

ELECTRICAL REQUIREMENTS FOR HEALTH CARE FACILITIES

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

SECTION ISOLATED POWER SYSTEMS

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Element Z General Design Requirements Existing Facilities Information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10

Element Z General Design Requirements Existing Facilities Information

NFPA 99 for Facility Managers

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved

GARCIA GALUSKA DESOUSA Consulting Engineers

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

ORDINANCE NO

NFPA Edition Review

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

SECTION ENCLOSED CONTROLLERS

16620 EMERGENCY POWER SYSTEMS

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

FIRE ALARM: BY OTHERS, IF REQUIRED.

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

PDH & Professional Training

Public Safety in the Healthcare Facility

FIRE ALARM: BY OTHERS, IF REQUIRED.

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION EXTERIOR LIGHTING

TONY ESPOSITO LIGHTING/ELECTRICAL TECHNICAL REPORT II SEPTEMBER 15, 2011 HUNTER S POINT SOUTH INTERMEDIATE SCHOOL AND HIGH SCHOOL QUEENS, NY

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

Demystifying Power Tap Use in Healthcare Settings John Garbarino Sr. Marketing Manager, Commercial/Industrial Leviton Manufacturing Co.

School Fire Safety Checklist

Machinery Room Electrical Best Practices

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

NFPA Changes

CONNECTICUT. Downloaded

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

27th Annual AHCA Seminar

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

CHAPTER 20 SERVICE EQUIPMENT

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Common Building Code Misinterpretations

Fire Alarm Wiring. Circuit types, styles and limitations

National Electrical Code

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

The following information shall become and form part of the contract documents.

Employee Health Protection

ELECTRICAL BULLETIN

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Chapter 1 General... 5

Facility Manager Training

SECTION INSPECTION AND TESTING OF WORK

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

ICC CODE CORNER 2015 International Fire Code

Compliance w/ the 2012 Life Safety Code

Are there any policies regarding outlets that contain USB ports?

Renovation Program. Renovation Program GENERAL

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

MOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

Enclosure 4- RISK ASSESSMENT

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

IEC and NCCER Mapping for Year 1

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Electrical Safety Requirements

EMERGENCY POWER SYSTEMS

PLAN REVIEW SUBMITTAL GUIDE

Fire Alarm System Fundamentals

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

State of North Carolina Department of Environment and Natural Resources Division of Waste Management. Safety and Risk Management Program

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

ELECTRICAL POWER SYSTEMS

Subcontract Agreement No.

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

Written Fire Safety Plans

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

Transcription:

Alex Masterton, PE Electrical Engineer Reviewer AHCA Neal Boothe, PE Electrical Engineer/Principal

FBC 419.3.15.6 All low-voltage system main or branch circuits entering or exiting the structure shall have surge suppressors installed for each pair of conductors and shall have visual indication for protector failure to the maximum extent feasible.

Does this mean TVSS must be at the device? Can TVSS be at panel serving the device? AHCA Interpretation: TVSS at Panel to be used. Maintain lead lengths per manufacturer s requirements. This would apply to: Rooftop AHU, exhaust fans, exterior lighting, exterior receptacles, exterior pumps, etc. Low voltage systems would include fire alarm, telephone system, network cabling, etc.

NFPA 312.29 Boxes, conduit bodies, and handhole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or, in underground circuits, without excavating sidewalks, paving, earth, or other substance that is to be used to establish the finished grade.

Interpretation from Health Guidelines Revision Committee (FGI) Trough can be used. AHCA Interpretation: Trough can be used. Trough cover to be flush with floor. Flooring to be sealed at trough.

From new 2012, NFPA 99 - not in effect yet but once adopted... 6.3.2.2.8.4 Operating rooms shall be considered to be a wet location, unless a risk assessment conducted by the health care governing body determines otherwise. Who is health care governing body AHCA Interpretation Hospital s risk management group

Normal and Critical Power still required in OR per NEC 517.19 Isolated Power Panel cannot serve multiple rooms per NEC 517.160 (4) So A normal and critical isolation panel will be required in each OR Exception: Two critical isolation panels (from separate ATS can be used) see NEC 517.19 Exception 2

Air movement is required on Equipment System Power per NEC 517.34 for some areas: The following equipment shall be permitted to be arranged for delayed connection to the alternate power source: (6) Supply, return, and exhaust ventilating systems for airborne infectious/isolation rooms, protective environment rooms, exhaust fans for laboratory fume hoods, nuclear medicine areas where radioactive material is used, ethylene oxide evacuation, and anesthesia evacuation. Where delayed automatic connection is not appropriate, such ventilation systems shall be permitted to be placed on the critical branch. (7) Supply, return, and exhaust ventilating systems for operating and delivery rooms.

Heating is required on Equipment system power in some areas per NEC 517.35: The following equipment shall be permitted to be arranged for either delayed automatic or manual connection to the alternate power source: (1) Heating equipment to provide heating for operating, delivery, labor, recovery, intensive care, coronary care, nurseries, infection/isolation rooms, emergency treatment spaces, and general patient rooms and pressure maintenance (jockey or makeup) pump(s) for water-based fire protection systems. Exceptions where design day temp is higher than 20 deg F

These codes require ventilation and heat. What about air conditioning: FBC 419.4.2.6.3 As determined by the facility these selected HVAC systems and their associated support equipment such as control air compressor essential to the maintenance of the occupied patient and patient support area(s) shall receive their power from the emergency power supply system(s). So Talk with Hospital Where is air conditioning required for operation of hospital?

Life Safety or Equipment System Power? NEC 517.32 (H) use LS power for auto doors used for building egress NEC 517.34 (B) (5) use EQ power for auto doors AHCA Interpretation: As all doors affect egress, use LS power for all auto doors

Per FGI 2.1-8.5 Min. inside dimension of 12 x 14 No more size exceptions from AHCA Mechanical & Electrical equipment/fixtures not related to support of room shall not pass through Circuits serving rooms shall be dedicated to room Reliable cooling required (emergency power) Be careful of location Try to avoid elec rooms as conduits cannot pass through the room

FBC 419.3.15.2 Where additions are constructed to existing buildings, the existing building s lightning protection system, if connected to the new lightning protection system, shall be inspected and brought into compliance with current standards. For Addition projects, Must meet this if you connect new LPS to existing system, or Provide independent LPS for new building addition

There are many issues with using Power Strips in OR environment: Loss of load control (too much equipment on one circuit) Circumvents FBC circuiting requirements (no more than 2 receptacles/circuit) Loss of redundant grounding in Critical Care area Affects access to patient Creates a trip hazard

Power strips should not be used in the OR See NFPA 99, 8.4.1.2.4 (6) The attachment plug (for equipment) shall be inserted only in a fixed approved receptacle This is an issue AHCA is reviewing in more detail.

For now, follow CMS Requirements: Power strips may not be used as a substitute for adequate electrical outlets in a facility. Power strips may be used for a computer, monitor, and printer. Power strips are not designed to be used with medical devices in patient care areas. Precautions needed if power strips are used include: installing internal ground fault and over-current protection devices; preventing cords from becoming tripping hazards; and using power strips that are adequate for the number and types of devices used. Overload on any circuit can potentially cause overheating and fire.

Radiology wiring separation Separation among wiring still required in troughs, conduits, etc. to the equipment 300V vs. 600V vs. 30V vs. Class 2 wire, etc. Don t let vendor tell you it s listed to be together Where necessary, use of rated sleeve material can be used to separate wiring as needed

NRTL Listings needed on equipment Nationally Recognized Testing Laboratory Program See www.osha.gov/dts/otpca/nrtl/ CE is not an NRTL Class 1 vs. Class 2 wiring Class 1 circuits need overcurrent protection; same wiring requirements as power circuits Class 2 circuits no external overcurrent protection needed Class 1 and Class 2 wiring must be separated from each other and from power wiring

449.3.11.11 All receptacles shall have engraved cover plates to indicate the panel board and circuit numbers powering the device. 449.3.11.12 Branch circuit over-current devices shall be readily accessible to nursing staff and other authorized personnel. 449.3.11.13 The electrical system shall have coordinated short circuit protection.

449.3.12.1 Fire Alarm Systems. A fire alarm annunciator panel shall be provided at a 24-hour monitored location. The panel shall indicate the zone of actuation of the alarm, and there shall be a trouble signal indicator. Each smoke compartment shall be annunciated as a separate fire alarm zone. A fire alarm system zone shall not include rooms or spaces in other smoke compartments and shall be limited to a maximum area of 22,500 square feet (2,090 sm) 449.3.14.8 Transfer switch contacts shall be of the open type and shall be accessible for inspection and replacement.

449.3.15.6 All low-voltage system main or branch circuits entering or exiting the structure shall have surge suppressors installed for each pair of conductors and shall have visual indication for protector failure to the maximum extent feasible. 449.4.2.9.1.5 Electric lighting required to provide care and service to the patient occupied areas and the necessary patient support areas shall be connected to the essential electrical system.

449.4.2.9.5 All panel boards, transfer switches, disconnect switches, enclosed circuit breakers or emergency system raceway systems required to support the occupied patient area(s), patient support area(s) or support utilities shall be contained within a protected area(s) designed and constructed to meet the structural requirements of the code and debris impact requirements of Sections 1626.2 through 1626.4, and shall not rely on systems or devices outside of this protected area(s) for their reliability or continuation of service. The equipment system shall be kept entirely independent of all other wiring and equipment and shall not enter the same raceways, boxes, or cabinets with other wiring.

449.4.2.9.7 If the facility does not have a permanent onsite optional stand-by generator to operate the normal branch electrical system, there shall be a permanently installed predesigned electrical service entry for the normal branch electrical system that will allow a quick connection to a temporary electrical generator. This quick connection shall be installed inside of a permanent metal enclosure rated for this purpose and may be located on the exterior of the building.