COMMERCIAL KITCHEN FIRE SAFETY

Similar documents
Chapter One Commercial Kitchen Fires

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

MOBILE FOOD VENDING Food Trucks & Trailers

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

CHAPTER 5: EXHAUST SYSTEMS

The following information is presented as a primer to inspect commercial cooking. We will deal with the form in parts as shown below.

Commercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

MSYS 4490 AC Systems

Mobile Vendors Bulletin

REQUIREMENTS FOR HOOD PLANS

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

READ AND SAVE THESE INSTRUCTIONS WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:

PREVENTING COOKING FIRES

Types of Detection. Fusible Link Detection - Most Common

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS

OUTLINE FOR FIRE PREVENTION ACTIVITY

Flue Fire Prevention Awareness

2012 ICC Commercial Kitchen Hoods

ICC CODE CORNER 2015 International Fire Code

Safety Tips for the Office

PORTABLE PERFORMANCE ANSUL Stored Pressure Fire Extinguishers

NFPA 101 Life Safety Code Culture change 2012

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event.

ANSUL TO-ANSUL. For more information... Check your local Yellow Pages for your authorized Ansul Restaurant Systems Distributor.

IVI WARNINGS: Must be followed carefully to avoid personal injury. [VL

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

TENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE

Builders Risk - Fire Prevention Inspection Checklist

REQUIREMENTS FOR TENTS, CANOPIES & MEMBRANE STRUCTURES

Outdoor Festival and Special Event Guidelines

Kitchen Fire Suppression Systems Post-Event Analysis

FIRE PREVENTION 29 CFR Ursinus College, Collegeville, PA

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

FOOD PREPARATION WITHIN EXHIBITS

Fire and Life Safety Review Form

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

SANDUSKY FIRE DEPARTMENT Fire Prevention Bureau. Dear Prospective Food Vendor:

School Fire Safety Checklist

enews 2012 Annual Conference

ISLAND MOUNT RANGE HOOD. This manual is made with 100 % recycled paper. Electronic version of this manual is available at:

Winnipeg Fire Department Fire Prevention Branch

Low Wall Back Shelf Exhaust Canopy

EXCELSIOR FIRE DISTRICT

To expedite the plan review and inspection processes, please refer to the information below.

User s Manual WS-4830SS WS-4836SS NOTE: PLEASE INSPECT HOOD IMMEDIATELY UPON RECEIVING. CLAIM OF DAMAGE AFTER 7 DAYS OF DELIVERY WILL BE DENIED.

2015 ICC Commercial Cooking Systems

User s Manual WS-69TB30 / WS-69TB36 (22 ) WS-69TB42 / WS-69TB48 (22 ) WS-69TS30 / WS-69TS36 (18 ) WS-69TS42 / WS-69TS48 (18 )

Tents and Temporary Membrane Structures Packet

Note: The event coordinator is responsible for compliance of all regulations.

User s Manual WS-3230SS WS-3236SS WS-3242SS WS-3248SS

Revolving Oven Gas Wood Model 140

TAMUCC Fire Safety Training

March 2015 (reprinted from March 2008 issue)

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Trade-Wind Professional Series Liners

Up on the Roof Fire Prevention BY David Laks, P. Eng., CFPS, ARM, RRC

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

User s Manual WS-63TB36SS WS-63TB42SS NOTE: PLEASE INSPECT HOOD IMMEDIATELY UPON RECEIVING. CLAIM OF DAMAGE AFTER 7 DAYS OF DELIVERY WILL BE DENIED.

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Euro-style Range Hood ESH5200

Dear Concessionaire,

Tents and Temporary Membrane Structures Permit Procedure

Exhibits and Trade Shows Permit Application

FOOD ESTABLISHMENT CONSTRUCTION GUIDE Revised December 19, 2011 Reviewed January 10, 2014

User s Manual WALL MOUNT SERIES TABLE OF CONTENTS RA7730SS/RA77B30SS RA7736SS/RA77B36SS RA7742SS/RA77B42SS RA7748SS/RA77B48SS.

Checklist For Building Inspection & Fire Safety

REQUIREMENTS FOR EVENTS AND TEMPORARY STANDS AT FAIRS AND SHOWS

CITY OF OKLAHOMA CITY SPECIAL EVENT REQUIREMENTS Revised January, 2011

Stillwater Area Community Services Center Inc.

User s Manual WS-62N30SS WS-62N36SS NOTE: PLEASE INSPECT HOOD IMMEDIATELY UPON RECEIVING. CLAIM OF DAMAGE AFTER 7 DAYS OF DELIVERY WILL BE DENIED.

WARNINGS: Must be followed carefully to avoid personal injury. IMPORTANT: Must be followed carefully to avoid damage or incorrect installation.

User s Manual ISLAND SERIES TABLE OF CONTENTS RA-7630SS RA-7636SS RA-7642SS RA-7648SS. Table of Contents. Safety Information...

Anticipated Date and Time for Completion of Break-Down:

FIRE DEPARTMENT PERMIT GUIDELINES

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY

General Festival Conditions & Temporary Use of Tents Conditions of Approval

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

Fire Prevention Plan Program

Integrated Hood Liner

SPECIAL EVENTS INSTRUCTIONS AND REQUIREMENTS Must apply at least 2 weeks PRIOR to Event Date

Business Fire Inspection. City of Guadalupe

Report on First Revisions with Statement June 2014 NFPA 101

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.

Product Dimensions Page 1 of 7. DA Downdraft Ventilation Hood

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Commerc al K tchen Hood

NFPA 96, 2017 REVIEW SUMMARY

SECTION COMMERCIAL-KITCHEN HOODS

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

WS-5530SS WS-5536SS WS-5542SS NOTE: PLEASE INSPECT HOOD IMMEDIATELY UPON RECEIVING. CLAIM OF DAMAGE AFTER 7 DAYS OF DELIVERY WILL BE DENIED.

AUTOMATIC FIREFIGHTING SYSTEMS IN KITCHENS

Transcription:

COMMERCIAL KITCHEN FIRE SAFETY COMMERCIAL KITCHEN FIRE SAFETY Commercial grade kitchens are a common feature found in senior living communities. Operation of a commercial grade kitchen, many safety considerations should be addressed, including food safety, employee and volunteer safety, and fire safety. This fact sheet addresses the specific issues associated with providing adequate fire safety for your kitchen. COMMERCIAL KITCHENS Commercial cooking operations are defined as kitchens that have cooking equipment that produce grease and grease laden vapors. This includes flat grills, char broilers and deep fat fryers. The typical residential range (electric or gas) would not be considered a grease producing appliance. Other equipment, such as ovens, microwaves and steam kettles also fall into the non-grease producing appliance category. The following is information regarding two of the most common types of equipment that produce grease and/or grease laden vapors. Deep Fat Fryers Deep fat fryers are a major cause of kitchen fires. Oil can splash and easily come into contact with an open flame from an adjacent piece of cooking equipment, such as a gas-fired range top. A 16-inch clearance must be maintained between the deep fat fryer and the open flame cooking equipment. If a 16-inch clearance is not possible, a vertical steel barrier extending 12 inches above the top of the deep fat fryer or open flame appliance(s) can be used as an alternative means of protection. The normal temperature range for food service frying is 325 to 375 degrees Fahrenheit. As the oil temperature increases, so does the risk of an accidental grease fire. All deep fat fryers should be equipped with a high temperature limiting device, which will shut off the fuel or energy in the event the cooking oil exceeds a temperature of 475 degrees Fahrenheit. This photo illustrates the correct installation of a metal baffle plate between the open flames from the range and the deep fat fryer. Metal baffles should be used only when there is not sufficient space available to provide a 16-inch clearance between the deep fat fryer and any source of open flames. CM 17265 (12/11) Commercial Kitchen Fire Safety goriskresources.com 1

Flat Grills/Griddles Flat grills and griddles are typically used for frying hamburgers and bacon. When used for this type of cooking, grease and grease laden vapors will be produced. To adequately control the fire hazard associated with these types of cooking operations, two fire protection components must be installed: a hood and ventilation system and an automatic extinguishing system. HOOD AND VENTILATION SYSTEM A kitchen hood and ventilation system will include an exhaust hood or canopy, ductwork, fan system, and a means of providing adequate make-up air. This system will effectively remove the heat, grease and grease laden vapors from the cooking area. Installation The hood and ventilation system should be professionally installed according to National Fire Protection Association Standard 96. (NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.) Local fire officials also should be consulted, as additional requirements under county and/or municipal codes could apply. The hood must be equipped with the appropriate grease removal filters. Only baffle style filters comply with NFPA 96 and should be used in cooking operations that produce a moderate to heavy amount of grease. Mesh filters are not appropriate for commercial cooking operations and do not comply with NFPA 96. Filters should be cleaned regularly to prevent the build-up of grease. Lighting units should be equipped with tight fitting protective globe lights with steel enclosures that are mounted on the outer surface of the hood. All electrical equipment should be installed in accordance with NFPA 70 National Electric Code by a licensed electrician. The photo to the left is an example of kitchen appliances that are properly equipped with an appropriate hood and ventilation system. 2 goriskresources.com Commercial Kitchen Fire Safety CM 17265 (02/12)

Maintenance Hoods, grease-removal devices, fans, ducts and other equipment should be serviced by a qualified contractor at intervals necessary to prevent the accumulation of grease. Frequency of cleaning will depend upon the amount of grease observed during an inspection. A six month interval is standard, but unusually heavy grease accumulation may require more frequent cleaning. A written cleaning schedule should be established indicating the methods of cleaning and the time intervals. COMMERCIAL KITCHEN FIRE SAFETY Following the inspection or cleaning, a label indicating the date cleaned and the name of the servicing company should be prominently displayed. It is recommended that this label be attached to the exterior of the hood in a visible location. This photo shows ductwork from a cooking area that has a heavy accumulation of grease. Maintaining and cleaning the hood and ventilation system is crucial, as the buildup of grease can become a serious fire hazard. The hood and ventilation system should be inspected and cleaned by a certified contractor every six months. AUTOMATIC EXTINGUISHING SYSTEM All cooking equipment that produces grease or greaseladen vapors should be equipped with an approved automatic extinguishing system. The automatic extinguishing system should meet the Underwriters Laboratory (UL) 300 standard. UL 300 went into effect in 1994 as the result of the high temperature oils used in cooking today. Dry-chemical systems do not adequately extinguish grease fires associated with using these high temperature cooking oils. The automatic extinguishing system should be inspected and serviced every six months only a qualified contractor. These photos are examples of two different brands of automatic extinguishing systems that contain a liquid extinguishing agent. Ansul and Range Guard are two well-known manufacturers. Also, note the inspection tag on the unit to the left. This is the inspection tag that the servicing company will leave after they service the system every six months. CM 17265 (02/12) Commercial Kitchen Fire Safety goriskresources.com 3

A minimum of one manual activator should be installed. The activator is to be used if a fire occurs and the automatic extinguishing system fails to activate. The manual activator must be accessible in the event of a fire and located along a route of egress from the kitchen area. Kitchen staff must be properly trained on the proper operation of the manual activator. These photos are examples of manual activators that should be used if the automatic extinguishing system fails to activate. This device should be installed away from the cooking surface, next to an entrance/exit for the kitchen. Kitchen staff should be aware of this manual activator and trained on its use. Also note the inspection tag. Many fire service companies will place these tags on the manual activator to indicate current servicing. The automatic extinguishing system must be inter-connected to an automatic fuel/power shut off that cuts all fuel/power from the cooking equipment immediately after the automatic extinguishing system is activated. Prohibit the operation of cooking equipment when the extinguishing system or exhaust system is non-operational or otherwise impaired. FIRE EXTINGUISHERS Wet chemical fire extinguishers are the best portable extinguisher available for kitchen operations. K-rated extinguishers are recommended for commercial kitchens. They operate in the same manner as a UL300 pre-engineered restaurant fire extinguishing system. The agent discharges as a fine mist, which helps prevent grease splash and fire re-flash, while cooling the appliance. The fire extinguisher should be located no more than 30 feet from the cooking area. Fire extinguishers should be maintained at regular intervals; at a minimum of once per year, or when specifically indicated by a manufacturers recommendations. Maintenance should be conducted only by an approved/licensed contractor. Servicing is intended to give maximum assurance that an extinguisher will operate effectively and safely. 4 goriskresources.com Commercial Kitchen Fire Safety CM 17265 (02/12)

COMMERCIAL KITCHEN FIRE SAFETY These pictures are of a portable K-rated fire extinguisher. A class K fire extinguisher is designed to better control grease and other kitchen related fires. If a kitchen contains any grease producing appliances, a portable Class K-rated fire extinguisher should be installed in the kitchen in a visible and easily accessible location. GENERAL HOUSEKEEPING The kitchen s floors and walls around cooking appliances need to be periodically cleaned to prevent the accumulation of grease. Frequency of cleaning will depend upon the frequency and type of cooking being conducted; however a minimum of once a week is recommended. Floor and wall coverings surrounding the cooking equipment need to be of an appropriate material that will prevent grease saturation and be easy to clean and maintain. Examples of appropriate material include ceramic tile on floors or stainless steel on walls. 2012 GuideOne Risk Resources for Health Care, a division of Lutheran Trust, Church Asset Management. All rights reserved. This material is for informational purposes only. It is not intended to give specific legal or risk management advice, nor are any suggested checklists or actions plans intended to include or address all possible risk management exposures or solutions. You are encouraged to consult with your own attorney or other expert consultants for a professional opinion specific to your situation. GuideOne Risk Resources for Health Care 1111 Ashworth Road West Des Moines, Iowa 50265 1-800-688-3628 CM 17265 (02/12) Commercial Kitchen Fire Safety goriskresources.com 5