User s Guide. Setpoint Option Card. Shop online at. omega.com For latest product manuals: omegamanual.

Similar documents
User s Guide. Shop online at. Made in China. Two-wire Display and Control Unit

OM-CP-Cryo-Temp Ultra Low Temperature Data Logger. Shop online at. omega.com For latest product manuals: omegamanual.

User s Guide. OSXL685 and OSXL689. High Performance Infrared Thermometer. Shop online at

LVCN-302 Set-Up Manual for Sump Model

User s Guide OS210-C4. IR Temperature Sensors. Shop online at omega.com. For latest product manuals: omegamanual.

User s Guide. LVU-800, & LV U Ultrasonic Level System

User s Guide. FLSW Series ROTAMETER WITH ALARM. Shop online at omega.com. For latest product manuals:

User s Guide. DPF-520 Series XXXXXX. Shop online at. omega.com For latest product manuals: omegamanual.info

User s Guide HHAQ-109. Portable Multi-gas Detector. Shop online at omega.com SM

User s Guide TOTE SERIES. Wrap-Around Tote Tank Headers. TOTE SERIES Wrap-Around Tote Tank Heaters. Shop online at omega.com

OMEGA (MODEL:610LF) OS642F-LS Infrared Thermometer With Laser Marker

LDP-124 AND LDP-144 SERIES FOR TEMPERATURE

User s Guide FST1000 SERIES. Air Flow Switch with Two SPST Relay Contact Closures. Shop online at omega.com

OMEGA. OS643E-LS/OS643E Infrared Thermometer With Laser Sighting

User s Guide OS137 SERIES. Miniature Non-Contact Infrared Temperature Sensor/Transmitter. Shop online at omega.com

User s Guide. Shop online at. omega.com CN Chromalox Rev Set Point. Load. Alarm.

User s Guide. CN606 / 612 AC Series & CN606 / 612 DC Series CONTRONAUTICS INCORPORATED. Table of Contents.

DPG300 SERIES M-5258/0213

OMB-DAQ-TC-RACK-EXP32

User s Guide RH650. Shop online at omega.com SM. 9-In-1 Thermo-Hygrometer/ Moisture Meter

Digital Pressure Gauges with Alarms and 4-20 ma Output

User s Guide. Shop online at omega.com. For latest product manuals: WITH REMOTE SENSOR PROBE FMA100XR

User s Guide OS-MINI22 SERIES. Shop online at omega.com SM. For latest product manuals: omegamanual.info

MDS8PT. Universal Temperature & Process Benchtop Meter with Alarms

PHH-60/PHH ph/conductivity Meter. Newport Electronics, Inc. Operator s Manual PHH-60 ON OFF. ph/conductivity METER

User s Guide OS100E SERIES. Mini-Infrared Transmitters. Shop online at omega.com. For latest product manuals: omegamanual.

Room Humidity/Temp Sensor

Duct Humidity/Temp Sensor

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Sierra Series 900 Single & Dual Channel System. Instruction Manual

NT DUAL CHANNEL DISPLAY. User Guide

Environmental Monitoring SmartSlot Card

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Outside Air Humidity & Temperature Sensor

Duct Temperature Sensors

Series: MBC1-TC Mini Benchtop Temperature Controller

1040 Gas Monitor INSTALLATION AND OPERATING INSTRUCTIONS AMC-1040 WITH INTEGRAL ELECTROCHEMICAL SENSOR

86BSD Digital Output

User s Guide. PHE-2724/2726 SERIES ORE 2725 SERIES ph/orp Electrodes

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Remote Relay Module (RRM)

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

STATUS ALARM HISTORY ALARM RESET

FRESHAIR USER S MANUAL. CAUTION: Read manual carefully for proper procedures and operation.

Duct Mount. Installation Instructions

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

User s Guide OSXL-101. Compact Thermal Image Sensor Application Software. Shop online at. omega.com

OWNERS MANUAL. CARBON MONOXIDE DETECTOR MODELS Panel Mount & Remote Detectors (R) Guardian Avionics 1951 E. AIRPORT DRIVE TUCSON, AZ.

EVD-1 Installation, Operation, and Instruction Manual

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

89BSD Digital Output

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

Mark 25 Ultrapure Water Conductivity Analyzer

Controllers. Instruction Manual WARNING

INSTRUCTION MANUAL P Heating and 1 Cooling

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

Model SC3004. Transducer Display and Signal Conditioning Unit DESCRIPTION. Fourteen channel chassis FEATURES

E340 BOILER CONTROL INSTALLATION MANUAL

KM300 Carbon Monoxide Detection System Installation Manual

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

3820, 3820i, 4820, 4820i

1022 R/T Remote Monitor

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Operator s Manual. The Quietek

User s Guide USA. Shop on line at. Temperature & Humidity Monitor DPiTH-i8DH, -i8dv, -i16d, -i32

Oakton TEMP 9500 Advanced Multiparameter Controller

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Installation Manual NPE-180A/240A WARNING. Add-on Controller Installation Kit

OWNERS MANUAL MODEL 451 (-101 & -201)

Operations Manual. Motion Detector Module Model ZS10

CA5000 Liquid CO 2 Freezer Backup System

Instruction Manual WARNING

Installation Manual WARNING. Add-on Controller Installation Kit NPE-180A/210A/240A

JDDT1 - Single Stage Digital Thermostat

430128A. B-Series Flow Meter SIL Safety Manual

QAS SERIES PLUG-IN CONTROLLERS c/w SOLID STATE SENSOR

86BSD Digital Output

HEIGHTS KEY LOCK & SAFE 920 San Mateo NE Albuquerque, NM Contact us for more information

GTC15 Temperature Controller Operation Manual

Standard SPECIFICATIONS FEATURES APPLICATIONS

MINI-BEAM Expert Series

OPERATION MANUAL. THE JENCO MODEL 6230 MICROCOMPUTER BASED ph/mv/temp PORTABLE METER JENCO ELECTRONICS, LTD. MANUFACTURER OF PRECISION INSTRUMENTS

Dolphin 9900 Mobile Computer

Module de relais Relay Module. Manuel de l utilisateur 301RW. User Manual ERP /07

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Frequently asked questions: Intelligent Transmitter Series

MODEL 8143 SIGNAL SELECTOR INSTALLATION AND OPERATION MANUAL

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Installation Manual. THM-0100 Setpoint Thermostat Version THM HBX Control Systems Inc.

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Environmental Monitoring Card

User s Guide DP606A/DP612A. Shop online at omega.com. Universal 6/12 Channel ¼ DIN Panel Meter

Incutrol/2 Regulator

QTC15 Temperature Controller Operation Manual

Master Prep Chopper OWNER S GUIDE QB600W

Model 4001 Series Single Channel Controller

1 4 DIN Dissolved Oxygen Controller

0 A EIS Intrinsically-Safe Plug-in Intelligent Photoelectronic Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS

Installation and Operations Manual

Transcription:

User s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info LDP6-CDS Setpoint Option Card LP0683X

OMEGAnet Online Service omega.com Internet e-mail info@omega.com Servicing North America: U.S.A.: One Omega Drive, P.O. Box 4047 ISO 9001 Certified Stamford, CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com Canada: 976 Bergar Laval (Quebec) H7L 5A1, Canada TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca For immediate technical or application assistance: U.S.A. and Canada: Sales Service: 1-800-826-6342/1-800-TC-OMEGA Customer Service: 1-800-622-2378/1-800-622-BEST Engineering Service: 1-800-872-9436/1-800-USA-WHEN Mexico: En Español: (001) 203-359-7803 e-mail: espanol@omega.com FAX: (001) 203-359-7807 info@omega.com.mx Servicing Europe: Czech Republic: Frystatska 184, 733 01 Karviná, Czech Republic TEL: +420 (0)59 6311899 FAX: +420 (0)59 6311114 Toll Free: 0800-1-66342 e-mail: info@omegashop.cz Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany TEL: +49 (0)7056 9398-0 FAX: +49 (0)7056 9398-29 Toll Free in Germany: 0800 639 7678 e-mail: info@omega.de United Kingdom: One Omega Drive, River Bend Technology Centre ISO 9002 Certified Northbank, Irlam, Manchester M44 5BD United Kingdom TEL: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in United Kingdom: 0800-488-488 e-mail: sales@omega.co.uk It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING : These products are not designed for use in, and should not be used for, human applications.

DESCRIPTION This bulletin serves as a guide for the installation, configuration and operation of LDP6-CDS Setpoint cards. The setpoint cards are available as dual relay, quad relay, quad sourcing transistor, or quad sinking transistor outputs. Only one setpoint card can be installed at a time. The meter can be fitted with up to three option cards. The slot bays of the option cards are dedicated to a particular card function. The option card functions are: serial communications, analog output and setpoint output. Only one card from each function category can be installed. INSTALLING AN OPTION CARD Caution: The option and main circuit cards contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation. TOP VIEW Warning: Exposed line voltage exists on the circuit boards. Remove all power to the meter AND load circuits before accessing the unit. 1. Remove the main assembly from the rear of the case. Squeeze the finger holds on the rear cover, or use a small screwdriver to depress the side latches to release it from the case. It is not necessary to separate the rear cover from the main circuit card. 2. Locate the option card connector for the type of option card to be installed. Hold the unit by the rear connector, not the display board, when installing an option card. 3. Install the option card by aligning the option card connector with the slot in the rear cover. The cards are keyed by position with different main board connector locations. Be sure the connector is fully engaged and the tab on the option card rests in the alignment slot on the display board. 4. Slide the assembly back into the case. Be sure the rear cover latches fully into the case. 5. Apply the option card label to the bottom side of the meter. Do not cover the vents on the top surface of the meter. The surface of the case must be clean for the label to adhere properly. Apply the label to the area designated by the large case label. REAR TERMINAL CONNECTIONS 3

SPECIFICATIONS Setpoint Output Cards: Four types of field installable cards Response Time: 200 msec. max. to within 99% of final readout value (digital filter and internal zero correction disabled) 700 msec. max. (digital filter disabled, internal zero correction enabled) DP63700 only: 1 sec. max. to within 99% of final readout value (digital filter disabled) DP63500 only: 200 msec. typ.; 700 msec max. (digital filter disabled) DP63700 Isolation For All Four Cards: Isolation To Sensor Common: 1400 Vrms for 1 min. Working Voltage: 125 V Isolation To User Input Common: 500 Vrms for 1 min. Working Voltage: 50 V Dual Relay Card: LDP6-CDS10 Type: Two FORM-C relays Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min. Working Voltage: 250 V Contact Rating: One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @120 VAC, inductive load Total Current With Both Relays Energized not to exceed 5 amps Life expectancy: 100 K cycles min. at full load rating. External RC snubber extends relay life for operation with inductive loads Quad Relay Card: LDP6-CDS20 Type: Four FORM-A relays Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min. Working Voltage: 250 V Contact Rating: One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load), 1/10 HP @120 VAC, inductive load Total Current With All Four Relays Energized not to exceed 4 amps Life Expectancy: 100 K cycles min. at full load rating. External RC snubber extends relay life for operation with inductive loads Quad Sinking Open Collector: LDP6-CDS30 Type: Four isolated sinking NPN transistors. Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Working Voltage: 50 V. Not Isolated from all other commons. Rating: 100 ma max @ V SAT = 0.7 V max. V MAX = 30 V Quad Sourcing Open Collector: LDP6-CDS40 Type: Four isolated sourcing PNP transistors. Isolation To Sensor & User Input Commons: 500 Vrms for 1 min. Working Voltage: 50 V. Not Isolated from all other commons. Rating: Internal supply: 24 VDC ± 10%, 30 ma max. total all four External supply: 30 VDC max., 100 ma max each output Sourcing Output Logic Card Sinking Output Logic Card Quad Sourcing Open Collector Output Card Supply Select For Quad Sourcing Plug-in Card (LDP6-CDS40), set the jumper for internal or external supply operation before applying power. MODULE 6 - Setpoint (Alarm) Parameters () PARAMETER MENU Indicates Program Mode Alternating Display. Parameter Factory Settings are shown. Selection/Value SETPOINT SELECT NO SP-1 SP-3 SP-2 SP-4 Enter the setpoint (alarm output) to be programmed. The in the following parameters will reflect the chosen setpoint number. After the chosen setpoint is completely programmed, the display will return to. Repeat step for each setpoint to be programmed. The chosen at will return to. The number of setpoints available is setpoint output card dependent. 4

OFF de-hi SETPOINT ACTION Ab-HI de-lo Ab-LO band AU-HI totlo AU-LO tothi Enter the action for the selected setpoint (alarm output). See Setpoint Alarm Figures for a visual detail of each action. = Setpoint always off, (returns to SPSEL NO) = Absolute high, with balanced hysteresis = Absolute low, with balanced hysteresis = Absolute high, with unbalanced hysteresis = Absolute low, with unbalanced hysteresis = Deviation high, with unbalanced hysteresis * = Deviation low, with unbalanced hysteresis * = Outside band, with unbalanced hysteresis * = Lower Totalizer absolute high, unbalance hysteresis** = Upper Totalizer absolute high, unbalance hysteresis** * Deviation and band action setpoints are relative to the value of setpoint 1. It is not possible to configure setpoint 1 as deviation or band actions. It is possible to use setpoint 1 for an absolute action, while its value is being used for deviation or band. ** The lower Totalizer action allows setpoints to function off of the lower 5 digits of the Totalizer. The upper Totalizer action allows setpoints to function off of the upper 4 digits of the Totalizer. To obtain absolute low alarms for the Totalizer, program the or output logic as reverse. SETPOINT VALUE -19999 to 99999 Enter desired setpoint alarm value. These setpoint values can also be entered in the Display Mode during Program Lockout when the setpoint is programmed as in Parameter Module 3. When a setpoint is programmed as deviation or band acting, the associated output tracks as it is changed. The value entered is the offset, or difference from. HYSTERESIS VALUE 1 to 65000 Enter desired hysteresis value. See Setpoint Alarm Figures for visual explanation of how setpoint alarm actions (balance and unbalance) are affected by the hysteresis. When the setpoint is a control output, usually balance hysteresis is used. For alarm applications, usually unbalanced hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on the low side for high acting setpoints and functions on the high side for low acting setpoints. Note: Hysteresis eliminates output chatter at the switch point, while time delay can be used to prevent false triggering during process transient events. Setpoint Alarm Figures With reverse output logic, the below alarm states are opposite. Absolute High Acting (Balanced Hys) = Ab-HI Absolute Low Acting (Unbalanced Hys) = AU-Lo Band Outside Acting = band Absolute Low Acting (Balanced Hys) = Ab-Lo Deviation High Acting (SP > 0) = de-hi Deviation High Acting (SP < 0) = de-hi Absolute High Acting (Unbalanced Hys) = AU-HI This is also for Totalizer alarms:, Deviation Low Acting (SP > 0) = de-lo Deviation Low Acting (SP < 0)= de-lo 5

ON TIME DELAY 0.0 to 3275.0 Sec Enter the time value in seconds that the alarm is delayed from turning on after the trigger point is reached. A value of 0.0 allows the meter to update the alarm status per the response time listed in the Specifications. When the output logic is, this becomes off time delay. Any time accumulated at power-off resets during power-up. OFF TIME DELAY 0.0 to 3275.0 Sec Enter the time value in seconds that the alarm is delayed from turning off after the trigger point is reached. A value of 0.0 allows the meter to update the alarm status per the response time listed in the Specifications. When the output logic is, this becomes on time delay. Any time accumulated at power-off resets during power-up. SETPOINT ANNUNCIATORS OFF nor rev The mode disables display setpoint annunciators. The mode displays the corresponding setpoint annunciators of on alarm outputs. The mode displays the corresponding setpoint annunciators of off alarms outputs. The mode flashes the corresponding setpoint annunciators of on alarm outputs. PROBE BURN-OUT ACTION (DP63500 ONLY) ON OFF FLASH Enter the probe burn-out action. In the event of a temperature probe failure, the alarm output can be programmed to go on or off. OUTPUT LOGIC nor rev Enter the output logic of the alarm output. The logic leaves the output operation as normal. The logic reverses the output logic. In, the alarm states in the Setpoint Alarm Figures are reversed. RESET ACTION Auto LAtC1 LAtC2 Enter the reset action of the alarm output. = Automatic action; This action allows the alarm output to automatically reset off at the trigger points per the Setpoint Action shown in Setpoint Alarm Figures. The on alarm may be manually reset (off) immediately by a front panel function key or user input.the alarm remains reset off until the trigger point is crossed again. = Latch with immediate reset action; This action latches the alarm output on at the trigger point per the Setpoint Action shown in Setpoint Alarm Figures. Latch means that the alarm output can only be turned off by front panel function key or user input manual reset, serial reset command or meter power cycle. When the user input or function key is activated (momentary or maintained), the corresponding on alarm output is reset immediately and remains off until the trigger point is crossed again. (Previously latched alarms will be off if power up Display Value is lower than setpoint value.) = Latch with delay reset action; This action latches the alarm output on at the trigger point per the Setpoint Action shown in Setpoint Alarm Figures. Latch means that the alarm output can only be turned off by front panel function key or user input manual reset, serial reset command or meter power cycle. When the user input or function key is activated (momentary or maintained), the meter delays the event until the corresponding on alarm output crosses the trigger off point. (Previously latched alarms are off if power up Display Value is lower than setpoint value. During a power cycle, the meter erases a previous Latch 2 reset if it is not activated at power up.) Setpoint Alarm Reset Actions Alternate Setpoints An Alternate list of setpoint values can be stored and recalled as needed. The Alternate list allows an additional set of setpoint values. (The setpoint numbers nor rear terminal numbers will change in the Alternate list.) The Alternate list can only be activated through a function key or user input programmed for in Module 2. When the Alternate list is selected, the Main list is stored and becomes inactive. When changing between Main and Alternate, the alarm state of Auto Reset Action alarms will always follow their new value. Latched on alarms will always stay latched during the transition and can only be reset with a user input or function key. Only during the function key or user input transition does the display indicate which list is being used. STANDBY OPERATION no YES When, the alarm is disabled (after a power up) until the trigger point is crossed. Once the alarm is on, the alarm operates normally per the Setpoint Action and Reset Mode. 6

WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 25 months from date of purchase. OMEGA s WARRANTY adds an additional one (1) month grace period to the normal two (2) year product warranty to cover handling and shipping time. This ensures that OMEGA s customers receive maximum coverage on each product. If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs. OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages. CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a Basic Component under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner. RETURN REQUESTS/INQUIRIES Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit. FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA: 1. Purchase Order number under which the product was PURCHASED, 2. Model and serial number of the product under warranty, and 3. Repair instructions and/or specific problems relative to the product. FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA: 1. Purchase Order number to cover the COST of the repair, 2. Model and serial number of the product, and 3. Repair instructions and/or specific problems relative to the product. OMEGA s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of OMEGA ENGINEERING, INC. Copyright 2006 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.

Where Do I Find Everything I Need for Process Measurement and Control? OMEGA Of Course! Shop online at omega.com TEMPERATURE ] Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies ] Wire: Thermocouple, RTD & Thermistor ] Calibrators & Ice Point References ] Recorders, Controllers & Process Monitors ] Infrared Pyrometers PRESSURE, STRAIN AND FORCE ] Transducers & Strain Gages ] Load Cells & Pressure Gages ] Displacement Transducers ] Instrumentation & Accessories FLOW/LEVEL ] Rotameters, Gas Mass Flowmeters & Flow Computers ] Air Velocity Indicators ] Turbine/Paddlewheel Systems ] Totalizers & Batch Controllers ph/conductivity ] ph Electrodes, Testers & Accessories ] Benchtop/Laboratory Meters ] Controllers, Calibrators, Simulators & Pumps ] Industrial ph & Conductivity Equipment DATA ACQUISITION ] Data Acquisition & Engineering Software ] Communications-Based Acquisition Systems ] Plug-in Cards for Apple, IBM & Compatibles ] Datalogging Systems ] Recorders, Printers & Plotters HEATERS ] Heating Cable ] Cartridge & Strip Heaters ] Immersion & Band Heaters ] Flexible Heaters ] Laboratory Heaters ENVIRONMENTAL MONITORING AND CONTROL ] Metering & Control Instrumentation ] Refractometers ] Pumps & Tubing ] Air, Soil & Water Monitors ] Industrial Water & Wastewater Treatment ] ph, Conductivity & Dissolved Oxygen Instruments M4537/0607