Air Distribution Fan and Outside Air Damper Recycling Control

Similar documents
Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Unvented Roof Summary Article

Results of Advanced Systems Research: Supplemental Humidity Control Systems

2006 Building Science Press All rights of reproduction in any form reserved.

Building America Special Research Project: Space Conditioning Systems for High Performance Homes

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Unvented Roof Assemblies for All Climates by Chris Schumacher

Time-Based Scheduling of Residential Ventilation

Practical and Effective Approaches to Residential Ventilation for Production Builders

Systems Engineering Approach to Development of Advanced Residential Buildings

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Design/Sizing Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Ventilation for New Low-Rise Residential Buildings July 20, 2015

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

RESNET HERS Rater Sample Test Questions 2

Effects of Kitchen Ventilation on Residential Dwellings

Supplement A- Improving Forced Air Heating Systems

Indoor Environmental Quality

The Heating System and Ventilation and Combustion Air

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

b.) Technical Information:

Measurement of Ventilation and Inter-zonal Distribution In Single Family Homes

Special Topics on Residential HVAC

Ventilation in Humid Climates: Data from Field Experiments

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems

BUILDING AMERICA SYSTEMS ENGINEERING APPROACH TO DEVELOPMENT

NEW HOME CERTIFICATION PROGRAM 2018 PROGRAM GUIDE

Measurement of Ventilation and Interzonal Distribution in Single-Family Homes

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

Comfort Series. Energy Recovery Ventilator. Why Fresh Air Ventilation is Vital for Today s Energy-Efficient Homes

BUILDING VENTILATION GUIDE

BUILDING VENTILATION GUIDE FOR LG HVAC SYSTEM INSTALLATION

COMcheck Software Version Mechanical Compliance Certificate

Preface. Overview. The above illustration shows a typical three zone Aprilaire Zoned Comfort Control system.

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Safety, Installation, and Operation Manual

NAHB Green Home Building Guidelines. 3.1 Prerequisites. ResCheck. Energy Efficiency

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

Uniform Dwelling Code 2017 Updates SPS 323

Using a Pressure Pan To Diagnose Duct Leakage

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

Steam Humidifier Fan Pack Installation & Maintenance Instructions

Residential Makeup Air Systems & Requirements

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

INDEX. ADDITIONS AND ALTERATIONS Defined Requirements ADMINISTRATION AND ENFORCEMENT... Chapter 1 AIR ECONOMIZERS

For information on any of these products, please contact your heating and air conditioning contractor or feel free to write or call us.

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

COMcheck Software Version Review Mechanical Compliance Certificate

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

COMMERCIAL ENERGY SAVINGS GUIDE

CHAPTER 4. HVAC DELIVERY SYSTEMS

Job Name Control Systems Description Date

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

Indoor Air Quality Product Brochure.

Choosing Heating and Cooling Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

A Necessity for Preventing Unsafe Backdrafts and Unhealthy Air

Building America AC Installation Using CheckMe!

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS

Ventilation Techniques. Topic 5 - Audio 53

The Art of Building Science

Whole House Ventilation System Options Phase 1 Simulation Study

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

Indoor Air Quality Product Brochure.

17 Interior Climate Control

WHOLE-HOUSE VENTILATION SYSTEMS

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Ventilation Strategies in Weatherization

Energy Recovery Ventilation

ASHRAE JOURNAL ON REHEAT

The Unplanned Impacts On Houses By Powered Attic Ventilators

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

2006 Building Science Press All rights of reproduction in any form reserved.

August 15, 2013 Page 1 of 19

Table of Contents. List of Figures and Tables. Executive Summary: 3 ASHRAE Standard 62.1 Section 6 Analysis 7

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Evaluate your insulation. Look for a tag in the attic that shows the R-Values of insulation in the floors, walls and ceiling.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Moisture, Ventilation & Global Weirding NEHERS Webinar Series

Safety & Installation Instructions

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

IAQ: Re-tuning Commercial Buildings

The V in HVAC: Mechanical Ventilation in ENERGY STAR Certified Homes

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Energy Efficient Options for Residential Water Heating

Ventilation BCBC 9.32 & Richard Kadulski Architect

What is Energy Star?

ACCA Quality Homes ACCA 12 QH 2011 (Existing Home Evaluation and Performance Improvement) Developed in cooperation with RESNET

WHAT S UNDER YOUR ROOF?

2009 Washington State Energy Code Residential Sections

Benefits Offered by Passive Dehumidification Wheel Speed Control

Desiccant Dehumidifier

In the past, contractors sized heating and cooling systems GETTING HVAC RIGHT

Chapter 7: Heating and Cooling Systems

Transcription:

building science.com 2008 Building Science Press All rights of reproduction in any form reserved. Air Distribution Fan and Outside Air Damper Recycling Control Research Report - 0991 5-July-1999 Armin Rudd Abstract: Energy efficient homes are inherently airtight and require ventilation for acceptable indoor air quality. Recognizing this fact, two building code jurisdictions, the federal department of Housing and Urban Development and the State of Washington, require mechanical ventilation for homes. The state of Minnesota will soon enact regulations for mechanical ventilation in homes, and it is expected that this trend will continue. Of all the options currently available, the low cost and low maintenance centralfan-integrated ventilation approach is the most acceptable to large production builders and manufactured home producers. In this approach, fresh air is filtered and ducted to the return air side of the central system fan. The central system fan and ducts then distribute the ventilation air throughout the living space. This is a resource and energy efficiency strategy that utilizes the existing air ducts and the normal cycling of the fan, in response to demand from the thermostat, to distribute ventilation air and conditioned air at the same time. The patented AirCycler control can be used to automatically operate the fan if the fan has been inactive for a period of time, and to control a motorized outside air damper to limit the intake of ventilation air independent of fan operation.

OVERVIEW Energy efficient homes are inherently airtight and require ventilation for acceptable indoor air quality. Recognizing this fact, two building code jurisdictions, the federal department of Housing and Urban Development and the State of Washington, require mechanical ventilation for homes. The state of Minnesota will soon enact regulations for mechanical ventilation in homes, and it is expected that this trend will continue. Of all the options currently available, the low cost and low maintenance central-fanintegrated ventilation approach is the most acceptable to large production builders and manufactured home producers. In this approach, fresh air is filtered and ducted to the return air side of the central system fan. The central system fan and ducts then distribute the ventilation air throughout the living space. This is a resource and energy efficiency strategy that utilizes the existing air ducts and the normal cycling of the fan, in response to demand from the thermostat, to distribute ventilation air and conditioned air at the same time. The patented AirCycler control can be used to automatically operate the fan if the fan has been inactive for a period of time, and to control a motorized outside air damper to limit the intake of ventilation air independent of fan operation. BACKGROUND A number of residential mechanical ventilation system types exist. These systems can be generally categorized as follows: Supply ventilation, with either central-fan-integrated, or single- or multi-point distribution Exhaust ventilation, with either single- or multi-point exhaust, and with or without passive inlet vents Balanced ventilation, with either central-fan-integrated, or single- or multi-point supply and exhaust, and with or without heat recovery or energy recovery Single point ventilation systems of any type suffer from lack of adequate distribution of fresh air, especially to closed rooms. Exhaust only ventilation systems suffer in two ways: 1) potential for creating or adding to pressure conditions conducive to back-drafting of combustion appliances, and; 2) air that replaces exhausted air may not be suitable as fresh ventilation air since the source cannot be controlled (i.e. replacement air may be coming from the garage, crawl space, sub-slab or other undesirable location). Of the residential ventilation options currently available, central-fan-integrated ventilation is the most acceptable to large production builders. The primary advantages to them are low cost, low maintenance, and improved comfort through full distribution of ventilation air and mixing of indoor air. This system has been demonstrated in over 300 homes as part of the U.S. Department of Energy s Building America Program (http://www.eren.doe.gov/buildings/building_america/). Page 1 of 5

Central-fan-integrated ventilation systems provide ventilation air through a duct that extends from a known location outdoors to the return air side of a central air distribution fan. This known location should be selected to maximize the ventilation air quality. Central-fan-integrated ventilation systems have an advantage in that they achieve full distribution of ventilation air using already existing ducts. A drawback is that these systems only supply ventilation air when the fan is operating, and during mild outdoor conditions, the central fan may not be activated by the thermostat for long periods of time. Until the introduction of the AirCycler fan recycling control, there were two available options to remedy this drawback: 1) run the central fan continuously; or, 2) operate the fan in parallel with the thermostat by a separate timer that has no relation to the fan s operation due to thermostat demand, causing overlapping or short-cycling operation. Both of those options create new problems: they are energy inefficient, and resource inefficient, in that the fan consumes more energy than needed and the operational life of the central fan will be shorter. In addition, operating the central system fan continuously can lead to moisture related problems in humid climates. During the cooling season in humid climates, operating the air distribution fan immediately after a cooling cycle is counter-productive, in that, moisture on the wet cooling coil is returned to the interior space by the recirculating air. In addition, immediately after a cooling cycle, depending on the percentage of outdoor air and the outdoor humidity level, moisture could condense inside cool supply ducts. AirCycler CONTROL The AirCycler control was first developed in 1993 to address the shortcomings of the available technology. The control will automatically cycle the fan only if it has been inactive for a period of time, thus eliminating overlapping or short-cycling operation caused by other timers. The AirCycler control method allows the fan to stay off immediately after a cooling cycle to improve moisture removal. For humid climates, the fan should not operate immediately after a cooling cycle to allow water on the cooling coil to drip off to the condensate drain and to allow cool supply ducts to warm up before introducing humid ventilation air. The amount of outside air brought in by the central-fan-integrated ventilation system with AirCycler can be limited independent of fan operation. Through the patented control of a standard, inexpensive motorized outside air damper, the AirCycler will stop the flow of ventilation air if the fan has been on long enough to satisfy ventilation needs. The AirCycler is produced by Lipidex Corporation in Duxbury, Massachusetts. The control is being used by many production home builders who have recognized and demonstrated its effectiveness. The AirCycler control employs an energy efficiency strategy that utilizes the normal cycling of the fan, as the fan operates to distribute conditioned air in response to calls from the thermostat, to also distribute ventilation air at the same time. Only if the fan has been inactive for a period of time will the fan be operated by the fan recycling control to distribute ventilation air and provide mixing. Page 2 of 5

In addition to providing effective ventilation, the AirCycler control can also provide enhanced temperature and humidity comfort control in conditioned spaces. Thermostats are typically located in a central area and are expected to serve an entire zone that usually includes closed rooms, and often, more than one floor level. Temperature conditions can vary widely between the thermostat location and extremities of the space the thermostat serves. Likewise, for climates where humidity is separately controlled, humidistats are usually located in a central area and suffer the same lack of uniform control. This air stratification problem can be especially pronounced during mild outdoor conditions when long periods elapse between space conditioning demands from the thermostat. Because of this, builders and HVAC contractors lose profit when they are called back to make heating and cooling system adjustments to provide better comfort throughout the house. An inexpensive and effective way to avoid this problem can be to use the AirCycler control to intermittently utilize the central air distribution fan to average overall space conditions by mixing. This intermittent fan operation can also improve the performance of air cleaning or special filtration systems that locate the cleaning or filtration media at the return air side of the central fan. The AirCycler creates more uniform temperature and humidity conditions throughout the conditioned space that may cause occupants to use more moderate temperature and humidity setpoints rather than exaggerating setpoints to overcome comfort problems in isolated locations. The result can be reduced energy cost. As a prerequisite for energy efficiency in any forced air system, the entire air distribution system must be substantially airtight, including all ducts, dampers, fittings, and the air handler cabinet itself. If the air distribution system is leaky to unconditioned space, this will defeat the purpose of intentionally sizing an outside air duct to provide a controlled amount of ventilation air. A reference leakage rate for substantially airtight could be defined as leakage to outdoors of less than five percent of the rated fan flow. The best solution to duct leakage is to locate the entire air distribution system inside conditioned space, however, many production builders are reluctant to do so because of space allocation and aesthetic concerns. Supply ventilation will tend to pressurize an interior space relative to the outdoors, causing inside air to be forced out through leak sites (cracks, holes, etc.) located randomly in the building envelope. This strategy is advantageous in warm, humid climates to minimize moisture entry into the building structure from outdoors. However, care should be taken with building envelope design and workmanship when using supply ventilation that could pressure buildings in climates with cold winters. To avoid potential problems with supply ventilation in cold climate buildings: 1) the building envelope must be constructed to avoid air leakage that will transport interior moisture into the building envelope; 2) interior humidity must be controlled such that surfaces inside wall and unvented ceiling cavities remain above the interior air dewpoint temperature; 3) surfaces inside wall and unvented ceiling cavities can be elevated through use of exterior insulating sheathing. Page 3 of 5

ENERGY AND ECONOMIC BENEFIT Since October 1994, all manufactured homes constructed under the Code of Federal Regulations, Housing and Urban Development (HUD), Manufactured Home Construction and Safety Standards have included a whole house ventilation system. Most of these HUD Code homes have central-fanintegrated ventilation systems installed. To achieve ventilation during mild outdoor conditions, the central fan must be operated continuously. Use of the AirCycler control could have a large impact on reducing fan energy use and space conditioning energy use by eliminating the need to operate the central fan continuously to provide ventilation. Based on hourly computer simulations for four U.S. climate zones, 28% savings in total heating, cooling, and fan energy could be realized, per year per house, by operating the fan intermittently with the AirCycler control compared to operating the fan continuously. This is equivalent to an average of 4459 or 2.6 barrels of oil per house per year. The building energy simulations were conducted using DOE2.1E and a reference 1500 ft 2 house. Table 1 shows the results for the four U.S. cities chosen to represent each climate zone (cold, mixed, hot-dry, hot-humid). Chicago Charlotte Las Vegas Orlando $ @.11 $ @.07 $ @.07 $ @.08 Fan Energy 1019 112 1284 90 1486 104 1216 97 2460 271 3066 215 3679 258 3066 245 Difference 1441 159 1782 125 2193 154 1850 148 Cooling Energy $ @.11 $ @.07 $ @.07 $ @.08 2290 252 2813 197 4728 331 5321 426 2197 242 2805 196 4814 337 5759 461 Difference -93-10 -8-1 86 6 438 35 Heating Energy $ @.02 $ @.03 $ @.02 $ @.08 13553 271 7807 234 5594 112 258 21 18119 362 10786 324 8009 160 443 35 Difference 4566 91 2979 89 2415 48 185 15 Net Annual Energy Net Annual Cost Difference Difference 16862 11904 11808 6795 22776 16657 16502 9268 5914 4753 4694 2473 $ $ $ $ 635 875 521 735 547 755 544 741 240 214 208 198 Central Fan Operational Hours Difference hours hours hours 3639 3668 3538 8760 8760 8760 5121 5092 5222 hours 3474 8760 5286 Central Fan Average Hourly Duty Cycle avg duty cycle avg duty cycle avg duty cycle avg duty cycle 42% 42% 40% 40% 100% 100% 100% 100.0% Table 1 Summary of hourly simulations for central-fan-integrated ventilation with 33% fan duty cycle versus constant fan operation Page 4 of 5

It was estimated that available motor timer controls, that operate the fan in parallel with the thermostat, would cause the central fan to operate at least 20% more than needed due to overlapping and shortcycling operation. This inefficient fan control method occurs because the ventilation timer control has no relation to the fan s operation due to thermostat demand. For example, the central system may have just completed ten minutes of operation to meet a thermostat demand when the ventilation timer re-initiates central fan operation to meet the ventilation demand. The AirCycler control automatically and efficiently allows the occurrence of thermostat demand to simultaneously meet ventilation demand. Page 5 of 5

Air Distribution Fan and Outside Air Damper Recycling Control About this Report This report first appeared in Heating Air Conditioning and Refrigeration News, 5 July 1999, pg. 45. About the Authors Armin Rudd is a principal engineer at Building Science Corporation in Westford, Massachusetts. More information about Armin Rudd can be found at www.buildingscienceconsulting.com. Direct all correspondence to: Building Science Corporation, 30 Forest Street, Somerville, MA 02143. Limits of Liability and Disclaimer of Warranty: Building Science documents are intended for professionals. The author and the publisher of this article have used their best efforts to provide accurate and authoritative information in regard to the subject matter covered. The author and publisher make no warranty of any kind, expressed or implied, with regard to the information contained in this article. The information presented in this article must be used with care by professionals who understand the implications of what they are doing. If professional advice or other expert assistance is required, the services of a competent professional shall be sought. The author and publisher shall not be liable in the event of incidental or consequential damages in connection with, or arising from, the use of the information contained within this Building Science document.