Service Literature GCS/CHA16 6, 7.5, 10 and 12.5 Ton (21, 26.4, 35.2 and 44.0 kw)

Similar documents
Service Literature GCS/CHA16 15 and 20 Ton (52.8 and 70.3 kw)

UNIT INFORMATION. Corp L7. Gauge Manifold Attachment... Page 30 Parts Arrangement... Page 8

HS25 SERVICE UNIT INFORMATION

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

TSA WARNING. Service Literature TSA SERIES UNITS. 6, 7.5, 10, 12.5, 15 & 20 ton

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

IMPORTANT CB26UH CBX26UH. Service Literature. CB26UH and CBX26UH Series Table of Contents. Model Number Information... 2

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

Corp L2 Revised

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

KGA092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

G51MP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

XC13. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

USER'S MANUAL PGE Single Package Rooftop

TGA/KGA024, 030, 036, 048, 060, 072, 090 (2, 2 1/2, 3, 4, 5, 6, and 7 1/2 TONS)

LRP14HP/LRP14DF/LRP14AC/LRP14GE/LRP16GE/LRP16HP SERIES UNITS

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

INSTALLATION INSTRUCTIONS

RGE 13 A T - 1 A

CBX32MV WARNING CAUTION. Service Literature CBX32MV (R410A) SERIES UNITS

HSXA15 HSXB15. IMPORTANT Operating pressures of this R410A unit are higher than pressures in R22 units. Always use service equipment rated for R410A.

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

G32V. Service Literature G32V SERIES UNITS

TGA WARNING CAUTION ROOFTOP UNITS. Service Literature. Table of Contents

13ACX. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R 410A.

USER S INFORMATION MANUAL (2,4)SG13B

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

user s information manual

G60UHV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

13 GEP A L P - 1 A

MERIT Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,500 to 59,000 Btuh AIR CONDITIONERS 13ACXN PRODUCT SPECIFICATIONS

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

UNIT INFORMATION Corp L10 Replaces Corp L4 10HP SERIES UNITS

XC16. IMPORTANT Operating pressures of this R 410A unit are higher than pressures in R 22 units. Always use service equipment rated for R410A.

48TF GAS HEATING/ ELECTRIC COOLING UNITS

INSTALLATION INSTRUCTIONS

ELITE SERIES Downflow - High Efficiency Blower Motor

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

USER S INFORMATION MANUAL

TGA WARNING CAUTION ROOFTOP UNITS. Service Literature. Table of Contents

SKYPAK II Heating & Cooling Self Contained Packages

G60DFV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

48TM GAS HEATING/ELECTRIC COOLING UNITS

INSTALLATION INSTRUCTIONS

SL280DFV. DAVE LENNOX SIGNATURE COLLECTION Downflow - Two-Stage Heat - Variable Speed Blower

MERIT SERIES Downflow

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

User s Information Manual

CATALOG. SKYPAK Self-Contained Heating/Cooling Units

GHR32Q/V SERIES UNITS

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

LGA/LGC036, 042, 048, 060, 072 (3, 3-1/2, 4, 5, and 6 TONS) LGA/LGC090, 102, 120, 150, (7-1/2, 8-1/2, 10, and 12-1/2 TONS)

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

SKYPAK II, 3 Ton Series, gives you a

Commercial High-Efficiency Condensing Units

Preventative Maintenance Tables

SKYPAK II, 3 Ton Series, gives you a

DuralokPlus Aluminized Steel Heat Exchanger G 32 V

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

REPLACEMENT PARTS LIST

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat)

MERIT Series R-410A - Upflow / Horizontal

HSXA16 WARNING. WARNING R 410A refrigerant can be harmful if it is inhaled. R 410A refrigerant must be used and recovered responsibly.

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

Service Facts. Air Handler - Convertible Model: Series 2 Air Handlers ton GAT2A0B42S31SA GAT2A0C48S41SA GAT2A0C60S51SA WARNING: GAT2-SF-1B

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

ARPT Series. Multi-Position, Multi-speed Air Handler with Internal TXV and PSC Motor 2 to 5 Tons. Contents. Product Features

GHR26. Service Literature GHR26 SERIES UNITS DOWN FLOW POSITION HORIZONTAL POSITION

HEATING & COOLING SPLIT SYSTEM HEAT PUMP & AIR CONDITIONER 14 SEER INTERTHERM SERIES

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

TECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE DESCRIPTION WARRANTY FEATURES

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

DRY CHARGE UNITS. 1.5 to 5 Tons. HEAT PUMP OUTDOOR UNITS lps13dc PRODUCT SPECIFICATIONS L P S 13 DC MODEL NUMBER IDENTIFICATION

ARPT Series. Multi-Position. 2 to 5 Tons. Internal TXV, Multi-Speed PSC Motor

MERIT Series R-410A - Upflow / Horizontal

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

User s Information Manual

8+* Bulletin No November 1997

2 shp 13 lc 1 36 t - 1 a

Installation, Operation and Service Manual

USERS INFORMATION MANUAL

MODELS B1PA024, 030 AND 036

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

User s Information Manual

Specially Designed. SilentComfort Fan Guard. Visit us at For the latest technical information,

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

McQuay. Commercial Unitary Rooftop. CUR Vintage G. Last Manufactured: Replacement Parts List No Revision A 11/2016

Transcription:

GCS16 series units in the 6, 7.5, 10 and 12.5 ton (21, 26.4, 35.2 and 44.0 kw) cooling sizes are packaged combination gas heat/dx cool units designed for commercial applications. Gas heat exchanger in 160,000, 200,000 and 270,000 (46.9, 58.6 and 79.1 kw) Btuh input sizes. Optional electric heat sections with inputs of 10 to 50 kw are available in the CHA16 series units and install inside the cabinet. Service Literature GCS/CHA16 6, 7.5, 10 and 12.5 Ton (21, 26.4, 35.2 and 44.0 kw) All GCS20 model units utilize a scroll compressor. The GCS/CHA16-072 has cone compressor and the GCS/CHA16-090, -120 and -150 has two. The scroll compressor offer high volumetric efficiency, quiet operation and the ability to start under system load. Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. The motor is internally protected from excessive current temperature. All GCS/CHA16 models are designed for horizontal or down discharge application and may be fitted with RMF16 mounting frame, REMD16 economizer and RTD11 ceiling diffuser. All GCS/CHA16 are designed to accept several different thermostat control systems such as the Honeywell T7300 or Honeywell T8621D with minimum field wiring. Control options such as economizer and warm up kit connect to the unit with jackplugs. When plugged in the controls become an integral part of the unit wiring. Units are also equipped with low voltage pigtails to facilitate thermostat field wiring. Information in this manual is for use by a qualified service technician only. All specifications are subject to change. Procedures outlined in this manual are represented as a recommendation only and do not supersede or replace local or state codes. GENERAL...Page 1 SPECIFICATIONS...Page 2 HIGH ALTITUDE...Page 3 ELECTRICAL DATA......Page 4 BLOWER DATA....Page 4 OPTIONAL ACCESSORIES......Page 10 PARTS ARRANGEMENT...Page 12 I APPLICATION...Page 14 II UNIT COMPONENTS...Page 14 III OPTIONAL ELECTRIC HEAT...Page 25 Table of Contents WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performend by a qualified installer or service agency. WARNING Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly. Failure to follow this warning may result in personal injury or death. IV PLACEMENT AND INSTALLATION...Page 30 V ELECTRICAL CONNECTIONS...Page 30 VI INDOOR BLOWER OPERATION...Page 30 VII START UP...Page 31 VIII REFRIGERATION SERVICE CHECKS...Page 32 IX HEATING SERVICE CHECKS...Page 33 X MAINTENANCE... Page 35 XI ACCESSORIES...Page 37 XII WIRING AND OPERATION SEQUENCE...Page 41 Page 1

Page 2

Page 3

Page 4

Page 5

Page 6

Page 7

Page 8

Page 9

Page 10

Page 11

Page 12

Page 13

I-APPLICATION GCS/CHA16 6 and 7.5 ton units are available in one cabinet size and GCS/CHA16 10 and 12.5 ton units are available in on size. All models are applicable for commercial three phase installations. GCS/CHA16 models are factory equipped with the hardware required for installing optional thermostat control systems like the T7300 or T8621D (refer to the Engineering Handbook for more specific application data). II-UNIT COMPONENTS GCS16 unit components are shown in figure 1. CHA16 unit components are shown in figure 2. A-Control Box Components The GCS/CHA16 control box is shown in figures 3 and 4. The control box is located in the upper portion of the compressor compartment behind the compressor compartment access panel. Note that the burner ignition control (GCS models only) is located in the heating control section located just above the manifold/burner assembly. The condenser fan can be accessed by removing the fan grill located on the top of the unit. The indoor blower access panel (all units) is located to the left side of the heating compartment access. 1-Transformer T1 All GCS/CHA16-072/090/120/150 units use a single line voltage to 24VAC transformer mounted in the control box. The transformer supplies power to control circuits in the unit. Transformers are rated at 70VA and are protected by a 3.5 amp circuit breaker (CB). Transformers use two primary voltage taps as shown in figure 5. 4-Outdoor Fan Relay K10 Outdoor fan relay K10 used in GCS/CHA16-090/120/150 units, is a DPDT relay with a 24V coil. K10 energizes outdoor fans B4 and B5 (120/150 units) in response to thermostat demand. 5-Cooling Contactor K1 & K2 K1 and K2 are 24V coil contactors used to energize the compressor(s) in response to thermostat demand. In GCS/ CHA16-072 units, K1 energizes condenser fan B4 along with compressor B1 and K2 energizes compressor B2 in response to second stage cooling demand. All GCS/ CHA16-072/090/120/150 units use three-pole-double-break contactors. CAUTION Remove all power to disconnect before servicing. Electrical shock resulting in death or injury may result if power is not disconnected. 6-Indoor Blower Contactor K3 All GCS/CHA16-072/090/120/150 units use a three-pole double brake contactor to energize the indoor blower and optional economizer. The coil is energized by a blower demand from indoor thermostat terminal G (cooling demand or fan switch in ON position). 7-Condenser Fan Motor Capacitor C1 & C2 GCS/CHA16-072/090/120/150 series units use single phase PSC condenser fan motors. See condenser fan motor nameplate for capacitor ratings. B-Heat Control Section (GCS Only) 2-Terminal Strip TB34 Terminal strip TB34 distributes 24V power from transformer T1 to the control box components. 3-Transformer T3 (G & J Voltage Only) All GCS16-072/090/120/150 G and J units use one 230VAC transformer mounted in the control box. The transformer has an output rating of 115VA.55A @ 230V. T3 transformer supplies 230VAC power to combustion air inducer motor B6. Page 14

Page 15

ÉÉÉ ÉÉ ÉÉÉ ÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉ ÉÉ ÉÉÉÉ ÉÉ ÉÉ ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉ ÉÉ É ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉ ÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉ ÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉ ÉÉ ÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ É ÉÉ ÉÉ ÉÉÉ ÉÉÉ Page 16

Page 17

2-Burner Assembly (Figure 13) The burners are controlled by the spark electrode, flame sensing electrode, gas valve GV1 and combustion air blower B6. The spark electrode, flame sensing electrode and gas valve GV1 are directly controlled by ignition control A3. a-burners All units use inshot burners. Burners are factory set and do not require adjustment. Burner shutters are designed to be fully open only. Units are furnished with a peep hole with cover in the access panel for flame viewing. Always operate unit with access panel in place. Burners can be individually removed for service. Burner maintenance and service is detailed in the MAINTENANCE section of this manual. 4-Primary High Temperature Limit S10 S10 is the primary limit for gas heat. See figure 15 for both types used. On GCS16-090-1 models units, S10 is located in the heating compartment and mounted to the lower portion of the panel dividing the heating compartment from the blower compartment. On GCS16-072 and GCS16-090-2 models, S20 is located in the return air area. On GCS16-120/150 models, S10 is located in the blower compartment. Primary limit S10 is wired in series with the burner control A3. S10 N.C. contacts open to de-energize the ignition control when excessive heat is reached in the heat exchanger. At the same time, the N.O. contacts close energizing K20 blower limit relay, which in turn energizes the blower relay K3 energizing indoor blower B3. See table 2 for factory set point. Stick type limit used on GCS16-072 and 090-2 models must be installed with limit face in DOWN position. b-orifice Each burner uses an orifice which is matched to the burner input. The orifice is threaded into the manifold. The burner is supported by the orifice and will easily slide off for service. Each orifice and burner are sized specifically to the unit. 3-Flame Rollout Switch S47 (figure 14) Flame rollout switch S47 is a high temperature limit located just above the burner on all units. See figure 13. The limit is a N.C. SPST manual re-set thermostat connected in series with ignition control A3. When S47 senses flame rollout, ignition control immediately closes the gas valve. The switch is factory set to open at 180 o and cannot be adjusted. Table 2 GCS16 Unit S10 Set Point o S21 Set Point o 072-1 200 175 090-1 180 150 090-2 200 175 120-1 180 150 120-2 170 150 150-1 170 150 5-Secondary Limit S21 All GCS16 model units are equipped with a secondary limit (disc type limit figure 15). On GCS16-072/090 models, S21 is located in the blower compartment. On GCS16-120/150 models, S21 is located in the return air (behind filters). The limit is auto-re-set thermostat which opens on temperature rise. S21 is wired in series with the ignition control. The limit is used to de-energize the ignition control and shut down the unit when temperature in the blower compartment becomes too high. The limit is factory set and is not adjustable. See table 2. This is a safety shutoff function of this unit and must never be bypassed. Page 18

Page 19

Page 20

Page 21

Page 22

Page 23

The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationay scroll. The liquid is worked toward the center of the scroll and is discharged. If the compressor is replace, conventional cleanup practices must be used. Due to its efficiency, the scroll compressor is capable of drawing a much deeper vacuum than reciprocating compressors. Deep vacuum operation can cause internal fusite arcing rsulting in damaged internal parts and compressor failure. It is permissible to pump-down the system using the compressor but never use a scroll compressor for drawing a vacuum on the system. The type of damage can be detected and will result in denial of warranty claims. 3-Indoor Blower Motor B3 All GCS/CHA16 model units use three-phase, PSC, belt driven blower motors. See motor nameplate or ELECTRI- CAL DATA section for motor specifications. 4-Evaporator Coil All GCS/CHA16 model units have a single slab evaporator coil. The ocil in the GCS/CHA16-072/090/120 has three rows and the GCS/CHA16-150 has four rows, of rifled copper tubes fitted with ripple-edged aluminum fins. A Thermal Expansion Valve (TXV) feeds multiple parallel circuits through the coil. See figure 27. CAUTION The head of a scroll compressor may be hot since it is in constant contact with discharge gas. Contact could result in serious burns. For compressor specifications see compressor nameplate or ELECTRICAL DATA section in this manual. All compressors are protected by internal overload protection circuitry. 2-Condenser Fan and Motor B4 & B5 The specificiations section in this manual shows the specifications of condenser fans used in GCS/CHA16s. The condenser fan is controlled by cooling contactor K1. Page 24

Page 25

Page 26

Page 27

Page 28

DL5 DL4 K9 K19 K18 K17 K16 K15 DL2 Page 29

Page 30

Page 31

Page 32

Page 33

Page 34

Page 35

Page 36

Page 37

Page 38

Page 39

Page 40

Page 41

Page 42

Page 43

Page 44

Page 45

Page 46

Page 47

Page 48

Page 49