Installation & Operating Instructions For Goettl Evaporative

Similar documents
INSTRUCTION MANUAL. FOR MODELS MobileMAX II & MobileMAX III High Performance Mobile Evaporative Coolers

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

AdobeAir USE AND CARE MANUAL. General Inspection Start-Up Inspection...4 Start-Up Checklist...4 Cabinet Inspection Checklist...4

Breezair RPA Series Installation Manual

SINGLE INLET. Evaporative Air Cooler. Instruction Manual! ESSICKAIR The Cool One. Horizontal And Down Discharge. Owner s Manual Model # s

USE AND CARE MANUAL HIGH CAPACITY FAN EVAPORATIVE COOLERS CFD4200 CFD4800 SERIES NOTE! NOTE:

Installation, Operation, and Maintenance Manual

Commercial Evaporative Air Conditioning Bonaire 700C 1500C. IMPORTANT NOTICE Please leave this manual with the owner of this air conditioner.

INSTALLATION MANUAL EA Evaporative Cooler

Commercial Evaporative Air Conditioning Bonaire B18 B36. IMPORTANT NOTICE Please leave this manual with the owner of this air conditioner.

WV Series Evaporative Cooler. Installation Manual

OWNER S & INSTALLATION MANUAL RPCQ / RPC Evaporative Cooler

Operation & Maintenance Manual for

SWP. (Models SWP08 through SWP20) IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

RPA. Installation. Operation. Service INDUSTRIAL EVAPORATIVE AIR CONDITIONERS. January 09

OWNERS INSTRUCTION MANUAL FOR FIXED INSTALLATION COMMERCIAL AND RESIDENTIAL EVAPORATIVE AIR CONDITIONERS

HT650 TM FAN DRIVE SERVICE INSTRUCTIONS

WET/DRY VACUUM. QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO MODEL: T1. Operating Instructions (ENG)

Operation and Maintenance Manual BLIZZARD50 CS6-50-VD 120V/60HZ

Panel Fan Series Operators Manual (Galvanized and Polymer)

Operation and Maintenance Manual 120V/60HZ

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

48 MaxxAir Portable Evaporative Cooler Owner s Manual

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation and Maintenance Manual GLACIER TALL BASE CS5-16-VD-TB CS5-18-VD-TB2 120V/60HZ

Manual for MC91 SETUP INSTRUCTIONS

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

Manual for MC21A SETUP INSTRUCTIONS

Manual for MC37/MFC3600

FOR FIXED INSTALLATION COMMERCIAL AND RESIDENTIAL EVAPORATIVE AIR CONDITIONERS

e Bath Fan with Light User s Guide

Operation and Maintenance Manual 120V/60HZ

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

Room Air Conditioner Service and Parts Manual

Operation & Maintenance Manual for

READ AND SAVE THESE INSTRUCTIONS. Air Boss Model T5200 Custom Packaged Electronic Air Cleaner. TRION

INSTALLATION MANUAL TBA Evaporative Cooler

Installation & Maintenance Instructions

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

IMPORTANT INSTRUCTIONS - OPERATING MANUAL

18 MaxxAir Portable Evaporative Cooler Owner s Manual This Manual covers the EC18DVS MaxxAir Portable Evaporative Cooler.

Manual update 2016 MC37/MFC3600

e Bath Fan with Light User s Guide

INSTALLATION MANUAL. TBA Evaporative Cooler. (English) (TBA) ILL1456-A

Drying Tumblers. Troubleshooting. 120 Pound Capacity 170 Pound Capacity. Refer to Page 5 for Model Numbers. Part No August 2007

1. SAFETY RULES. 8. Avoid placing objects in the path of the blades.

60" Hatteras BayTM. Patio. Instruction Manual. Includes our new Wall Control System. A Kichler Décor ceiling fan

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

Hatteras BayTM. Patio. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Euro-style Range Hood ESH5200

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

SeasonMaker Hi-Line Fan-coil Units Model HSS S10 & S12

Group 7 COOLING SYSTEM CONTENTS

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

Breezex (BX) Heavy Duty Reversible Supply/Exhaust Fans with Reversing Switch. IMPORTANT! Read before proceeding! OPERATION & MAINTENANCE MANUAL

e Bath Fan with Light User s Guide

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.

SeasonMaker Hi-Line Fan-coil Unit Model HSS S30 through S80

52 StarkkTM. Instruction Manual. A Kichler Select ceiling fan

SUPRA 52. U.S. Patents: D450,830 INSTRUCTION MANUAL WARRANTY CERTIFICATE

Select. Sutter PlaceTM. Instruction Manual. A Kichler Select ceiling fan

SECTION (15833) - HVAC POWER VENTILATORS

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

OPERATING & SERVICE PARTS MANUAL HDS-215 COMBINATION SHRINK SYSTEM

CAR-MON DUST COLLECTORS SERIES 207, 2410, 3015

CEILING FAN OWNER'S MANUAL

Installation & Maintenance Instructions

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

e Heater/Exhaust Fan/Light User s Guide

42 Kevlar. Instruction Manual. Kichler Lighting 7711 East Pleasant Valley Road P.O. Box Cleveland, Ohio

60" Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

Sunburst. Instruction Manual. Includes our new Wall Control System. A Kichler Décor ceiling fan

READ AND SAVE THESE INSTRUCTIONS

User Manual Box Exhaust Fan Series (Belt Drive)

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

Pocket Hardmount. Preventative Maintenance.

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

52 Lacey LED. Instruction Manual. 6 Speed DC Wall Control System

INSTALLATION and OPERATION BALL WASHER MODEL NO: BW-022

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

Component. Maintenance. Manual Z SERIES. Evaporator Assembly

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Installation & Maintenance Data IM Contents

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

Wax Base Heater & Dispenser

52 DorsetTM. Instruction Manual. Basic Function Wall Control System Included. A Kichler Decor ceiling fan

BESB Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

Panel Fan Series Operators Manual (Galvanized and Polymer)

Orrin. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

Installation Electric Dryers Instructions 01

INSTALLATION & OPERATING INSTRUCTIONS

The Extraordinaire OWNER S MANUAL. Orbital Ceiling Fan. Model No. OF110** READ AND SAVE THESE INSTRUCTIONS. Net Weight 14.5 lbs. or 6.59 kg.

Portable Evaporative Cooling System

LIMITED LIFETIME WARRANTY

Transcription:

Installation & Operating Instructions For Goettl Evaporative Coolers Manufactured By GOETTL AIR CONDITIONING, INC. P.O. Box 52029, Phoenix, Arizona 85072-2029

INSTALLATION 1. Before you start, read all of the instructions.. Installations may require that you adapt these instructionsto special requirements. 3. On receiving your cooler, check for concealed shipping damage, and note any damage on the freight bill. Such damage is the responsibility of the freight carder, and any claims must be filed with them. Unpack the unit carefully, being sure that accessories and instructionsare not discarded with the packing material. ROOF MOUNTED UNITS Step 1: Select location of cooler and roof opening as determined by requirements of ductwork, roof construction and cooler appearance. Cut the roof opening. Do not cut any structural members without approval of your architect, builder, or authorized persons having jurisdiction. Follow their instructions. If approval is received to cut joists or roof rafters, it is suggested they be'headed as shown in figure la. Where the rafter or joist must be left in place it should be capped both top and bottom to deflect air flow, as shown in figure 1b. Note that leaving such framing in the duct can cut down cooler air delivery as much as 10%. Fig. la. Cut and framed roof opening for cooler installation. Figure lb. Capped rafter or joist. -2-

Step 2: Construct an angle iron or wood platformto provide a level mounting surface for the cooler. Typical roof platforms are shown in Figure 2 for down discharge coolers and Figure 3 for horizontal discharge coolers. Measure cooler, or find size from catalog to determine size of platform. Platform must be located.so cooler discharge opening will line up with duct work. On a pitched roof the open sides of the platform frame may be covered with galvanized sheet steel or other weatherproof material. An opening or removable panel must be left in one side, large enough for access for the drain fitting in the cooler bottom. For down discharge coolers the duct should be fastened to the platform collar before setting cooler in place. The duct should have a standing flange over which the cooler discharge opening will fit. Flash and seal around the duct. Figures 2 and 3 show flashing and rain shield to provide weather tightness with flexibility. WALL MOUNTED HORIZONTAL DISCHARGE UNITS Step 1. Determine location of cooler, and of opening in the building wall, depending on duct work and building arrangement. Check with your architect or builder before cutting any structural member. Approval received, cut the wall opening frame, as shown in Figure 4. Any stud which must be cut should be headed and the opening framed as shown. Figure2. Construction of roof platform for down discharge coolers, t _""_ jl. horizontal discharge coolers, ing for wall mounted, horizontal t discharge cooler installation. -3-

step 2. Construct a platform, either from the ground or fastened to the building wall, to provide a level mounting surface for the cooler. A typical mounting platform is shown in Figure 5. Measure cooler orflnd size from catalog to determine size of platform and position of duct opening in wall. It is usually easiest to install main duct in the attic space before liftingthe cooler into place. Flash and seal around the duct so the entire entry is weathertight. Step 3. ALL UNITS Mount the cooler on the platform. For large coolers, sign and rigging companies are often available to lift the unit into place. Large coolers are of bolted construction and can be disassembled and taken up in pieces if necessary. The unit should be sealed and isolated from the platform and from the duct flange with sponge rubber or plastic seal strips. Figures 6 and 7 show typical completed installations. Anchor lines from top of cooler to roof may be necessary in areas with very high winds. / Figure 5. Typical waft-type platform for evaporative cooler. Figure6. Typical installation of roofmounted down discharge unit. Figure 7. Typical completed installation of waft mounted horizontal discharge unit. -4-

Step 4, Connect 1/4" O.D. water tubing to cold water supply, Either an adapter faucet or a saddle valve can be used for connection to the water supply line. Connect electrical conduit to junction box assembly located in corner of cooler top. EleIctrical knock outs are provided on the corner post for electrical connection convenience. Refer to wiring diagrams (located within the manual) for proper connections. All wiring must be done in accordance with all local codes. All units must be grounded in accordance to all code Step 5. requirements. Each unit contains a heavy duty constructed motor cradle. Each cradle is secured to the motor mounting bracket. Mount motor in motor cradle and secure with motor clamps provided in the bag assembly. Attach motor sheave and align belt. Adjust belt tension by sliding motor cradle. Belt tension should be set until belt can easily be deflected 1/2 to 3/4 of an inch. Secure motor cradle into position by tightening four bolts. Step 6. Connect duct work as required and install room grilles or discharge vents. For simple installations a duct equal in size to the cooler discharge opening will be satisfactory. Grilles should have four-way adjustable vanes for air flow direction. Step 7. Make the final adjustment on cooler according to the following check list: 1. Be sure duct work is complete, all dampers are open and all grilles are wide open. Check electrical input to unit for correct voltage. 2. Turn on electrical power supply. Check blower and pump motors to be sure both are operating freely.._ / ") -. Figure 8. Combination duct and direct type cooling is often used in multi-unit commercial installations. -5-

3. Check current draw of blower motor. A tong type ammeter is usually the most convenient method of m_asuring. Be sure motor current is not greater than name plate full load rating at the supply voltage used. If motor current is too high, the motor pulley can be adjusted to slow the blower wheel. Turning the free half counter-clockwise (decreasing pitch diameter) will decrease blower speed and air delivery, and decrease motor amperes. Turning clockwise will increase blower speed and increase motor amperes. The pulley must not be opened so far as to allow the belt to ride on the hub, since this will cause rapid wear. The locking set screw should only be tightened down on the flat provided. Tightening down on the threads will make the pulley difficult to adjust at any later time. Motor adjusting bolts must be moved to compensate for tighter or looser belt, depending on which way the pulley was adjusted. Set belt tension so that moderate hand pressure will depress belt at center point between pulleys approximately 1 inch. Remember that too-loose belts cause belt slippage, wear and noise, while too-tight belts cause excessive bearing wear. Refer to Figure 1. Step 8. Turn on water. Check float valve operation, and adjust to provide correct water depth in cooler bottom. Water should be 2 1/2 inches deep. " Step 9. Check for equal water flow from all distributor tubes. If water flow is too great, reduce by closing pinch fitting on pump discharge tube. Then check water flow from water trough in louver troughs. Step 10. After entire s tstem is operating, adjust dampers and grille louvers to provide air in various rooms as re_ uired for comfort. i 2 1. Motor clamps 2. Motor 3. Motor pulley i =i i " 4. Motor cradle 5. Adjustment bolts 6. Motor mount 4 6-6-.:\ (Fig. 1)

SERVICE UNIT MAINTENANCE WATER CONTROL: Coolers are controlled manually by linevalve. Turn valve on untilwater flows freely from all water distributortubes and in sufficient quantity to thoroughly soak pads. Before turning on motor, let water run a few minutes to remove dust from pads and prevent delivery of untreated air. ADJUSTABLE MOTOR PULLEY: Adjustable motor pulleys are set at the factory for maximum motor load and maximum air delivery of cooler not connected to a duct and register system. When cooler is connected to a duct system, the cooler air capacity and motor amperage decreases due to static pressure duct resistance. The adjustable motor pulley is used ONLY to compensate for duct system resistance by returning cooler and motor to maximum load capacity and should not be adjusted except for this purpose. CAUTION: When it is necessary to adjust pulley, AMPERAGE OF MOTOR MUST BE CHECKED TO MAKE CERTAIN IT DOES NOT EXCEED THE MAXIMUM ALLOWED AS STAMPED ON MOTOR SPECIFICATION PLATE. Only person with proper electrical equipment and thorough knowledge of adjustable pulleys'should attempt adjustment of motor pulley on your cooler. IMPROPER PULLEY ADJUSTMENT COULD OVERLOAD AND BURN OUT MOTOR. BELT ADJUSTMENT: Correct belt tension and alignment is important as it cuts power consumption and prolongs life of belt and motor. When installing or adjusting belt, loosen the four motor mount bolts and adjust until belt can be easily deflected 1/2 to 3/4 of an inch. DO NOT TIGHTEN BELT BY ADJUSTING MOTOR PULLEY. Align belt vertically by centering motor pulley in-line with blower pulley. Re-tighten the four motor mount bolts. m \ -,_r t_ AIR EXHAUSTING: Windows or doors at a point most distant from cooler air inlet should be left open to permit free movement of air out of area being cooled, and avoid building up static pressure. Proper location of exhaust openings is important as they guide flow of air through areas where cooling is desired. -7-

UNIT MAINTENANCE! (CONT.) WATER CONTROL: The overflow standpipe screwed into drain bushing forms a water reservoir of the cooler bottom. The floating valve regulates water supply into cooler reservoir. The depth of water is regulated by loosening the float adjustment screw and raisingor lowering float until water level remains approximately 2 1/2 deep. If manual valve is present in water supply line, open valve and allow to remain open during the cooling season. Water flow to cooler pads is furnished by the recirculating pump, and the desired amount of water is regulated by the water check clamp located on pump hose between pump and water distributor. BLEED OFF A'I-rACHMENT KIT: A small, pinpoint amount of =used"water is bled off or discarded whenever the pump is in use. This keeps the water fresh and free from mineral concentrations. CLEANING: The cooler cabinet and recirculating pump should be periodically inspected, cleaned and all scratches or bare metal should be covered with suitable protective paint. To prevent excessive deposits of water minerals and sediment, the reservoir pan should be cleaned at least every sixty days of operation. When a recirculating pump is used, remove overflow standpipe from drain fitting and allow water to drain, thoroughly clean pump and components making sure that impeller is free before cooler operation. Replace standpipe and fill reservoir. Operate cooler 15 minutes, then allow all water to drain through, thus cleaning entire system, always drain water reservoir completely when cooler is not in use over prolonged periods and particularly at end of cooling season. OILING: All motors and blower shaft bearings are oiled at the factory, but should be checked before operating cooler. If need for oiling is indicated, use any good grade S.A.E. No. 20 or 30 oil. Apply 2 or 3 drops of oil to each oil cup on cooler motor and pump motor. The oil cups on blower shaft bearings should be filled. Under normal use, oiling is required every three months of operation. THE SLIDING DAMPER: (Optional) On the blower, housing should be closed in the fall to keep cold air from entering the building. For pre-season cleaning, with the damper still closed, the blades of the blower are accessible for cleaning through the opening in the blower housing, this makes it possible to keep debris from entering the home. IMPORTANT: Before operating cooler at the beginning of each cooling season, turn blower wheel, cooler motor and pump motor shafts by hand to make sure they turn freely. Failure to do this may result in burning out motor. FILTER PADS: Filter pads should be replaced with fresh aspen fiber excelsior and DUSTRAP filter at least once a year, at the beginning of each cooling season. The need for changing pads mor_ ff_quently varies with locality and rapidity with which dirt, alkali, and o.th0rforeign matter accumulates in pads. If cooling efficiency is impaired, it may be desirable to change pads several times during cooling season. -8-

PAD REPLACEMENT: 1. With Iouvered panel lying on flat surface, wire retainer face up, grasp retainer in center and pull upward, thus bowing retainer, at the same time pulling out ends of wire from underneath flange of Iouvered panel. 2. Clean Iouvered panels, if necessary. 3. Replace pad with new material, being sure pad is of uniform thickness, without voids, which permit untreated air to enter the cooling system. 4. Replace wire pad retainer and reverse steps to complete pad replacement in same manner as removal. MOTOR REPLACEMENT: The motor can easily be replaced by removing plug from junction box and removing motor clamps. CAUTION: DISCONNECT ALL ELECTRICAL POWER SOURCE PRIOR TO PERFORMING ANY MAINTENANCE ON UNIT. Remove louver panels using lower handles. Do not remove panels by inserting hands into open louver sections. Replace motor and motor cord, and secure motor with clamps. Secure motor sheave and connect motor plug to junction box receptacle. Turn on power and check amp draw on motor. Adjust motor sheave as necessary (Ref. Page 7). Turn off power and secure louver panels. Turn on power. -9-

TROUBLESHOOTING Here is a listing of some common service problems, with probable causes and suggested remedies: PROBLEM PROBABLECAUSE SUGGESTED REMEDIES Inadequate Cooling: Cooler undersized Clogged or dirty filters Replace with larger cooler Replace with pads Dry pads or lack of water while cooler is operating Insufficient air discharge openings or inadequate exhaust from area being cooled, causing humidity building up and discomfort. Check water distributing system for possible obstruction in tubing. Check pump. Make sure there is adequate provision for exhausting air from area being cooled. Excessive humidity. (See also item above re: inadequate exhaust) In some areas, there may be a few days during the summer when the relative humidity is high, resulting in complaints about poor cooling. The limitations of an evaporative cooler under conditions of high wet bulb temperature should be explained to the customer. Blower turning backwards Reconnect motor for correct direction Blower installed backward Remove and reinstall blower wheel to turn in correct direction Belt slipping or... -._ wearing excessively: Blower runningtoo slow Belt loose. Moisture getting on belt. Pulleys out of line Check motor amps. If below name plate amperage, readjust variable pitch motor pulley to increase blower speed, Adjust belt Check Align pulleys for loose water connections -10-

PROBLEU PROBABLECAUSE : SUGGESTED REMEDY Belt slipping or wearing excessively (cont.): Blower fails to start: Worn belts Replace belts Worn or imperfect pulleys Replace pulleys No fuse or fuse blown Replace fuse Loose electrical Check all electrical connections Connections Defective switch Replace switch Motor burned out Replace motor Belt or pulley loose Check belts or pulleys Motor overheats or burns out: Pump fails to operate: Belt broken or missing Belt too tight Improper adjustment of variable pitch motor pulley causing motor overload Low voltage Incorrect power supply Incorrect motor, motor has been changed Pump motor failure Improper wiring of pump leads to motor and switch Loose electrical connections Install new belt Check belt tension Check variable pitch motor pulley for proper adjustment. A variable pitch motor pulley can be adjusted to accommodate the speed of the blower to the ductwork used. Adjust pulley so motor amperes do not exceed fullload amperes shown on motor name plate, Check voltage and consult with power company if voltage is low Check power supply against motor name plate specifications Be sure motor is correct size for cooler Replace complete pump Recheck pump leads connected to power and switch. Check electrical connections Pump switch faulty Replace pump switch -11 -

PROBLEM PROBABLE CAUSE SUGGESTED REMEDY Pump runs but does not circulate water, pump runs but pads lack water: Cooler noisy: Insufficient water in bottom of cooler pan Pump screen plugged Clogged tubing Foreign matter lodged in the water distributingtee Wheel rubbing on housing Wheel out of balance due to dirt, etc: Cooler delivering more air than needed Improper alignment of blower bearings Improper adjustment of blower shaft set collars Belt "squealing" Check float adjustment, water should be maintained at approximately 2 1/2" depth. Clean screen Clean the tubing Remove pump hose from the tee and clean out foreign matter Re-position wheel Check wheel and clean Adjust motor pulley to slow down blower Loosen blower bearings and realign Adjust blower shaft, set collars snug but not too tight Tighten bell by adjusting motor. Apply bell dressing to belt. In some cases it may be necessary to replace bell Continuous overflow of water: Float valve adjustment incorrect Adjust float valve Water being thrown into room: Valve stuck open because of lime deposits Loose Dist. tubing or pump hose connections Break in copper tubing or pump hose Cover not installed on float valve to prevent spray Pads not properly installed in holders and have sagged -12- Clean valve and adjust Check and tighten all tubing and hose connections Replace any cracked or I_rol_en tubing or hose Install cover on float valve to prevent spray Make sure filters are properly installed in holders, which prevent sagging filters.

PROBLEM PROBABLECAUSE SUGGESTED REMEDIES Water being thrown into room, (cont): Discharge ends of water distribution tube do not fit into the water distributing troughs in top of pad frames Make sure water distribution tubing discharges water into water distribution troughs in top of pad frames Foam or suds Old pads that have developed thin spots Pump delivering excessive water to filters When filter pads are installed where the water is relatively soft, if the wood has a higher than normal amount of saponin, the pump may churn up suds f Algae in sump water Filters remain wet after shut down Water Keeps lower always wet level too high. edge of filter Replace with new pads Install hose clamps on hose to restrict supply of water. Drain and refill cooler sump with fresh water. May need to be repeated for severe cases Drain cooler bottom and clean thoroughly, fill with fresh water. Install new pads Allow blower to run for about 10 minutes after pump is shut off to dry off pads Re-adjust water level so filters are above water in cooler bottom Rapid formation of white deposits on pads and louvers: Dust and alkali pulling off pads: High mineral content of supply water Pads dry when cooler started up Install drain connections from cooler with a shut-off valve in a convenient location. Instruct user to open valve about once a week to flush out all the water in the cooler. Frequency of flushing will vary depending on hardness of water supply and amount of usage of the cooler. Adjust m bleed off. Turn pump on about 10 minutes before blower is turned on -13-

BASIC WIRING DIAGRAMS MOTOR _1_ BLACK IiRED WHITE JUNCTION SWITCH ] 115 VOLT i 115 V. LINE T SW_TCH POWER LINE REC. PUMP Q MOTOR JUNCTION I ',', _ RED E WHITE BLACK SWITCH I 115 VOLT 115 V. LINE ii POWER LINE REC. PUMP O \ GREEN GROUND RELAY JUNCTION AUTO SWITCH BOX _'_ YELLOW _ BLK. V. LINE MOTOR LOO RED io c PWR. LINE WHITE LO /.j_.%_ REC. I [ 'i PUMPI k_" WHITE GREEN ol I 11 5 i GROUND CAUTION: Always make sure unit is properly grounded in accordance with National Bectric Code. Do not connect pump wire to Hi and Low terminals. Important -- Improper wiring will void warranty. -14-