FEO Initiation Devices Dean McLellan

Similar documents
ELEVATORS AND FIRE ALARM SYSTEM INTERFACES CANADIANFIRE ALARM ASSOCIATION 2011 ONTARIO ANNUAL TECHNICAL SEMINAR

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Recent Revisions and Proposed Key Changes to Fire Code

Emergency Power & Fire Service Checklist

CFAA Technical Seminar Ontario Building Code Updates to 2015

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

Introduction Limited-Use / Limited-Application

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

NFPA Changes

COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW?

rpsa FIRE PROTECTION ENGINEERS

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

BUILDING CODE COMMISSION

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

Elevator Emergency Equipment Instructor s Guide

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

TG FIRE DRILLS. Office of the Fire Marshal and Emergency Management

Bold items are particular to the City of Euless

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

Fire Alarm, Water Flow Alarm & Signaling Systems

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016

SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS

Module 9: Ontario Building Code Fire Fighting Provisions

AEDARSA. Alberta Elevator Stakeholders What s NEW Alberta Regulation AR 192/2015

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

The Owner will provide the QEI inspection and certification services.

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

FORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION

Understanding and Managing Fire Safety in Housing Accommodation

APPENDIX K MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS

Short Term Accommodations Fire Code Requirements

FIRE SAFETY PLAN. Building Name. Address. Prepared By. Date Prepared. Page 1 of 36

A17 Standards Committee Interpretations Volume 3

Presentation Material: The material will be presented in a PowerPoint format and available digitally/ paper.

Category V. NOTE: Fire Investigations are covered in Criterion 5D.

FIRE PREVENTION AND PROTECTION*

Smoke Control Design and Activation. CFAA NCA Technical Seminar 2015

BUILDING CODE COMMISSION

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

You are required to READ ALL PAGES. of this application

FIRE CODE ENFORCEMENT POLICY GARY LAFRAMBOISE CHIEF FIRE PREVENTION OFFICER

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

APPENDIX A International Building Code Amendments

ASME A17.1/CSA B44 Handbook

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Fire Alarm System Fundamentals

Recommended Amendments to the 2009 International Building Code North Central Texas Council of Governments region

Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007

Building Emergency Response Scenario

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

CAN/ULC-S561. To comply, or not to comply. actually it s not even a question! Underwriters Laboratories of Canada. By Alan Cavers & Brian McBain

El Reno Fire Department Fire Alarm Plan Review Worksheet

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

2012 Ontario Building Code Update

ICC CODE CORNER 2012 IFC Code & Commentary

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

Chubb Monitoring Solutions

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

Review of Revisions to NFPA 1, 2015 Edition

FIRE SAFETY PLAN FOR NAME OF BUSINESS (IF APPLICABLE) STREET ADDRESS CITY, PROVINCE POSTAL CODE BUILDING USE # OF UNITS

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

Building and Development

WEST VIRGINIA UNIVERSITY

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

FLORIDA DEPARTMENT OF FINANCIAL SERVICES

GENERAL AREAS OF INSPECTION

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Large Family Daycare Guideline

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

ELEVATORS AND FIRE SERVICE. CODE CHANGES in. Presenter: Eric Peterson, P. Eng.

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

BY-LAW AMENDING THE BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL (RCG )

Winnipeg Fire Department Fire Prevention Branch

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

Purpose of Emergency Response Program Emergency Response Team / Leader Evacuation Procedures Building Life Safety System Virtual Evacuation Building

Transcription:

FEO Initiation Devices Dean McLellan

Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC)

A17/B44 Code Code harmonization took place in 2000 Current Code enforced in Ontario for new construction or altered devices; ASME A17.1-2010/CSA B44-10

Current Enforcement in Ontario A17/B44 Code with exceptions in CAD for some sections of code Section 2.27.3.2.2 is one exception from code and replaced with that in the CAD this was done in order to help owners better comply with existing systems

Existing Device VS Existing Building Existing Building with Existing Elevator and elevator being ungraded comply to CAD 2.27.3.2.2 a thru h New or Existing Building with new device elevator must comply to CAD 2.27.3.2.2 a thru c

New Elevator/New Building 2.27.3.2.2 In jurisdictions enforcing the NBCC, the requirements of (a) through (c) are applicable to new installations: (a) smoke detectors, or heat detectors in environments not suitable for smoke detectors (fire alarm initiating devices), used to initiate Phase I Emergency Recall Operation, shall be installed in conformance with the requirements of the NBCC, and shall be located (1) at each floor served by the elevator (lobby) (2) in the associated elevator machine room, machinery space containing a motor controller or electric driving machine, control space, or control room, and (3) in elevator and dumbwaiter shafts per, (i) O. Reg. 350/06 Article 3.2.4.10.(e) if a fire alarm system is required by O. Reg. 350/06 Article 3.2.4.1, except as provided in O. Reg. 350/06 Article 3.2.4.15., or (ii) O. Reg. 332/12 Article 3.2.4.11.(e) if a fire alarm system is required by O. Reg. 332/12Article 3.2.4.1, except as provided in O. Reg. 332/12 Article 3.2.4.16.

New Elevator/New Building cont d (b) alternate floor recall required by 2.27.3.2.4 is not required if the floor area containing the recall level is sprinklered. (ref O.Reg 350/06 article 3.2.4.14.(3) or O. Reg. 332/12 article 3.2.4.15.(3)). Note: If fire detectors are provided in the hoistway at or below the lowest landing of recall, an alternate (upper) recall shall be provided in accordance with 2.27.3.2.3(d).

New Elevator/Existing Building (c) where a building fire alarm system is not required by OBC or where an alteration is being performed and the existing building fire alarm system does not provide suitable signaling, the devices referred to in 2.27.3.2.2(a) shall be installed and shall be connected to a Dedicated Function Fire Alarm (DFFA). The installation of this control panel shall conform to the following:

New Elevator/Existing Building (1) in a building with an existing fire alarm system, the building fire alarm system and the Dedicated Function Fire Alarm system shall be interconnected. [CAD Amendment-261/13] (2) in a building without an existing fire alarm system, the Dedicated Function Fire Alarm control panel used to initiate elevator recall shall be permanently identified as Elevator Recall Control and Supervisory Control Unit in lettering not less than 6mm (0.25in.) in height. (3) the installation or alteration of any fire alarm systems or DFFA system must be installed in accordance with CAN/ULC-S524 (Installation of Fire Alarm Systems), and (4) where a DFFA has been installed to serve as an Elevator Recall Control and Supervisory Control Unit, the system shall be subject to inspection and testing in accordance with CAN/ULC-S536 (Inspection and Testing of Fire Alarm Systems). For these systems the owner or contractor shall provide written confirmation of testing at the initial inspection, and confirmation of annual testing shall be available to an inspector upon request.

New Elevator/Existing Building NOTE(S): 1. (2.27.3.2.2(a) (b) and (c) ): Smoke and heat detectors (fire alarm initiating devices) are referred to as fire detectors in the NBCC. Pull stations are not deemed to be fire detectors. 2. The installation or alteration of a fire alarm system, including dedicated function fire alarm systems require permits and installation by qualified personnel. 3. See 8.6.11.1 for notes related to DFFA testing. This requirement is for monthly testing of fire system

Existing Elevator/Existing Building (d) for alterations 8.7.2.16, 8.7.3.17 (change in type of service) and 8.7.2.27.6, 8.7.3.31.7 (operation control), that require conformance to 2.27, (1) requirements 2.27.3.2.2(a)(1), 2.27.3.2.2(a)(2) and 2.27.3.2.2(c) do not apply within a floor area if the floor area is sprinklered and the sprinkler system is electrically supervised in conformance with O. Reg. 350/06 Sentence 3.2.4.9.(2). The activation of the electrically supervised system shall cause automatic recall. (2) requirements 2.27.3.2.2(a)(3) does not apply.

Existing Elevator/Existing Building (e) for alterations 8.7.2.27.4 and 8.7.3.31.5 (controllers), if firefighters emergency operation was required or provided at the time of the original installation, or required or provided by a subsequent alteration, the requirements of (1) below apply, otherwise the requirements of (2) below apply: (1) requirements, 2.27.3.2.2(a), 2.27.3.2.2(b) and 2.27.3.2.2(c) (2) the installation shall as a minimum conform to the requirements of 2.27.3.1 (manual recall),unless the introductory exemption in 2.27.3 applies.

Existing Elevator/Existing Building (f) for alterations 8.7.2.27.5 and 8.7.3.31.6 (motion control), emergency operation and signaling devices where required by NBCC at the time of the original installation, or required or provided by a subsequent alteration, the requirements of (1) below apply, otherwise the requirements of (2) below apply: (1) requirements of 2.27.3.2.2(a), 2.27.3.2.2(b) and 2.27.3.2.2(c) (2) the installation shall as a minimum conform to the requirements of 2.27.3.1 (manual recall), unless the introductory exemption in 2.27.3 applies.

Existing Elevator/Existing Building (g) for alterations under 8.7.2.28 or 8.7.3.31.8 (emergency operation and signaling devices) or 8.7.2.28 2 or 8.7.3.31 9 (fire code retrofit) that Require conformance to all or part of 2.27 the requirements of 2.27.3.2.2(a), 2.27.3.2.2(b) and 2.27.3.2.2(c) apply.

Question #1 So if I have a brand new building that an elevator is being installed in what do I need?

Answer to Question #1 As a minimum you will need; smoke detectors, or heat detectors in environments not suitable for smoke detectors in every elevator lobby elevator machine room, machinery space containing a motor controller or electric driving machine, control space, or control room elevator shafts

Additional Information to Question #1 You may have to install a separate detector if the recall level is not sprinkled in order to send the elevator to a different landing

Question #2 If a new elevator is installed in an old building to I have to replace the existing fire alarm system, and do I still need smoke/heat detectors?

Answer to Question #2 No you do not have to replace the existing system as along as the DFFA (Dedicated Function Fire Alarm) will tie into it Yes you will still need smoke/heat detectors in the designated areas

Question #3 Can a sprinkler pressure switch be used instead of a smoke detector to recall the elevators?

Answer to Question #3 The pressure switch cannot be used instead of smoke detectors on a new elevator however on an existing elevator with an existing fire alarm system it may be used.

Question #4 If an elevator company installs a new controller do I have to do anything to the fire alarm system or if it does not have one does one have to be installed?

Answer to Question #4 If the device has an existing fire alarm system smoke/heat detectors will have to be installed in the elevator lobby s, machine room, machinery space etc and the elevator shaft If the device did not have an existing system then as a minimal you will have to have manual recall

Summary The key for a fire alarm company is to work with the elevator company as the fire system on an exiting building may vary depending on what part of the elevator was changed.

TSSA Contacts Rob Kremer, Manager Engineering rkremer@tssa.orgg, 416-734-3344 Marc Tevyaw, Technical Specialist mtevyaw@tssa.org, 905-379-9117 Dean McLellan, Incident Management Specialist dmclellan@tssa.org, 613-329-8758

QUESTIONS