Certification Report of the ST3000 Pressure Transmitter

Similar documents
Certification Report of the ST 3000 Pressure Transmitter with HART 6

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

PPA Michaël GROSSI - FSCE PR electronics

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

IEC Functional Safety Assessment

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, MN USA

Failure Modes, Effects and Diagnostic Analysis

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

United Electric Controls One Series Safety Transmitter Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

Soliphant M with electronic insert FEM52

Failure Modes, Effects and Diagnostic Analysis

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Digital EPIC 2 Safety manual

IEC Functional Safety Assessment

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Technical Report Proven In Use SITRANS P500

Failure Modes, Effects and Diagnostic Analysis

FUNCTIONAL SAFETY CERTIFICATE

Failure Modes, Effects and Diagnostic Analysis

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Pressure Transmitter cerabar M PMC 41/45 cerabar M PMP 41/45/46/48 with Output Signal ma/hart

Failure Modes, Effects and Diagnostic Analysis

Session Ten Achieving Compliance in Hardware Fault Tolerance

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

SLG 700 SmartLine Level Transmitters Guided Wave Radar Safety Manual 34-SL Revision 4.0 December 2017

Safety in the process industry

Report Nr

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. February Valves

Mobrey Magnetic Level Switches

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions

FUNCTIONAL SAFETY: A PRACTICAL APPROACH FOR END-USERS AND SYSTEM INTEGRATORS

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

Proof Testing Level Instruments

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

FUNCTIONAL SAFETY CERTIFICATE. BG Break Glass Unit

Integrated but separate

Automation, Software und Informationstechnologie

The agri-motive safety performance integrity level Or how do you call it?

Proservo NMS5- / NMS7-

Changes in IEC Ed 2

New Developments in the IEC61511 Edition 2

Measurement of Safety Integrity of E/E/PES according to IEC61508

IEC61511 Standard Overview

Functional Safety: the Next Edition of IEC 61511

Is your current safety system compliant to today's safety standard?

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

Rosemount 2140:SIS Level Detector

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

Functional Safety Manual June pointek CLS500/LC500

ADIPEC 2013 Technical Conference Manuscript

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Technical Manual for the Manual Alarm Call Point BG

New requirements for IEC best practice compliance

Deltapilot S FMB70. Functional Safety Manual. Level and Pressure Measurement with Output Signal ma

Automation, Functional Safety. Assessment of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT Rockwell Automation, USA

Siemens Process Automation End-user Summit- 2011

SAFETY INTEGRITY LEVEL MANUAL. IEC and IEC XP95 and Discovery SIL Approved Product Range

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

Cerabar S PMC71, PMP71, PMP75

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

Simply reliable: Process safety from Endress+Hauser

Options for Developing a Compliant PLC-based BMS

ACCURATE FAILURE METRICS FOR MECHANICAL INSTRUMENTS IN SAFETY APPLICATIONS

Australian Standard. Functional safety Safety instrumented systems for the process industry sector

Report to the Certificate

FUNCTIONAL SAFETY IN FIRE PROTECTION SYSTEM E-BOOK

SAFETY MANUAL. IR5000 Open Path Hydrocarbon Gas Monitoring System

Addressing Challenges in HIPPS Design and Implementation

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure

2015 Functional Safety Training & Workshops

INTERNATIONAL STANDARD

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

Functional Safety Solutions

Safety Transmitter / Logic Solver Hybrids. Standards Certification Education & Training Publishing Conferences & Exhibits

Transcription:

Certification Report of the ST3000 Pressure Transmitter Revision No.: 1.0 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2006-Dec-12 SAS-128/2006T ST3000 Pressure Transmitter Honeywell International Inc. Industrial Measurement & Control 1100 Virginia Dr. Fort Washington, PA 19034, USA M.IB5.03.085.02.SLA Branch South Digital Control & Communication Systems Section Computer Based Systems Software & Electronics Laboratory Halderstr. 27 / Germany Dipl. Ing. (FH) Josef Neumann Functional Safety Manager Reviewer: Josef Neumann Dipl.-Ing. Gerhard M. Rieger Branch Manager Gerhard Rieger This document is only valid in it s entirety and separation of any part is not allowed.

Content Page 1 Subject of certification...3 2 Basis of certification...4 3 Standards...5 4 Definitions...6 5 Overview about the system configuration...7 5.1 Primary Safety Functions...8 5.2 Secondary Safety Functions...8 5.3 Logic Solver Inputs...8 6 Hardware and software identification...9 7 Documentation...9 8 Assessment activities and results...11 8.1 Development Process...11 8.2 System Architecture...14 8.3 Proven In Use...15 8.4 Hardware Design and FMEDA...16 8.5 Software Design and Implementation...19 8.6 Verification and Validation...19 8.7 Safety Manual...20 9 Summary...21 Page 2 of 21

1 Subject of certification This report compiles the results of the assessment of the ST3000 Pressure Transmitter of Honeywell International Inc. Honeywell International Inc. ordered the services of (thereafter known has TÜV NORD SysTec) to certify the ST3000 Pressure Transmitter because of its use in safety-relevant applications by the process industry (e.g. oil & gas and chemical industry) with the goal of achieving a successful approval of ST3000 Pressure Transmitter in the framework of the certification of safety-components. The ST3000 Pressure Transmitter is to be certified in accordance with IEC 61508 for single use in Safety Integrity Level 2 (SIL 2) applications. The development and software process should be certified in accordance with SIL 3 requirements allowing the use of dual redundant ST3000 Pressure Transmitters in SIL 3 applications. The Honeywell International Inc. ST3000 Pressure Transmitter is based upon the standard ST300 Smart Pressure Transmitter which already has a documented history starting at 1983 for the proven in use consideration under IEC 61508, the new industry standard for safety electronic systems. Page 3 of 21

2 Basis of certification An effective assessment in order to meet all the requirements for a complete certification requires the following testing segments to be successfully completed: Functional Safety Management (FSM) Development process Architecture Safety system structure Hardware design Software design and implementation Proven in use verification and validation Test specification Including the following principal functional safety considerations: Hardware failure-behaviour Software failure-avoidance Probabilistic and Common Cause consideration Safety Manual Page 4 of 21

3 Standards Because of the application area of the ST3000 Pressure Transmitter, the following standard is relevant: Functional Safety IEC 61508 IEC 61508-1:1998 IEC 61508-2:2000 IEC 61508-3:1998 Functional safety of electrical/electronic/programmable electronic safety-related systems Part 1: General Requirements General definitions: Type B, Low Demand Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems, Required SIL 2 Part 3: Software requirements Required SIL 3 Page 5 of 21

4 Definitions FIT FMEDA FSM HART Low demand mode PFD PFDAVG SFF SIL SRS Type A component Type B component λ du Failure In Time (1 * 10-9 failures per hour) Failure Mode Effect and Diagnostic Analysis Functional Safety Management Highway Addressable Remote Transducer Mode, where the frequency of demands for operation made on a safety-related system is no greater than one per year and no greater than twice the proof test frequency Probability of Failure on Demand Average Probability of Failure on Demand Safe Failure Fraction Safety Integrity Level Safety Requirements Specification Non-Complex component (using discrete elements); for details see 7.4.3.1.3 of IEC 61508-2 Complex component (using micro controllers or programmable logic); for details see 7.4.3.1.3 of IEC 61508-2 Dangerous Undetected (DU) Failure Rate [1/h] Page 6 of 21

5 Overview about the system configuration The Honeywell International Inc. ST3000 Pressure Transmitter is a two-wire 4 20 ma smart device classified as Type B according to IEC61508. The transmitter contains self-diagnostics and is programmed to send it s output to a specified failure state, either high or low upon internal detection of a failure. The device can be equipped with or without display. The software extensions include the following functionality: Compliance with HART specification version 6.2 (HCF_SPEC-12, Revision 6.2, dated 25 Jan 05). Addition of automatic diagnostic to detect microprocessor failures PROM ST3000 Electronics Housing Pressuresensor Multiplexer A/D Micropro cessor D/A Proportional 4 to 20 ma PV Output Meter Body Digital I/O Pressure Picture 1: Block structure Page 7 of 21

5.1 Primary Safety Functions The Honeywell International Inc. ST3000 Pressure Transmitter measures the (pressure gauge, differential, absolute) of a process and reports the measurement within a safety accuracy of 2%. 5.2 Secondary Safety Functions The Honeywell International Inc. ST3000 Pressure Transmitter performs automatic diagnostics to detect internal failures and reports these failures via out of band signals on the 4 20 ma output. 5.3 Logic Solver Inputs The logic solver must be configured so that the engineering range in the transmitter matches the expected range of the logic solver. To take advantage of the internal diagnostics in the ST3000, the logic solver must be configured to annunciate an out of band current reading (greater than 20.8 ma. or less than 3.8 ma.) in standard instrument or (greater than 21.0 ma. or less than 3.6 ma.) with Namur NE option as a diagnostic fault. The logic solver configuration must consider the slew time of the current signal and ensure that filtering is used to prevent a false diagnostic failure annunciation. Page 8 of 21

6 Hardware and software identification The following versions are considered for the certification: Schematic: 51205697, C 9/23/02 Hardware (Layout): 51309397-002 Software: Rev. 34 7 Documentation The evaluation is based on the following documents of the ST3000 Pressure Transmitter [D1] Project Plan, Vers. 1.5, 2006-01-25 [D2] Program Management Plan, Vers. 0.7, 2006-07-11 [D3] Product Abstract, Vers. 0.3, 2006-02-23 [D4] Firmware Development Process, ST3000 and STT25H Upgrade Projects, Vers. 0.7, 2006-07-11 [D5] Software Maintenance Document, R300SMD, Vers. 4.0, 1999-08-20 [D6] Risk Management Plan, Vers. 0.6, 2006-04-28 [D7] Software Requirements Specification, Vers. 1.5, 2006-02-14 [D8] High Level Design for SIL 2 implementation, Vers. 1.02, 2006-05-17 [D9] HART Burst Mode Communications for ST3000, Vers. 1.3, 2005-12-26 [D10] Proven In Use Assessment, Vers. 1.1, 2004-11-12 [D11] Failure Modes, Effects and Diagnostic Analysis, Vers. 1.1, 2006-06-16 [D12] Integration Test Plan, Vers. 1.02, 2006-06-06 [D13] Unit Test Plan for SIL2 implementation, Vers. 1.11, 2006-07-17 [D14] Unit Test Procedure, Vers. 1.0, 2006-05-23 [D15] Unit Test Report, Vers. 1.01, 2006-07-13 [D16] Fault Injection Testing, Vers. 4.0, 2006-07-14 [D17] ST3000 Hart 5 Test Plan and Test Case Design, Vers. 0.6, 2006-08-06 [D18] Test Plan Results, Vers. 1.00, 1999-07-29 Page 9 of 21

[D19] Test Report, Vers. 0.3, 2006-12-07 [D20] Traceability Matrix, V1.0, 2006-07-11 [D21] Internal Review Comments Document, V1.01, 2006-07-13 [D22] Safety Manual, Doc. No. 34-ST-25-31, 2006-07-10 [D23] Team Competency Summary, Vers. 1.0, 2006-07-11 The assessment is based on the following documents of Fehler! Verweisquelle konnte nicht gefunden werden.: [D24] Offer for a type approval and certification of the ST3000 HART Pressure Transmitter, Vers. 1.0, 2006-03-22 [D25] Protocol of the document reviews, Vers. 1.0, 2006-07-11 [D26] Fault injection test report, Vers. 1.0, 2006-07-11 [D27] Checklist according IEC 61508, Vers. 1.0, 2006-12-01 Page 10 of 21

8 Assessment activities and results 8.1 Development Process General aspects and scope: In this step of assessment, a safety management audit has been performed to cover the relevant requirements of the IEC 61508, in respect of the fulfilment of the requirements to the safety quality procedures. The scope of the Functional Safety Management Audit covers the specified Safety Lifecycle Phases of the IEC61508. The scope for Honeywell International Inc. is as follows: For design, developing, manufacturing and integration of microprocessor based transmitters. For the Functional Safety Management Audit according to IEC 61508 it was essential that the functional safety management and the software development process are designed for the SIL 3 level to allow the set up of a redundant ST3000 Pressure Transmitter system in a SIL 3 environment. The FSM procedures are used to reduce the systematic failure rate. Honeywell International Inc. has created the following documents to define the FSM activities: Project Plan [D1] Program Management Plan [D2] Product Abstract [D3] Firmware Development Process [D4] Software Maintenance Document [D5] Within the project all safety relevant definitions are defined by the Functional Safety Management and the normative requirements. Page 11 of 21

Structuring of the development process: The documents [D1] to [D5] describe the Honeywell International Inc. development processes, procedures and work-instructions. TÜV NORD SysTec visited the Honeywell International Inc. development site as an external assessment department, toured the facilities and interviewed the Safety Design Team in order to understand all the relevant corporate procedures. They then extracted the most important functional safety management requirements from the standards and prepared documents indicating needed enhancements of the standard processes. TÜV NORD SysTec has reviewed this document to discuss the overall FSM requirement activities for the project with Honeywell International Inc. TÜV NORD SysTec has than discussed the relevant items with Honeywell International Inc. in a meeting and reviewed the documents for the safety aspects of the system. Honeywell International Inc. is covering the following areas: Functional Safety Management Quality Management System Development of Safety Sub-Systems (Realization) Verification & Validation activities (Testing) The focus of the interview with Honeywell International Inc. was to demonstrate compliance with the appropriate sections of the IEC61508 standard. The following sections were considered: Specific Objectives for Functional Safety Change Management (Modification Process) Maintenance The reviews with Honeywell International Inc. were related to the following areas: Page 12 of 21

Safety Requirement specification Safety Architectural Constrains Safety Hardware Requirements Safety Software Requirements Proven In Use documentation Verification & Validation of Safety Products Safety Manual It was essential for the audit to discuss the safety aspects of the project with the participants and to ask for the relevant documents and to access all relevant information. Actual documentation from the ST3000 Pressure Transmitter project was partly reviewed and the statements of the participants were compared with the relevant parts of the documents. Verification & Validation activities (Testing): For verification & validation the independent test engineers are responsible for all activities within this segment. They create the test specifications for specific projects used by the development engineers. The functional tests and integration and validation testing was done by independent test engineers. The test engineers must have specific knowledge about safety functions of the specific project. Internal training is therefore an important method to improve the knowledge of the test engineers. This could be proved by interviews and with reviews of examples of the corresponding documents. Result: The audits and document reviews performed from the 10 to 11 of July 2006 with Honeywell International Inc. have shown that the Functional Safety Management System, defined in the documents [D1] to [D5] complies with the applicable sections of the IEC 61508. No major findings were detected in the audit. Page 13 of 21

If changes to the Safety Management Systems are performed than TÜV NORD SysTec must be informed. 8.2 System Architecture The system documents [D7] to [D9] have been reviewed to verify compliance of the system architecture with the standard listed in clause 3 "Standards". Based on the set of requirements TÜV NORD SysTec has evaluated whether the implemented fault detection and fault control measures which are defined for the ST3000 Pressure Transmitter were sufficient to meet the requirements. The system architecture was evaluated in regards to completeness and correctness against the Safety Requirements Specification and the System FMEDA. The system architecture have to be designed for a Type B subsystem according the IEC 61508-2 with a Safe Failure Fraction of 90% or higher. The FMEDA verified the defined safe state of the ST3000 Pressure Transmitter in the event of possible malfunctions. Probable deviation from the specified function of the unit was also considered to be a malfunction. Result: The review from TÜV NORD SysTec has shown that the system architecture of the ST3000 Pressure Transmitter is consistent against the Safety Requirements Specification. The specifications in the documentation are consistent and complete and clearly presented. The system concept with the chosen architecture design and the selected measures of fault detection and fault control is able to fulfil the Safety Integrity Level 2 with a Safe Failure Fraction of >90%. Page 14 of 21

8.3 Proven In Use For a device to be considered proven-in-use the volume of operating experience needs to be considered. For the Honeywell International Inc. ST3000 Pressure Transmitter this information is obtained from the Operation Experience and Warranty Information. The Honeywell International Inc. ST3000 Pressure Transmitter was first introduced in January 1983. In this time period there have been no significant revisions or changes to the design. The operating experience and warranty information indicates that the total number of shipped units during this time period is 1,291,023. For failure rates calculated on the basis of field returns only the hours recorded during the warranty period of the manufacturer are used, since this is the only time frame when failures can be expected to be reported. It must be assumed that all failures after the warranty period are not reported to the manufacturer. Honeywell International Inc. offers a 12-mounth warranty period; this period starts on the date of shipment. Volume of operating experience must be based on installation dates and not on shipment dates. Since installation dates are not available it is assumed that the pressure transmitters are installed 6 months after shipment. Using this assumptions and restrictions the number of operational hours is estimated to be: Operation Hours = 10,075,132,920 hrs These operating hours are considered to be sufficient taking into account the medium complexity of the sub-system and the use in SIL 3 safety functions. In the calculation of the operation hours it is assumed that the units shipped include units up to a year before the field failure reporting hereby ensuring that all failures that occur to the included units are accounted for. Page 15 of 21

Result: The documented operating hours are considered to be sufficient for the use at SIL 2 or SIL 3 applications, depending on redundancy and the calculation of the PDF and SFF and taking into account the medium complexity of the subsystem. 8.4 Hardware Design and FMEDA A Failure Modes and Effects Analysis (FMEA) is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or reduce the chance of failure, and to document the system in consideration. A FMEDA (Failure Mode Effect and Diagnostic Analysis) is an extension of the FMEA. It combines standard FMEA techniques with additional analysis to identify online diagnostic techniques and the failure modes relevant to safety system design. It is a technique recommended to generate failure rates for each important category (detected, dangerous undetected, fail high, fail low, annunciation) in the safety model. The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the ST3000 Pressure Transmitter: Only a single component failure will fail the entire product An additional ROM testing is implemented (CRC16 checksum) An additional RAM test is implemented (walking 1 and walking 0) Failure rates are constant, wear out mechanisms are not included. Propagation of failures is not relevant. All components that are not part of the safety function and cannot influence the safety function (feedback immune) are excluded. The application program in the safety logic solver is configured to detect under-range (Fail Low), over-range (Fail High) and Fail Detected failures and does not automatically trip on these failures; therefore these failures have been classified as dangerous detected failures. The HART and DE protocol are only used for setup, calibration, and diagnostic purposes; not for safety critical operation. Page 16 of 21

The stress levels are average for an industrial environment and can be compared to IEC 60654-1, Class C with temperature limits within the manufacturer s rating and an average temperature over a long period of time of 40ºC. Humidity levels are assumed within manufacturer s rating. The listed failure rates are valid for operating stress conditions typical of an industrial field environment similar to IEC 60654-1 class C with an average temperature over a long period of time of 40ºC. For a higher average temperature of 60 C, the failure rates should be multiplied with an experience based factor of 2.5. A similar multiplier should be used if frequent temperature fluctuation must be assumed. External power supply failure rates are not included. The following tables show the failure rates resulted from the Honeywell International Inc. ST3000 Pressure Transmitter FMEDA [D11]. Failure category Failure rate (in FITs) Fail Dangerous Detected 377 - Fail Detected (detected by internal diagnostics) 268 - Fail High (detected by the logic solver) 20 - Fail Low (detected by the logic solver) 89 Fail Dangerous Undetected 40 No Effect 64 Annunciation Undetected 6 Table 1 Failure rates ST3000 Pressure Transmitter The failure rates that are derived from the FMEDA for the ST3000 pressure transmitter are in a format different from the IEC 61508 format. Table 2 lists the failure rates for ST3000 pressure transmitter according to IEC 61508, assuming that the logic solver can detect both over-scale and under-scale currents. It is assumed that the probability model will correctly account for the Annunciation Undetected failures. Otherwise the Annunciation Undetected failures have to be classified as Dangerous Undetected according to IEC 61508 (worst-case assumption). The No Effect and Annunciation Undetected failures are classified Page 17 of 21

as safe and therefore need to be considered in the Safe Failure Fraction calculation and are included in the total failure rate. According to IEC 61508, also the Safe Failure Fraction (SFF) of the ST3000 pressure transmitter should be calculated. The SFF is the fraction of the overall failure rate of a device that results in either a safe fault or a diagnosed unsafe fault. This is reflected in the following formula for SFF: SFF = 1 - גּ du / גּ total Device גּ sd גּ su גּ dd גּ du SFF ST3000 Pressure Transmitter 0 FIT 70 FIT 377 FIT 40 FIT 91,8% Table 2: Failure rates and Safe Failure Fraction according to IEC 61508 The architectural constraint type for the ST3000 Pressure Transmitter is B. The SFF and required SIL determine the level of hardware fault tolerance that is required per requirements of IEC 61508. The SIS designer is responsible for meeting other requirements of applicable standards for any given SIL as well. The expected lifetime of the Honeywell International Inc. ST3000 Pressure Transmitter is 50 years. The failure rates of the Honeywell International Inc. ST3000 Pressure Transmitter may increase sometime after this period. When plant experience indicates a shorter useful lifetime, the number based on plant experience should be used. Result: With these results from the calculation it can be shown, that the ST3000 Pressure Transmitter fulfils SIL 2 for the hardware design in a single configuration. Page 18 of 21

8.5 Software Design and Implementation The software of the ST3000 Pressure Transmitter is based upon the standard ST300 Smart Pressure Transmitter and is considered to be proven in use according to the calculated operating hours. To provide the necessary internal testing of the hardware module to cover the IEC 61508 requirements for the Safe Failure Fraction (SFF) according SIL 2 additional tests has been implemented. This was done by adding software modules following the IEC 61508-3 SIL 3 process for software developing and implementation. These additional tests includes RAM and ROM testing and a flow control to reach a sufficient safe failure fraction > 90%. The corresponding documents have been reviewed by TÜV NORD SysTec. Result: The software design and implementation is compliant to IEC 61508 part 3 according SIL 3. 8.6 Verification and Validation The verification activities are defined by the reviews of the documentation according the specific phases of the development model (V-model). The review documentation has been discussed with responsible engineers from Honeywell International Inc. and has been reviewed by TÜV NORD SysTec. The test specification defined in the Integration Test Plan [D12] from the manufacturer has been reviewed. The list of validation tests are referenced to the Requirement Specification. The review has shown that the requirements are covered by the validation plan. After the execution of the validation tests by the manufacturer [D13] to [D19], the test results have been reviewed by TÜV NORD SysTec. The test results are also referenced to the Design Specification. Additional sample testing of the ST3000 Pressure Transmitter have been defined by TÜV NORD SysTec and a separate list of test items has been generated. The defined of tests have been executed by TÜV NORD SysTec Page 19 of 21

together with the manufacturer. The definition and results are documented in the Fault Injection Test Report for the ST300 Pressure Transmitter [xxx]. Result: The review of the Integration Test Plan and the Test Reports from the manufacturer and the execution of the sample tests by TÜV NORD SysTec have shown that the defined tests are consistent to the Design Specification and the tested results can be compared to the tests of the manufacturer. The test definitions are sufficient to prove compliance with the standard. 8.7 Safety Manual The Safety Manual [D22] has been reviewed to fulfill the requirements of the considered standard. Specifically the section about Proof Testing has been checked according the defined measures to be followed up by the end user to be compliant with the considered standard according failure detection which are not covered by the diagnostic of the transmitter. Result: The review has shown that the Safety Manual meets the requirement of the considered standard. Detailed descriptions are included for the end user to install, operate and maintain the transmitter in the required safety level. Page 20 of 21

9 Summary The assessment of the ST3000 Pressure Transmitter has shown that the system design, the safety functional management and the system structure are compliant with the IEC 61508, SIL 2 under consideration of the proven in use of the transmitter and the additional measures implemented to the transmitter. The defined development process of the software for modifications together with the proven in use consideration is in accordance with SIL 3 requirements allowing the use of dual redundant ST3000 Pressure Transmitter in SIL 3 applications. The validation and testing activities has shown compliances between the realised transmitter implementation and the safety requirements specification. The actual version of the Safety Manual must be considered for the use in safety relevant applications. Page 21 of 21