Understanding NFPA, NEC 2005 Article 409 a White Paper by Paul A. Terry, P.E.

Similar documents
ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS

National Electrical Code

Short Circuit Current Rating

SECTION ENCLOSED CONTROLLERS

Control Circuits in acc. with UL508A

2017 NEC: Impact to Electrical System Designs

Control Panel Technical guide. How to ensure trouble-free approval of your UL-compliant control panels

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

SECTION AUTOMATIC TRANSFER SWITCHES

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

SECTION FIRE PUMP AND CONTROLS

FTA550 JOCKEY PUMP CONTROLLERS

SECTION EXTERIOR LIGHTING

Molded Case Circuit Breakers, Bulletin 140G

Compatibility between Smoke Alarms and Arc-Fault Circuit Interrupters

a thriving company in a dynamic industry

Get it Right the First Time Avoid These Commonly Cited Errors

CONTENTS AUTOMATIC TRANSFER SWITCHES

Drawing Submittal Package

Guide Specification Model CTG Automatic Transfer Switch

FTA550F JOCKEY PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

Interfacing Fire Alarm, Sprinkler and Elevator Systems

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

Welcome! Siemens Industry Inc All rights reserved.

Product Specifications Warning Light Control Cabinet

NEC Requirement Guidelines 2002 Code Options for the Installation of Listed Less-Flammable Liquid-Filled Transformers

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Overview on North American Standards

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Elevator Control ES Switch

ANSI/NETA Standards Update

Drawing Submittal Package

Electrical Safety Program

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

Article by: Ark Tsisserev, Principal, Stantec Consulting Ltd.

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

PART GENERAL 1.01 SECTION INCLUDES

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

B. Section Transfer Switches: Automatic transfer switch.

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Welcome! Siemens Industry Inc All Rights Reserved.

Product Specifications Warning Light Control Cabinet

Property risk solutions

Guide to Compliance with the Electrical Workplace Safety Standards in the United States

SECTION GENERATOR PARALLELING CONTROLS

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000

PANELBOARDS & BUILDING DISTRIBUTION

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

UFGS (August 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Components and Systems suitable for World Markets and Export to North America

Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers

SEL Arc-Flash Solutions

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

Construction Codes Advisory Council

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Rutgers Environmental Health and Safety (REHS)

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Machinery Room Electrical Best Practices

SECTION LIGHTING CONTROLS

ON THE BUTTON A reference guide to environmental ratings used for push button enclosures

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

SEL Arc-Flash Solutions

Tempco s process controllers provide integrated solutions to manage your thermal loop system.

Approvals and certification

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

NEMA Applications Guide

SECTION ISOLATED POWER SYSTEMS

PUMP CONTROL CENTER (PCC)

YOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE.

EHB Series. STONESTEEL Commercial Electric Water Heaters Individually Mounted Elements Vertical or Horizontal CEMLINE CORPORATION

Fire Sprinklers Working Group Final Report

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

A. Introduction 1. Title: Transmission and Generation Protection System Maintenance and Testing

Worldwide Contacts.

SECTION 4000 LIFT STATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

RELEASE DEVICE CONTROLS

GLOBAL ENCLOSURE STANDARDS WITHIN THE ELECTRICAL INDUSTRY

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Transcription:

a White Paper by Paul A. Terry, P.E.

NFPA 70, NEC 2005: Article 409 Industrial Control Panel Short Circuit Panel Ratings Executive Summary Many panel shops are providing industrial control panels with improper short circuit current ratings or no short circuit current ratings at all. This creates a potential for accidental improper installation of control panels by trained installers, plus a possible fire and safety hazard. The National Fire Protection Association (NFPA) has implemented strict and very concise rules in the latest National Electric Code (NEC) to facilitate the safe design, marking, installation, and inspection of industrial control panels (ICP). This white paper provides an overview of the following: The National Fire Protection Association s jurisdiction and actions NEC changes that affect proper marking for industrial control panels (ICPs) Methods that can be used to ensure that an ICP is in compliance with the new code When the new NEC code will be enforced Examples that illustrate these topics and show how ICP s should be marked to meet the new NEC code NFPA s mission is to reduce the worldwide burden of fire & other hazards... Introduction NEC 2005 has incorporated a brand new article, Article 409, to facilitate the safe design, marking, installation, and inspection of industrial control panels (ICP). The new article closes the loop and addresses areas of inconsistencies found in previous versions of the National Electric Code (NEC). This paper will discuss brief background information regarding NFPA and NEC code, Article 409, types of panels affected, enforcement timing, and methods that can be used to ensure panels meet Article s 409 short circuit marking requirements. Who is the NFPA? The National Fire Protection Association (NFPA) was established in 1896 and is a nonprofit organization. The organization consists of more than 75,000 members representing approximately 100 nations and over 300 employees around the world. Their mission is to reduce the worldwide burden of fire and other hazards on the quality of life by providing and advocating scientifically-based consensus codes and standards, research, training, and education. The NFPA has developed 300 codes and standards that are intended to minimize the possibility of and effects of fire and other risks. One of the most widely used NFPA electrical codes is the National Electric Code (NEC), NFPA 70. The NEC code has evolved over time (since 1897) and is updated approximately every 3 years. Like any set of evolving rules, inconsistencies can develop within the code. The NFPA eventually identifies and corrects these inconsistencies. NEC 2005 Key Change Affecting the ICP Industry Industrial control panels are currently installed based on general requirements from various NEC Articles. Because of inconsistent practice of installing equipment drawn from various 2 White Paper by Paul. A. Terry, P.E.

articles, NEC 2005 has been updated to address this issue. One of the key changes within NEC 2005 is to focus on the safe design, application, and inspection of industrial control panels. The most influential change is the inclusion of Article 409 on Industrial Control Panels. Article 409 was added because of the increasing misapplication of ICP s caused by inadequate short circuit ratings. Refer to Figure 1 to understand some of these conditions and how the new requirement helps. The NEC defines and Industrial Control Panel as follows: An assembly of a systematic and standard arrangement of two or more components such as motor controllers, overload relays, fused disconnect switches and circuit breakers and Unique Condition Industrial control panels can be moved around from installation to installation thus encountering varying electrical systems, environments, grounding means, and short-circuit current levels. Many industrial control panels are constructed by a manufacturer and installed by someone else. Many industrial control panels are field assembled and not assembled according to a product standard. There are an increasing number and variety of components, devices and equipment being used in industrial control panels. Issue Therefore, it is critical to supply the ratings associated with the industrial control panel assembly via markings in order to insure a safe installation. Without an exchange of information between the installer and manufacturer, any special requirements associated with the panel will not be known by the installer and possiblly cause an unsafe installation. Compliance of field assembled control panels is a complex process. Often unsafe installations are due to: * Assemblers confused over what rule applies (NEC, NFPA79,etc. * AHJ s not able to meet review demand * Miscommunication The increasing amount of information needed for safe application is difficult to manage leading to accidental unsafe installations. How this new requirement helps These markings help the installer understand the equipment s ratings to ensure a safe installation. They allow comparison of the equipments ratings with the location s maximum short circuit current. These new requirements ensure a proper exchange of information through equipment markings. The new short circuit current rating marking requirement ensures that field assembled panels where product standards are not used, are properly marked and lessens the burden on AHJs to ensure compliance with 110.10. These new marking requirements will ensure that cricial information needed for the proper application of the components, devices and equipment being used in industrial control panels will be provided. Fig. 1 - Benefits associated with inclusion of Article 409 IAEI s, January/February 2005, Short-Circuit Current Rating Requirements Facilitate compliance with 110.10, used by permission of IAEI News. related control devices such as pushbutton stations, selector switches, timers, switches, control relays, and the like with associated wiring, terminal blocks, pilot lights, and similar components. The industrial control panel does not include the controlled equipment The main goal of Article 409 is to ensure that all ICP s are marked with a proper short circuit current rating. Compliance of field assembled control panels is a complex process. Industrial control panels are also specified as assemblies rated 600V or less. The main goal of the new article is to ensure that all ICP s are marked with a proper short circuit current rating. Properly listed short circuit current ratings allow the safe installation and relocation of ICP s within the intended location. The article addresses general requirements for all industrial control products. In addition to Article 409, all other appropriate articles relating to the construction and installation of ICP s used in specific White Paper by Paul. A. Terry, P.E. 3

applications such as Article 430 (Motors, Motor Circuits, and Controllers), Article 440 (AC and Refrigeration Equipment), Article 620 (Elevators, Escalators, etc), and Article 670 (Industrial Machinery) still must be referenced and followed in order to complete the code requirements. What is Meant by Short Circuit Rating? It is important to note that Article 409 addresses field and factory assembled control panels. This implies short circuit ratings for an entire assembly not just the rating of the main overcurrent protective device. By assembly, we mean all components contained within an enclosure. The short circuit current rating of a component or equipment represents the maximum short circuit current level the device or equipment can safely withstand without compromising safety for buildings and personnel. Withstand ratings & interrupt ratings should not be confused. It is noteworthy to mention that withstand ratings and interrupt ratings should not be confused. Interrupt ratings are ratings associated with overcurrent protective devices, such as fuses or circuit breakers, and is referred to the ability of the overcurrent protective device to safely interrupt a short circuit at the specified marked interrupt rating. One should not assume that the interrupt rating of the overcurrent protective device represents the short circuit rating of the assembly. In fact, in most cases where many control components are used in the control panel (disregarding tested starter assemblies), the assembly short circuit rating will likely be less than the overcurrent protective device interrupt rating. How is the Assembly Short Circuit Rating Determined? Article 409.110 (3) clearly summarizes how the short circuit rating of an ICP is to be determined. According to 409.110, the short circuit current rating of an ICP must be based on one of the following methods: 1. Short circuit current rating of a listed and labeled assembly 2. Short circuit current rating established utilizing an approved method (Note: UL508A-2001, Supplement SB, is an example of an approved method) The use of method one above may fair well with OEM equipment that has a fixed and consistent design but does not fair well for panel shops where every panel will likely be different. Once an overall assembly has been tested, one small change in the design requires the panel to be retested. Since most panel shops build unique panels to meet a customer specific requirement, method one would be time consuming and cost prohibitive for most panel builders. Therefore, method two is typically the method of choice for determining an ICP short circuit current rating. What is UL 508A-2001, Supplement SB? 1 UL508A-2001, Supplement SB is one approved method for determining an ICP short circuit current rating. Supplement SB contains the following instructions for determining the short circuit rating: Step 1: Determine the short circuit current rating of individual power circuit components by using one of the following methods: A. Use the short circuit current rating marked on the component or on the instructions provided with the component. B. For unmarked components, use the assumed short circuit current rating from Table SB4.1 (see below) of Supplement SB. C. Use the tested short circuit current rating from a combination of components or component from UL508A 1 Summarized from UL508A, used by permission of UL 4 White Paper by Paul. A. Terry, P.E.

Step 2: When current limiting components are included within a portion of a circuit in the panel, modify the available short circuit current based on the let-through values of the current limiting device. Step 3: Determine the overall panel short circuit current rating according to SB4.4 of Supplement SB. Note: All power circuit components must have a short circuit current rating (expressed in amperes or kilo-amperes and voltage) except the following: Components exempt from short circuit current ratings: 1. Power Transformers 2. Reactors 3. Current Transformers 4. Dry-type Capacitors 5. Resistors 6. Varistors 7. Voltmeters Short circuit Component current rating, ka Bus bars 10 Circuit breaker (including GFCI type) 5 Current meters a Current shunt 10 Fuseholder 10 Industrial control equipment a. Auxiliary devices (overload relay) 5 b. Switches (other than mercury tube type) 5 c. Mercury tube switches Rated over 60 A or over 250 V 5 Rated 250 V or less, 60 A or less, and over 2kVA 3.5 Rated 250 volts or less and 2kVA or less 1 Motor controller, rated in horsepower (kw) a. 0-50 (0-37.3) 5a b. 51-200 (38-149) 10c c. 201-400 (150-298) 18c d. 401-600 (299-447) 30c e. 601-900 (448-671) 42c f. 901-1500 (672-1193) 85c Meter socket base 10 Miniature or miscellaneous fuse 10b Receptacle (GFCI type) 2 Receptacle (other than GFCI type) 10 Supplementary protector 0.2 Switch unit 5 Terminal block or power distribution block 10 a. A short circuit current rating is not required when connected via a current transformer or current shunt. A directly connected current meter shall have a marked short circuit current rating. b. The use of a miniature fuse is limited to 125 volt circuits. c. Standard fault current rating for motor controller rated within specified horsepower range. Table SB4.1 - Assumed maximum SSCR for unmarked components (Note: Reference only refer to UL508A Supplement SB for determining SSCR s) The steps above are very generalized and can become very complicated depending on the complexity of the industrial control panel. The goal of this paper is to simply provide a basic understanding of the concept. Contact the factory to obtain short circuit current ratings for ICP s of interest. A couple of basic examples have been included below to help illustrate some of the basic concepts. White Paper by Paul. A. Terry, P.E. 5

Example #1 ICP Rating for Untested Combinations This example illustrates how an ICP must be marked for a simple combination motor starter (20HP at 480V) where the circuit breaker/motor starter has not been short circuit tested as a combination. This particular example uses the assumed short circuit current rating for the contactor/overload from UL 508A Table SB4.1 from Supplement SB. For unmarked components, use UL508A, Table SB4.1 for assumed SCCR values. Since the circuit breaker and starter combination has not been tested together for a short circuit current rating, we must use Step 1: A and B & Step 3 only from What is UL 508A-2001, Supplement SB? above. We cannot use Step 1: C. The first step is to determine each individual component short circuit current rating. The ratings for this example are shown in Figure 2 below. The next step is to determine the lowest S1N050TL Interrupt rating = 20kA A26-30-10-84 & TA25DU32 (Assumed SCCR = 5kA from Table SB4.1 of UL508A) Required ICP Marking: 5kA Fig.2 - Example #1, Industrial Control Panel short circuit current rating of the lowest rated component. In this particular case, 5kA is the smallest short circuit current rating. The industrial control panel must be marked with the lowest rated component: 5kA. Combination tested components can increase the ICP s SCCR. Example #2 ICP Rating for Tested Combinations This example illustrates how an ICP can be marked for a simple combination motor starter (20HP at 480V as before) where the circuit breaker/motor starter has been tested as a combination. Since the circuit breaker and starter combination have been tested together for a short circuit current rating, we can use Step 1: C & Step 3 from What is UL 508A-2001, Supplement SB? above. ABB has tested the A26 contactor with a S3 100A circuit breaker as a combination. This tested combination has a 35 ka rating. Remember, these components have been stringently tested as a set of combination components by UL. Since the only component in this example is the combination starter and it has been tested as a combination, the ICP can be rated 35kA. By using a tested combination, the ICP short circuit current rating has been significantly increased. 6 White Paper by Paul. A. Terry, P.E.

When will NEC 2005 be Enforced? NEC 2005 is effective January 1, 2005 for jurisdictions that immediately adopt this version of the code. Currently, there are 25 states that have implemented Article 409. It is very important that all OEM s and panel builders in the industry are made aware of the new code requirements. The OEM and panel builder should check the existing code requirements for their jurisdiction to determine the enforcement of the new article. Underwriters Laboratory (UL) will begin enforcing the new requirements associated with Article 409 by April 2006. Conclusion Industrial control panels must be supplied with the proper short circuit current ratings to OEMs & panel shops should check their jurisdictions for current code requirements. Combination tested: 35kA { S3L100MW Interrupt rating = 65kA A26-30-10-84 & TA25DU32 (Assumed SCCR = 5kA from Table SB4.1 of UL508A) Required ICP Marking: 35kA Fig.3 - Example #2, Industrial Control Panel ensure panels are safely installed. Proper marking allows the installer to positively identify if the location s available short circuit current ratings could exceed the panels safe design limits. The goal is to ensure panels are designed to maximize equipment and personnel safety and to reduce the risk of fires. By following the basic guidelines within the specified time period presented in this paper, panels shops can be certain to provide safe, reliable, and code compliant products. ABB demonstrated it s industry leadership by implementing the new NEC code requirements a full year in advance of UL s target date. Processes and procedures are implemented to include short circuit current ratings on all enclosed control panels (see illustration). UL begins enforcement April 1, 2006 SSCR Marking Fig.4 - Sample label White Paper by Paul. A. Terry, P.E. 7

1SXU000046G0201 Printed in USA, March, 2006 ABB Inc. Low Voltage Control Products 16250 W. Glendale Drive New Berlin, WI 53151 Phone: 888-385-1221 Fax: 800-726-1441 USA Technical support & Customer Service: 888-385-1221, Option 4 7:30AM to 5:30PM, CST, Monday - Friday lvps.support@us.abb.com Web: www.abb.us/lowvoltage