Installation instructions for Plenum-mounted add-on electric heaters

Similar documents
Installation instructions for Plenum-mounted add-on electric heaters MODEL TU. MARCH 2011 version 7

Installation instructions for Plenum-mounted add-on electric heaters MODEL TU. September 2016 Version 7

B SERIES ELECTRIC FURNACE

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER

INSTALLATION INSTRUCTIONS FOR FANLESS MAKE-UP AIR MODEL NER (USA)

Model RGAC/SGAC Self Contained Cooling/Gas Heat MODELS RGAC & SGAC - R22 USER'S INFORMATION, MAINTENANCE AND SERVICE MANUAL

AUXILIARY ELECTRIC HEATER KITS FOR 7.5 AND 10 TON COMMERCIAL AIR HANDLERS

R Series B & T2 Model

INSTALLATION INSTRUCTIONS FOR MINI MAKE-UP AIR MODEL FER

BLOWER ACCESSORY MODEL #FIB100 Español p. 17

FOR EASY, FAST INSTALLATION AND FOR RESULTS

Quest Power Electric Heat EHS 62 Pro

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

T-Series Air Conditioner T15 Model

POSITION FEM10-M2301CM-A FEM15-M2301CM-A FEM18-M2301CM-A FEM20-M2301CM-A FEM23-M2301CM-A FEM20-M2301DM-A FEM23-M2301DM-A FEM27-M2301DM-A

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Quest Power Electric Heat EHS 31 Pro

Installation & Maintenance Instructions

Owner s Manual Phoenix FireBird

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

Models: Comfort SUPXX-C120D12 SUPXX-C240D12 SUPXX-C120D20 SUPXX-C240D20. Advantage SUPXX-A120D12 SUPXX-A240D12 SUPXX-A120D20 SUPXX-A240D20

INSTALLATION INSTRUCTIONS

RPI Industries, Inc.

ALIMENTATION 240 VAC POWER SUPPLY

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

FEM10-M2401AM-A FEM15-M2401AM-A FEM18-M2401AM-A FEM20-M2401AM-A FEM23-M2401AM-A FEM20-M2401BM-A FEM23-M2401BM-A FEM27-M2401BM-A

T-Series Air Conditioner T20 Model

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

RPI Industries, Inc.

Model REAC / SEAC Self Contained Cooling / Electric Heating Units

Air Storm Fans. Air Storm 54 Fiberglass Fan Installation and Operation Manual

COMBUSTION AIR SYSTEM Model: CAS-3

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

WATLOW ELECTRIC MFG CO. WATROD Duct Heater (module only) I& M Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.00

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

INSTALLATION INSTRUCTION

Installation, Operation and Service Manual

Surna 25-Ton Chiller Operating & Maintenance Manual

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Heatrix Electric Duct Heater HXOB Installation Instructions

Instruction Manual. Part No Revised September 2004

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

WARNING Important Safety Information

RPI Industries, Inc.

User Manual Box Exhaust Fan Series (Belt Drive)

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

Service Manual Models CPH2 & CPH3

WARNING Important Safety Information

OPERATING INSTRUCTIONS

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

WARNING Important Safety Information

user s information manual

Installation Instructions

USER MANUAL OLM SERIES WARM AIR OIL FIRED FURNACE

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

SC Installation, Operation & Application Guide

FLCH4R Garage and Utility Electric Heater

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

WIRING DIAGRAMS R410A MODELS PAC 2OAC/2OACH CAC OWC PWC

REFRIGERATED DROP-INS (2-6)FT-DI Installation and Operating Manual

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

Operation Manual. Instructions for Installation, Operation & Maintenance. PortaPac 5-, 8 and 10-ton Portable Air Conditioners

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

OPERATING INSTRUCTIONS SMO112 WARM AIR OIL FIRED FURNACE

Installation Instructions

Panel Fan Series Operators Manual (Galvanized and Polymer)

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

OWNER S MANUAL. FLAT PANEL FIREPLACE HEATER Model Number: Serena (EF202A) WARNING CAUTION

T-Series Air Conditioner T53 Model

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROOFTOP UNITS

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

CENTRAL, SPLIT SYSTEM REFRIGERATED AIR-CONDITIONING INSPECTION INTERIOR

INSTALLATION AND MAINTENANCE INSTRUCTIONS EF Electric Furnace

VERTICAL HIGH OUTPUT VHC-IOM INSTALLATION AND MAINTENANCE INSTRUCTIONS VHC INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE TECHNICIAN

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

Installation, Operation & Service Manual

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

DR-180 Through the Wall Exhaust Fan PRODUCT MANUAL & INSTALLATION GUIDE

SERIES 500. Installation & Maintenance Instructions. Ceiling Mounted Fan Forced Heater WARNING SAVE THESE INSTRUCTIONS. Recessed Mount.

INSTALLATION INSTRUCTIONS AND HOMEOWNER S MANUAL: ELECTRIC FURNACE

MANUAL INSTALLATION. Fan Column. v200 Issue Date: 01/18/ Price Industries Limited. All rights reserved.

USER MANUAL SLO / SFLO115 SERIES OIL FIRED WARM AIR FURNACES

HRV Vertical Unit Ventilators

INSTALLATION, OPERATION AND MAINTENANCE

WARNING Important Safety Information

OWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference

Installation, Operation, and Maintenance Information

Transcription:

Installation instructions for Plenum-mounted add-on electric heaters Aug. 2008 Version 4

THESE INSTALLATION INSTRUCTIONS COVER: MODEL T-4 to T-30 (4 Kw to 30 Kw) GENERAL NOTES - Please refer to CSA Standard B139, installation code for oil burning equipment and to the Canadian Electrical Code, Part 1, for recommended installation practices. - The installation of this unit should be in accordance with the regulations of the authorities having jurisdiction. CAUTIONS 1. Before installation, ensure that the local electrical inspection authority will accept connection of this equipment to the existing panel. 2. This equipment may only be installed and tested by qualified personnel. 3. The electrical power supply should be checked for adequacy for the proposed additional load. 4. Ensure that the heat output capacity of the installed electrical Add-on Heaters does not exceed the rated output capacity of the furnace burner. 5. This heater is for use with an in-line (hi-boy) or up-flow (lo-boy) oil or gas fired furnace. OPERATING INSTRUCTIONS The controls provided with this unit prevent simultaneous operation of the add-on heater and the oil burner. In the case of malfunction, shut down the equipment and call a qualified electrician. Page 1

FIELD TESTS: A. BEFORE Installation of the Add-on Heater: 1. Ensure that the burner does not cycle due to repeated operation of the furnaces high limit control. 2. Determine whether stabilized outlet air temperature during burner operation is below 66 C (150 F) in the main outlet duct. If it does exceed 66 C (150 F) make the following adjustments to the Ventilation System in progressive steps: Note: In most cases, only steps A & B will be necessary. a) Check if filters are clogged. b) Check if fan blades are clean. If not, remove the blower from its compartment and clean with a brush. c) Adjust the motor pulley to increase its diameter. d) Change the fan pulley for a smaller size. e) Change the motor pulley for a larger size. f) Change the motor and make sure that the fan control and wiring are adequate. Note: If steps c), d) & e) are necessary, make sure that the existing motor is adequate. The current drawn must not exceed the nameplate specifications. Important: The blower must not be changed. If the system cannot provide sufficient airflow after changing the motor, do not install the add-on heater in that furnace. B. AFTER installation of the Add-on Heater: 1. Ensure that the burner does not cycle due to repeating operation of the furnace's high limit control. 2. Ensure that stabilized outlet air temperature during burner operation does not exceed 72 C (160 F) in the main outlet duct. 3. Run burner to ensure that the blower starts soon enough to prevent the manually resettable temperature limiting control on the Add-on Heater from tripping. 4. Operate the Add-on Heater to ensure satisfactory operation without overheating. Note: Where a cooling coil is present, additional checks should be made to ensure adequate airflow exists for cooling system operation. Page 2

MECHANICAL SECTION A. Product Inspection 1) Inspect the carton and heater and report any damage at once. NEVER INSTALL A DAMAGED HEATER 2) Content of carton: - One Add-on plenum heater - Three (3) sheet metal baffles to adapt heater to plenum. 3) File claim with shipping company if shipment is damaged or incomplete. B. Installation Instructions: "Cautions" - The installation, location, position and orientation of the add-on heater must conform to the following: 1) This heater must be installed downstream of the furnace in the warm air plenum. 2) This heater must be installed downstream of the furnace safety limit control. 3) No deformation, removal or displacement of any part of the furnace is permitted. 4) The position of the add-on heater must be as indicated on the front of the heater control box (Please see Fig. 1). 5) The heater axis must be in line with the plenum axis. 6) Do not install heater from top or bottom of duct. (Please see Fig. 2). STANDARD INSTALLATION CLEARANCE The heater must be installed in the warm air plenum. A minimum distance of 14 inches is required from the furnace to the elbow, Tee or plenum end take-off of the main supply duct (Please see Fig. 3). Page 3

If a cooling coil is installed in the warm air plenum a minimum distance of 3" or 7" is required between the top of the cooling coil and the add-on heater (depending from which side of the plenum the add-on heater is inserted). (Please see Fig. 4) In both cases, a minimum distance of 2" must be kept between the top of the add-on heater and the elbow, Tee or plenum-end take off of the main supply duct. 1 The heater may be installed on any available side of the plenum. An installation and service clearance of 28 inches is required from the heater control box to a wall, partition or any other obstruction. If the heater is installed on the same side as the flue pipe a minimum clearance of 10 inches must be maintained between the flue pipe and the heater control box. (Please see Fig. 5) Select the plenum side, which offers the most space for installation and service. VERY IMPORTANT BAFFLES MUST ASSURE MAXIMUM AIR FLOW OVER THE HEATING ELEMENTS. - Screw the baffles to bottom flanges of casing, as shown in Fig. 6. - Cut baffles to size allowing only 1/8" clearance for insertion of heater. AIR FLOW All the air from the furnace must pass through the heater element. If the heater element casing is smaller than the plenum the space between the plenum and the element casing must be blocked off with baffles. (Please see Fig. 7) Page 4

HE ATER MOUNTING Cut out heater opening at a minimum distance of 6 inches from the furnace. Center the opening on the plenum. Provide slots for insertion if baffles are installed. (Please see Fig. 8). The 6 inch minimum dimension from the top of the furnace to the heater opening in the plenum may be increased. If increased, 14 inch minimum dimensions in Fig. 3 must be increased accordingly. Slip the heater element into the opening. Make sure that the opening and slots are entirely covered by the heater mounting flanges. Secure the heater to the plenum by means of metal screws. HUMIDIFIER DO NOT USE PAN & PL ATE TYPE HUMIDIFIERS WITH THE WATER RESERVOIR INSIDE THE WARM AIR SUPPLY PLENUM. Only "Pressure Differential" type humidifiers (preferably a power humidifier) should be used. If the round inlet duct of the humidifier is connected on the hot side of the heater, it is strongly recommended to insert a reducing ring between the round inlet duct of the humidifier and the opening in the plenum such that the effective opening for the humidifier will approximate 4" in diameter. This will reduce the volume of short-circuited air through the humidifier connection (Please see Fig. 9). WARRANTY The Manufacturer warrants the heating elements of its "Series T" Plenum Heaters against any defect in material and workmanship for a period of ten years, and all others components for a period of two years starting from the date of installation of the heater. The Manufacturer will repair or replace without charge in its factory or in the field, at its sole discretion, the heater or part thereof which shall in the Manufacturer's opinion prove defective. Misuse of this product or repairs made by persons other than the Manufacturer's authorized personnel without the Manufacturer's written approval will void this warranty. The Manufacturer shall not be held responsible for any incidental or consequential damage or delays and shall not be held liable for any damages resulting from the removal or replacement of the allegedly defective heater. Page 5

ELECTRICAL SECTION (ALL MODELS) A. Disconnect all power sources before opening electrical boxes and working within. B. Read the nameplate and markings carefully and consult the wiring diagram before you start wiring. C. Wires and protective equipment should be sized according to the National Electrical Code requirements. D. Use only wires suitable for at least 75 C. E. Disconnect room thermostat connection to furnace and connect to C and W1 terminals of heater. F. Connect two (2) wires from BB control terminals of plenum heater to furnace room thermostat connection. G. Connect the fan relay supplied with the heater (terminals F F) to the existing fan controls in order to permit the functionnning of the fan in the electric mode. H. Anticipation. Set the room thermostat heat anticipator at 0.2. Perform start-up and required field tests. (Please see fig. 10) or schematic wiring. I. Outdoor thermostat. If required install an outdoor thermostat on an exterior north wall and connect to terminals S1 and S2 in the plenum heater to allow for automatic transfer in the dual energy mode. Page 6

START UP AND SEQUENCE OF OPERATION 1 - The heater is supplied with a built-in 3 position mode selector switch. position - Electric heat. position - Heating by means of original furnace. position - Dual-energy mode. In the "electric" mode the room thermostat will call upon the electric heater to maintain the house temperature at the level desired by the user. In the "oil" mode the oil furnace is ready to respond to the house thermostat's call for heat. The third position or "Dual-Energy" mode gives automatic control to the outdoor thermostat or other switching signal for dual-energy control. When the contacts are closed, the electric mode is selected. When the contacts are open, the oil mode is selected. A green pilot light indicates the mode in operation. 2- a. Do required fields tests after installation of the Add-on Heater as detailed on page 2. b. Turn ON the disconnect switch controlling the heater. c. Simulate a heating demand by setting the room thermostat above the room temperature. d. Switch the mode selector to position. The fan will start and the heating elements will come on in sequence at 5 seconds interval (wait approx. 2 minutes). e. Measure the amperage drawn by the heater and compare it with the one shown on the nameplate. f. Lower the heating demand by setting the room thermostat. All the relays will disconnect and the amperage should go down to zero (wait approx. 2 minutes). g. Switch the mode selector to position and check if the burner responds to thermostat demand. h. Switch the mode selector to the dual-energy position. If you jump terminals S1 and S2 the electric mode is selected and if you disconnect terminals S1 and S2 the oil / gas mode should be selected. i. Switch the mode selector to the desired position and set the room thermostat to the desired set point. Your heater is now ready and functional. Page 7

Characteristics Models kw @ 240V Heating Current (Amps) Sequences Plenum Heaters Fuses Breakers AWG T-5 5 1 20.8 30 30 10 T-9 9 2 37.5 50 50 8 T-15 15 4 62.5 80 100 4 T-18 18 4 75.0 100 100 3 T-20 20 4 83.3 110 125 3 T-25 25 4 104.0 150 150 1 T-30 30 4 124.0 175 175 0 Page 8