A-4400 Series Refrigerated Air Dryers for Pneumatic Control Systems

Similar documents
Refrigerated Air Dryers

SECTION AIR COMPRESSORS AND ACCESSORIES

RN SERIES REFRIGERATED COMPRESSED AIR DRYERS NON-CYCLING REFRIGERATEDERATED COMPRESSED AIR DRYERS SCFM

RHP & FHP Series. High Pressure Air Treatment Global Air Treatment

CNC Series Refrigerated Air Dryer CFM

MR3CCUHV Temperature/Defrost Control

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

CHC Series High Capacity Refrigerated Dryer 2,000 20,000 SCFM

RNC Series SCFM Global Air Treatment

RNC Series SCFM Global Air Treatment

REFRIGERATED AIR DRYERS

TEC210x-2 Series Networked Thermostats

ACT2-CS Convenience Store Controller

Noncycling Refrigerated Air Dryers Range AD 10 to AD 4000

WILKERSON MODELS DE3, DE4 AND DE5 COMPACT HEATLESS AIR DRYERS

Refrigerated Air Dryers VF Series. DHT Series. Non-Cycling 10-2,000 scfm scfm

MANUFACTURED with high-quality components and innovative techniques. DESIGNED for economical, trouble-free performance and long-life reliability

Refrigerated Air Dryers

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

RN SERIES REFRIGERATED COMPRESSED AIR DRYERS NON-CYCLING REFRIGERATED COMPRESSED AIR DRYERS SCFM

TEC2100 Series Networked Thermostats

V48 Series 3-Way Water Regulating Valves For Cooling Tower Systems

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

CRN Series MCGUIRE AIR COMPRESSORS INC MCGUIRE AIR COMPRESSORS INC Refrigerated Compressed Air Dryers

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

RLD-H10G Refrigerant Leak Detectors

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

RDS SERIES REFRIGERATED COMPRESSED AIR DRYERS ENERGY SAVING REFRIGERATED COMPRESSED AIR DRYERS SCFM

ThermoStar Refrigeration Air Dryers

TEC1100 Series Thermostats

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

Single Tower Heat Reactivated Desiccant Air Dryer

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

Refrigerated Compressed Air Dryers

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

W43A Humidistat. Features and Benefits

Owners Manual Refrigerated Air Dryer MHT SERIES

Global Leader in Efficiently Treating Compressed Air EXCELLENCE IN DESIGN, MANUFACTURING AND SERVICE

Desiccant Drying DRYPOINT XC. efficient low dew point heatless desiccant drying. Truth in Compressed Air.

Refrigerated Compressed Air Dryers

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

F261 Series Fluid Flow Switches

SECTION AIR COMPRESSORS AND ACCESSORIES

A99B Series Temperature Sensors

MCGUIRE AIR COMPRESSORS Compressed Air Dryers. CRN Series. Refrigerated. Leading Technology. MCGUIRE AIR COMPRESSORS

HS Dryer. Smart Solutions for Drying Compressed Air. Single Tower Heat Reactivated Desiccant Air Dryer. Engineered Air Products

PROdry. High Inlet. Temperature. refrigerated. compressed air. dryers. Contents. For Sales & Service please contact:

HS Dryer. Smart Solutions for Drying Compressed Air. Single Tower Heat Reactivated Desiccant Air Dryer. Engineered Air Products

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Catalog 9CW-SD-9 Manual Desiccant Dryers Models X0, X0, X0 and X5 Wilkerson's Manual Desiccant Dryers offer the most cost effective method to remove m

RLD-H10P Refrigerant Leak Detector

UA Series Air Dryers. 10 Year Warranty Limited ( SCFM) Setting a new standard in Quality and Reliability WAS 360

UA Series Air Dryers. 10 Year Warranty Limited ( SCFM) Setting a new standard in Quality and Reliability WAS 360

Rev. A AUGUST 2012 RNP SERIES REFRIGERATED COMPRESSED AIR DRYERS OPERATOR MANUAL RNP25 RNP35 RNP50

clean, dry compressed air

Refrigerated Air Dryers

REFRIGERATED AIR DRYERS

WT-4000 Series Pneumatic-to-Direct Digital Control (DDC)

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

Commercial High-Efficiency Condensing Units

Refrigerated Compressed Air Dryers

In follow up to our conversation this morning, please find the enclosed revised proposal.

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

HYDROGARD Refrigerated Air Dryers HGD and DES Series

600-10,000 scfm AES Series. AES Series Energy Saving. Refrigerated Air Dryer ,000 scfm. Front Page

Non-Cycling Refrigerated Air Dryers

PACKAGE AIR CONDITIONER

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page

V A C U U M A N D P R E S S U R E T E C H N O L O G Y

Fixed Speed Rotary Screw Compressors UP6 Series 4-11 kw (5-15 hp)

CLEAN, DRY COMPRESSED AIR

BULLETIN: APPL-QAF-133R1

20 21,250 SCFM GLOBAL AIR TREATMENT. FIL Series

CFH Series High Efficiency Filters

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

MODEL MW200 MODEL MW600 AIR DRYER

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

TM-3100 Series Room Temperature Sensor

Nirvana Cycling Refrigerated Dryers

Refrigeration Training System

MultiPlex INNOVATIVE COMPRESSED AIR SOLUTIONS LARGE CAPACITY TRUE-CYCLING TM REFRIGERATED COMPRESSED AIR DRYERS

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Rev. 06/27/14

GCS Multipoint Carbon Dioxide Gas Concentration Sampler

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. Refrigerated Air Dryers

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

Polar Air Dryer. Instructions Manual PDRCF PDRCF R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

HEATLESS DESICCANT AIR DRYERS

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

A19, A28 Series Thermostats for Agricultural Buildings

ZPA Heatless Regeneration ZHA Heated Regeneration ZBA Heated Blower Regeneration

Transcription:

Pneumatic Air Supply Manual 718 Air Dryers Section Product Bulletin A-4400 Issue Date 1213 A-4400 Series Refrigerated Air Dryers for Pneumatic Control s The A-4400 Series Refrigerated Air Dryers are designed for continuous operation to supply dry air to pneumatic control systems. All components are selected and assembled to provide dependable service over a long period of time with a minimum amount of maintenance. The air dryer uses R-134a refrigerant, an environmentally friendly HFC, minimizing the risks and/or costs associated with use and disposal of refrigerants. Figure 1: A-4400 Series Refrigerated Air Dryer with Optional Factory Mounted Air Figure 2: A-4400 Series Refrigerated Air Dryer without Optional Factory Mounted Air Features and Benefits Superior Part Load Performance Continued on next page... Dew point remains steady as air consumption and cooling loads decrease, ensuring consistent water removal performance at all conditions including critical low-load operating points (without threat of unit freeze-up). Evaporator design eliminates the need for, and maintenance of, a hot gas bypass valve. 2013 Johnson Controls, Inc. 1 Code No. LIT-718050P

Features and Benefits (Cont.) Available with Optional Factory Mounted Air Particle filter (standard)/coalescing filter/activated carbon filter/service bypass valve/pressure reducing valve combination provides precise, clean, dry, oil-free air, enabling the control system to operate at peak performance. Full instrumentation including coalescing filter pressure drop indicator, refrigerant and air pressure gauges, and power on/fail lamp simplifies operation and maintenance with quick and easy visual identification of unit performance. Minimizes installation time via factory mounting and piping of all components, including service bypass valve. P roduct Overview Available in Three Flow Capacity Sizes Utilizing One Universal Cabinet; UL Listed for US and Canada Uses R-134a Refrigerant Six variations of A-4400 Series Refrigerated Air Dryers are available with flow capacities of 12, 17, and 23 scfm (5.7, 8.0, and 10.9 L/s). Models can be ordered with an optional factory mounted Air consisting of a coalescing oil removal filter with integral pressure drop indicator, packed column type activated carbon oil vapor removal filter, service bypass valve, pressure reducing valve, safety relief valve, and power on/fail lamp. On models featuring an Air, a low pressure gauge is furnished on the reducing valve to provide output pressure indication. Refer to Table 1 for a comprehensive listing of refrigerated air dryers available. As outlined in Product Data A-4000 and the Installation and Service Manual for PureFlow Air Compressors (Publication No. 2629), clean, dry, oil-free air is essential to any pneumatic control system. Existence of water, oil, and/or particulate in air lines and instruments can cause instrument calibration to drift, often Allows application flexibility to minimize cost. Standardized design with common footprint. Environmentally friendly HFC, minimizes risks/costs associated with use and disposal of refrigerants. leading to equipment failure. For A-4400 Series Refrigerated Air Dryers not equipped with an optional factory mounted Air, a properly configured air supply system must include a coalescing oil removal filter as well as an activated carbon oil vapor removal filter. All A-4400 Series Refrigerated Air Dryers feature a hermetically sealed compressor, heat exchanger, and automatic condensate drain trap. An insulating sleeve, that easily slips on and off, covers the automatic condensate drain trap to eliminate external condensation. An evaporator pressure gauge and the automatic condensate drain trap with particle filter are internally mounted and are easily accessible through the end of the unit. All refrigerated air dryers also include a standard cord and plug for 115 volt 60 Hz, single-phase electrical service. Where permanent wiring is required, the cord is easily removed and conduit may be used. 2 Air Dryers A-4400 Series Product Bulletin

Table 1: Ordering Data Code Number A-4412-1 A-4412-2 A-4417-1 A-4417-2 A-4423-1 A-4423-2 Flow Capacity at Rated Condition* scfm (L/s) 12 (5.7) 12 (5.7) 17 (8.0) 17 (8.0) 23 (10.9) 23 (10.9) Air Shipping Weight lb** Yes 72 No 67 Yes 78 No 73 Yes 78 No 72 * The rated condition is 20 psig (140 kpa) supply pressure, 100 F (38 C) saturated inlet air temperature, 100 F ambient temperature, and 80 psig inlet pressure. ** lb x 0.454 = kg Table 2: Cross-Reference Guide Refrigerated Air Dryer Configuration 12 scfm (5.7 L/s) Flow Capacity with Air 12 scfm (5.7 L/s) Flow Capacity without Air 17 scfm (8.0 L/s) Flow Capacity with Air 17 scfm (8.0 L/s) Flow Capacity without Air 23 scfm (10.9 L/s) Flow Capacity with Air 23 scfm (10.9 L/s) Flow Capacity without Air Johnson Controls A-4412-1 A-4412-2 A-4417-1 A-4417-2 A-4423-1 A-4423-2 Hankison 8010 8010 8015 8015 8025 8025 Robertshaw 2815-201 2815-001 -- 2815-003 -- 2815-004 Honeywell Wilkerson HKN8010B HKN8210B WLKA00AHC6 6 A00-AH-P00 A01-AH-P00 T01-AH-P0L AK3480H HKN8010A KNE10 WLKA00AHA6 6 4302-5 A00-AH-000 A01-AH-000 H01-AH-000 T01-AH-P0K -- A02-AH-P00 AK3481 AK3479 HKNE-15 HKN8015A 4302-10 A02-AH-000 H02-AH-000 -- HKN8025A -- 4302-15 H03-AH-000 SpeedAire -- 3Z528 -- 3Z529 -- 3Z530 Norgren -- 60-010-996 D10-100-0005 D10-100-0010 D11-010-1DA3 -- D10-100-0015 D11-015-1DA3 -- D10-100-0020 Curtis-Toledo -- CDP10 -- CDP18 -- CDP25 Ingersoll-Rand -- HG10 -- HG15 -- HG25 Discontinued Johnson Controls A-4110-1 A-4312-1 A-4110-3 A-4110-6 A-4312-2 A-4317-1 A-4317-2 A-4210-1 A-4210-5 A-4323-1 A-420-1 A-421-1 A-4210-3 A-4210-6 A-4323-2 Air Dryers A-4400 Series Product Bulletin 3

S ervice Bypass A service bypass valve is furnished on all A-4400 Series Refrigerated Air Dryers equipped with an optional factory mounted Air, in order to make it possible to service the oil removal filters or the heat exchanger section of the air dryer without interrupting the control system air supply. Depressing the bypass valve plunger causes the air supply to bypass the oil removal filters and evaporator, and flow directly through the pressure reducing valve. An automatic pressure bleed is incorporated in the bypass position to relieve the pressure for safe removal and service of the oil removal filters and the components housed within the dryer cabinet (as illustrated in Figures 3 and 4). Evaporator Pressure Gauge Discharge Line Service Suction Line Condenser Line Voltage Heat Exchanger Auto Exp. Tube-In-Tube Counterflow Evaporator Automatic Condensate Drain Trap Service Bypass Inlet From Air Compressor Coalescing Oil Removal Filter With Automatic Drain Activated Carbon Oil Vapor Removal Filter PRV With Low Pressure Gauge High Pressure Output Figure 3: Schematic of A-4400 Series Refrigerated Air Dryer with Service Bypass Positioned for Normal Operation (Shown with Optional Factory Mounted Air ) Safety Relief Regulated Output Inlet From Air Compressor Safety Relief Evaporator Pressure Gauge Discharge Line Service Suction Line Condenser Line Voltage Heat Exchanger Auto Exp. Tube-In-Tube Counterflow Evaporator Automatic Condensate Drain Trap Coalescing Oil Removal Filter With Automatic Drain Service Bypass Activated Carbon Oil Vapor Removal Filter Exhaust PRV With Low Pressure Gauge High Pressure Output Regulated Output Figure 4: Schematic of A-4400 Series Refrigerated Air Dryer with Service Bypass in Bypass Position (Shown with Optional Factory Mounted Air ) 4 Air Dryers A-4400 Series Product Bulletin

Dew Point at 20 psig ( F) Table 3: Inlet Pressure Correction Factors for Dew Point (See Figures 5, 6, and 7.) Inlet Pressure psig (kpa) 70 (490) 80 (560) 90 (630) 100 (700) Change In Dew Point F (C ) +2.5 (+1.4) 0 (0) -2.5 (-1.4) -4.5 (-2.5) Inlet Pressure psig (kpa) 110 (770) 120 (840) 130 (875) Change In Dew Point F (C ) -6.5 (-3.6) -8.5 (-4.7) -11.0 (-6.1) -- -- 28 26 24 130 F Inlet 120 F Inlet 110 F Inlet 100 F Inlet 22 20 18 0 2 4 6 8 10 12 14 Flow Rate (scfm) Figure 5: A-4412-1 and A-4412-2 Dew Point vs. Flow Rate (At 20 psig supply pressure, 100 F ambient temperature, and 80 psig inlet pressure; for ambient temperatures above 100 F, consult a Johnson Controls representative.) Air Dryers A-4400 Series Product Bulletin 5

Dew Point at 20 psig ( F) Dew Point at 20 psig ( F) 32 30 28 140 F Inlet 130 F Inle t 120 F Inlet 110 F Inlet 100 F Inlet 26 24 22 20 18 0 2 4 6 8 10 12 14 16 18 Flow Rate (scfm) Figure 6: A-4417-1 and A-4417-2 Dew Point vs. Flow Rate 20 (At 20 psig supply pressure, 100 F ambient temperature, and 80 psig inlet pressure; for ambient temperatures above 100 F, consult a Johnson Controls representative.) 34 32 30 28 26 120 F Inlet 110 F Inlet 100 F Inlet 24 22 20 18 16 14 0 2 4 6 8 10 12 14 16 18 20 22 24 Flow Rate (scfm) Figure 7: A-4423-1 and A-4423-2 Dew Point vs. Flow Rate (At 20 psig supply pressure, 100 F ambient temperature, and 80 psig inlet pressure; for ambient temperatures above 100 F, consult a Johnson Controls representative.) 6 Air Dryers A-4400 Series Product Bulletin

I nstallation The A-4400 Series Refrigerated Air Dryer must be located in an open area that will permit free circulation of air through the ends of the unit. The A-4400 requires 12 in. (305 mm) top clearance (as measured from the top of the cabinet) and 12 in. clearance at either end. When the unit is wall mounted, it is recommended that there also be 10 in. (254 mm) bottom clearance. Two key slots are provided at the rear of the A-4400 for wall mounting the unit. These key slots can be hand adjusted approximately 1/2 in. (13 mm) if needed when hanging the unit on the appropriate mounting bolts (field furnished). Refer to Figure 8 for space requirements and additional mounting details. After the A-4400 has been mounted in place, connect a suitable drain line to both the automatic condensate drain trap and the coalescing oil removal filter. Tighten the drain line fitting at both locations to secure the drain line in place. Refer to Figure 9 for location of the drain trap and the coalescing oil removal filter. Note: Since condensate may contain entrained oil, be certain to dispose of this waste properly, in accordance with local, state, and federal regulations. Refer to the A-4400 Series Technical Bulletin in the Pneumatic Air Supply Manual (FAN 718) for additional installation and maintenance procedures including comprehensive wiring instructions. Air Dryers A-4400 Series Product Bulletin 7

+ + Note: The A-4400 requires 12 in. (305 mm) top clearance and 12 in. clearance on either end. When wall mounting the A-4400, 10 in. (254 mm) bottom clearance is recommended. 12-15/16 329 Also, attach the 3/8 in. discharge main air line to the PRV before mounting. A-4412-1: 21-3/4 552 17-1/2 445 A-4417-1 and A-4423-1: 22-1/16 560 In A-4412-1: 18-1/16 459 16 406 Key Slots (Two Locations) for 1/4 in. Bolts (Field Furnished) 12-5/8 321 14-1/4 362 A-4417-1 and A-4423-1: 23-3/16 589 Out Capped High Pressure Connection for High Pressure Riser (Models with a Factory Mounted Air ) Figure 8: A-4400 Series Refrigerated Air Dryer Shown with Optional Factory Mounted Air Dimensions in. mm 8 Air Dryers A-4400 Series Product Bulletin

Figure 9: Front View of A-4400 Series Refrigerated Air Dryer Air Dryers A-4400 Series Product Bulletin 9

Figure 10: A-4400 Series Refrigerated Air Dryers with Cover Removed 10 Air Dryers A-4400 Series Product Bulletin

Evaporator Pressure (psig) 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 40 50 60 70 80 90 100 110 120 130 Ambient Temperature ( F) Acceptable Operating Zone Nominal Setting Figure 11: Evaporator Pressure vs. Ambient Temperature (Sea Level--No Load Condition) E vaporator Pressure Correction Variations in the evaporator absolute pressure due to altitude will not show up on the evaporator pressure gauge, making it necessary to readjust the expansion valve using an adjusted gauge pressure. For altitudes from 1500 to 5000 ft, increase the expansion valve setting by 2.5 psig (17.5 kpa), and for altitudes over 5000 ft, increase the expansion valve setting by 4.0 psig (28 kpa). This increase in evaporator pressure must be added to the value determined in Figure 11 to account for altitude effects. Refer to the A-4400 Series Technical Bulletin in the Pneumatic Air Supply Manual (FAN 718) for additional information. Example: If: Altitude = 4,000 ft above sea level Ambient temperature = 80 F Evaporator pressure gauge reading at no load condition = 35 psig Then: Corrected evaporator pressure = 35 psig + 2.5 psig = 37.5 psig Air Dryers A-4400 Series Product Bulletin 11

G uide Specification The air dryer shall be of the refrigeration type, designed for continuous operation and sized to reach a maximum dew point of 30 F (0 C) at 20 psig (140 kpa) at expected air flow rates and ambient temperature conditions (100 F saturated inlet air temperature, 100 F ambient air temperature, and 80 psig inlet pressure). The refrigeration system shall operate on HFC R-134a refrigerant. For proper removal of water, oil, and particulate, the air dryer shall be furnished with a complete Air consisting of a service bypass valve, automatic condensate drain trap with integral particle filter, coalescing oil removal filter, activated carbon oil vapor removal filter, S pecifications Product A-4400 Series Refrigerated Air Dryers Electrical Rating Models Included in Table 1 Current Draw Refrigerant Compressor 115 Volt 60 Hz, Single-phase Electrical Service 5.75 Amperes R-134a (HFC) Hermetically Sealed and pressure reducing valve. Visual indication of dryer operation shall be provided by means of a power on/fail lamp, refrigerant and air pressure gauges, and a coalescing filter pressure drop indicator. A pplication and Drawing Identification Agency Listings UL Listed, cul Listed, Category Code SROT, File SA8490 Ambient Operating 40 to 115 F (4 to 46 C) with maximum dew point of 86 F (30 C), non-condensing. Temperature Limits If operation is outside the ambient temperature limits, refer to the Commissioning section of the A-4400 Technical Bulletin for additional information. Ambient Storage Temperature Limits -40 to 140 F (-40 to 60 C) Maximum Flow Rate As Illustrated in Figures 5 through 7. Pressure Drop with A-4412-1: 10 psig (70 kpa); A-4412-2: 4 psig (28 kpa) 80 psig (560 kpa) Supply and A-4417-1: 17 psig (117 kpa); A-4417-2: 8 psig (55 kpa) Rated Flow Maximum Input Pressure Connections Finish Accessory (Order Separately) A-4423-1: 33 psig (228 kpa); A-4423-2: 15 psig (103 kpa) 125 psig (862 kpa) 3/8 in. Compression Fittings for Polytubing or Copper Tubing Gray Enamel AD- See Beims 45-2.03-1. A-4000-154 Manual Override for Coalescing Oil Filters The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. I O Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2013 Johnson Controls, Inc. 12 Air Dryers A-4400 Series Product Bulletin