Things To Know About Tankless Water Heaters II

Similar documents
Installing Ventfree Propane Appliances

TANKLESS WATER HEATING

VENTING GAS APPLIANCES NFPA 54 CODE

Gas Piping Facts. Information for properly sizing gas lines for use with tankless water heaters and other gas appliances TANKLESS WATER HEATING

INFORMATION FOR TANKLESS WATER HEATERS

Have you downloaded the groovy show App? Search in the Apple App store or the Google Play Store for Everything Under the Sun

Vent Supplement Ultra-80, -105, -155, -230 & -310

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

CHIMNEYS AND VENTS CHAPTER 8

CHAPTER 8 CHIMNEYS AND VENTS

SEPARATED COMBUSTION WARNING

Venting of Gas Fired Equipment RV

CHAPTER 8 CHIMNEYS AND VENTS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

MFC Series Boiler Vent and Combustion Air Guide

GOLD. Venting Supplement. Water Boiler Series 3 & 4. for 3" venting

GOLD GV. Venting Supplement for 3 venting. Water Boiler Series 3 & 4

C O D E S & A M M E N D M E N T S

on a 98 percent AFUE furnace, less water vapor passes into the vent.

GAS FIRED BOILERS FOR FORCED HOT WATER VENTING ADDENDUM. ECR International Ltd. - Olsen Division P.O. Box 900 Wallaceburg, Ont.

SEPARATED COMBUSTION. General

INSTALLATION OF VENTING SYSTEM COMPONENTS WARNING

SEPARATED COMBUSTION. General WARNING

ASX7-5-IOM-3 J

qüé=`üáãåéó An effective chimney is an important part of any successful wood-burning system.

Direct Vent Training & Installation Instructions for Venting 40/50 gallon models Telescoping Vent Kit (standard)

INSTALLATION AND SERVICE MANUAL

Commercial Tankless Rack System

The. Steam ONE-PIPE STEAM SYSTEMS

Section 9 - Tumble Dryers. Tumble Dryers LEPH

INSTALLATION AND SERVICE MANUAL

Pellet Vent INSTALLATION INSTRUCTIONS

Commercial Tankless Rack System

INS A T LL T A ION, OPER T A ING AND SERVICE INSTRUCTIONS FOR FREEDOM CONDENSING HIGH EFFICIENCY DIRECT VENT GAS - FIRED HOT

Venting Supplement Saf-T Vent 3" venting Special gas vent system vent and combustion air supplement for 3" diameter venting Hazard definitions

Side by side. Cascade Venting System for RTG 199HE. Extension Set for units 3 or Installation instructions

ASX7-4-IOM-6 J

GOLD GV. Venting Supplement. Water boiler Series 3. Special gas vent system vent and combustion air supplement. Hazard definitions.

Water Heater. Promising endless. Installing an On-Demand

INSTALLATION AND SERVICE MANUAL. Hot Water Heating Boilers Domestic Hot Water Supply Boilers 399, ,000 Btu/hr Models

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type D)

INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual )

Ventis Direct Vent. Installation Instructions

Back to back. Cascade Venting System for RTG 199HE. Basic Set for units 1 and Installation instructions

EUTECTIC EC-10DV Series

Commercial Tankless Rack System

SOLID. STATE. Commercial Tankless. Rack System TANKLESS WALL MOUNT LIGHTWEIGHT EXPANDABLE REDUNDANCY EASY FIELD INSTALLATION EASILY INTEGRATE STORAGE

TOYOTOMI U.S.A., INC. P.O. Box 176, Brookfield, CT

GWS. Venting Manual. Gas-Fired Water Boilers. Hazard definitions. Contents. Venting method definitions

6. Within an internal combustion engine, the can-shaped component that moves up and down the cylinder

2012 UPC Chapter 6 Water Systems Part 2 RV

Inspection Checklist Mechanical Final

INSTALLATION AND OPERATING INSTRUCTIONS

! WARNING: FIRE OR EXPLOSION HAZARD. Applies to: Model SC, Separated-Combustion Duct Furnace. Model SC INSTALLATION / OPERATION / MAINTENANCE

INFRARED RADIANT TUBE HEATER

CHAPTER 6. HEATING PRODUCTION EQUIPMENT AND SYSTEMS

Commercial Water Heaters. Genesis. Water Heater Design Guide

Commercial Tankless Rack System

SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

Instantaneous Oil-Fired Water Heater. Installation Manual OM-148. (Type B)

comfort and peace of mind

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

Fully-automatic Gas tankless Water Heater USER'S MANUAL FOR MODEL EZ-101 ISO9001 certified

SUBJECT: SELKIRK MODEL DT DIRECT VENT SYSTEM FOR PELLET & CORN FIRED APPLIANCES / TERMINATION CLEARANCES TO OPENINGS IN BUILDINGS

MODEL GWH 2700 ES NG and GWH 2700 ES LP - INDOOR MODEL

On-Demand Water Heater Installation Manual and Owner s Guide

Do not use this vent pipe or fittings for venting incinerators of any kind.

Installation Operation Maintenance

THELIN GNOME PELLET HEATER PLANNING & INSTALLATION GUIDE

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

200i. Vent/air manual. Installation instructions for vent and air piping. Also read and follow: 200i Boiler manual 200i Control manual

2012 International Fuel Gas Code Design, Installation and Inspection Principles

Models CB-45 through CB-180 Cast-iron Hot Water Boilers Gas-fired Sealed Combustion Direct Vent, Category I, or Category IV Venting Flexibility

Submittal Data GA Line AYF Series Commercial and Specialty Chiller-Heaters 2 or 4 pipe Gas Fired Absorption Chiller-Heater Cooling and Heating

Technical Datasheet. FHG-S Models 28, and 45. Benefits at a Glance: State Route 22 Salem, NY 12865

TANKLESS WATER HEATER HEATING SOLUTIONS

COMBUSTION AIR SYSTEM

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

Commercial Tankless. Rack System TANKLESS WALL MOUNT LIGHTWEIGHT EXPANDABLE REDUNDANCY EASY FIELD INSTALLATION EASILY INTEGRATE STORAGE WARRANTY

Installation, Operation and Service Manual

A. Product Data: Include rated capacities, furnished specialties and accessories.

INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS RSTP17C

Boilers Variable Fire Boilers

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address

SuperStor Ultra Stainless Steel Storage Tank

The intelligent alternative for flue gas venting systems

Instantaneous Oil-Fired Water Heater. Installation Manual. OM-180 (Type D)

Corn Flame Energy Corn Stove Model 3000

Pellet Stove. Flex Pipe. Appliance Connector

Direct Vent System Required

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document

C1050ES Tankless Water Heater

HIGH-EFFICIENCY UPFLOW FURNACE INSTALLER'S INFORMATION MANUAL

Odyssey Model Numbers: CT Version Date:

2013 Efficiency Requirements for Gas Furnaces

WV-DV. Series. Oil. Boilers. Installation, Operation & Maintenance Manual

CVS. Venting System for Category II, III, and IV gas appliances. Listed to UL-1738 and ULC S636.

Utica Boilers MAC Submittal

Transcription:

Fall 2012 Things To Know About Tankless Water Heaters II Inside... Sizing Tables... Page 2 Two-pound Systems... Page 3 Two-pound Line Table... Page 3 Venting Specifications... Page 3 In the last Think Safety, we looked at some basic elements of a tankless water heater such as how they work, when to use them and sizing the water heater for the application. In this issue, we will focus on some essentials of installation. The water heater will not work to its maximum efficiency and output if the water and gas lines are sized incorrectly. Undersized gas and water lines Sizing Supply Lines: In order for the tankless water heater to operate correctly and supply the most hot water possible, both the water and gas supply lines must be sized correctly. Water and gas lines coming into the water heater should be around ¾ inch. If the water line is too small, the water heater will be unable to produce its maximum flow rate downstream. If the gas line is too small, the water heater will act like any other appliance starved for fuel. It may even shut down. are the most common culprits of early service calls. Venting is another important component in the tankless water heater installation. An improper vent installation can lead to several problems that can shorten the life of the water heater, produce troublesome operation, or in extreme cases keep the water heater from functioning at all. The gas line leading to the water heater must be sized correctly. Let s assume we are going to install a tankless water heater with a maximum BTU rating of 199,000. The home also will have an 80,000 BTU furnace, a 65,000 BTU gas range and a 32,000 BTU set of gas logs. The tank will be 50 feet from the house. Use Table 1, 2 or 3 on page two to determine the size yard line needed to supply adequate gas pressure. Table 1 is for copper tubing and Table 2 or 3 for Continued to Next Page Articles in this publication are for information only. Nothing in this publication is to be construed as setting standards or requirements. Please consult with appropriate regulatory and rulemaking bodies for all legal requirements.

Think Safety! Page 2 Fall 2012 Sizing Supply Lines: Continued from Page One poly tubing. The total BTU/hour load would be 376,000 BTU/hour. The tank will be set 50 feet from the house, so the first stage length will be just over 50 feet when taking into consideration the upturn of the lines to the first and second stage regulators. If either copper tubing or poly pipe is used, ½ inch tubing would be required. For second stage piping, measure the distance from the second stage regulator to the appliance furthest away. For simplicity, we are going to use schedule 40 black iron (Table 4). There are other piping materials that can be used such as CSST. In this example, we will use a distance 60 feet. The total load will be 376,000 BTU/hour. Use Table 4. The first section of pipe or main trunk line, will carry the whole load. This section of pipe will be one inch schedule 40 piping. You can size each branch line from there using the same table to determine the appropriate siae line based on the distance of that branch and the Btu/hr rating to be carried by the branch. These pipe sizes are minimums. For simplicity, of course all lines could be piped with the larger pipe sizes. For instance, all of the second stage piping could be piped with one inch piping for the main trunk and ¾ inch schedule 40 black iron for the branches as long as the minimum pipe sizes are met. Table 1 First Stage Piping between first stage and second stage regulator: Outside diameter copper tubing. 10 psi with a 1 psi pressure drop. Capacities are in 1000 Btu/hr. 3/8 1/2 5/8 3/4 7/8 30 309 700 1303 2205 3394 40 265 599 1115 1887 2904 50 235 531 988 1672 2574 60 213 481 896 1515 2332 70 196 443 824 1394 2146 80 182 412 767 1297 1996 90 171 386 719 1217 1873 100 161 365 679 1149 1769 Table 2 Polyethylen plastic pipe between first stage and second stage regulator: Nominal Outside Diameter (IPS). Capacities are in 1000 Btu/hr. 1/2 3/4 1 1 1/4 1 1/2 30 2143 4292 7744 13416 20260 40 1835 3673 6628 11482 17340 50 1626 3256 5874 10176 15368 60 1473 2950 5322 9220 13924 70 1355 2714 4896 8483 12810 80 1261 2525 4555 7891 11918 90 1183 2369 4274 7404 11182 100 1117 2238 4037 6994 10562 Table 3 Polyethylen plastic pipe between first stage and second stage regulator: Nominal Outside Diameter (CTS). Capacities are in 1000 Btu/hr. 1/2 1 30 762 5225 40 653 4472 50 578 3964 60 524 3591 70 482 3304 80 448 3074 90 421 2884 Table 4 Second State or integral twin stage pipe sizing between regulator and appliance. Maximum capacity of pipe or tubing in 1000 Btu/hr. 3/8 1/2 5/8 3/4 7/8 1 10 49 110 206 348 536 1146 20 34 76 141 239 368 788 30 27 61 114 192 296 632 40 23 52 97 164 253 541 50 20 46 86 146 224 480 60 19 42 78 132 203 435 70 16 36 67 113 174 400 80 14 32 59 100 154 372

Think Safety! Page 3 Fall 2012 Two Pound Systems: Two pound systems are an option to the installation of larger pipe sizes and can be especially useful in a home where the existing gas lines are inadequate to supply a tankless water heater. When installing a twopound system, a twopound delivery regulator is installed in place of the second stage regulator. The two-pound regulator delivers two pounds of pressure inside the structure. Another line pressure regulator is mounted upstream of the appliances. This regulator is equipped with a vent limiting device and Venting Specifications: Venting for tankless water heaters is hardly a one size fits all. Here are a few of the different vent types. 1. Horizontal Side Wall Concentric Vent the vent exits the building through the outside wall. Concentric pipe is a pipe within a pipe. Flue gas exits through the inside pipe, air for combustion is drawn in around the space between the inner and outer pipe. 2. Horizontal Side Wall Double Pipe (Separate flue gas pipe out and another pipe for air in) 3. Vertical Double Pipe vent exits the building through the roof. (Separate flue gas pipe out and another pipe for air in) 4. There are some water heaters that vent the exhaust and use air from inside the installation space for combustion. 5. Vertical Concentric Vent the vent exits the building through the roof. Some types of this venting require a condensate drain to be incorporated into the system. In some cases they may be direct vent or they may be classified mechanical exhausting. There are different requirements for those as to termination outside the building. There are usually requirements for maximum vent and air intake lengths as well as in some cases minimum lengths. Vent terminals vary with manufacturers and are not interchangeable from manufacturer to manufacturer. Side out venting is popular, Continued on Next Page performs similar to that of an appliance regulator. One line pressure regulator can either be mounted per appliance, or one regulator can serve a trunk line with multiple appliances. (Consult the regulator manufacturer to determine BTU load limits. Some of these regulators have a lower load limit for single appliance use than for use in a trunk line due to the single load surge of that individual appliance.) The higher delivery pressure allows for the use of smaller piping. Table 5 is an example of 2-psi system line sizing. A comparision to Table 4 illustrates the reduced piping size allowed verses a traditional two-stage system. Table 5 Copper tubing or pipe sizing between 2 psi service regulator and line pressure regulator. Capacity listed in 1000 Btu/hr. 3/8 1/2 5/8 3/4 7/8 10 451 1020 1900 3215 4948 20 310 701 1306 2210 3401 30 249 563 1049 1774 2731 40 213 482 898 1519 2337 50 189 427 795 1346 2071 60 171 387 721 1219 1877 70 157 356 663 1122 1727 80 146 331 617 1044 1606

Think Safety! Fall 2012 Page 4 Venting Specifications: Continued from Page Three usually requiring less venting materials, here are some of the typical side out venting requirements: Vent terminal must be at least 1 foot from any door, window, or gravity inlet into the building. The double pipe (Example: The vent and air intake terminals must be at the same height and their center lines must be between 12 and 36 inches apart. Both terminals must be on the same wall) All terminal bottoms must be 12 inches above normal snow line or no less than 12 inches above grade. (Note: it is often difficult to determine normal snow line) 7 feet above public walkway Do not install directly above windows or doors The bottom of the vent terminal must be at least 3 feet above any forced air inlet located within 10 feet. A horizontal distance of at least 4 feet between the vent terminal and gas meters, electric meters, regulators and relief equipment. Do not install vent terminal over this equipment due to condensate. Do not locate vent under decks. Top of vent terminal must be at least 5 feet below eves, soffits, or overhangs. Maximum depth of overhang is 3 feet. Vent terminal must be 6 feet from an inside corner. Be aware that condensate may freeze and cause damage to structures nearby. Install vent termination away from prevailing winds in excess of 40 MPH. Air intake must not be near possible combustion air contaminants. Failure to observe these equivalent calculations can result in an inadequate air supply for direct-vent units. The venting for condensing water heaters has different requirements, due to their high efficiency. Venting must be accomplished with a fan, because the vent gases are not hot enough to operate the natural draft vent. Water will condense in the vent and will dissolve some of the gases produced during combustion, which are slightly acidic. The vent materials used with these appliances must be able to resist the acidic condensate. Plastic vent material is acceptable and preferred for corrosion reasons. Observe the following limitations on the location of all vertical vent terminals. The top of the vent pipe must be at least 2 feet above any object located within 10 feet. The vertical distance between top of the vent and air inlet terminal openings must be at least 12. The bottom of the air inlet terminal must be at least 12 above the normal snow accumulation that can be expected on the roof. The air intake terminal must be located on the roof and must be no further than 24 horizontally from the exhaust pipe. Wall thimbles - Wall thimbles are often required where single wall vent pipe passes through combustible walls. Pitch of Horizontal Piping - Pitch all horizontal piping so that any condensate, which forms in the piping, will run away from the water heater Pitch horizontal concentric venting 5/8 per foot Pitch Stainless steel venting 1/4 per foot. Vertical and horizontal sections of pipe must be properly supported: Support concentric venting near the female end of each straight section of pipe. Support stainless steel venting as called for by the vent manufacturer s instructions. Pay attention to maximum distances for the vent run while remembering to calculate lost run footage for elbows. An example would be: 90-degree concentric elbow equals 4.5 feet, a 45-degree concentric elbow equals 4 feet, a 3 90 degree elbow equals 5.5 feet, a 3 45 degree elbow equals 4 feet. Tom Osina: Executive Director 107 S. West Street, #110 Alexandria, VA 22314 Phone: 703/530-9772 Fax: 703/530-9653 Web address: www.wvpropanegas.org Email address: wvpga@aol.com

Training Quiz Name Social Security Number 1. In order for the tankless water heater to operate correctly and supply the most hot water possible, both the water and gas supply lines must be sized correctly. 2. Water and gas lines coming into the water heater should be around inch. A. 3/4 B. 1/2 C. 1 D. 3/8 3. Using the sizing tables on page two, determine what size copper gas line would be needed from the first state regulator to the second stage regulator for the following example: Tankless water heater (199,000 Btu/hr), gas range (65,000 Btu/ hr) and a gas furnace (80,000 Btu). The tank is 50 feet from the house. 4. Using the tables on page two and the example in number 4, what size poly line would be used for the same yardline. 5. Using Table 4, what size second stage line would be needed for schedule 40 black iron in the example from question 3 if the distance from the second stage regulator to the furthest appliance is 60 feet? 6. Two-pound systems allow the installation of a smaller pipe size inside a structure. A.True B. False 7. When installing a two-pound system, a two-pound delivery regulator is installed in place of the second stage regulator. 8. When using a two-pound system, a line pressure regulator is mounted downstream of the appliances. 9. The line pressure regulator is equipped with a vent limiting device and performs similar to that of an appliance regulator. 10. Depending on the model of tankless water heater, it can be vented either vertically or horizontally. 11. Vent terminals vary with manufacturers but are interchangeable from manufacturer to manufacturer. 12. Using the example in question 3, what size piping would be required for the main trunk line inside the structure if a two-pound system was used? A. 3/4 B.3/8 C. 1/2 D. 1 13. A side-out vent terminal must be at least from any door, window, or gravity inlet into the building. A. 1 foot B. 2 feet C. 3 feet D. 4 feet 15. All terminal bottoms must be inches above normal snow line or no less than inches above grade. A.24, 24 B. 12, 12 C. 36, 36 D. 18, 18 16. Do not install vent terminations directly above windows or doors

Training Quiz Answers Name Social Security Number 1. In order for the tankless water heater to operate correctly and supply the most hot water possible, both the water and gas supply lines must be sized correctly. 2. Water and gas lines coming into the water heater should be around inch. A. 3/4 B. 1/2 C. 1 D. 3/8 3. Using the sizing tables on page two, determine what size copper gas line would be needed from the first state regulator to the second stage regulator for the following example: Tankless water heater (199,000 Btu/hr), gas range (65,000 Btu/ hr) and a gas furnace (80,000 Btu). The tank is 50 feet from the house. 4. Using the tables on page two and the example in number 4, what size poly line would be used for the same yardline. 5. Using Table 4, what size second stage line would be needed for schedule 40 black iron in the example from question 3 if the distance from the second stage regulator to the furthest appliance is 60 feet? 6. Two-pound systems allow the installation of a smaller pipe size inside a structure. A.True B. False 7. When installing a two-pound system, a two-pound delivery regulator is installed in place of the second stage regulator. 8. When using a two-pound system, a line pressure regulator is mounted downstream of the appliances. 9. The line pressure regulator is equipped with a vent limiting device and performs similar to that of an appliance regulator. 10. Depending on the model of tankless water heater, it can be vented either vertically or horizontally. 11. Vent terminals vary with manufacturers but are interchangeable from manufacturer to manufacturer. 12. Using the example in question 3, what size piping would be required for the main trunk line inside the structure if a two-pound system was used? A. 3/4 B.3/8 C. 1/2 D. 1 13. A side-out vent terminal must be at least from any door, window, or gravity inlet into the building. A. 1 foot B. 2 feet C. 3 feet D. 4 feet 15. All terminal bottoms must be inches above normal snow line or no less than inches above grade. A.24, 24 B. 12, 12 C. 36, 36 D. 18, 18 16. Do not install vent terminations directly above windows or doors