COMMON WATERSIDE ECONOMIZER APPLICATIONS:

Similar documents
Are uncontrollable humidity problems costing you a bundle?

water to water heat pumps

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GUIDE SPECIFICATIONS AQUARIUS ii

The Premium Quality Fan Coil Units for Vertical, Horizontal (Left or Right) Application with Direct Expansion, Hydronic or Electric Heat

MODULE-AIRE VERTICAL PACKAGE UNITS MB SERIES MB SERIES. Energy Wise HVAC Equipment

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Technical Development Program

GUIDE SPECIFICATIONS AQUARIUS ii

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

VertiCool Aurora Engineering Guide

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

C13-Series Engineering Guide

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

MC SERIES. Optional reverse cycle heating Takes full advantage of building diversity

Rev. 2/13

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

VERTICOOL TECHNICAL DATA MANUAL. Vertical Air/Water Cooled 3-25 Tons

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Split System Heat Pumps

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

COMMERCIAL HVAC EQUIPMENT Coils: Direct Expansion, Chilled Water, and Heating

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

EC SERIES MODEL NOMENCLATURE

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

AP SERIES VOLTAGE DESIGNATION: 1-208/1/60 & 230/1/60 CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Reinventing Energy Efficiency

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

GS SERIES. Table of Contents CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

HVAC Mandatory Provisions Part II, Page 1

Commercial High-Efficiency Condensing Units

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

50TM TFF COMBINATION HEATING/COOLING UNITS

Installation and Maintenance Manual TA Series

50TM COMBINATION HEATING/COOLING UNITS

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

1.1 This section applies to air handling units for HVAC Systems.

I/O ZONE 560/583 AND OPERATION MANUAL

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

MX Series Indoor Modular Blowers Electric Heat, Hot Water Heat, or No Heat

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

48TF GAS HEATING/ ELECTRIC COOLING UNITS

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

RDT Refrigeration Book

LV Model Water Source Heat Pump

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

FCC Fan-Coil Units High-Performance, Vertical

COMMERCIAL PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 20 TONS

VERTICAL AHU INSTALLATION MANUAL BULLETIN

MAC-120HE-03 Air-Cooled Chiller

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

"SWVP - SWHP" COMMERCIAL WATER SOURCE HEAT PUMPS & AIR CONDITIONERS

SKYPAK II, 3 Ton Series, gives you a

PACKAGE AIR CONDITIONER

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

Models PF1A PF1B PACKAGED AIR-HANDLING UNITS. 6to10Tons. Form No. PDS PF1A.72.1 FEATURES/BENEFITS

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

COOLING / HEATING COILS

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

WJH4 Product Specifications

FEATURES AND BENEFITS

Gas-Fired Indoor and Outdoor Duct Furnaces

ACCESSORY KIT INSTALLATION INSTRUCTIONS

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

48TM GAS HEATING/ELECTRIC COOLING UNITS

SpaceKeeper Console (SKC)

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

2009 IECC Commercial Mechanical Requirements

Owner s Manual Therma-Stor II Heat Recovery System

Greensource Residential Geothermal Heat Pumps. Think Green Think Renewable Think. iseries: SV Model Split System. boschheatingandcooling.

VariCool VAV. (Variable Air Volume) 9 to 70 tons Variable Air Volume Water-Cooled and Chilled Water. Unique Solutions for All-Indoor HVAC Projects

HORIZONTAL SERIES. AIRPAC HORIZONTAL PACKAGED SERIES 24,000 to 180,000 BTU/h

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

Energy Use in Refrigeration Systems

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

CM R-410A High Efficiency Water Source Heat Pump

PAR5. Product Specifications

30GT FLOTRONIC AIR-COOLED CHILLERS

Product Specifications. Vertical Floor Consoles By First Co.

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Low Profile Unit Coolers

Transcription:

APPLICATION MANUAL WATERSIDE ECONOMIZER TABLE OF CONTENTS Safety Approvals...1 Common Waterside Economizer Applications...1 Sequence of Operation (Single)...1 Cooling Mode...2 Heating Mode...2 Sequence of Operation (Dual)...2 Special Application...2 Fluid Flow...2 Condensate Drain...2 Aquastat...3 Maximum Design Pressures...3 Air Side Pressure Drop...3 Cooling Data Single Compressor...4 Fluid Temperature Correction Table...4 Cooling Data Dual Compressor...5 Air Temperature Correction Table...5 Dimensions (HZ) with Valve Package & Coil...6 Dimensions (VT) with Valve Package & Coil...7 Wiring Diagram...8 SAFETY APPROVALS: ENERGY WISE HVAC EQUIPMENT FHP MANUFACTURING COMPANY 601 N.W. 65th Court Fort Lauderdale, FL 33309 Phone: 954/776-5471 Fax: 800/776-5529 http://www.fhp-mfg.com This factory installed option is Underwriter Laboratories (UL) and The City of New York Materials Equipment Acceptance Division (MEA) safety listed on all EM, and GT models. COMMON WATERSIDE ECONOMIZER APPLICATIONS: Commercial application where perimeter heating is being done while core cooling is required. Perimeter heat pumps operation in the heating mode extract heat from the building loop thus dropping the building loop fluid temperature. Internal core cooling requirements are usually high even in the winter months due to people, lighting, and equipment loads. The moderate temperature loop water circulated through a core heat pump s waterside economizer coil can provide free-cooling without the use of mechanical cooling (Compressors). Also, in many areas code requires some type of economizer cycle. Waterside Economizers in lieu of air side economizers are an inexpensive way to satisfy code requirements in commercial applications.

2 WATERSIDE ECONOMIZER Tenant build out commercial applications where the central chilled water fluid loop serves as a individual zoned heat pump condenser water. In this application low temperature fluid is always available for free-cooling. Residential applications where moderate temperature ground water is utilized, mainly in the midwest and northern regions. In these areas the cooling loads are relatively low compared to the heating requirements. Summer months are relatively mild so often the freecooling coil can handle total summer cooling requirements without the use of mechanical cooling. Some mechanical cooling may be required during peak loads. SEQUENCE OF OPERATION (SINGLE COMPRESSOR MODELS) (Utilizing 2 Stage Cool, 2 Stage Heat Thermostat) COOLING MODE: On a call for cooling from the space sensor the following sequence is initiated: The G terminal energizes the blower relay, powering the blower motor. The O terminal energizes the reversing valve coil, setting the heat pump in the cooling mode and energizing the pre cooling relay PC. The normally closed contacts of PC open and the normally open contacts of PC close. The motorized ball valve will be energized in the bypass mode, routing water directly to the water to refrigerant heat exchanger, until the Y1 terminal closes. On a rise in space temperature Y1 will close. If the temperature of the water is below the aquastat set point the motorized ball valve relay MBVR will be energized. This will energize the motorized ball valve in the economizer mode, diverting water first through the economizer coil then the water to refrigerant heat exchanger in series. Should the space temperature continue to rise Y2 will be energized allowing mechanical cooling. If at any time the water temperature rises above the aquastat set point the motorized ball valve will be energized in the bypass mode and fluid will bypass the economizer coil. HEATING MODE: On a call for heating from the space sensor the sequence of operation is identical to the above with the exception that the reversing valve and pre-cooling relay are not energized so locking the motorized ball valve in the bypass mode. SEQUENCE OF OPERATION (DUAL COMPRESSOR MODELS) The sequence of operation is exactly the same as above. The second compressor circuit is in parallel with the first compressor across Y2. A delay on make timer is located in the second stage compressor contactor circuit to avoid dual compressor in-rush starting current. Both compressors are energized thru Y2 in heating and Y2 in cooling. SPECIAL APPLICATIONS UTILIZING WATERSIDE ECONOMIZER COILS AS PREHEATING COIL: Waterside Economizer coils can also be applied as pre-heating coils in outside air pre-heating application. When utilizing high temperature condenser water a pre-heating coil can elevate the entering outside air temperature to a minimum entering air temperature of 40º F into the heat pump during the heating mode. CAUTION: When introducing outside air below 32º F anti-freeze solution is required. Coil damage due to freezing is not covered under FHP warranty. Usually some means of heating outside air to above 40º F is field provided. Pre-heating coils can also be supplied by a hydronic boiler loop or a dedicated water to water heat pump for pre-heating outside air. In this application the coil only is utilized without the valve package and associated controls. Field installed pumping means, piping systems, and associated controls are required. (Consult factory for heating coil capacity data). FLUID FLOW: Fluid flow through heat pumps equipped with waterside economizer coils is directed by the use of a single three way motorized ball valve. Flow is either through the waterside economizer coil and then through the condenser or through the condenser only. When applying these units to a variable speed pumping system a field provided means of positive flow shut-off is required. (Re: A positive shut-off solenoid valve located downstream of the heat pump). (See Figure #1) CONDENSATE DRAIN: A drain line must be connected to the Waterside Economizer drain pan and pitched away from the unit a minimum of 1/8 per foot to allow the condensate to flow away from the unit. A trap must be installed in the condensate line to insure free condensate flow. A vertical air vent tube is sometimes required to avoid air pockets. The depth of the trap depends on the amount of positive or negative pressure on the on the drain pan. A second trap must not be installed. This connection should be in conformance to local plumbing codes. (See Figure #2)

WATERSIDE ECONOMIZER 3 3-Way motorized ball valve Aquastat N.O. MBV N.C. N.O. Waterside economizer coil Fluid to refrigerant heat exchanger Fluid in (Figure #1) Bulb Strapped to Fluid in Line (field installed) Positive shut-off solenoid valve for variable speed pumping system (field installed) The Waterside economizer coil and the heat pump must be trapped independently per Figure #2. AQUASTAT: The aquastat controller is mounted to the heat pump electrical control box. All electrical control wiring is factory installed. The controller is supplied with an external range adjustment and screwdriver slot. Actual range is -30 to 100 F and requires field setting. The remote bulb stored inside the heat pump for shipping requires field mounting. (Figure #1) Care should be taken not to dent or deform this sensitive remote bulb. A dent or deformation will change the calibration and cause the control to cycle at a temperature lower than the selected setting. (Figure #2) MAXIMUM DESIGN WORKING (OPERATING) PRESSURES: The maximum design fluid side working pressure is 400 PSIG. This applies to waterside economizer coils, water to refrigerant heat exchangers, and motorized ball valves. In multi-story high rise applications care needs to be taken with regards to high static pressures generated by elevation. AIR SIDE PRESSURE DROP: The air side pressure drops shown on the waterside economizer performance tables is considered as additional heat pump external static pressure. Refer to the individual heat pump specification sheets to determine if the CFM delivered versus the total external static pressure (including waterside economizer coil drop) is adequate to meet specified air flow requirements. In certain instances oversized drive packages may be required. Please consult factory for oversized drive specifications.

4 WATERSIDE ECONOMIZER COOLING CAPACITY DATA Heat Pump Model Waterside Air Cooling EM GT Flow GPM PSI Press. Ft.HD NOM. CFM Press. Drop in H 2 O (avg.) Total Sensible 007 --- 2.68 1.6 4 1.7 3.9 300.03 5600 3920 6500 4290 009 010 3.04 1.7 5 2.0 4.6 350.05 7700 5360 8700 5720 012 --- 3.04 1.7 5 2.0 4.6 400.07 8800 6100 9900 6500 015 018 4.5.08 1.8 7.5 2.2 5.1 550.07 11500 8180 13100 8710 018 022 4.5.08 1.8 7.5 2.2 5.1 650.08 13600 9670 15500 10300 024 026 4.5 0.8 1.8 7.5 2.2 5.1 850.10 16800 11950 19200 12730 028 --- 4.5.98 2.3 7.5 2.7 6.2 950.10 18100 13300 21100 14300 031 030 6 1.2 2.8 10 3.1 7.2 1000.11 21700 16100 24200 17800 036 036 6.95 2.2 10 2.4 5.5 1200.12 24400 17600 28300 19000 041 042 8.99 2.3 12 2.8 6.5 1200.13 25100 17900 29200 19200 042 048 8.99 2.3 12 2.8 6.5 1500.14 26500 20000 31300 21600 048 054 9.82 1.9 15 2.0 4.6 1700.15 33400 24300 38700 26100 060 062 9.82 1.9 15 2.0 4.6 2000.17 35500 26600 41600 28600 070 070 9.82 2.0 15 2.0 4.8 2200.18 37300 29000 44800 32400 NOTES: 1. For total system waterside pressure drop add heat pump pressure drop and waterside economizer coil pressure drop. 2. Air side pressure drop based on 1 thick clean filter and wet coil. 3. Capacities shown are based on 45º E.F.T. and 80º DB/67º WB E.A.T. 4. See correction tables for other conditions. FLUID TEMPERATURE CORRECTION TABLE Ent. Fluid Temp. Total Sensible Deg. F BTUH BTUH 45 1.000 1.000 50.790.890 55.610.780 60.470.470 65.350.350 70.240.240

WATERSIDE ECONOMIZER 5 COOLING CAPACITY DATA Heat Pump Model Waterside Air Cooling EM Flow GPM PSI Press. Ft. HD NOM. CFM Press. Drop in H 2 O (avg.) Total Sensible 072 10 1.3 3.0 18 6.0 8.3 2300.22 56000 46200 67200 50400 096 10 1.3 3.0 22 6.0 13.9 2800.25 61400 52000 79800 59400 120 16 2.5 5.7 32 9.2 21.4 4000.30 91900 75300 113400 84200 140 18 2.7 6.2 38 9.4 21.8 5000.25 94700 77800 113500 84300 144 20 1.2 2.8 45 4.2 9.7 5000.25 97600 81300 113600 84400 168 20 1.2 2.8 45 4.2 9.7 6000.28 106000 92100 125200 97300 210 24 1.4 3.3 52 6.2 14.4 7000.28 155400 131000 203600 151600 240 32 2.5 5.7 64 9.2 21.4 8000.30 183800 150600 226800 168400 300 38 3.0 7.3 75 11.3 27.3 10000.33 213000 174600 256000 190300 360 45 4.1 9.4 90 7.8 18.0 12000.37 307900 251500 370000 275000 NOTES: 1. For total system waterside pressure drop add heat pump pressure drop and waterside economizer coil pressure drop. 2. Air side pressure drop based on 1 thick clean filter and wet coil. 3. Capacities shown are based on 45º E.F.T. and 80º DB/67º WB E.A.T. 4. See correction tables for other conditions. AIR TEMPERATURE CORRECTION Ent. WB Deg. F Total Correction Sensible Correction for Ent. DB 70 75 80 85 95 57.851.961 --- --- --- --- 61.910.763 1.030 --- --- --- 64.955.615.881 1.148 --- --- 67 1.000 ---.733 1.000 1.267 --- 73 1.090 --- ---.703.970 --- 78 1.164 --- --- ---.723 1.257

6 WATERSIDE ECONOMIZER MODELS: EM007 thru EM042 and EM070 GT009 thru GT070 RETURN AIR VIEW MODELS: EM048 thru EM060 RETURN AIR VIEW MODELS: EM072, EM096, EM120, EM140 RETURN AIR VIEW NOTES: 1. All drain connections 3/4 2. Not all cabinet configurations are shown

WATERSIDE ECONOMIZER 7 MODELS: EM009 thru EM070 GT009 thru GT070 RETURN AIR VIEW MODELS: EM072, EM096, EM120 MODELS: EM144, EM168, EM210, EM240, EM300, EM360 TOP VIEW TOP VIEW NOTES: 1. All drain connections 3/4 2. Not all cabinet configurations are shown

8 WATERSIDE ECONOMIZER CAUTION: FHP Manufacturing will not warranty waterside economizer coil failures or assume any associated liabilities resulting there of caused by the following mis-applications: 1. Freezing of waterside economizer coils due to low temperature outside air entering the coil 2. Freezing of waterside economizer coils caused by heat pump fan failure, belt failure, or restricted airflow caused by any outside circumstances including acts of God. Convection from the DX evaporator during this situation may cause coil freezing. (Field installed sail switches may be utilized to confirm air flow.) 3. High pressure hydraulic hammer due to pumping system start-ups and shutdowns splitting tubes seam wise. 4. High velocity water caused by excessive flow rates which erode and thin the inner wall of the coils copper tubing and resulting in a pressure burst situation. 5. Particulate matter or foreign debris contained in the systems water loop which may cause erosion of the inner tube walls resulting in a pressure burst. REV. 2/05