KHP Models. KHP Series. Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

Similar documents
SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

HEPA Filtration. HEPA Series. Air Filtration System IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

SH, VH & SE Series. Installation, Operation and Maintenance Manual. Heat & Energy Recovery Ventilators SH 704 VH 704 SE 704

Light commercial models

SER Series. fantech. Installation Manual. Energy Recovery Ventilators. ser 1504 ser 1504n ser 2004 ser 2004n ser 3204d ser 3204n

SER150. Installation Manual. Energy Recovery Ventilators

SHR & VHR Models. SHR & VHR Series. Installation Manual. Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

SER Series. Installation Manual. Energy Recovery Ventilators SER 1504 SER 2004 SER 3204D

SER Models. SER Series Energy Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

KHP 6000 KHP MODEL FOR LIGHT COMMERCIAL

IAQ VENTILATION SOLUTIONS

VHR SERIES VHR 704. Installation Manual. Heat Recovery Ventilator INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Light Commercial Heat/Energy Recovery Ventilator

DBF 4XL Dryer Booster Fans

Quest Power Electric Heat EHS 31 Pro

Owner s Manual Phoenix FireBird

IAQ VENTILATION SOLUTIONS

Quest Power Electric Heat EHS 62 Pro

CVS Model Inline Multi-Port Ventilators

OPERATION & MAINTENANCE MANUAL MODEL SC-924A SELF-CONTAINED ELECTRONIC AIR CLEANER IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Owner s Manual. Portable Air Conditioner ARP-5008 ARP Royal Sovereign International, Inc.

SER Models. SER Series Energy Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

Installation Instructions for Heat Recovery Ventilators with 2 Speed RNC Electronics. RNC Series. Residential Heat Recovery Ventilators (HRV)

Energy Recovery Ventilators

RP, GP, XP Pro Series Installation Instructions

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

Please Read and Save These Instructions.

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

OPERATION & MAINTENANCE MANUAL MODEL SC SELF-CONTAINED ELECTRONIC AIR CLEANER IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT

INSTALLATION AND OPERATION INSTRUCTIONS

DEHUMIDIFIER. User Manual 50BT, 70BT

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

IN020 Rev F Page 1 of 8

MANUAL 8/12/05. Model BKP TM 100 INSTALLATION, OPERATION & MAINTENANCE. Commercial High Efficiency Heat Pipe Dehumidifier

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

Portable Dehumidifier

CAUTION WARNING INSTALLATION INSTRUCTIONS FOR HEALTHY CLIMATE WHOLE HOME DEHUMIDIFIER MODEL HCWH-065 (Y3013) DEHUMIDIFIERS

Model 1870F Dehumidifier Installation and Operating Manual

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

IMPORTANT INSTRUCTIONS - OPERATING MANUAL

Xaact Spot. Xaact Hot Spot

Quest Dry. Quest 110 Dual. Read and Save These Instructions. Installation, Operation and Maintenance Instructions

NU800, NU1200 & NU1600

Model 8140 & 8141 Fresh Air Ventilator Installation and Operations Manual

VENTILATORS VH30100 COMPACT HEAT RECOVERY VENTILATOR VE30100 COMPACT ENERGY RECOVERY VENTILATOR. Installation and Operation Manual.

HEAT RECOVERY AND ENERGY RECOVERY VENTILATORS

Portable Dehumidifier with Internal Pump

SF180 Installation Instructions

Owner s Manual HI-E Dry Vehere

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Phoenix AirMAX - Radial Air Mover

TR Series - The Ultimate ERV

IMPORTANT SAFETY INFORMATION:

MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS

User Manual HEAT RECOVERY VENTILATORS 1000 HE HE HE HE HE HE COMPACT 5585 COMPACT READ AND SAVE THESE INSTRUCTIONS.

VERTICAL FAN COIL UNITS

10-year industry best core warranty. 5-year warranty on balance of unit.

(The chances are you re never going to read me) Owner s Manual HEAVY DUTY SHD-1T.

READ MANUAL BEFORE OPERATING SYSTEM Read the owner s manual thoroughly before operating to ensure the most efficient use of the system.

HEALTHY CLIMATE Heat / Energy Recovery Ventilator

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Owner s Manual Phoenix Aquadry TX 200

IN014 Rev P Saber Way, Ward Hill, MA radonaway.com

HEAT RECOVERY VENTILATOR

Heat or Energy Recovery Ventilation System

IMPORTANT SAFETY INFORMATION

Quest Dry 105, 155, and 205 Dual

CS90H INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

IMPORTANT SAFETY INFORMATION:

Model: C C Ambassador 20. Automatic Carpet Scrubber OPERATION SERVICE PARTS CARE

NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

SINGLE MOTOR UPRIGHT VACUUM CLEANER MODEL C

Ceiling Mount Air Purification System

WIDE AREA VACUUM MODEL PF2030 WARNING: OPERATOR MUST READ AND UNDERSTAND THIS MANUAL COMPLETELY BEFORE OPERATING THIS EQUIPMENT.

INSTALLATION INSTRUCTIONS

AGITATOR V DO NOT OPERATE THE MACHINE UNTIL YOU HAVE READ ALL SECTIONS OF THESE INSTRUCTIONS IMPROPER USE OF THE MACHINE WILL VOID THE WARRANTY

Model No. GB-PAC-08E4. 8,000 BTU Portable Air Conditioner Operating Instructions

Operation and warranty Manual

Quest Dry 150 Dual. quest Asset Protection and IAQ Solutions. Read and Save These Instructions. Installation, Operation and Maintenance Instructions

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCS. Voltage rating: 115V~60Hz Power rating : 1400W

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

MRS-6 Maxi-Guard II. Model: C , 12, 13, 14 OPERATION SERVICE PARTS CARE. Revised 2/02

GENIUS 14 GENIUS 18 OPERATING & MAINTENANCE

IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS

Portable Dehumidifier with Internal Pump Portable Dehumidifier with Internal Pump OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS

For cleaning machines, parts & supplies click/visit Electrolux Home Care Products Ltd.

Model 1850F Dehumidifier Installation and Operating Manual

InstructIon Manual KrEs EQuIPMEnt stands

READ AND SAVE THESE INSTRUCTIONS

Healthy Climate Whole-Home Dehumidifier. Nominal Capacity - 70 to 130 pints per day INDOOR AIR QUALITY HCWHD PRODUCT SPECIFICATIONS.

PW 150 / PW 100. Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1

Quest PowerHeat HFC 100 Pro

Model 8140 and 8140NC Fresh Air Ventilator Installation and Operating Instructions

DELUXE OPERATIONAL MANUAL

Heat Recovery Ventilators models:

READ AND SAVE THESE INSTRUCTIONS. Air Boss Model T5200 Custom Packaged Electronic Air Cleaner. TRION

Transcription:

KHP Series Heat Recovery Ventilator IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT CAUTION - Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipement, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s of the Heat Recovery or Energy Recovery Ventilators by using the balancing procedure found in this manual. It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.). NEVER - install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!! Your ventilation system should be installed in conformance with the appropriate provincial or state requirements or in the absence of such requirements with the current edition of the National Building Code, and / or ASHRAE s good Engineering Pratice. KHP Models KHP 20000 KHP 30000 INSTALLATION, OPERATION AND MAINTENANCE MANUAL

The Best Limited Warranty in the Business The limited warranty covers normal use. It does not apply to any defects, malfunctions or failures as a result of improper installation, abuse, mishandling, misapplication, fortuitous occurrence or any other circumstances outside Fantech s control. Inappropriate installation or maintenance may result in the cancellation of the warranty. Any unauthorized work will result in the cancellation of the warranty. Fantech is not responsible for any incidental or consequential damages incurred in the use of the ventilation system. Fantech is not responsible for providing an authorized service centre near the purchaser or in the general area. TABLE OF CONTENTS INSTALLATION Safety Instructions... 3 Installing the Unit... 4 OPERATION......6 MAINTENANCE...6 TROUBLESHOOTING...7 TECHNICAL DATA... 8 TECHNICAL DATA KHP 20000...9 TECHNICAK DATA KHP 30000...10 Fantech reserves the right to supply refurbished parts as replacements. Transportation, removal and installation fees are the responsibility of the purchaser. The purchaser is responsible to adhering to all codes in effect in his area. The warranty is limited to 2 years on parts and 1 years on the motor from the date of purchase, including parts replaced during this time period. If there is no proof of purchase available, the date associated with the serial number will be used for the beginning of the warranty period. * This warranty is the exclusive and only warranty in effect relative to the ventilation system and all other warranties either expressed or implied are invalid. Please fill out the warranty registration and return it within two weeks of purchase or the warranty will be voided. NOTE: Some products may not be exactly as illustrated in the Installation, Operation and Maintenance Manual. Fantech Inc. reserves the right to modify, at any time and without notice, any or all of its products features, designs, components and specifications, to maintain their technological leadership position.

INSTALLATION SAFETY INSTRUCTIONS 1 Do not attempt installing the unit without first reading the entire manual. 2 It is always important to determine how the operation of any Heat Recovery Ventilator may interact with vented combustion equipment (i.e. Gas furnaces, Oil furnaces, Wood stoves etc.) 3 Never install a Heat Recovery Ventilator in a situation where its normal operation ( including defrost function), lack of operation or partial failure may result in the back drafting or improper functioning of vented combustion equipment. 4 If combustible appliances are used in the dwelling, the fresh air hood is to be kept free of obstacles at all times, to prevent improper functioning of these appliances. 5 Make sure the outside supply hood is not near a source of contaminated air, which may cause health problems. 6 Before opening the access door, either for service or maintenance, make sure that power supply is shut off to prevent injuries due to electrical shock (230v). 7 Make sure mounting chains are properly fastened so the unit does not fall, and to prevent any possible injuries.

INSTALLATION (CON T) Main Power The main power is to be connected to the main electrical box. Both unit require a single phase, 230 VAC, 20 amps circuit. Remote override switch The override switch needs to be connected to allow the unit to go on high speed. The switch has to be connected to the two pin terminal block inside the main electrical box. This switch will close the contact of a 24 VAC coil inside the electrical box. Drain Connection The condensate drain is connected to the Exhaust Air out compartment. The drain line is connected to a 1/2 OD tube. A serpentine loop is recommended on the external drain line. Drain Connection Drain Line Loop Mounting Brackets The mounting bracket, which is already fastened to the unit, is mounted in place using threaded rods. The rods are then connected to the base plates provided with the bracket. The plates have to be at a minimum of 2 from the edge of the rail and in a range of 6 as shown in the drawing below. Rods

INSTALLATION (CON T) Winter/Summer Settings To set the unit in the winter setting, lower the unit 1/2 on the exhaust side from the level line. This will be achieved by adjusting the support nut on the threaded rods. For the summer setting, you have to rise the unit back to its level line, and then 1/2 more to incline it. The exhaust side should be higher than the supply side on this setting. 1/2 1/2

OPERATION Speed Control The function of the speed controller is to regulate the continuous ventilation rate. This achieved by a solid state speed control. It permits the operator to set the ventilation at a moderate rate for normal conditions. Override Switch The purpose for the override switch is to activate the ventilation to its maximum capacity. Achieving this contact can be either through a manual switch or a timer control. Voltage for this circuit is 24 VAC. MAINTENANCE Make sure unit is unplugged before attempting any maintenance work. Filters The filters need to be checked and cleaned every three(3) months. Cleaning the filters can be done with a vacuum cleaner. Filters need to be replaced every 6 months, or sooner depending on the operating and environmental conditions. Heat Pipe Core The heat pipe core needs to be visually checked for cleanliness every six (6) months. If it needs to be cleaned, it is recommended to use commercial condenser coil cleaners. Blower Belts The belts need to be checker for wear and ensure a correct tension is applied. A simple Rule of Thumb for checking the belt tension is illustrated on the side. When the belt is grasped as shown, a total deflection of approximately 1 should be easily attained. A visual check of the wear of the belt is also necessary. The drain and drain line Units with drain lines should have their line and connection checked regularly.

TROUBLESHOOTING Problem Air is too dry Air is too humid Persistent condensation on window Causes Dehumidistat control is set too low Dehumidistat control is set too high Sudden change in temperature Storing too much wood for heating Dryer vent exhaust is inside home Slow combustion heating only Poor air circulating near windows Basement door is closed Improper adjustment of control Solutions Increase the desired level of humidity. Change ventilation mode from continuous mode to standby. Reduce the desired level of humidity. Combine this step with use of continuous exchange mode. Wait until outside temperature stabilizes (winter). Heating will also improve situation. Store a majority of your wood outside. Even dried, a cord of wood contains more than 20 gallons of water. Arrange outside vent for dryer. Combine with central heating. Open curtains or blinds. Bay or bow windows may require mechanical method. Open the door or install a grill on the door. Reduce the desired level of humidity. Combine this with the use of continuous exchange mode.

TECHNICAL DATA COMPONENTS HEAT PIPE - Face Area..4 square feet (KHP 20000) Dimensions KHP 20000 A - 1400 mm (55.125 ) B - 1332 mm (52.4375 ) C - 260 mm (10.25 ) Face Area..6 square feet (KHP 30000) Dimensions KHP 30000 A - 1778 mm (70.00 ) B - 1713 mm (67.4375 ) C - 457 mm (18.00 ) Rows.4 Fins per Inch 12 Fin Material..Aluminum alloy 7072-2 Fin Design Corrugated Tube Material...Copper Alloy 122 Tube Size.0.625 inches OD Partition Thickness..14 gauge Partition Material.Galvanized Steel End cover Thickness 14 gauge End cover Material..Galvanized Steel The heigth is the same for KHP 20000 & KHP 30000 at 37.00 FILTERS - Drawer type filter rack throw-away fiberglass filters Filter Thickness 1.0 inch Insulated cabinet BLOWERS ELECTRIC MOTORS UNIT CONTROLS CONDENSATE DRAIN - Double inlet / Double width blower belt driven galvanized wheel and housing ball bearing operation temperature range of -54 C (-65 F) to +121 C (+250 F) of airflow capacity of 2000 cfm (KHP 20000) airflow capacity of 3000 cfm (KHP 30000) variable pulleys self-contained insulated cabinet rubber mounted - Resilient base / Totally closed air over Epoxy enamel finish 3/4 horse power, single phase, 115/230 Volts (KHP 20000) 1 horse power, single phase, 230 Volts (KHP 30000) Start capacitor Over load protection F56 frame - Fully variable speed control, automatic frost control, override terminal (24VAC) - 18 gauge galvanized steel drain pan Easy hookup to standard 1/2 ID Flexible PVC braided hose 8

KHP 20000 TECHNICAL DATA PERFORMANCE & DIMENSIONS Performance External Static Pressure (inches of W.G.) Airflow CFM (cubic feet per minute - CFM) 1 0.9 0.8 The airflow chart is given at 0.1 interval for fast and precise readings Static Pressure (in WC) 0.7 0.6 0.5 0.4 0.3 0.2 Dimensions & Weight Unit Weight 435 pounds 1733 mm (68.25 ) 0.1 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 Airflow (cfm) Main Electrical Box 1397 mm (55.00 ) 83 mm (3.25 ) 292 mm (11.50 ) 292 mm (11.50 ) 159 mm (6.25 ) 381 mm (15.00 ) 1499 mm (59.00 ) 1194 mm (47.00 ) 350 mm (13.75 ) 584 mm (23.00 ) 1220 mm (48 ) 699 mm (27.50 ) 686 mm(27.00 ) 395 mm (15.50 ) 1455 mm (57.25 ) 25.4 mm (1.00 ) 343 mm (13.50 ) 343 mm (13.50 ) 343 mm (13.50 ) 584 mm (23.00 ) 679 mm (26.75 ) 533 mm (21.00 ) 343 mm (13.50 ) 140 mm (5.50 ) 629 mm (24.75 )

KHP 30000 TECHNICAL DATA PERFORMANCE & DIMENSIONS Performance External Static Pressure (inches of W.G.) The airflow chart is given at 0.1 interval for fast and precise readings Airflow CFM (cubic feet per minute - CFM) Static Pressure (in WC) 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 Dimensions & Weight Unit Weight 535 pounds 2184 mm (86.00 ) Main Electrical Box 1778 mm (70.00 ) Airflow (cfm) 83 mm (3.25 ) 356 mm (14.00 ) 356 mm (14.00 ) 270 mm (10.63 ) 441 mm (17.38 ) 1880 mm (74.00 ) 1619 mm (63.75 ) 405 mm (16.2 ) 711 mm (28.00 ) 1220 mm (48 ) 813 mm (32.00 ) 851 mm(33.50 ) 470 mm (18.50 ) 1836 mm (72.25 ) 25.4 mm (1.00 ) 425 mm (16.75 ) 425 mm (16.75 ) 425 mm (16.75 ) 711 mm (28.00 ) 851 mm (33.50 ) 638 mm (25.13 ) 425 mm (16.75 ) 146 mm (5.75 ) 778 mm (30.63 )

United States 1712 Northgate Blvd., Sarasota, FL. 34234 Phone: 800.747.1762; 941.309.6000 Fax: 800.487.9915; 941.309.6099 www.fantech.net; info@fantech.net Canada 50 Kanalflakt Way, Bouctouche, NB E4S 3M5 Phone: 800.565.3548; 506.743.9500 Fax: 877.747.8116; 506.743.9600 www.fantech.ca; info@fantech.ca Fantech, reserves the right to modify, at any time and without notice, any or all of its products features, designs, components and specifications to maintain their technological leadership position. Item #: 401336 Rev Date: 020205