OFFSHORE SUPPORT VESSELS 2014

Similar documents
ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

RESOLUTION MSC.98(73) (adopted on 5 December 2000) ADOPTION OF THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

Notice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world

F-03 FIXED FIRE DETECTION AND FIRE ALARM SYSTEM

Notice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)

RESOLUTION MSC.339(91) (adopted on 30 November 2012) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE)

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

Requirements for ships carrying hydrogen and compressed natural gas vehicles

MSC Guidelines for General Emergency Alarm & Public Address Systems

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

RESOLUTION MSC.217(82) (adopted on 8 December 2006) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

CERTIFICATE OF FIRE APPROVAL

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

RESOLUTION MSC.44(65) (adopted on 11 May 1995) STANDARDS FOR FIXED SPRINKLER SYSTEMS FOR HIGH SPEED CRAFT

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2)

AMENDMENTS NO. 3/2012 to

MOBILE OFFSHORE DRILLING UNITS 2012

Part 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels

E-20 COMPARTMENT FLOODING WATER LEVEL DETECTORS (INCLUDING SENSORS)

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

UNIFIED INTERPRETATIONS OF SOLAS CHAPTER II-2, THE FSS CODE, THE FTP CODE AND RELATED FIRE TEST PROCEDURES ***

RULES FOR CLASSIFICATION OF MOBILE OFFSHORE UNITS

ADDITIONAL FIRE PROTECTION (F-AMC)

RESOLUTION MSC.291(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS

RESOLUTION A.752(18) adopted on 4 November 1993 GUIDELINES FOR THE EVALUATION, TESTING AND APPLICATION OF LOW-LOCATION LIGHTING ON PASSENGER SHIPS

IACS RESOLUTION CHANGES (GMO ) BEKİR SITKI TÜRKMEN

IMO. Resolution A.952(23) Adopted on 5 December 2003 (Agenda item 17) GRAPHICAL SYMBOLS FOR SHIPBOARD FIRE CONTROL PLANS

STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 )

Government of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE

ENHANCED FIRE PROTECTION ARRANGEMENTS

Additional Fire Protection (F-AMC)

MOBILE OFFSHORE DRILLING UNITS 2014

IMO WORK PROGRAMME. Central control stations and safety centres on passenger ships. Submitted by Argentina and ICCL

Technical Information

IMO DEVELOPMENT OF MODEL PROCEDURE FOR EXECUTING SHIPBOARD EMERGENCY MEASURES. Fire-fighting drills. Submitted by the Republic of Korea

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

***** 2. Rev.1 is to be uniformly implemented by IACS Members from 1 July 2004.

Fire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200

Guideline No.: S-02(201510) S-02 Navigation Light and Signal Light Controllers. Issued date: October 20,2015. China Classification Society

ClassNK Technical Information No. TEC-0838 (iii) The dormant period, visual indication, first stage audible alarm, second stage remote audible alarm a

Part 4 Systems and components Chapter 5 Control and Monitoring Systems

RESOLUTION MSC.188(79) (adopted on 3 December 2004) PERFORMANCE STANDARDS FOR WATER LEVEL DETECTORS ON BULK CARRIERS AND SINGLE HOLD CARGO SHIPS

RESOLUTION MSC.145(77) (adopted on 5 June 2003) PERFORMANCE STANDARDS FOR WATER LEVEL DETECTORS ON BULK CARRIERS

IMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009

Fixed Fire Extinguishing Equipment and Systems

Technical Information

GUIDELINES FOR THE APPROVAL OF HELICOPTER FACILITY FOAM FIRE-FIGHTING APPLIANCES

Order on fixed CO 2 fire-extinguishing systems 1

ClassNK Technical Information No. TEC-0453 Attachment (1) to ClassNK Technical Information No. TEC-0453 Guidance on SOLAS Chapter II-2 as amended in 2

PATROL BOATS HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT RULES FOR CLASSIFICATION OF DET NORSKE VERITAS SPECIAL SERVICE AND TYPE ADDITIONAL CLASS

Iranian Classification Society Convention and Legislation Department Code: Tech Contents

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

E-17 Flammable Gas Detection and Alarm System

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

CERTIFICATE OF FIRE APPROVAL

FIRE SAFETY SHIPS RULES FOR CLASSIFICATION OF NEWBUILDINGS DET NORSKE VERITAS MACHINERY AND SYSTEMS MAIN CLASS PART 4 CHAPTER 10 JULY 2006

MOBILE OFFSHORE DRILLING UNITS 2018

Crosswalk: Weight-Based Rating versus Performance-Based Rating

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

MSC Guidelines for Foam Fire Suppression Systems

CREW BOATS HIGH SPEED, LIGHT CRAFT AND NAVAL SURFACE CRAFT RULES FOR CLASSIFICATION OF DET NORSKE VERITAS SPECIAL SERVICE AND TYPE ADDITIONAL CLASS

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Schedule of Accreditation

ACCOMMODATION BARGES GUIDE FOR BUILDING AND CLASSING JANUARY 2014

FirePro ANNEX 1 MARINE MANUAL. Version 1,

Changes in NFPA

MSC Guidelines for Automatic Sprinkler Systems

Red Ensign Group Passenger Yacht Code Industry Working Group Meeting 2015

THÔNG BÁO KỸ THUẬT TÀU BIỂN TECHNICAL INFORMATION ON SEA-GOING SHIPS

GUIDE TO APPROVAL OF RETROFIT BALLAST WATER MANAGEMENT SYSTEM INSTALLATIONS

Main changes in BV Rules for Steel Ships

DNV STATUTORY INTERPRETATIONS

CODE ON ALERTS AND INDICATORS, 2009

ClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

MARINE CIRCULAR MC-7/2011/1

RULES FOR THE CLASSIFICATION OF SHIPS. Part 17 FIRE PROTECTION

Interferry Ro Ro Deck Fire Safety Operational Best Practice Guidance

EU RO Mutual Recognition Technical Requirements

RESOLUTION MSC.99(73) (adopted on 5 December 2000) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFE AT SEA, 1974, AS

ALARM DEVICES FOR MAN OVER BOARD AND RESCUE ACTIONS (DAHMAS)

MSC Guidelines for Vital System Automation Procedure Number: E2-01 Revision Date: 11/10/2011

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

Main changes in BV Rules for Steel Ships

Attachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

Void. Technical Information. Subject. Bulk Carrier Safety:Water Ingress Detection and Alarm System. No. TEC-0537 Date 3 July 2003

Report on First Revisions with Statement June 2014 NFPA 101

INTERNATIONAL STANDARD

RESOLUTION MSC.86(70) (adopted on 8 December 1998) ADOPTION OF NEW AND AMENDED PERFORMANCE STANDARDS FOR NAVIGATIONAL EQUIPMENT

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

E-16 Main Engine Remote Control System

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Guidance on the construction of CO 2 systems

Transcription:

RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS 2014 NOTICE NO. 1 JULY 2014 The following Rule Changes were approved by the ABS Rules Committee on 28 May 2014 and become EFFECTIVE AS OF 1 JULY 2014. (See http://www.eagle.org for the consolidated version of the Rules for Building and Classing Offshore Support Vessels 2014, with all Notices and Corrigenda incorporated.) Notes - The date in the parentheses means the date that the Rule becomes effective for new construction based on the contract date for construction, unless otherwise noted. (See 1-1-4/3.3.) PART 3 CHAPTER 2 SECTION 17 HULL CONSTRUCTION AND EQUIPMENT HULL STRUCTURES AND ARRANGEMENTS BULWARKS, RAILS, FREEING PORTS, SIDE SCUTTLES, WINDOWS, VENTILATORS, TANK VENTS AND OVERFLOWS 11.7 Ventilators, Tank Vents and Overflows on the Fore Deck 11.7.2 Applied Loading to the Air Pipes and Ventilators (Revise Item 3-2-17/11.7.2(a), as follows:) 11.7.2(a) Pressure (1 July 2014). The pressures p, in kn/m 2 (tf/m 2, Ltf/ft 2 ), acting on air pipes, ventilator pipes and their closing devices may be calculated as follows: where: p = f ρ V 2 C d C s C p kn/m 2 (tf/m 2, Ltf/ft 2 ) f = 0.5 (0.05, 0.0156) ρ = density of sea water, 1.025 t/m 3 (1.025 t/m 3, 0.0286 Lt/ft 3 ) V = velocity of water over the fore deck = 13.5 m/sec (44.3 ft/sec) for d 0.5d 1 d = 13.5 2 1 m/sec (44.3 d1 d 2 1 d1 d = distance from summer load waterline to exposed deck d 1 = 0.1L or 22 m (72.2 ft), whichever is the lesser ft/sec) for 0.5d 1 < d < d 1 ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014 1

C d = shape coefficient = 0.5 for pipes = 0.8 for ventilator heads of cylindrical form with their axis in the vertical direction = 1.3 for ventilator heads of non-cylindrical form with their axis in the horizontal direction C s = slamming coefficient, 3.2 C p = protection coefficient: = 0.7 for pipes and ventilator heads located immediately behind a breakwater or forecastle = 1.0 elsewhere, including immediately behind a bulwark PART 4 CHAPTER 7 SECTION 3 VESSEL SYSTEMS AND MACHINERY FIRE SAFETY SYSTEMS FIRE-EXTINGUISHING SYSTEMS AND EQUIPMENT (Revise Subsection 4-7-3/11, as follows:) 11 Fixed Fire Detection and Fire Alarm Systems (1 July 2014) 11.1 Definitions 11.1.1 Section A group of fire detectors and manually operated call points as reported in the indicating unit(s). 11.1.2 Section Identification Capability A system with the capability of identifying the section in which a detector or manually operated call point has activated. 11.1.3 Individually Identifiable A system with the capability to identify the exact location and type of detector or manually activated call point which has activated, and which can differentiate the signal of that device from all others. 11.3 Engineering Specifications 11.3.1 General Requirements 11.3.1(a) System Capability. Any required fixed fire detection and fire alarm system with manually operated call points is to be capable of immediate operation at all times (this does not require a backup control panel). Notwithstanding this, particular spaces may be disconnected, for example, workshops during hot work and ro-ro spaces during on and off-loading. The means for disconnecting the detectors are to be designed to automatically restore the system to normal surveillance after a predetermined time that is appropriate for the operation in question. The space is to be manned or provided with a fire patrol when detectors required by regulation are disconnected. Detectors in all other spaces are to remain operational. 11.3.1(b) System Functionality. The fire detection system is to be designed to: i) Control and monitor input signals from all connected fire and smoke detectors and manual call points; 2 ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014

i Provide output signals to the navigation bridge, continuously manned central control station or onboard safety center to notify the crew of fire and fault conditions; Monitor power supplies and circuits necessary for the operation of the system for loss of power and fault conditions; and The system may be arranged with output signals to other fire safety systems including: a) Paging systems, fire alarm or public address systems; b) Fan stops; c) Fire doors; d) Fire dampers; e) Sprinkler systems; f) Smoke extraction systems; g) Low-location lighting systems; h) Fixed local application fire-extinguishing systems; i) Closed circuit television (CCTV) systems; and j) Other fire safety systems. 11.3.1(c) Decision Management System. The fire detection system may be connected to a decision management system provided that: i) The decision management system is proven to be compatible with the fire detection system; i The decision management system can be disconnected without losing any of the functions required by 4-7-3/11 for the fire detection system; and Any malfunction of the interfaced and connected equipment must not propagate under any circumstance to the fire detection system. 11.3.1(d) Detectors and Manual Call Points Connections. Detectors and manual call points are to be connected to dedicated sections of the fire detection system. Other fire safety functions, such as alarm signals from the sprinkler valves, may be permitted if in separate sections. 11.3.1(e) Environmental Design. The system and equipment is to be suitably designed to withstand supply voltage variation and transients, ambient temperature changes, vibration, humidity, shock, impact and corrosion normally encountered in vessels. All electrical and electronic equipment on the bridge or in the vicinity of the bridge are to be tested for electromagnetic compatibility, taking into account the recommendations developed by the IMO*. * Refer to the General requirements for electromagnetic compatibility for all electrical and electronic equipment, adopted by the IMO by resolution A.813(19). 11.3.1(f) Individual Identification of Detectors. Fixed fire detection and fire alarm systems with individually identifiable fire detectors are to be so arranged that: i) Means are provided so that any fault (e.g., power break, short circuit, earth, etc.) occurring in the section will not prevent the continued individual identification of the remainder of the connected detectors in the section; i All arrangements are made to enable the initial configuration of the system to be restored in the event of failure (e.g., electrical, electronic, informatics, etc.); The first initiated fire alarm will not prevent any other detector from initiating further fire alarms; and No section will pass through a space twice. When this is not practical (e.g., for large public spaces), the part of the section which by necessity passes through the space for a second time shall be installed at the maximum possible distance from the other parts of the section. ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014 3

11.3.1(g) Activation. In passenger vessels, the fixed fire detection and fire alarm system is to be capable of remotely and individually identifying each detector and manually operated call point. Fire detectors fitted in passenger vessel cabins, when activated, are to also be capable of emitting, or cause to be emitted, an audible alarm within the space where they are located. In cargo vessels and on passenger vessel cabin balconies the fixed fire detection and fire alarm system are to, as a minimum, have section identification capability. 11.3.2 Sources of Power Supply 11.3.2(a) Number of Power Sources. There are to be not less than two sources of power supply for the electrical equipment used in the operation of the fixed fire detection and fire alarm system, one of which shall be an emergency source of power. The supply is to be provided by separate feeders reserved solely for that purpose. Such feeders are to run to an automatic changeover switch situated in or adjacent to the control panel for the fire detection system. The changeover switch is to be arranged such that a fault will not result in the loss of both power supplies. The main (respective emergency) feeder is to run from the main (respective emergency) switchboard to the change-over switch without passing through any other distributing switchboard. 11.3.2(b) Automatic Changeover. The operation of the automatic changeover switch or a failure of one of the power supplies are not to result in loss of fire detection capability. Where a momentary loss of power would cause degradation of the system, a battery of adequate capacity is to provide continuous operation during changeover. 11.3.2(c) Power Capacity. There is to be sufficient power to permit the continued operation of the system with all detectors activated, but not more than 100 if the total exceeds this figure. 11.3.2(d) Emergency Power. The emergency source of power specified in paragraph 4-7-3/11.3.2(a) above may be supplied by accumulator batteries or from the emergency switchboard. The power source is to be sufficient to maintain the operation of the fire detection and fire alarm system for the periods required by 4-8-2/5 and, at the end of that period, is to be capable of operating all connected visual and audible fire alarm signals for a period of at least 30 min. 11.3.2(e) Batteries. Where the system is supplied from accumulator batteries, they are to be located in or adjacent to the control panel for the fire detection system, or in another location suitable for use in an emergency. The rating of the battery charge unit is to be sufficient to maintain the normal output power supply to the fire detection system while recharging the batteries from a fully discharged condition. 11.3.3 Component Requirements 11.3.3(a) Detectors i) Detectors are to be operated by heat, smoke or other products of combustion, flame, or any combination of these factors. Detectors operated by other factors indicative of incipient fires may be considered by ABS provided that they are no less sensitive than such detectors. i Smoke detectors required in all stairways, corridors and escape routes within accommodation spaces are to be certified to operate before the smoke density exceeds 12.5% obscuration per meter, but not until the smoke density exceeds 2% obscuration per meter, when tested according to standards EN 54:2001 and IEC 60092-504. Alternative testing standards may be used as determined by ABS. Smoke detectors to be installed in other spaces shall operate within sensitivity limits to the satisfaction of ABS having regard to the avoidance of detector insensitivity or oversensitivity. Heat detectors are to be certified to operate before the temperature exceeds 78 C (172 F) but not until the temperature exceeds 54 C (129 F), when the temperature is raised to those limits at a rate less than 1 C per min (1.8 F per min), when tested according to standards EN 54:2001 and IEC 60092-504. Alternative testing standards may be used as determined by ABS. At higher rates of temperature rise, the heat detector is to operate within temperature limits to the satisfaction of ABS having regard to the avoidance of detector insensitivity or oversensitivity. 4 ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014

The operation temperature of heat detectors in drying rooms and similar spaces of a normal high ambient temperature may be up to 130 C (266 F), and up to 140 C (284 F) in saunas. v) Flame detectors are to be tested according to standards EN 54-10:2001 and IEC 60092-504. Alternative testing standards may be used as determined by ABS. All detectors are to be of a type such that they can be tested for correct operation and restored to normal surveillance without the renewal of any component. vi) v Fixed fire detection and fire alarm systems for cabin balconies are to be approved by ABS, based on the guidelines developed by the IMO*. * Refer to the Guidelines for approval of fixed fire detection and fire alarm systems for cabin balconies (MSC.1/Circ.1242). Detectors fitted in hazardous areas are to be tested and approved for such service. Detectors required by SOLAS regulation II-2/20.4 and installed in spaces that comply with SOLAS regulation II-2/20.3.2.2 need not be suitable for hazardous areas. Detectors fitted in spaces carrying dangerous goods, required by regulation II-2/19, table 19.3, of the SOLAS to comply with regulation II-2/19.3.2 of the Convention, are to be suitable for hazardous areas. 11.3.3(b) Control Panel. The control panel for the fire detection system is to be tested according to standards EN 54-2:1997, EN 54-4:1997 and IEC 60092-504:2001. Alternative standards may be used as determined by ABS. 11.3.3(c) Cables. Cables used in the electrical circuits are to be flame retardant according to standard IEC 60332-1. On passenger vessels, cables routed through other main vertical zones that they serve, and cables to control panels in an unattended fire control station are to be fire resisting according to standard IEC 60331, unless duplicated and well separated. 11.3.4 Installation Requirements 11.3.4(a) Sections i) Detectors and manually operated call points are to be grouped into sections. i A section of fire detectors which covers a control station, a service space or an accommodation space is not to include a machinery space of category A or a ro-ro space. A section of fire detectors which covers a ro-ro space is not to include a machinery space of category A. For fixed fire detection systems with remotely and individually identifiable fire detectors, a section covering fire detectors in accommodation, service spaces and control stations are not to include fire detectors in machinery spaces of category A or ro-ro spaces. Where the fixed fire detection and fire alarm system does not include means of remotely identifying each detector individually, no section covering more than one deck within accommodation spaces, service spaces and control stations is to normally to be permitted except a section which covers an enclosed stairway. In order to avoid delay in identifying the source of fire, the number of enclosed spaces included in each section is to be limited as determined by the Administration. If the detection system is fitted with remotely and individually identifiable fire detectors, the sections may cover several decks and serve any number of enclosed spaces. v) In passenger vessels, a section of detectors and manually operated call points are not to be situated in more than one main vertical zone, except on cabin balconies. 11.3.4(b) Positioning of Detectors i) Detectors are to be located for optimum performance. Positions near beams and ventilation ducts, or other positions where patterns of air flow could adversely affect performance, and positions where impact or physical damage is likely, shall be avoided. Detectors are to be located on the overhead at a minimum distance of 0.5 m (1.65 ft) away from bulkheads, except in corridors, lockers and stairways. The maximum spacing of detectors shall be in accordance with the table below: ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014 5

Type of detector Maximum floor area per detector TABLE 3 Spacing of Detector Maximum distance apart between centers Maximum distance away from bulkheads Heat 37 m 2 398 ft 2 9 m 29.5 ft 4.5 m 14.8 ft Smoke 74 m 2 796 ft 2 11 m 36 ft 5.5 m 18 ft i ABS may require or permit other spacing based upon test data which demonstrate the characteristics of the detectors. Detectors located below moveable ro-ro decks are to be in accordance with the above. Detectors in stairways are to be located at least at the top level of the stair and at every second level beneath. v) When fire detectors are installed in freezers, drying rooms, saunas, parts of galleys used to heat food, laundries and other spaces where steam and fumes are produced, heat detectors may be used. vi) Where a fixed fire detection and fire alarm system is required by 4-7-2/3, spaces having little or no fire risk need not to be fitted with detectors. Such spaces include void spaces with no storage of combustibles, private bathrooms, public toilets, fire-extinguishing medium storage rooms, cleaning gear lockers (in which flammable liquids are not stowed), open deck spaces and enclosed promenades having little or no fire risk and that are naturally ventilated by permanent openings. 11.3.4(c) Arrangement of Cables i) Cables which form part of the system are to be so arranged as to avoid galleys, machinery spaces of category A, and other enclosed spaces of high fire risk except where it is necessary to provide for fire detection or fire alarms in such spaces or to connect to the appropriate power supply. A section with individually identifiable capability is to be arranged so that it cannot be damaged at more than one point by a fire. 11.5 System Control Requirements 11.5.1 Visual and Audible Fire Signals* * Refer to the Code on Alerts and Indicators, 2009, as adopted by the IMO by resolution A.1021(26). 11.5.1(a) Manual Operation. The activation of any detector or manually operated call point is to initiate a visual and audible fire detection alarm signal at the control panel and indicating units. If the signals have not been acknowledged within 2 min, an audible fire alarm is to be automatically sounded throughout the crew accommodation and service spaces, control stations and machinery spaces of category A. This alarm sounder system need not be an integral part of the detection system. Interpretation (IACS) Power supply to the alarm sounder system when not an integral part of the detection system 1. The alarm sounder system utilized by the Fixed Fire Detection and Fire Alarm System shall be powered from no less than two sources of power, one of which shall be an emergency source of power. 2. In vessels required by SOLAS regulation II-1/42 or 43 to be provided with a transitional source of emergency electrical power the alarm sounder system shall also be powered from this power source. 11.5.1(b) Control Panels. In passenger vessels, the control panel is to be located in the onboard safety center. In cargo vessels, the control panel shall be located on the navigation bridge or in the fire control station. 6 ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014

11.5.1(c) Individual Detector Identification. In passenger vessels, an indicating unit that is capable of individually identifying each detector that has been activated or manually operated call point that has operated is to be located on the navigation bridge. In cargo vessels, an indicating unit is to be located on the navigation bridge if the control panel is located in the fire control station. In vessels with a cargo control room, an additional indicating unit is to be located in the cargo control room. In cargo vessels and on passenger cabin balconies, indicating units are to, as a minimum, denote the section in which a detector has activated or manually operated call point has operated. 11.5.1(d) Information on Covered Spaces. Clear information is to be displayed on or adjacent to each indicating unit about the spaces covered and the location of the sections. 11.5.1(e) Power Supply Monitoring. Power supplies and electric circuits necessary for the operation of the system are to be monitored for loss of power and fault conditions as appropriate including: i) A single open or power break fault caused by a broken wire; i A single ground fault caused by the contact of a wiring conductor to a metal component; and A single wire to wire fault caused by the contact of two or more wiring conductors. Occurrence of a fault condition shall initiate a visual and audible fault signal at the control panel which shall be distinct from a fire signal. 11.5.1(f) Manual Acknowledgment of Alarm. Means to manually acknowledge all alarm and fault signals are to be provided at the control panel. The audible alarm sounders on the control panel and indicating units may be manually silenced. The control panel is to be clearly distinguished between normal, alarm, acknowledged alarm, fault and silenced conditions. 11.5.1(g) Automatic Reset. The system is to be arranged to automatically reset to the normal operating condition after alarm and fault conditions are cleared. 11.5.1(h) Local Audible Alarm. When the system is required to sound a local audible alarm within the cabins where the detectors are located, a means to silence the local audible alarms from the control panel are not to be permitted. 11.5.1(i) Audible Alarm Pressure Level. In general, audible alarm sound pressure levels at the sleeping positions in the cabins and 1 m (3.3 ft) from the source is to be at least 75 db(a) and at least 10 db(a) above ambient noise levels existing during normal equipment operation with the ship under way in moderate weather. The sound pressure level must be in the 1/3 octave band about the fundamental frequency. Audible alarm signals are not to exceed 120 db(a). 11.5.2 Testing Suitable instructions and component spares for testing and maintenance are to be provided. Detectors are to be periodically tested using equipment suitable for the types of fires to which the detector is designed to respond. Detectors installed within cold spaces such as refrigerated compartments are to be tested using procedures having due regard for such locations.* Vessels with self-diagnostic systems that have in place a cleaning regime for areas where heads may be prone to contamination may carry out testing in accordance with the requirements of ABS. * Refer to the recommendations of the International Electrotechnical Commission, in particular publication IEC 60068-2-1 Section one -Test Ab, Environmental Testing Part 2-1: Tests Test A: Cold. ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014 7

PART 5 CHAPTER 4 SECTION 3 SPECIALIZED VESSELS FIRE FIGHTING FIRE FIGHTING SYSTEMS, ARRANGEMENTS, AND EQUIPMENT 3 Pumps and Piping for Fire Fighting and Water Spray (1 July 2012) (Delete Subparagraph 5-4-3/3.3.2 and renumber Subparagraph 5-4-3/3.3.3 as 5-4-3/3.3.2, as follows:) 3.3 Piping Systems (1 July 2014) 3.3.1 Protection Piping systems are to be protected from overpressure. All piping is to be suitably protected from corrosion and freezing and capable of being thoroughly drained. 3.3.2 Independency (1 July 2012) Piping systems used for water spray are to be independent from the system supplying water to the monitors, except that the same pumps may be used for both purposes. See also 5-4-3/9.1. Where water supply to the hose connections is provided by the pumps for the water monitors, and/or water spray (5-4-3/7), isolation valves are to be fitted to separate the fire main system from the water monitors and/or water sprays systems and necessary pressure regulation means are to be taken so that the fire main system can be operated independently and/or simultaneously with the fire monitors and /or water spray system. 8 ABS RULES FOR BUILDING AND CLASSING OFFSHORE SUPPORT VESSELS. 2014