FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

Similar documents
SFC-200 SERIES LED FIRE ALARM PANEL

FX-350/351 Series. Analog/Addressable Fire Alarm Control Panel. User Guide

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

INSTALLATION & OPERATION GUIDE

RAX-LCD-LITE. Remote Annunciator. Installation and Operation Manual

INTELLIGENT FIRE ALARM CONTROL PANEL

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

MMX TM. Intelligent Fire Alarm Network. User Guide

FX Intelligent Analog Fire Alarm Control Panel. Installation and Operation Manual

NETWORK FIRE ALARM CONTROL PANEL. Features

Conventional Releasing Control Panel

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

CATALOG NUMBER. Features. Description

NETWORK FIRE ALARM CONTROL PANEL. Features S7010 S :111

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

SFC-200 SERIES LCD FIRE ALARM PANEL

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX NDS Intelligent Network Fire Alarm Control Unit. Features. Description

Contents. Glossary

User Operation Manual

FX-350/351/353 SERIES

MR-2602 Two Zone Fire Alarm Control Panel

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Conventional Fire Alarm System 2014 V1.2

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

CSP-204 CSP-208 CSP-104 CSP-108

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

MR-2350/2351 Series Analog/Addressable Fire Alarm Panel

Installation, Operating and Maintenance Manual

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

IDS816 User Manual H Issued January 2009

Contents. Glossary Introduction to the IDS Notes Understanding the Keypad Indicators Operation of the Keypad...

Fire Command Keypad. XR5 User s Guide

Specification/ Data Sheet

Operating Instructions MXL Multi-Line Keyboard/Display Panel

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

NetworX NX-8V2. LED Keypad User Manual

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features

NetworX Series NX-1500E LED Keypad

IDS800 USER MANUAL. Summary of Operation. + [ ] 2 IDS800 USER MANUAL NO K ISSUED APR 2003 VER 1.44

IDS S E C U R I T Y IDS816. User Manual. MANUAL NO A ISSUED November 2004 VERSION 1.00

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

ID2000. operating manual

NETWORX TM. User manual NX-4

RA-1000 Series. Remote Multiplex Annunciator Panels. Installation and Wiring Manual

L900 series USER MANUAL

Intelligent Security & Fire Ltd

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

MR-2316-AT/Z Remote Annunciator

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

LT-6098 FR-320NetK Installation

MPC-6000 / MPC-7000 / RND-2

FDG-008 and FDX-008. Fan Damper Control Modules. Installation and Operation Manual

FX-350/351 SERIES. Analog/Addressable Fire Alarm Panel. Programming Manual

U ser's Guide PC6010

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

MIR2. System Operations Manual. P/N Rev 1.5 OCT98

Destiny Destiny Owners Manual

ABORT Light flashes during an abort delay time; is on during or after an alarm report to the central station. EMERGENCY ACTIVATION KEYS

RAM-208. Remote Multiplex Annunciator Panel. Wiring & Installation Installation Manual COMMON TROUBLE A.C. ON SIGNAL SILENCED BUZZER SILENCE

Using Your. Security System With LED Keypad S5030, S5031, S5032

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

SECURITY SYSTEM NOTES

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

EN 54-2 EN 54-4 EN CPD CPD CPD-0230

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

IDS S E C U R I T Y IDS816. User Manual MANUAL NO B ISSUED DEC 2004 VERSION 2.00

MGD-32 and AGD-048. Remote Multiplex Graphic Driver Annunciators and Adder Boards. Wiring and Installation Manual

DESTINY OWNER S MANUAL

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

FireNET FN-LCD-S Serial Annunciator Installation and Operation Manual

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

FA-300 Series. LCD Fire Alarm Control Panel. Installation and Operation Manual

Control Panel User Guide

INSTALLATION INSTRUCTIONS

IDS S E C U R I T Y IDS816. User Manual MANUAL NO C ISSUED APRIL 2005 VERSION 2.00

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Power864. User s Guide. Now classified in accordance with ANSI/SIA CP (SIA-FAR)

Functional Performance Test

TrueAlarm Fire Alarm Systems

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

VISTA-32FBPT. Commercial Fire and Burglary Partitioned Security Systems with Scheduling. User Guide /12 Rev. B

Application Manual LT-6617 Rev. 1 July 2017

FX Fire Alarm Control Panel. Installation and Operation Manual

Version 1.03 January-2002 USER S MANUAL

Summit 3208GLD USER MANUAL. Electronics Line

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

Transcription:

LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET AUXILIARY DISCONNECT LAMP TEST MENU LAMP TEST REMOTE CPU FAULT GROUND FAULT SIGNAL SILENECE FIRE DRILL BUZZER SILENCE INFO AC ON ALARM SUPERVISORY BATTERY SYSTEM RESET LAMP TEST MENU ZONE DISCONNECT ZONE DISCONNECT FA-300 Series LED Fire Alarm Control Panel Advanced Life Safety Solutions Advanced Life Safety Solutions AUXILIARY DISCONNECT ZONE DISCONNECT ZONE DISCONNECT FA-300 SERIES Fire Alarm Control Panel FA-300 SERIES Fire Alarm Control Panel User Guide LT-953 Rev. 1 Feb. 2016

Contents 1.0 Introduction 5 1.1 About this Manual... 5 1.2 Technical Support... 5 2.0 Main Display 6 2.1 Paper labels for buttons and indicators... 7 3.0 The Buzzer and LED Indicators 8 3.1 Common LED Indicators... 8 3.2 Indicating Circuit Indicators... 10 4.0 Main Display Buttons 14 4.1 SYSTEM RESET Button... 14 4.2 SIGNAL SILENCE Button... 14 4.3 FIRE DRILL Button... 14 4.4 AUTOMATIC ALARM SIGNAL CANCEL Button (or ALM/SUP/TBL/BLDG AUDIBLE SIL button for single stage system)... 14 4.5 GENERAL ALARM Button... 14 4.6 AUXILIARY DISCONNECT Button... 15 4.7 LAMP TEST Button... 15 4.8 ALM/SUP/TBL/BLDG AUDIBLE SIL Button (or MENU for single stage systems)... 15 5.0 Circuit (Zone) Disconnect Buttons 16 6.0 Glossary 17 3 (20)

4 (20)

1.0 Introduction 1.1 About this Manual This user s guide provides information on the main indicators and controls of the FA-300 Fire Alarm Control Panel. Specifically, with this manual you will learn about what the LEDs indicate and what the buttons on the main display do. Refer to the Glossary on page 17 for an explanation of commonly used terms in this manual. 1.2 Technical Support For all technical support inquiries, please contact Mircom s Technical Support Department between 8 A.M. and 5 P.M. (EDT) Monday through Friday, excluding holidays. Local Phone: 905-695-3535 Toll-Free Phone: 1-888-449-3535 Local Fax: 905-660-4113 Toll-Free Fax: 1-888-660-4113 Email: techsupport@mircom.com 5 (20)

2.0 Main Display Refer to the diagram below for the LED indicators and control buttons locations. WALK TEST REMOTE CPU FAIL GROUND FAULT A.C. ON ALARM SUPV BATTERY SIGNAL SILENCE SYSTEM RESET FIRE DRILL AUX AUTOMATIC ALARM SIGNAL CANCEL LAMP TEST (MENU) GENERAL ALARM ALM/SUP/TBL/BLDG AUDIBLE SIL ZONE-1 ZONE-2 ZONE-3 ZONE-4 ZONE-5 ZONE-6 ZONE-7 DISCONNECT ZONE-8 ZONE-9 ZONE-10 ZONE-11 ZONE-12 NAC-1 NAC-2 NAC-3 NAC-4 Figure 1 Main Display The main display panel on the main fire alarm control board consists of: 18 common LED indicators (top half of display) 8 common buttons (top half of display) Up to 12 Initiating circuit alarm LEDs and 12 initiating circuit trouble LED indicators 4 indicating circuit LEDs (labeled NAC - Notifying Appliance Circuit) Up to 16 disconnect buttons (12 for initiating circuit and 4 for indicating circuits) LED indicators may be amber, red, or green, and may illuminate continuously (steady), or at one of two flash rates: Fast flash (supervisory): 120 flashes per minute Trouble flash (trouble): 20 flashes per minute 6 (20)

Main Display 2.1 Paper labels for buttons and indicators Each display is supplied with laser printable labels. These labels slide into the plastic label templates on the panel.the label paper for the main display includes English and French versions (Mircom # NP-2005). 7 (20)

3.0 The Buzzer and LED Indicators 3.1 Common LED Indicators 3.1.1 Buzzer The buzzer sounds if there is a fire alarm, a supervisory alarm, or a trouble in the fire alarm system. It turns off if the condition causing the buzzer to sound goes away or if the ALM/SUP/ TBL/BLDG AUDIBLE SIL (buzzer silence) button is pressed. 3.1.2 A.C. ON LED A.C. ON The green A.C. ON LED illuminates steadily as long as the main power is above minimum level. The indicator turns off when the level falls below the minimum level and the panel switches to standby (battery) power. 3.1.3 ALARM LED ALARM The red ALARM LED will illuminate steadily whenever there is a fire alarm. If the panel is set for two stage operation, pressing the red GENERAL ALARM button will also turn on the ALARM LED. This LED will remain on until the system is reset. 3.1.4 SUPERVISORY LED SUPV The amber SUPERVISORY LED illuminates at the fast flash rate when there is a supervisory alarm in the fire alarm system. For non-latching supervisory alarms, the SUPERVISORY LED will turn off when the condition causing the alarm goes away. For latching supervisory alarms, this LED remains on until the panel is reset. 3.1.5 LED The amber LED flashes at the trouble flash rate when the panel detects any trouble condition. For non-latching trouble conditions, the LED will turns off when the condition causing the alarm goes away. For latching trouble conditions, this LED remains on until the panel is reset. 3.1.6 REMOTE LED REMOTE The amber REMOTE LED flashes at the trouble flash rate if the panel detects a trouble at the City Tie or UDACT module, communication trouble with a remote annunciator, or a local trouble at a remote annunciator. 3.1.7 FIRE DRILL LED FIRE DRILL The amber FIRE DRILL LED illuminates steadily after you press the FIRE DRILL button. This LED remains on until you press the FIRE DRILL button again. 8 (20)

The Buzzer and LED Indicators 3.1.8 AUTOMATIC ALARM SIGNAL CANCEL LED AUTOMATIC ALARM SIGNAL CANCEL If the panel is configured as a two-stage system, the AUTOMATIC ALARM SIGNAL CANCEL LED illuminates steadily when the Alarm timer is canceled by the activation of the AUTOMATIC ALARM SIGNAL CANCEL or SIGNAL SILENCE buttons. The LED goes out when the SYSTEM RESET button is pressed. This LED can be configured to flash amber at the fast rate while the Auto General Alarm timer is running. If the Auto General Alarm timer times out and puts the panel into General Alarm, the LED turns off. Note: If this LED is configured to flash, then the panel is outside of UL/ULC certification acceptability. The authority having jurisdiction must approve this selection. If the panel is not configured as a two-stage system, this LED is ALM/SUP/TBL/BLDG AUDIBLE SIL (buzzer silence). It flashes at the slow rate when the ALM/SUP/TBL/BLDG AUDIBLE SIL button is pressed. 3.1.9 GENERAL ALARM LED GENERAL ALARM The red GENERAL ALARM LED illuminates steadily when the GENERAL ALARM button is pressed, a General Alarm Initiating circuit is activated, or the Auto General Alarm timer times out. Once the GENERAL ALARM LED has turned on, it will stay active until the panel is reset. 3.1.10 WALK TEST LED WALK TEST The amber WALK TEST LED illuminates steadily to indicate that the panel is in walk test mode. If the panel is left in this mode for over an hour with no operator activity, the panel will return to normal and the WALK TEST LED will turn off. 3.1.11 CPU FAULT LED CPU FAIL The CPU FAULT LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the main board. 3.1.12 AUXILIARY DISCONNECT LED AUX DISCONNECT The amber AUXILIARY DISCONNECT LED flashes at the trouble rate when the AUXILIARY DISCONNECT button is pressed. It turns off when the AUXILIARY DISCONNECT button is pressed a second time. When on, the AUXILIARY DISCONNECT LED signifies that auxiliary alarm relay and relay adder modules (if disconnect is enabled) are not activated. If installed and enabled, the city tie module and the smart relay annunciator relays are also inactive. 3.1.13 SIGNAL SILENCE LED SIGNAL SILENCE The SIGNAL SILENCE LED flashes amber at the trouble rate when indicating circuits are silenced either by the SIGNAL SILENCE button or by the Auto Signal Silence timer. It turns off when the signals are re-sounded by a subsequent alarm or when the panel is reset. 9 (20)

The Buzzer and LED Indicators 3.1.14 BATTERY LED BATTERY The amber BATTERY LED flashes at the trouble rate when the battery is either low or disconnected. 3.1.15 GROUND FAULT LED GROUND FAULT The amber GROUND FAULT LED flashes at the trouble rate when the ground fault detector detects a ground fault on any field wiring. It turns off when the ground fault is cleared. 3.1.16 SYSTEM RESET LED SYSTEM RESET The amber SYSTEM RESET LED illuminates for a short time when the SYSTEM RESET button is pressed. 3.2 Indicating Circuit Indicators The panel has 1 indicator for each of the 12 initiating circuits (shown in Figure 1). Each indicator has a button and 2 LEDs, shown in Figure 2. Circuit Disconnect Button ZONE-1 Circuit Status LED Circuit Trouble LED Figure 2 Alarm Circuit Indicator The Circuit Disconnect Button is described in 5.0 Circuit (Zone) Disconnect Buttons on page 16. The LEDs are described below. 10 (20)

The Buzzer and LED Indicators 3.2.1 Alarm Circuit Indicators This operation applies to Initiating Circuits configured as Verified Alarm, Non-Verified Alarm, Water flow Alarm, Sprinkler Alarm, or General Alarm Circuits. Table 1 summarizes the indications at different events: Table 1 Alarm Circuit Indicators Event Circuit Status LED Configuration Circuit in Alarm Steady (red) Pre-alarm Fast flash rate (red) Verified Alarm Sprinkler Alarm Activated circuit reconnected (when you press the Disconnect button a second time) Fast flash rate (red) for 5 seconds to indicate a pending alarm Water flow Alarm Event Circuit Trouble LED Configuration Open circuit (Class B) Open circuit or Style D/Class A trouble Disconnected (Style D/Class A) Circuit in Alarm OFF Verified Alarm Non-Verified Alarm Water flow Alarm Sprinkler Alarm General Alarm 3.2.2 Supervisory Circuit Indicators This operation applies to initiating circuits configured as latching or non-latching supervisory circuits. The following table summarizes the indications in response to different events: Table 2 Supervisory Circuit Indicators Event Circuit Status LED Configuration Circuit in Alarm Activated circuit reconnected Steady Fast flash rate (red) for 5 seconds to indicate a pending alarm Latching Sup. Non-Latching Sup. Event Circuit Trouble LED Configuration Open circuit (Class B) Open circuit or Style D/Class A trouble Disconnected (Style D/Class A) Latching Sup. Non-Latching Sup. Circuit in Alarm OFF 11 (20)

The Buzzer and LED Indicators 3.2.3 Property and Building Safety Circuit Indicators This operation applies to initiating circuits configured as property and building safety circuits. The following table summarizes the indications in response to different events: Table 3 Property and Building Safety Circuit Indicators Event Circuit Status LED Configuration Circuit Active Steady Activated circuit reconnected Fast flash rate (red) for 5 seconds to indicate a pending alarm Property and Building Safety Event Circuit Trouble LED Configuration Open circuit (Class B) Open circuit or Style D/Class A trouble Disconnected (Style D/Class A) Circuit Active OFF Property and Building Safety 3.2.4 Trouble-only Circuit Indicators This operation applies to initiating circuits configured as Trouble-Only Circuits. The following table summarizes the indications in response to different events: Table 4 Trouble-Only Circuit Indicators Event Circuit Trouble LED Configuration Open circuit (Class B) Open circuit or Style D/Class A trouble Disconnected (Style D/Class A) Short Circuit Trouble Only 12 (20)

The Buzzer and LED Indicators 3.2.5 Signal Circuit Indicators This operation applies to indicating circuits of any type. The Circuit Trouble Indicator flashes amber at the Trouble Rate to indicate short-circuit or open-circuit trouble, or if the circuit is Disconnected. Table 5 Signal Circuit Indicators Event Circuit Trouble LED Configuration Open circuit Short Circuit Disconnected Signal 13 (20)

4.0 Main Display Buttons 4.1 SYSTEM RESET Button SIGNAL SILENCE The SYSTEM RESET button resets the fire alarm control panel and all circuits. 4.2 SIGNAL SILENCE Button SIGNAL SILENCE Pressing the SIGNAL SILENCE button when the panel is in alarm deactivates any silenceable signal devices in the fire alarm system. Non-Silenceable signal devices are unaffected. If you press the SIGNAL SILENCE button a second time, or if there is a subsequent alarm, the signals will re-sound. If the panel has been configured with a Signal Silence Inhibit timer, this button will not work until the timer times out. This button also does not work if you have pressed the FIRE DRILL button. In a two-stage system, the SIGNAL SILENCE button silences the stage 1 and stage 2 alarms. 4.3 FIRE DRILL Button FIRE DRILL Pressing the FIRE DRILL button will simulate a fire alarm by activating the fire alarm signals without transmitting an alarm to the central station. To cancel the fire drill, press the button again. If the fire alarm system goes into a real alarm while you are performing a fire drill, this button will not turn off the signals or activate any programmed relays. 4.4 AUTOMATIC ALARM SIGNAL CANCEL Button (or ALM/SUP/ TBL/BLDG AUDIBLE SIL button for single stage system) AUTOMATIC ALARM SIGNAL CANCEL If the Panel is configured as a two-stage system, pressing the AUTOMATIC ALARM SIGNAL CANCEL button while the Auto General Alarm timer is running (there is an alarm in the panel, but it is still in the first stage), cancels the timer and illuminates the amber AUTOMATIC ALARM SIGNAL CANCEL LED steadily, thereby acknowledging the alarm. If the Panel is not configured as a two-stage system, this button becomes ALM/SUP/TBL/ BLDG AUDIBLE SIL (buzzer silence). Press ALM/SUP/TBL/BLDG AUDIBLE SIL to silence the buzzer. 4.5 GENERAL ALARM Button GENERAL ALARM Press the GENERAL ALARM button to immediately send the panel into General Alarm or total evacuation. It also re-activates the signals if they have been silenced during General Alarm. The General Alarm condition remains active until the SYSTEM RESET button is pressed. 14 (20)

Main Display Buttons 4.6 AUXILIARY DISCONNECT Button AUX DISCONNECT Pressing the AUXILIARY DISCONNECT button activates the auxiliary disconnect function. Pressing the button again de-activates this function. 4.7 LAMP TEST Button LAMP TEST Pressing and holding the LAMP TEST button causes all front panel LEDs to illuminate and sounds the buzzer. Use this button to test that all LEDs in the main display are working. If you hold the LAMP TEST button for more than ten seconds, the LED will illuminate. 4.8 ALM/SUP/TBL/BLDG AUDIBLE SIL Button (or MENU for single stage systems) ALM/SUP/TBL/BLDG AUDIBLE SIL If the Panel is configured as a two-stage system, press the ALM/SUP/TBL/BLDG AUDIBLE SIL (buzzer silence) button to silence the buzzer. The buzzer resounds if there is a subsequent event. Pressing the button when the buzzer is not sounding has no effect. If the Panel is configured as a single stage system, press the MENU button to select the command menu when a CFG-300 Service Tool with LCD is connected. Otherwise, this button has no effect. 15 (20)

5.0 Circuit (Zone) Disconnect Buttons There are circuit (zone) disconnect buttons for all initiating and indicating circuits on the fire alarm control panel. These buttons are located beside their respective indicating LEDs. Pressing a circuit disconnect button disconnects that circuit from the system and turns on its trouble indicator. While a circuit is disconnected, the panel will ignore all changes in the status (alarms and troubles) of that circuit. Circuit disconnect buttons are toggle switches; therefore, pressing an activated button a second time will reconnect the circuit. Disconnecting an active latching initiating circuit such as alarms, water-flow alarm, sprinkler alarm, general alarm, and latching supervisory does not affect its status until the panel is reset. Disconnecting active non-latching initiating circuits including non-latching supervisory and trouble-only causes them to behave as if the alarm situation has disappeared. Disconnecting an active indicating circuit immediately deactivates the circuit. When an initiating circuit disconnect button is pressed a second time, the panel checks the state of the circuit. If the circuit is active and will cause a false alarm, the Status LED flashes for ten seconds at the fast flash rate (red for alarm or amber for supervisory) without processing the input. If the circuit is not re-disconnected by then, it will be processed as a new input. 16 (20)

6.0 Glossary Alarm Condition Circuits Fast Flash Rate General Alarm Timer Indicating Circuit Initiating Circuit Latching Circuit LED Occurs when devices such as detectors, pull stations, or sprinklers are activated. In a single stage system, this condition will activate all signalling devices throughout the building. In a two stage system, this condition will activate an alert signal and the General Alarm timer. Refers to an actual electrical interface and can be classified as initiating (detection), indicating (signal), or relay. The terms circuit and zone are often used interchangeably in the fire alarm industry. 120 flashes per minute is the rate at which an LED will flash to indicate a supervisory alarm. In a two stage system, the general alarm timer begins timing when the panel is in the alert stage. When the general alarm timer times out, the system will go into a general alarm, where all signals in the building will sound. A circuit in a fire alarm system that is connected to audible or visual signalling devices. A circuit in a fire alarm system that is connected to detectors, pull stations, or sprinkler flow switches. A circuit that, when activated, will cause a condition on the panel that cannot be cleared until the panel is reset. The light-emitting diodes (LEDs) of the FA-300 ar colored either amber, red, or green. When lit, LEDs provide information regarding the status of the panel. Property and Building Safety Condition Non-latching Circuit Non-Silenceable Circuit Occurs when dampers open or close, when supply and return fans are running, etc. A circuit that, when activated, will cause a condition on the panel that will be cleared once the circuit is deactivated. This term is used to describe supervisory and trouble circuits. A signal circuit that cannot be silenced by pressing the Signal Silence button. 17 (20)

Glossary Relay Circuit Remote Annunciator Single Stage System Silenceable Circuit A circuit in a fire alarm system that connects relay devices (e.g. fan damper relays, etc). A device that visually indicates, either by LCD or LEDs, the floor or zone where the alarm originated. A type of fire alarm system that immediately sounds all the signals throughout the building when an alarm is detected in any part of the system. A signal circuit that can be silenced by pressing the Signal Silence button. Supervisory Condition Trouble Condition Trouble Flash Rate Two Stage System Walk Test Zones Occurs when the system detects open circuits, short circuits, and grounds. A supervisory condition is one that would interfere with the operation of the fire alarm system. Occurs when an abnormal condition such as a problem in the wiring, battery or power circuits exists in the fire alarm system. 20 flashes per minute is the rate at which an LED will flash to indicate a trouble condition. A type of fire alarm system that causes an alert signal to sound when an alarm is detected in any part of the system. An alert signal advises designated persons of a fire emergency. If the alert signal is not acknowledged within five minutes of its initiation, an alarm signal will automatically sound throughout the building. A test performed by a technician to ensure that each detection device is connected to the panel and working properly. A fire alarm protected area that consists of at least one circuit. The terms circuit and zone are often used interchangeably in the fire alarm industry. 18 (20)

Glossary 19 (20)

20 Mircom 2016 Printed in Canada Subject to change without prior notice www.mircomgroup.com TECHNICAL SUPPORT North America Tel: (888) Mircom5 (888) 647-2665 International Tel: (905) 647-2665 U.S.A 4575 Witmer Industrial Estates Niagara Falls, NY 14305 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113 CANADA - Main Office 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) 660-4655 (905) 660-4655 Fax: (905) 660-4113