Leakage of Mildly Flammable Refrigerants into a Room

Similar documents
Safety research of A2L/A3 refrigerants and risk assessment in Japan. Eiji Hihara The University of Tokyo

Risk Assessment of Mildly Flammable Refrigerants

Compressor Explosion Accident at Pump-Down of Air Conditioners

Low GWP Refrigerants for Air Conditioning Applications

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Air-Cooled Heat Exchanger Performance for R410A

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Safety concerns for A2L refrigerants in AC service procedures

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Study of R161 Refrigerant for Residential Airconditioning

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Main Anthropogenic Sources of Greenhouse Gases Refrigerants


Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Industry co-operation on Natural Refrigerant technology development Kenji Matsuda

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Flammability and New Refrigerant Options

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

*Corresponding author;

Transitioning to Alternatives and Challenges in Japan

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

Control Method Of Circulating Refrigerant Amount For Heat Pump System

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

A Risk Assessment for Leakages of Flammable Refrigerants into a Closed Space

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

A Study on Compression Characteristic of Wet Vapor Refrigerant

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Measurement of R32 Vapor Injection Heat Pump System

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

System Using Exhaust Heat from Residential GHPs

Purdue e-pubs. Purdue University

CHAPTER 1 INTRODUCTION

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

CHAPTER 1 INTRODUCTION

Sub-Critical Operation of the CO2 Expander/ Compressor

Dynamic Simulation of Liquid Chillers

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

High-efficiency Turbo Chiller (NART Series)

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 214 Leakage of Mildly Flammable Refrigerants into a Room Hiroaki Okamoto The university of Tokyo, Japan, hiroaki-okamoto@hee.k.u-tokyo.ac.jp Tatsuhito Hattori The university of Tokyo, Japan, halcyon93@yahoo.co.jp Chaobin Dang The university of Tokyo, Japan, dangcb@k.u-tokyo.ac.jp Eiji Hihara The university of Tokyo, Japan, hihara@k.u-tokyo.ac.jp Follow this and additional works at: http://docs.lib.purdue.edu/iracc Okamoto, Hiroaki; Hattori, Tatsuhito; Dang, Chaobin; and Hihara, Eiji, "Leakage of Mildly Flammable Refrigerants into a Room" (214). International Refrigeration and Air Conditioning Conference. Paper 1496. http://docs.lib.purdue.edu/iracc/1496 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2459, Page 1 Simulation of leakage of mildly flammable refrigerants Hiroaki OKAMOTO*, Tatsuhito HATTORI, Chaobin DANG, Eiji HIHARA Department of Human and Engineered Environment, Graduate School of Frontier Sciences, The University of Tokyo, 5-1-5 Kashiwanoha, Kashiwa-shi, Chiba 277-8563, Japan Phone: +81-4-7136-4678, Fax: +81-4-7136-4659, E-mail: hiroaki-okamoto@hee.k.u-tokyo.ac.jp ABSTRACT The use of chlorofluorocarbons (CFCs) and hydrochlorofluorocarbons (HCFCs) has been widely restricted. They have been replaced with hydrofluorocarbons (HFCs) in order to protect the ozone layer. However, the leakage of refrigerant into the air from active or end-of-life air conditioners is a serious environmental issue owing to the high global warming potential (GWP) of HFCs. Therefore, replacing HFCs with low-gwp refrigerants has been recognized as a reasonable solution to the problem. In Japan, low-gwp refrigerants such as R1234yf, R1234ze, and R32 have been considered as alternatives to conventional HFC refrigerants. However, these low-gwp refrigerants are often flammable. When refrigerants leak into a space, they tend to accumulate above the floor if they are heavier than air. The refrigerant may ignite if the refrigerant concentration is higher than the low flammable limit (LFL), there is an ignition source, and the air velocity is lower than the burning velocity. When leakage occurs from an air conditioner, there is always a region where the refrigerant concentration is higher than the LFL because the refrigerant concentration is 1% near the outlet from the air conditioner. Thus, understanding the refrigerant diffusion phenomena of low-gwp refrigerants is important to acquiring sufficient information for developing safety standards to assess the risks of using these refrigerants. Numerical analysis is an effective tool because it is very difficult to measure the diffusion of a refrigerant in a large space. In this study, diffusion phenomena were numerically analyzed when a refrigerant leaked slowly from a room air conditioner (RAC) and package air conditioner (PAC) and rapidly from a chiller into a large space. Based on the calculation results, the refrigerant concentration distributions, the volumes and positions of the flammable regions, and their changes in were examined. 1. INTRODUCTION According to the Kyoto Protocol, emissions of greenhouse gases such as hydrofluorocarbons (HFCs) should be reduced. Therefore, refrigerants with low-global warming potential (GWP) such as R32 and R1234yf are expected to be the next generation of refrigerants. However, these low-gwp refrigerants are often flammable. Table 1 lists the physical and flammability properties of typical refrigerants (Takizawa, 212; JFMA, 212). Here, LFL is the lower flammability limit, UFL is the upper flammability limit, BV is the burning velocity, and MIE is the minimum ignition energy. To obtain the information needed to assess the risks of using these refrigerants, the leakage of mildly flammable refrigerants was simulated in this study. When refrigerants leak into a space, they tend to accumulate above the floor when they are heavier than air (Kataoka et al., 1996). As shown in Fig. 1, the refrigerant may ignite when the refrigerant concentration is greater than the LFL, there is an ignition source, and the air velocity is lower than the burning velocity. When leakage occurs from a room air conditioner (RAC), there is always a region where the refrigerant concentration is higher than the LFL because the refrigerant concentration is 1% near the outlet of the leakage port. Thus, appropriate safety standards must be prepared for air-conditioning equipment containing flammable refrigerants because of the risk of explosion. Understanding refrigerant diffusion phenomena is important to preparing safety standards. The effects of parameters on the diffusion phenomena of refrigerants that are heavier than air must also be clarified. 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 2 Table 1 Physical and flammability properties of low-gwp refrigerants (Source Takizawa, 212; JFMA, 212 ) Refrigerant GWP *1 LFL *2 UFL *3 BV *4 MIE *5 R29 (propane) < 3 2.1 vol.% 9.5 vol.% 38.7 cm/s.246 mj R717 (ammonia) < 1 15.5 vol.% 27 vol.% 7.2 cm/s 38 68 mj R32 675 13.3 vol.% 29.3 vol.% 6.7 cm/s 15 mj R1234yf 4 6.2 vol.% 12.3 vol.% 1.5 cm/s 2 mj R1234ze(E) 4 7. vo.l% 9.5 vol.% - - *1 GWP: Global warming potential *2 LFL: Lower flammable limit *3 UFL: Upper flammable limmit *4 BV: Burning velocity *5 MIE: Minimum ignition energy Numerical analysis is an effective tool for this purpose because measuring the diffusion of a refrigerant in a large space is very difficult. Goetzler and Burgos (214) numerically simulated the leakage of class 2L flammable refrigerants into a residential space to evaluate the viability of using these refrigerants in heating, ventilation, and air conditioning (HVAC) systems and refrigeration systems. In this study, diffusion phenomena when a refrigerant leaks into a large space from a room air conditioner (RAC), variable refrigerant flow (VRF), and chiller were numerically analyzed. Based on the calculation results, the refrigerant concentration distributions, the volumes and positions of the flammable regions, and their changes over were determined. For the RAC, the calculation results were verified by using the results of a refrigerant leakage experiment. 2. CALCULATION METHOD Table 2 lists the leakage scenarios considered in this study. The commercial computational fluid dynamics (CFD) program STAR-CD was used to simulate refrigerant diffusion phenomena. The advection diffusion problem for a mixture in a three-dimensional space was governed by the continuity, Navier Stokes, energy conservation, and convective diffusion equations. Both the air and refrigerant were assumed to be ideal gases, and the density was calculated by using the equation of state of an ideal gas. PISO or SIMPLE was used for the pressure velocity coupling scheme, and UD and MARS were employed for the discretization scheme. Standard and realizable k ε turbulence models were used in cases 1 22 (RAC and VRF) and 23 32 (chiller), respectively (Table 2). For the boundary conditions, a constant flow at the inlet boundary was assumed, and a constant pressure corresponding to the amospheric pressure or a free outflow condition at the outlet boundary was assumed. The law of the wall was assumed at the wall boundary. 3 ANALYTICAL MODELS Figure 2 shows the analyzed geometries. The details of these geometries are described below. (a) Leakage from a Wall-mounted Indoor RAC Unit The refrigerant was modeled as leaking from a wall-mounted indoor RAC unit into a space with dimensions of 2.8 Concentration higher than LFL Ignition Existence of the ignition source Air velocity slower than burning velocity Fig. 1 Ignition mechanism 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

case No. Type Refrigerant Table 2 Leakage scenarios Charged amount Leakage velocity Ventilation air flow 2459, Page 3 Air vent 1 wall-mounted indoor unit R32 1. kg 125 g/min m 3 /h exist 2 of RAC 25 g/min m 3 /h exist 3 1 g/min m 3 /h exist 4 R1234yf 1.4 kg 175 g/min m 3 /h exist 5 35 g/min m 3 /h exist 6 14 g/min m 3 /h exist 7 R29.2 kg 5 g/min m 3 /h exist 8.5 kg 125 g/min m 3 /h exist 9 floor-mounted indoor unit R32 1. kg 25 g/min m 3 /h exist 1 of RAC R1234yf 1.4 kg 35 g/min m 3 /h exist 11 outdoor unit of RAC R32 1. kg 25 g/min m 3 /h (outdoor) 12 R1234yf 1.4 kg 35 g/min m 3 /h (outdoor) 13 VRF R32 26.3 kg 1 kg/h m 3 /h none 14 m 3 /h exist 15 169 m 3 /h exist 16 169 m 3 /h exist 17 1 kg/h m 3 /h exist 18 R1234yf 29.4 kg 1 kg/h m 3 /h none 19 m 3 /h exist 2 169 m 3 /h exist 21 169 m 3 /h exist 22 1 kg/h m 3 /h exist 23 water-cooled chiller R32 23.4 kg 75 kg/h (burst leak) m 3 /h exist 24 1 kg/h (rapid leak) m 3 /h exist 25 545 m 3 /h exist 26 R1234yf 23.4 kg 7 kg/h (burst leak) m 3 /h exist 27 9 kg/h (rapid leak) m 3 /h exist 28 545 m 3 /h exist 29 R1234ze(E) 23.4 kg 54 kg/h (burst leak) m 3 /h exist 3 545 m 3 /h exist 31 7 kg/h (rapid leak) m 3 /h exist 32 545 m 3 /h exist (a) wall-mounted indoor unit of RAC Opening to the air RAC. (b) floor-mounted indoor unit of RAC Opening to the air (c) outdoor unit of RAC (d) VRF (e) water-cooled chiller Air supply Machine room Air supply Point 1~6 VRF Convection Point 1~6 Exhaust port Outdoor unit Point 1~6 1.8 m 2.4 m Point 1~6 RAC. 2.4 m 1.1 m 2.4 m 2.7 m 5. m Chiller body Under cut Fig. 2 Analytical geometries 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 4 m 2.5 m 2.4 m. The indoor unit was located 1.8 m above the floor at the center of one of the walls. The dimensions of the indoor unit were.6 m.24 m.3 m, and the indoor unit had an air outlet with dimensions of.6 m.6 m. The refrigerant leaked from this air outlet. Approximately 2, non-equidistant mesh points were used to discretize the governing equations. The refrigerants considered were R32, R1234yf, and R29 (propane). (b) Leakage from a Floor-mounted Indoor RAC Unit Refrigerant was modeled as leaking from a floor-mounted indoor RAC unit into a space equal in size to that used for leakage from the wall-mounted indoor RAC unit. The size of the space where the refrigerant leaked from the floor-mounted indoor unit was equal to that where the refrigerant leaked from the wall-mounted indoor unit. The indoor unit was located on the floor at the center of one of the walls. The dimensions of the indoor unit were.7 m.21 m.6 m, and the indoor unit had an air outlet with dimensions of.46 m.45 m. The refrigerant leaked from this air outlet. Approximately 24, non-equidistant mesh points were used to discretize the governing equations. The refrigerants considered were R32 and R1234yf. (c) Leakage from an Outdoor RAC Unit Refrigerant was modeled as leaking from an outdoor unit placed on a balcony with dimensions of 5. m 1.2 m 1.1 m. The outdoor unit was located on the floor at the left side of the balcony. The dimensions of the outdoor unit were.77 m.29 m.68 m, and the outdoor unit had a fan with a diameter of.4 m. The refrigerant leaked from the fan. In addition, wind with a velocity of.5 m/s was assumed to be blowing around the balcony. Approximately 35, non-equidistant mesh points were used to discretize the governing equations. The refrigerants considered were R32 and R1234yf. (d) Leakage from a Variable Refrigerant Flow Refrigerant was modeled as leaking from a VRF placed in an office with dimensions of 6.5 m 6.5 m 2.7 m. The indoor unit of the VRF was located on the ceiling at the center of the office. This indoor unit had an air outlet with dimensions of.45 m.645 m and a suction opening that was.37 m in diameter. The refrigerant leaked from the air outlet and suction. The office also had an air supply with dimensions of.2 m.2 m and exhaust grills, and the gap under the door was 1.5 m.1 m. Approximately 2, non-equidistant mesh points were used to discretize the governing equations. The refrigerants considered were R32 and R1234yf. When the leakage velocity is higher than the burning velocity, there may be no flammable volume. Therefore, for the calculations of (a) (d), the leakage flows were set to be very slow to consider high-risk situations. (e) Leaks from Water-cooled Chiller Refrigerant was modeled as leaking from a water-cooled chiller placed in a machine room with dimensions of 1.28 m 1.28 m 1.28 m. The chiller was located 1.1 m from the wall and was assumed to have a nozzle-shaped leakage port 1 mm in length located 15 mm from the floor. The inner diameter of the nozzle depended on the type of leakage: φ = 4. mm for rapid leakage and φ = 8. mm for burst leakage. The air inlet and exhaust duct inlet were located on the ceiling above the chiller and at the bottom of the machine room, respectively. The areas of the air inlet and exhaust duct inlet were calculated as follows. The velocity and openness at the air inlet and exhaust port were as follows: (at air inlet) velocity: v in = 2. m/s, aperture ratio: α in =.7 (at air exhaust duct) velocity: v out = 4. m/s, aperture ratio: α out =.3 The air ventilation volume per hour q was calculated from the following equation. Air ventilation volume: q = XV (m 3 /h) where X and V are the number of air vents and volume of the machine room (m 3 ), respectively. The areas of the air inlet A in and exhaust duct inlet A out were obtained from the following equation. q v in in A in out v out A out 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 5 where α in and α out are the aperture ratios of air inlet and air exhaust duct, respectively. The refrigerants considered were R32, R1234yf, and R1234ze(E). For the calculation of the case with the chiller, the leakage speed was assumed to be that of a burst leakage or rapid leakage from the hole, like a nozzle; therefore, the leakage velocity was much higher than those in the case of RAC and VRF. This is why a different type of turbulence model was selected from those used for RAC and VRF. Here, the realizable k ε turbulence model was used because Pattamatta and Singh (212) reported that the near wall velocity profile captured using the realizable k ε turbulence model showed the best agreement with the experimental data compared to other models. 4 RESULTS AND DISCUSSION Table 3 presents the calculation results. The term Σ(V t) represents the product of the flammable gas volume and presence. This value is associated with the risk of combustion and is called the flammable volume (FVT). The term V FL represents the flammable gas volume, and the term V BVFL represents the flammable gas volume with an air velocity lower than the burning velocity. (a) Leakage from the Wall-mounted Indoor RAC Unit The calculation results in Table 3 for cases 1 8 represent the leakage from the wall-mounted indoor RAC unit. Case 1 is shown in Figs. 3 and 4 as a representative result. Fig. 3 shows the LFL isosurface when V FL reached its maximum value, and Fig. 4 shows how Σ(V FL t) and V FL changed with. The FVT was very small, even if a mildly flammable refrigerant leaked from the wall-mounted indoor unit. As shown by the results for cases 1 6, the FVT values determined while considering the burning velocity were equal to zero. These results suggest that ignition does not occur, even if an ignition source exists, because of the convection caused by the refrigerant leakage. Therefore, no combustion occurs if no ignition source exists inside the indoor unit. For case 7, although the calculated value was higher than the maximum allowable fill ratio of propane, the refrigerant leakage represented a large hazard because the FVT value was very high compared to the other cases. For case 8, the MIE of propane was lower than that of R32 and R1234yf, and the quenching distance of propane was very narrow. Therefore, the leakage of propane is a hazard because the flame is easily transmitted. (b) Leakage from the Floor-mounted Indoor RAC Unit The calculation results in Table 3 for cases 9 and 1 represent the leakage from a floor-mounted indoor RAC unit. Case 1 is shown in Figs. 3 and 4 as a representative result. According to Table 3, both the terms Σ(V FL t) and Σ(V BVFL t) were very similar. These results suggest that the air velocity is lower than the burning velocity in the combustion region. Therefore, if an ignition source exists in the combustion region, there is a risk of combustion throughout much of the combustion region. In addition, because the LFL of R1234yf is lower than that of R32, the presence of R1234yf is longer than that of R32. Thus, the risk with R1234yf is higher than that with R32. Therefore, safety regulations are required when flammable refrigerants are used in air conditioners because the risk of leakage from a floor-mounted indoor unit is higher than that from a wall-mounted indoor unit. (c) Leakage from the Outdoor RAC Unit The calculation results in Table 3 for cases 11 and 12 represent the leakage from the outdoor RAC unit. Case 12 is shown in Figs. 3 and 4 as a representative result. The results in Table 3 show that the flammable gas volume existed for a long for the same reason as explained for the floor-mounted indoor unit. Therefore, a balcony with drains and undercuts is preferred for safety because an outdoor unit has a fan near the floor level, which may lead to the flammable region spreading over the entire balcony area. (d) Leakage from the Variable Refrigerant Flow The calculation results in Table 3 for cases 13 22 represent the leakage from the VRF. Case 15 is shown in Figs. 3 and 4 as a representative result. According to Table 3, the existence of an air vent as an air supply source affects the FVT and presence. In addition, the release period of the VRF was more than 15 min because of the large amount of refrigerant leaked. Therefore, although the flammable gas volume is small, the FVT (Σ(V FL t)) is longer than that for leakage from a wall-mounted RAC unit. On the other hand, the FVT decreases significantly when the air velocity is considered. For R1234yf, the risk of ignition is very low because the burning velocity is low. For R32, safety regulations pertaining to, for example, a refrigerant leakage sensor, alarm, and ventilation are required when flammable refrigerants are used in air conditioners. 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 6 Table 3 Predicted Σ(V FL t) and Σ(V BVFL t) case No. Presence, min Σ(V FL t ), m 3 min Σ(V BVFL t ), m 3 min case No. Presence, min Σ(V FL t ), m 3 min Σ(V BVFL t ), m 3 min 1 4.1 1.18 1-2 17 8.36 3.14 1-2 2 4.1 1.23 1-2 18 176.47 2.152 3 8.1 9.79 1-3 19 176.42.661 4 8.1 1.7 1-2 2 176.41.583 5 1.3 3.73 1-2 21 176.41.592 6 1.5 4.34 1-2 22 1.25 2.14 1-2 7 1473. 7689 7688 23 18.72.13 8 4.73.258.161 24 14.4.599.22 9 111. 136.83 136.81 25 14.4.2 1 39. 57.82 57.5 26 *1 up to22.62 up to 127.84 up to 3.449 11 45. 43.1 42.5 27 *1 up to 157.67 up to 118.44 up to 44.15 12 93. 62.54 61.53 28 156..8 13 157.85 1.622.21 29 *1 up to 27.67 up to 361.62 *2 14 157.82.831.11 3 26..14 *2 15 157.82.72.14 31 2.58 16.352 *2 16 157.82.725.11 32 2.58.9 *2 *1 Calculation was stopped at 1 second after refrigerant leaked out completely. *2 R1234ze(E) is non-flammable when relative humidity is zero. Case no.1 R32, velocity: 125 g/min ventilation: m 3 /h Case no.1 R1234yf, 35 g/min ventilation: m 3 /h Case no.12 R1234yf, velocity: 35 g/min ventilation: (outdoor) Case no.2 R1234yf, velocity: 1 kg/h ventilation: 169 m 3 /h t = 24 s t = 24 s t = 24 s t = 1 s Case no.25 R32, rapid leakage ventilation: 545 m 3 /h Case no.26 R1234yf, burst leakage ventilation: m 3 /h Case no.27 R1234yf, rapid leakage ventilation: m 3 /h Case no.28 R1234yf, rapid leakage ventilation: 545 m 3 /h t = 84 s t = 1287 s t = 936 s t = 936 s Fig. 3 LFL isosurface when V FL reached its maximum value 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 7 (e) Leakage from the Water-cooled Chiller The calculation results in Table 3 for cases 23 32 represent the leakage from the water-cooled chiller. Cases 25 28 are shown in Figs. 3 and 4 as representative results. For cases 26, 27, and 29, the calculation was stopped 1 s after the refrigerant had leaked out completely, although there was a flammable region at that. Therefore, the actual existence and FVT must be larger than the values listed in Table 3. In addition, although humidity was not considered in this study, humidity should be considered for leakage of R1234ze(E) because this refrigerant is nonflammable when the humidity is zero. These results indicate that the ventilation air flow has a large effect on the FVT, similar to the VRF results. For example, the effects of enough air ventilation volume (X = 5) on the rapid leakage of R32 and R1234yf are evident for cases 24 and 25 and cases 27 and 28, respectively. According to the results, for rapid leakage of both R32 and R1234yf, Σ(V FL t) is very small and Σ(V BVFL t) equals zero. This is because the ventilation air makes the refrigerant flow through the exhaust duct to the outlet. This result may be attributed to the enough air ventilation volume. On the other hand, for the non-ventilation case, the FVT of R1234yf was larger than that of R32 because the former has a lower LFL and longer presence than the latter, as noted previously. Furthermore, the leakage velocity was assumed to be much higher than that for leakage from an RAC or VRF; this leads to a zero or very small Σ(V BVFL t), even if Σ(V FL t) increases. However, if there is no ventilation air flow and there is a high-concentration region after the refrigerant leaks out completely, as in cases 26, 27, and 29, Σ(V BVFL t) may increase. The results for the leakage from the water-cooled chiller indicate that sufficient ventilation air flow is needed to keep the room safe when flammable refrigerants are used in chillers. A leakage sensor is also required. 5 EXPERIMENT ON REFRIGERANT LEAKAGE (a) Experiment Method and Conditions The refrigerant concentration was measured in an experimental room with the same dimensions as that used in the numerical calculation of RAC. Figure 5 shows the diagram of the experiment system. Refrigerant from the gas cylinder was cooled by evaporative latent heat and raised to the prescribed temperature through a thermostat bath. The mass flow rate was controlled by the mass flow controller. Refrigerant was leaked into the experimental room, Σ(V FL t ) [ 1-5 m 3 min] 15 12 9 6 3 Case no.1 R32, velocity: 125 g/min ventilation: m 3 /h 4 32 24 16 8 V FL [ 1-5 m 3 ] Σ(V FL t ) [m 3 min] 5 4 3 2 1 Case no.1 R1234yf, 35 g/min ventilation: m 3 /h 3 2.4 1.8 1.2.6 V FL [m 3 ] Σ(V FL t ) [m 3 min] Case no.12 R1234yf, velocity: 35 g/min ventilation: (outdoor) 75 6 45 3 15 1.5 1.2.9.6.3 V FL [m 3 ] Σ(V FL t ) [m 3 min].6.48.36.24.12 Case no.2 R1234yf, velocity: 1 kg/h ventilation: 169 m 3 /h 5 4 3 2 1 V FL [ 1-3 m 3 ] Σ(V FL t) [ 1-5 m 3 min] 1, 8 6 4 2 1 2 3 4 [min] Case no.25 R32, rapid leakage ventilation: 545 m 3 /h 1 8 6 4 2 V FL [ 1-5 m 3 ] Σ(V FL t) [m 3 min] 18 15 12 5 1 15 2 25 3 35 [min] 9 6 3 Case no.26 R1234yf, burst leakage ventilation: m 3 /h 6 5 4 3 2 1 V FL [m 3 ] Σ(V FL t) [m 3 min] 2 4 6 8 1 [min] 15 12 9 6 3 case no.27 R1234yf, rapid leakage ventilation: m 3 /h 15 12 9 6 3 V FL [m 3 ] Σ(V FL t) [ 1-5 m 3 min] 1, 8 6 4 2 3 6 9 12 15 18 [min] Case no.28 R1234yf, rapid leakage ventilation: 545 m 3 /h 1 8 6 4 2 V FL [ 1-5 m 3 ] 2 4 6 8 1 12 14 [min] 4 8 12 16 2 25 5 75 1 125 15 [min] [min] Fig. 4 Σ(V FL t) and V FL changes with 25 5 75 1 125 15 [min] 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 8 and the refrigerant concentration was measured by the concentration sensor. The experiment was carried out under the same conditions as those used for cases 1, 3, and 9; these are listed in Table 2. (b) Results and Discussion Figure 6 compares the experimental and calculation results. The experimental leakage from the wall-mounted indoor unit at low measurement points indicated a higher refrigerant concentration, while the refrigerant arrival also showed a positive inclination relative to the calculation results. However, for the wall-mounted indoor unit, the refrigerant concentration at low measurement points was lower than the calculated results when the leakage ended; thus, the experimental results indicated that the wall-mounted indoor unit was safer than the calculation results. For the experiment on leakage from the floor-mounted indoor unit, the measured refrigerant concentration on the floor was almost equal to the calculation results. However, the before the concentration on the floor became less than the LFL was much shorter than that in the calculation results. This was caused by the imperfect experimental conditions without air flow. The exhaust duct equipped in the experimental room may have led to convection caused by the pressure difference between the experimental room and outdoor environment. Therefore, convection provided safer results, which is favorable for the risk assessment. On the other hand, the experimental results showed that the refrigerant concentration on the floor, which was thought to be least affected by convection, did not reach the LFL during leakage from the wall-mounted indoor unit, and the refrigerant concentration exceeded the UFL when the leakage from the floor-mounted indoor unit ended. These tendencies were generally consistent with those of the calculation results. From a regulation standpoint, the CFD simulation is preferred for the development of strict regulations. However, the experimental results can be used to confirm the qualitative trend of the refrigerant concentration distributions. T T Model of RAC. Regulator Thermostat bath Mass flow controller Gas cylinder Sensor Sensor Experiment room Sensor Fig. 5 Schematic diagram of experimental apparatus Fig. 6 Results of refrigerant leakage experiment (right): Wall-mounted, R32, 1 g, 25 g/min, (left): Floor-mounted, R32, 1 g, 25 g/min 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 9 6. Conclusion The simulation and experiments conducted in this study on the leakage of refrigerants into a space yielded the following findings. 1. In the case of leakage from a wall-mounted indoor unit, combustion does not occur if an ignition source does not exist inside the indoor unit. 2. In the case of leakage from a floor-mounted indoor unit, safety regulations are required when flammable refrigerants are used in air conditioners. 3. In the case of leakage from a floor-mounted indoor unit or outdoor unit, the risk of combustion is higher with R1234yf than with R32. 4. In the case of leakage from an outdoor unit, a balcony with drains and undercuts is preferred because an outdoor unit has a fan near the floor level, which may lead to spreading of the flammable region over the entire balcony area. 5. In the case of leakage from a VRF, the FVT is much smaller when the burning velocity is considered. 6. In the case of leakage from a water-cooled chiller, the ventilation air flow has a large effect on the FVT. When there is no ventilation air flow and the velocity of the refrigerant leakage is high, the FVT may increase after the refrigerant leaks out completely. 7. The experiment confirmed that the refrigerant concentration on the floor does not reach the LFL in the case of leakage from a wall-mounted indoor unit and exceeds the UFL in the case of leakage from a floor-mounted indoor unit. 7. Future Works Future works will involve the simulation of leakage from an air-cooled chiller. In addition, the analytical conditions for leakage from a water-cooled chiller in particular, the ventilation, shape of the exhaust duct, and area of the machine room will be reconsidered. NOMENCLATURE A in area of air inlet (m 2 ) A out area of air exhaust duct (m 2 ) q air ventilation volume per hour (m 3 h -1 ) v in air velocity at air inlet (m s -1 ) v out air velocity at air exhaust duct (m s -1 ) V volume of machine room (m 3 ) X number of air vents per hour (h -1 ) α in aperture ratio of air inlet α out aperture ratio of air exhaust duct φ inner diameter of nozzle (m) ACKNOWLEDGEMENT The authors gratefully acknowledge the financial support from New Energy and Industrial Technology Development Organization (NEDO). REFERENCES Japan Fluorocarbon Manufacturers Association (JFMA) ed., 212. List of CFCs, HCFCs and fluorocarbons environmental and safety data, JFMA, http://www.jfma.org/atabase/table.html (in Japanese) Kataoka, O., Yoshizawa, M., Ohnishi, H., and Ishida, S., 1996. Flammability evaluation of HFC-32 and HFC- 32/134a under practical operating conditions, Proceedings of the International Refrigeration Conference, Purdue, USA, July 1996. Pattamatta, A., and Singh, G., 212. Assessment of turbulence models in the prediction of flow field and thermal characteristics of wall jet, Frontiers in Heat and Mass Transfer, 3, 235, pp.1-11. 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214

2459, Page 1 Takizawa, K., Tokuhashi, K., Kondo, S., and Nagai, H., 211. Flammability evaluation of R-1234yf and R- 1234ze(E), Proceedings of the 49th Combustion Symposium, 146-147, Yokohama, Japan (in Japanese). Takizawa, K., 212. Flammability properties of 2L refrigerants, Proceedings of the International Symposium on New Refrigerants and Environmental Technology 212, Kobe, Japan. Goetzler, W., and Burgos, J., 214. Study of input parameters for risk assessment of 2L flammable refrigerants in residential air-conditioning and commercial refrigeration applications, Proceedings of 214 ASHRAE: TC 3.1- Refrigerants and Secondary Coolants, RP-158, New York City, USA, January 214. 15 th International Refrigeration and Air Conditioning Conference at Purdue, July 14-17, 214