Smoke Master SMIA Compact pressurisation and smoke exhaust system

Similar documents
Smoke Master SMPA Compact pressurisation system

Smoke extract fan SMHA HATCH

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

Smoke Master SMPA Installation, operation and maintenance

Unit heater with accessories

PFS Single stage axial fan The axial fan for modern boiler plants

ClimaFläkt. Chillers and condensing units

EU Air Handling Units with SEMCO EXCLU-SIEVE

Climatix LON communication with POL SNVTs for eq zone application v1.x

Climatix LON communication with POL SNVTs for Twin Wheel application v1.x

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS

Climatix Basic reference addresses for eq Fläkt application v1.x

DIF-OT Ceiling Filter. The optimized laminar airflow

Mechanical Smoke Extract Shaft Systems

ROLL-DOWN FIRE DOORS AND SMOKE CURTAINS

Cleaning doors. Good indoor air also means cleanability of ductwork

Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

Ceiling swirl diffusers

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

Type VDW WITH LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH INDIVIDUALLY MANUALLY ADJUSTABLE AIR CONTROL BLADES

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

LYRA » ENERGY EFFICIENT CASSETTE CHILLED BEAM AIR DIFFUSION LYRA

TopMaster Air Handling unit. Installation instructions

SMOKE CONTROL - NEW DIRECTIONS

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

Technical Information

iq Star by Fläkt Woods Multi-service Chilled Beam Guide Star by Fläkt Woods

CI/SfB X. DF / IDF Series GAS FIRED COMBINED HEATING AND VENTILATION

AIR COMPACT. Air handling units. Ultra high performance USE RANGE DESCRIPTION

Ceiling swirl diffusers

"WHHR125DC" Whole House Heat Recovery Unit with Low Energy DC Motor. Installation, Operating and Maintenance Instructions domestic and commercial use

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

CE-marked ESAD - Smoke Control Duct System Installation instructions 08/2013

TopMaster Air Handling unit. Technical data

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

MECHANICAL SERVICES 101. Ian White

Primo Hotel. General. Indoor climate units for hotel rooms

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU

Intumescent Fire Dampers

Smoke Vents. Certified to CE EN Roof Access Systems

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEB Kitchen exhaust fan

iq Star LYRA II chilled beam cassette

Mechanical Ventilation with Heat Recovery: Designing and implementing a robust and effective ventilation system

DF-IDF air handling units

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

AGA TOTAL CONTROL. Model No s: TC3 & TC5 (ROOM VENT OPTION)

IPSUM OPTIMIZATION SYSTEM» DEMAND CONTROLLED VENTILATION OVERVIEW

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU

Fire dampers. For diverse applications

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design

Systemair product news - Fans NEWS

UNIJET CAR PARK VENTILATION SYSTEM

Element Z General Design Requirements Existing Facilities Information

technical specification smoke venting systems

Homepage > Products > Decentralised ventilation Systems > Vertical devices > Type FSL-V-ZUS. Type FSL-V-ZUS

Schueco Fire and Smoke Protection Systems

AUTOMATIC FIRE DETECTION AND ALARM SYSTEMS

THE SMOKE AND ACCESS SPECIALISTS. Compliance without compromise

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

ABLOY DOOR CLOSERS Exactly the right choice

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

VERSO Air Handling Units

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

Innovative solutions for air and climate technology. Air handling Climate ceilings Air distribution technology Fire safety products Chilled beams

... DF / IDF Gas fired combined heating and ventilation ...

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

Welcome to the. Firestop Seminar. Hilti Technical and Engineering Support

Installation and user manual CLOSED WOOD FIRES DON T COMPROMISE.

KLIMA Active Chilled Beams

ECO ROOF FAN. A modern, energy-saving roof fan with a DC motor. INSTALLER Register the roof fan for an extended 5 year guarantee!

more than just a fan supplier more than just a fan supplier Axair Fans UK Limited

Domestic & Commercial Fans

CARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE

Element Z General Design Requirements Existing Facilities Information

VETO CLEANER 500 FLUE GAS CLEANER

Bevent Rasch BSKC6. - Fire /06/17

Halton Rex for Vario R6O - Variable air volume chilled beam

X-Stream Air Natural Ventilation kits are predominantly designed for self-installation. Suitable for ventilating existing and new build applications.

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

Construction Method, Material Selection, Fire Prevention & Building Security System For Project 9a : Board 4 ; For Project 9b : Part 4

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

recooler HP EQKR HEAT PUMP

Zehnder Comfosystems. ComfoAir 180 Datasheet

DESIGNER HOOD MODEL: EH-E9122ST(BK) Owner s Manual. Please read this manual carefully before operating your set. Retain it for future reference.

Typologies of Hybrid Ventilation in Schools

0.4 m 3 /s. Plastic and Steel cased fan Units. Round Fans. Latest EC Fan Technology. Compact and Powerful. Easy to install

Safety - a full time job

WHHR Midi & Midi Lite

SHEVTEC Extended Travel Distance. System for Chettles Yard, Nottingham

Smoke ventilation. Complete smoke ventilation solutions for all building types

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

COOLSTREAM S T A R PRODUCT OVERVIEW COOLSTREAM S T A R

GOLD RX, GOLD RX 12 GOLD RX,

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

VERSO Air Handling Units

Transcription:

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Fläkt Woods FIFLO EN 2009.09 2 All rights reserved.

Contents System overview... 4 Design and operation... 5 Technical specification... 6 Electrical and control equipment... 7 Apartment air release path... 9 Installation... 10 Product code... 11 Fläkt Woods FIFLO EN 2009.09 3 All rights reserved.

System overview 1 3 2 4 SMIA-1 1 Fan unit SMOKE MASTER SMIA is an all-inclusive total solution for stairwell pressurisation and smoke exhaust. The system has been designed and the components have been constructed to the pressurisation standard EN 12101-6, and the smoke extract fans conform to EN 12101-3. SMIA is CE-marked according to EN 12101-3. The system has been tested by VTT Technical Research Centre of Finland, and it has also been subjected to full-scale fire tests, performed in Myllypuro, Helsinki, in a block of flats. SMIA has been designed for use in residential buildings up to eight storeys high. The SMIA fan unit is, due to its compact external dimensions, suitable for use in new build as well as many refurbishment projects. For ease of design, it is only available in one size with constant air volumes that works for stairwells of many different heights. An SMIA total solution comprises integrated smoke hatches, a fan unit, a control panel, and a control unit. The apartment air release path solutions with the necessary spindle motors, smoke detectors and control units are supplied by our partners. A video illustrating the operation of SMOKE MASTER SMIA in the event of a fire is available on DVD. Please contact your local Fläkt Woods dealer for a copy. SMIZ-2 Control unit SMIZ-3 Control panel 2 3 SMIZ-4 Differential pressure transmitter 4 Fläkt Woods FIFLO EN 2009.09 4 All rights reserved.

Design and operation General SMOKE MASTER SMIA is a complete system tested by VTT Technical Research Centre of Finland. It is designed for the pressurisation and ventilation of stairwells in residential buildings rising to a maximum height of eight storeys. The stairwell shall be pressurised at the earliest stages of a fire. With SMOKE MASTER SMIA, pressurisation is started within approximately 20 seconds of the activation of a smoke detector. It takes an average of 4 10 minutes, in urban areas, for the fire department to arrive. The fire fighters can then use the control panel to choose the pressurisation / smoke exhaust option that is most appropriate to the situation. Pressurisation The system has been designed based on the requirements of EN 12101-6, pressurisation class A. The aim of pressurisation design is to make it possible to create, without delay, a positive pressure within the stairwell, 50 Pa higher than the pressure in the adjacent spaces, in the event of a fire in an apartment. The pressurisation fan is automatically activated by a smoke detector in the apartment on fire. The smoke detector shall also automatically control the opening of an air release path in the apartment (smoke extract window). The air release path shall have a minimum opening (free area) of 0.5 m 2. If the door of the apartment on fire opens, the system automatically raises the air flow so that air flows through the door to the apartment at a velocity of 0.75 m/s. Smoke exhaust and fire attack The system has been designed based on the requirements of EN 12101-3. SMOKE MASTER SMIA provides a constant smoke exhaust air flow of 2.0 m 3 /s. Smoke ventilation is started by the fire department using the control panel. When smoke ventilation starts, pressurisation automatically stops. While attacking the fire, the fire fighters can choose to use pressurisation for greater ease of entry to the apartment on fire. The smoke extract fan is CE marked and F400 rated (400 C/2h). Quick guide New build projects The SMOKE MASTER SMIA system perfectly meets the above design criteria up to eight storeys. Refurbishment projects Please contact Fläkt Woods for expert consultation on the suitability of SMIA for the project. Airflow criterion Pressure difference criterion (doors closed) 1 3 0,75 m/s 50 Pa 3 2 Design conditions for pressurisation class A. 1. Door open. 2. Door closed. 3. Air release path. Fläkt Woods FIFLO EN 2009.09 5 All rights reserved.

Technical specification Dimensions, materials and weight Safety switches 1540 1365 704 704 Fan unit SMIA-1 Materials: Fan unit: The outer and inner casings are made of galvanised steel sheet, and the casing is insulated with 100mm of mineral wool. The smoke hatches are made of galvanised steel sheet and are insulated with mineral wool. Extension: If the length of SMIA-1 is not sufficient, it can be extended with SMIZ-1, available as an optional extra. The outer and inner casings of the extension are made of galvanised steel sheet, and the casing is insulated with 100mm of mineral wool. The telescopic inner tube (200mm) is adjusted during installation to give the desired total length. The joint shall be sealed with fire sealant, and the exposed part of the telescopic tube shall be insulated with mineral wool (included). Moreover, the bottom grille incorporated into SMIA-1 shall be transferred to the extension. L 200 704 Weights SMIA-1: 145 kg SMIZ-1: 60 kg/m Extension SMIZ-1 L = a multiple of 100mm as ordered, max. 2000mm Fläkt Woods FIFLO EN 2009.09 6 All rights reserved.

Electrical and control equipment General: Every SMOKE MASTER SMIA system comes with the necessary electrical and control equipment. The SMIA basic package includes the following electrical and control equipment: control unit SMIZ-2 control panel SMIZ-3 differential pressure transmitter SMIZ-4 safety switches Control unit SMIZ-2 junction box frequency converter automatic control system Wiring diagram and electrical connections FREQUENCY CONVERTER SMIA CONTROL UNIT EXTERNAL START OF PRESSURISATION SUPPLY CABLE SHIELDING 'RUN' SIGNAL 'FAULT' SIGNAL BL BK BR Y/GR CONTROL PANEL STAR CONNECTION PRESSURISATION FAN TF01 LINEAR MOTORS ST01/02 PRESSURE TRANSMITTER dpt 01 MOTOR SAFETY SWITCH CABLING IS INCLUDED IN THE PACKAGE SUPPLIED BY FLÄKT WOODS. OTHER CABLES SHALL BE INSTALLED ON SITE BY AN ELECTRICIAN. THE CABLES SHOULD BE FIRE RESISTANT OR OTHERWISE PROTECTED FROM FIRE. STAIRWELL SMOKE DETECTORS NOT SUPPLIED BY FLÄKT WOODS APARTMENT SMOKE EXTRACT WINDOW CONTROL UNIT 1 APARTMENT SMOKE EXTRACT WINDOW CONTROL UNIT n SUPPLY APARTMENT SMOKE DETECTOR WINDOW OPENING MOTOR MANUAL WINDOW OPENING 'FAULT' SIGNAL SUPPLY APARTMENT SMOKE DETECTOR WINDOW OPENING MOTOR MANUAL WINDOW OPENING 'FAULT' SIGNAL Fläkt Woods FIFLO EN 2009.09 7 All rights reserved.

Electrical and control equipment Control panel SMIZ-3 for controlling pressurisation and smoke ventilation with indicator lights PRESSURISATION AND SMOKE EXHAUST PRESSURISA- TION ON SERVICE STANDBY SMOKE EXHAUST FAN ON MAN PRESSURISATION SMOKE EXHAUST Differential pressure transmitter SMIZ-4 for controlling the fan to be installed in the stairwell Smoke detector FDRC-2-SMIA (Optional extra) Fläkt Woods FIFLO EN 2009.09 8 All rights reserved.

Apartment air release path General For proper operation of the pressurisation system, there must be an automatic opening air release path in the apartment on fire that opens at the same time as the smoke detector is activated, allowing gases to escape outside. The air release path shall be located near the apartment entrance to prevent interior doors, etc. from restricting the gas flow. The air release path can be a window, a smoke extraction damper, or other appropriate solution. A key design principle to consider is that the minimum free area of the air release path shall be 0.5 m 2. Air release paths to be incorporated into the facade shall always be designed in close consultation with the architect and fire authorities, which means that the need for smoke extract solution in apartments is an issue that should be addressed as early as the initial meeting of a new project. The SMOKE MASTER SMIA control unit needs a signal from the apartment system via a volt-free normally open contact. Total smoke extract window solutions (complete with spindle motors, control units and smoke detectors) facilitate the design and implementation process. The following companies supply smoke extract window solutions that are compatible with the SMOKE MASTER SMIA system: Pressurisation without apartment air release path For the pressurisation system to comply with the relevant standards, there should be a air release path in each apartment. In reality, however, it may not always be possible, for some reason or another, to use apartment smoke extract windows. If a decision is made, in consultation with rescue authorities and building control officers, to deviate from the standards and use the SMOKE MASTER SMIA pressurisation system without air release paths in the apartments, the following should be observed: To minimise the risk of having a door open to a burning apartment, door closers or similar equipment should be used to ensure that the doors close in the event of a fire. Moreover, through guidance and fire drills the occupants can be advised to close the apartment doors in case of fire. If the smoke detectors are placed in the stairwell, there should be detectors at each landing. Fläkt Woods supplies smoke detectors (FDRC-2-SMIA) that allow direct connection to the control unit. MOVETEC Oy, ESPOO, FINLAND Tel. +358 400 412543, +358 9 5259230 www.movetec.fi ROCA Finland Oy, TURKU, FINLAND Tel. +358 20 7438937 www.roca.fi Fläkt Woods FIFLO EN 2009.09 9 All rights reserved.

Installation These instructions are also supplied with every SMIA system. For more information, please contact your local Fläkt Woods dealer. 1. Installation in a flat roof insulated with hard mineral wool Compliant waterproof protection of the penetration Modified bitumen Mineral wool 220 mm NOTE! The opening should be 30 40 mm larger than the outer casing of the unit. Seal with grout or a sealant in compliance with the type approval. Screed to falls ~50 mm Hollow-core slab 265 mm or cast-in-situ concrete 240 mm NOTE! Align the upper surface of the unit s bottom grille with the roof s lower surface. Self-drilling screw 6,3x25 3-5 pcs per mounting bracket Wedge anchor M6x50-2-4 pcs per mounting bracket Mounting bracket 80x80 4 pcs Fläkt Woods FIFLO EN 2009.09 10 All rights reserved.

Installation and Product code 2. Installation in a pitched roof Secure with 5x40 coach screws or similar Self-drilling screw 6,3x25 3-5 pcs per mounting bracket Mounting bracket 80x80 4 pcs Cover the joint on the outside with the two cover plates provided with the extension. Secure the plates to the outer casing of the fan unit / extension with 4.2x13 self-tapping screws. Length of the extension L=max. 2000 mm, multiples of 100 mm Self-drilling screw 6,3x25 3-5 pcs per mounting bracket Wedge anchor M6x50-2-4 pcs per mounting bracket Range of adjustment 0 200 mm Compliant waterproof protection of the penetration Wooden mounting frame between rafters Insulate the joint between the fan unit s inner casing and the extension s inner tube with fireproof sealant. Cut the fire-resistant mineral wool slabs (included) into pieces that fit between the fan unit and the extension. NOTE! The opening should be 30 40mm larger than the outer casing of the unit. Seal with grout or a sealant in compliance with the type approval. Mounting bracket 80x80 4 pcs NOTE! Align the upper surface of the unit s bottom grille with the roof s lower surface. Product code Pressurisation and smoke exhaust system The basic package includes: Fan unit Control unit Control panel Differential pressure transmitter SMOKE MASTER SMIA SMIA-1 SMIZ-2 SMIZ-3 SMIZ-4 Component codes (when ordering individual components): Fan unit SMIA-1 Control unit SMIZ-2 Control panel SMIZ-3 Differential pressure transmitter SMIZ-4 Optional extras: Extension SMIZ-1-aaaa Length L (mm) L to be expressed in multiples of 100 mm, max. length L=2000 (see page 6) Smoke detector FDRC-2-SMIA Fläkt Woods FIFLO EN 2009.09 11 All rights reserved.

We Bring Air to Life Fläkt Woods is a global leader in air management. We specialise in the design and manufacture of a wide rande of air climate and air movement solutions. And our collective experience is unrivalled. Our constant aim is to provide systems that precisely deliver required functions and performance, as well as maximise energy efficiency. Solutions for all your air climate and air movement needs Fläkt Woods is providing solutions for ventilation and air climate for buildings as well as fan solutions for industry and infrastructure. Air Handling Units (AHUs) Modular, compact and small AHU units. Designed to ensure optimisation of indoor air quality, operational performance and service life. Air Terminal Devices and Ducts Supply and exhaust diffusers and valves for installation on walls, ceiling or floor are all included in our large range and fit all types of applications. Chilled Beams Active induction beams for ventilation, cooling and heating, and passive convection beams for cooling. For suspended or flush-mounted ceiling installation - and multi-service configuration. With unique Comfort Control and Flow Pattern Control features. Residential ventilation A complete range of products for residential ventilation. Consists of ventilation units, exhaust air fans and cooker hoods designed to optimise indoor comfort and save energy. Fans Advanced axial, centrifugal and boxed fans for general and specialist applications. Comprehensive range including high temperature and ATEX compliant options. Engineered for energy efficiency and minimised life cycle cost. Chillers Air-cooled and water-cooled chillers with cooling capacity up to 1800 kw. Designed to minimise annual energy consumption in all types of buildings. Controls and drives Variable speed drives and control systems, all tested to ensure total compatibility with our products. Specialist team can advise on energy saving and overall system integration. Smoke Master SMIA / Technical data / EN / 09.2009 / All rights reserved. Fläkt Woods Oy Kalevantie 39, FI-20520 Turku, FINLAND Tel. +358 20 442 3000 www.flaktwoods.com