Air-Cooled Heat Exchanger Performance for R410A

Similar documents
Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

Low GWP Refrigerants for Air Conditioning Applications

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Study of R161 Refrigerant for Residential Airconditioning

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Purdue e-pubs. Purdue University

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

The Effect of Inner Grooved Tubes on the Heat Transfer Performace of Air-Cooled Heat Exchangers of Co2 Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

R32 Compressor for Air conditioning and Refrigeration applications in China

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Experimental Study on the Performance of Twisted Capillary Tube

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Control Method Of Circulating Refrigerant Amount For Heat Pump System

The Development of the Energy-Saving Technology by the Composition Control of R407C

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Efficiency of Non-Azeotropic Refrigerant Cycle

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Evaluation of a Virtual Refrigerant Charge Sensor

Experimental Study on Fractionation of R-407C and Recharge Operations

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Leakage of Mildly Flammable Refrigerants into a Room

TERNARY ZEOTROPIC MIXTURE WITH CO 2 COMPONENT FOR R-22 HEAT PUMP APPLICATION

System Using Exhaust Heat from Residential GHPs

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Refrigerant Glide and Effect on Performances Declaration

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Performance of CO2 Cycles with a Two-Stage Compressor

Purdue e-pubs. Purdue University. Ian H. Bell Purdue University. Eckhard A. Groll Purdue University

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Real Time Upright Freezer Evaporator Performance Under Frosted Conditions

The Use Of Attic Space For Cooling and Dehumidification

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Optimization Strategies for Unitary Air Conditioners Using R-410A

System Modeling of Gas Engine Driven Heat Pump

Investigation of Evaporator Performance with and without Liquid Overfeeding

A STUDY ON THE BEHAVIOR OF STEAM CONDENSATION IN U-SHAPED HEAT TUBE

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Dynamic Simulation of Liquid Chillers

High Efficiency R-134a Compressor for Domestic Refrigerator

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

Sub-Critical Operation of the CO2 Expander/ Compressor

Performance of an Improved Household Refrigerator/Freezer

Compressor Capacity Control

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1996 Air-Cooled Heat Exchanger Performance for R41A T. Ebisu Daikin Industries K. Yoshida Daikin Industries K. Torikoshi Daikin Industries Follow this and additional works at: http://docs.lib.purdue.edu/iracc Ebisu, T.; Yoshida, K.; and Torikoshi, K., "Air-Cooled Heat Exchanger Performance for R41A" (1996). International Refrigeration and Air Conditioning Conference. Paper 14. http://docs.lib.purdue.edu/iracc/14 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

AIRCOOLED HEAT EXCHANGER PERFORMANCE FOR R41A Takeshi Ebisu, Kaori Yoshida and Kunikazu Torikoshi Mechanical Engineering Laboratory, Daikin Industries, Ltd. 14 Kanaoka-cho, Sakai, Osaka 591 Japan ABSTRACT The present study was carried out experimentally to evaluate the air -cooled heat exchanger performances for R 41 OA. The experiments were performed with the heat exchangers for three different refrigerant flow s. Measurements were made on heat exchanger performances for R41 OA and R in cooling and heating modes. The results obtained in the present study showed that the difference of the heat exchanger performance for R41A in cooling mode significantly occurred in individual flow s. Comparison results between for R41A and R showed that the heat exchanger performance for R41A was higher than that for R. In heating mode, the heat exchanger performance for R41A was insensitive to the change in s, and the heat exchanger performance for R41A was almost the same as that for R. The difference of individual heat exchanger performance for three different flow s was explainable by the reason that the lower pressure difference of refrigerant, the larger is heat flux at the surface of the heat exchanger. NOMENCLATURE A Surface area of the heat exchanger subscript Cp Specific heat of air a air G Refrigerant flow rate c condensation L1P Pressure difference e evaporation Q Heat capacity inlet T Temperature outlet.6t: Temperature difference r refrigerant h Enthalpy s saturation L1h Enthalpy difference sc: sub cooling u Air velocity SH: superheat X Quality w wall INTRODUCTION The 4th amendment of the Montreal Protocol made at Copenhagen Conference in 199 has called for a new phaseout schedule ofhcfcs, including R, due to the enforced protection of the stratospheric ozone l_ayer. A production cap for HCFCs has just started from January 1, 1996. Concerning the candidates for R used in air-conditioning machines, a ternary zeotropic mixture R47C and a binary azeotropic mixture R41A are currently nominated to be the promising replacements from the view point of environmental friendship such as zero ODP and nonflammability. Besides the basic characteristics such as thermal properties, lubrication and flammability, information on the heat transfer characteristics inside heat transfer tubes and the salient features of air-cooled heat exchanger performances for the alternative refrigerants have been the subjects of fundamental importance to design air-cooled heat exchangers installed into air-conditioning machines. The authors have provided with much information on the evaporation and condensation heat transfer characteristics inside a horizontal tube for the alternative refrigerants such as Rl4a(I), R(), R/14a(), R47C(4) andr41a(5). For R47C, which is one of the most promising replacements for R, the report(4) by the authors indicated that the evaporation and condensation heat transfer coefficients inside a horizontal heat transfer tube fell about - 5% below those for R. In addition to the heat transfer characteristics inside a heat transfer tube, evaluation of heat exchanger performance is needed for designing the optimum air-conditioners and heat pumps with R47C. The authors have conducted the experimental study(6) concerning the air-cooled heat exchanger performance for R47C. The experimental results confirmed that the heat exchanger performances for R47C were consistent with those for R in the cooling mode, while the heat exchanger performances for R47C in the heating mode were higher than those for R. Regarding another promising alternative refrigerant R41A, the authors(5) presented the heat transfer data during 19

evaporation and condensation in a heat transfer tube. The heat transfer coefficients for R41 OA were found to be almost the same as those for R, and the comparisons of the pressure drop between R41 OA and R showed the significant result that the pressure drop for R41A was about 5 5% lower than that for R. Although the lower pressure drop inside a heat transfer tube for R41A gives considerable advantage to the heat exchanger performance, it is difficult to evaluate quantitatively the effects of the pressure drop on the heat exchanger performance for R41A. This is because the pressure drop of the refrigerant inside the tube results in the change in the evaporation/condensation pressures, the surface temperature of the heat exchanger and the refrigerant flow rate. The objective of the present study is to evaluate experimentally the aircooled heat exchanger performances for R41A. In the present study, the experiments were performed with the heat exchangers for three different refrigerant flow s. The heat exchangers to be tested are actually used in the inner unit of the residential air conditioning machine with kw. Measurements were made on heat exchanger performances for R41A in cooling and heating modes. The heat exchanger performance for R was also examined in order to compare the heat exchanger performances between for R41A and R. EXPERIMENTS Air inlet ' I Bel; mouth Experimental Apparatus A schematic diagram of the experimental apparatus is shown in Figure 1. The apparatus is designed to draw the room air over the test section, while supplying the refrigerant into the heat exchanger. The wind tunnel illustrated upper side in Figure 1 was set up in the hermetic testing room in which both of temperature and humidity of air are maintained to be the desired conditions. The wind tunnel was composed of the bell mouth section, test section, diffusion section and blower. The bell mouth was designed to provide air velocity distributions within 5% in the test section. The room air was admitted to the wind tunnel by a blower, and the air flow rate was determined from the measurement with the calibrated nozzle. In order to measure the temperature and humidity at the inlet and outlet of the test section, two psychrometers were located near to the wind tunnel Each sampling device Psychrometer ----r-=::::::::::::::::----:::;:::::::;::::;::::::::;=:::::::=]:::_1 Airflow.. Refrigerant flow of the psychrometer was mounted upstream of the wind tunnel entrance and downstream of the test section, respectively. The dry-bulb and wet bulb temperatures in the psychrometers were taken by the Pt resistance sensors within an accuracy of.k. In order to reduce heat losses from the air side of the test section, all walls of the test section and the wind tunnel were insulated with Scm styrofoam. The refrigerant loop is shown in lower side in Figure 1. The loop consisted of a pump, mass flow meters, electric heaters and two heat exchangers. In place of a compressor, the pump was used to circulate the refrigerant into the loop without lubricant. The main heat exchanger was installed in the refrigerant loop to regulate the desired pressure of the refrigerant, while the auxiliary heat exchanger was used to liquidize the refrigerant flowing into the pump. The mass flow meters and flow regulating valves were connected downstream of the pump to allow the desired - Pump GJ :Thermocouple : Pressure gauge @ : Differential pressure gauge Figure 1 Schematic diagram of experimental apparatus Table 1 Description of test heat exchanger X9 tubes 4mm Geometry of : air-side aluminum louvered fin 7 in fin pitch.18mm Cross section of heat transfer tube 14

refrigerant flow rate. To control the quality and superheat of the refrigerant flowing into the test section, the electric heaters were located upstream of the test section. Gas chromatography was prepared to check the composition of the refrigerant mixture. Description of Test Heat Exchanger An appearance of the heat exchanger to be tested in the present experiments is shown in Table 1 with the geometrical information. Table 1 includes information on the fin and tube consisting of the test heat exchanger. The heat exchanger corresponds to the actual inner unit of the residential air-conditioning machine with kw. The heat exchanger, having 65X 189mm in face area, was mounted into the test section of the wind tunnel and connected with the refrigerant loop to supply the refrigerant. The heat transfer tubes of the test heat exchanger were positioned in a staggered array with two rows, schematically shown in Figure. In the present experiments, the heat exchangers for three different refrigerant flow s were employed to examine the effect of the tube length on the heat exchanger performance. The flow configurations of the refrigerant and air were also shown in Figure, respectively. In order to measure both the pressures of the refrigerant at the inlet and outlet of the heat exchanger, the pressure taps in O.Smm diameter were equipped at the inlet and outlet of the heat exchanger. Measurements of the refrigerant temperatures were made with the thermocouples. The thermocouples were located near the pressure taps. In addition, a total of 19 thermocouples was attached on the U-turn bends of the heat transfer tube to measure the tube wall temperatures along the length of the heat exchanger. The thermocouple reading data was utilized to obtain the surface temperature of the heat exchanger. Experimental Conditions Experimental conditions in cooling and heating modes are listed in Table. The experiments were conducted for air in velocity ranging from.7 to 1.rnls in the face area of the heat exchanger. The evaporation and condensation temperatures of the refrigerant were determined from the saturation temperature corresponding to the refrigerant pressures measured at the outlet and inlet of the test heat exchanger for evaporation and condensation, respectively. In the cooling mode, the refrigerant superheat, TsH, was given as the temperature difference between the saturation temperature, Tc, and the measured refrigerant temperature, Tro, while the refrigerant subcooling, Tsc, in the heating mode represented the temperature difference between Ts and Tro. In the present experiments, To and To were maintained constant at 78K(5 C) and 1K( 4 oc), respectively. Further, both oftsh and Tsc were held constant at 5K. Data Reduction The capacity of the heat exchanger, Q, was calculated with the following equation: Air 1 Refrigerant Air Air s s : Thermocouples Q=GX.6.h (1) Figure Tube arrangements of test heat exchangers where G and.6. h denote the refrigerant flow rate and the enthalpy difference between the inlet and outlet the refrigerant..6. h was defined by equations () and ().6. h=ho -hi for evaporation ().6. h=hi -ho for condensation () On the other hand, Q was also obtained by the air side measurements : Q=pXCpXuXAX.6.T (4) In the equation (4),.6. T represents the temperature difference between the air temperature at the inlet and outlet of the test section. Comparisons between the heat quantities in the air and refrigerant sides show that both values were in excellent agreement within %. Accordingly, the capacity of the heat exchanger was calculated from the 141 Table Experimental conditions Cooling mode Heating mode Dry bulb temp. (K) 8 (K) Air side Wet bulb temp. 9 (K) 79 (K) Air face velocity.7, 1., 1. (m/s) Saturation temp. 78 (K) 1 (K) Ref side Inlet X=. Tsrf 7 (K) Outlet Tsi-F5 (K) Tsc= s (K)

4..5 88 [-;:';:r::::::!:::r::::::!!::!:::r:j;:-r-t""""""r"t""t"""t""l'l 8 I R41 OA, Cooling mode I. 78..7 1. u, m/s 1. Figure Effect of refrigerant flow on the heat exchanger capacity for R41A 5 1 15 19 Number of thermocouples Figure 5 Effect of refrigerant flow on tube wall temperature 4..5..5.. 1 ::.::: 1 1 i!= «< a....>:: a.. <l 15 1 5 «l a.....>:: a... <l 15 1 5 Figure 4 Experimental data as a function of refrigerant flow Figure 6 Comparison of data between for R41 OA and R refrigerant side in the present experiments. Cooling Mode RESULTS AND DISCUSSION The performance results of the heat exchanger used as evaporator are shown in Figure, as a function of air velocity passing through the heat exchanger. In the figure, the data are given for R41A. The figure shows that the heat exchanger performances are dependent on the number of s, and the maximum performance is attainable for the s in this study. Also comparisons among the results for three different refrigerant flow s at u=l.omls show that the heat exchanger performances for and s surpass that for 1 by 17% and 19%, respectively. In order to clarify the experimental findings, the data on heat capacity, Q, refrigerant temperature at the inlet of the heat exchanger, Tn, and pressure difference between at the inlet and outlet of the heat exchanger, P, are prepared in 14

4.5 4..5 a. a.o --------- ;-- --------.- : -----. ---- ' --------.. --; ----f);- I Circuit.7 - ---o- Circuits 1. u, m/s -----o----- Circuits 1. Figure 7 Effect of refrigerant flow on the heat exchanger capacity for R41A Figure 4. Figures 4(a), 4(b) and 4(c) corresponds to the results of Q, T,; and.6. P, respectively. Figure 4( c) shows that 6.. P decreases as the heat exchanger increases. Decreasing 6.. P results in the decrease oftn as shown in Figure 4(b). The decrease oftn brings about the decrease of the surface temperature of the heat exchanger. Eventually, the increased heat flux at the surface of the heat exchanger occurs when T ri is decreased. The results in Figure 4(a) are explainable by the reason that the lower Tn, the larger is heat flux. Surface temperature distributions of the heat exchanger along the tube length for three different s are displayed in Figure 5. The figure is prepared for the purpose of confirming the reason above mentioned. The data in the figure are given for u=l.om!s. As seen in the figure, the surface temperatures on the heat transfer tubes for 1 are higher than those for and s. Representative comparison results between for R 41 OA and R are shown in Figures 6(a), 6(b) and 6(c) for u=l.om/s. Figure 6(a) demonstrates that the heat exchanger performance for R41A is significantly higher than those for R. The ratios of the heat exchanger performance for R41 OA to that for R depend on the number of. For I, and s, the ratios are about 4%, 8% and 5%, respectively. The results as shown in Figures 6(b) and 6(c) show that 6.P for R41A is smaller than that for R, and that Tn for R41A is lower than that for R. Therefore, the results in Figure 6( a) are considered to be due to the reason that the lower T ri, the larger is heat flux at the surface of the heat exchanger for R41 OA ::.::: 4.. -------r-=="""'"""f'lo-----1.-------- - 8... T "' a...::.:: 1 a. <I.. ---------------- ---- -r ----.. -- -----...,.... 6 ------------------- ---------------- 1 ----- ----... -----------t ------- 15 ---... ----- --. ---- -.,. - :- ' - ---- ----- -- -;-- ----- -----1 --- 5 ---- ---------- ----j-'---- ------.. -----------1------- -- L i -- Figure 8 Experimental data as a function of refrigerant flow ::.::: ' : 1-- 1 4cr?= R41A, Heating mode U=1.m/s ----f);- 1 Circuit ----.. --------------- -----.. -------------- -o-- Circuits -o- Circuits ----- --------------------------- -------------- --------- -------- Number of thermocouples Figure 9 Effect of refrigerant flow on tube wall temperature Heating Mode Figure 7 shows the performance results of the heat exchanger used as condenser for R41A. The heat exchanger performance results for three different refrigerant flow s exhibit to be unaffected by tube length of the heat exchanger. To confirm the results different from those in cooling mode, the data for Q, T ro and 6.. Pare prepared in Figures 8(a), (b) and (c), respectively. Figure 8(c) shows that 6.P decreases with increase in number of. However, the value of 6.. P is significantly smaller in heating mode when compared to that in cooling mode. Examination of Figure 8(b) reveals that the refrigerant temperatures at the outlet of the heat exchanger for three different s are independent on 6.. P. From the figure, it is clear that the surface temperature of the heat exchanger maintains constant for all refrigerant flow 14

s in the present experiments. The surface temperature distributions along the tube length are shown in Figure 9. The figure reveals that the surface temperatures of the heat exchangers are almost the same among three different refrigerant flow s. Figures lo(a), lo(b) and lo(c) show the comparisons of the experimental data between for R41A and R. Figure lo(a) shows that the heat exchanger performance for R41A is almost same as that for R. This is because /:::. P and Tro for R41 OA are similar to those for R as shown in Figure 1 O(b) and lo(c), respectively. CONCLUSIONS This study was carried out experimentally to evaluate the heat exchanger performance for R 41 OA. Experiments were performed with the heat exchangers for three different refrigerant flow s. The findings obtained in the present experiments are as follows: 1. In cooling mode, the heat exchanger performances were significantly different from the individual s of the heat exchangers. The heat exchanger performances for and s surpassed that for 1 by 17% and 19%, respectively. In particular, for the 1 heat exchanger, comparison results between for R41 OA and R demonstrated that the heat exchanger petformance for R41 OA was far above that for R.. In heating mode, the heat exchanger performance results for three different refrigerant flow s exhibited to be insensitive to the change in the corresponded to the change in the tube length of the heat exchanger. The heat exchanger petformance for R41 OA was almost the same as that for R. REFERENCES 5. 4... 4 ::.:: 4 8 ctl c.. 6 15.:.:::_ 1 c.. <l 5 : :;: :J----[:.. :::::::.:::::::::::::::: :::::.:::::r:::::::::::::::::::::::r:::::::: (c) i i u-=1.m/s : i -e- R... i..... i..... --o- R41 OA - - ----" - -------r ------------ = ------- -- - r------- - ------"--- - Figure 1 Comparison of data between for R41 OA and R (1) Torikoshi, K., K. Kawabata and T. Ebisu, Heat transfer and pressure drop characteristics of HFC-14a in a horizontal heat transfer tube, Proceedings of 199 International Refrigerant Conference at Purdue, (199), VoL 1, pp 167-176. () Torikoshi, K. and T. Ebisu, In-tube condensation of alternate refrigerants, Proceedings of Condensation and Condenser Design, (199), pp 59-6. () Torikoshi, K. and T. Ebisu, Heat transfer and pressure drop characteristics ofr14a, R and a mixture ofr/rl4a inside a horizontal tube, ASHRAE Transactions (199), Vol. 99, Part, pp 9-96. ( 4) Ebisu, T. and K. Torikoshi, In-tube heat transfer characteristics of refrigerant mixtures ofhfc-/14a and HFC-/ 15/14a, Proceedings of 1994 International Refrigeration Conference at Purdue, (1994), pp 9-98. (5) Ebisu, T., K.Torikoshi and K. Okuyama, ASHRAE Transactions, to be submitted. ( 6) Ebisu, T. and K. Torikoshi, Experimental studies on cross flow heat exchanger performance using non-azeotropic refrigerant mixture, Proceedings of 19th International Congress ofrefrigeration 1995, (1995), VoL 4a, pp 16-17. 144